Cambi e Nap Yokogawa
Cambi e Nap Yokogawa
Cambi e Nap Yokogawa
IM 01C21C01-01E
IM 01C21C01-01E
12th Edition
i
Contents
1. Introduction................................................................................................ 1-1
Regarding This Manual................................................................................................. 1-1
1.1 For Safe Use of Product ................................................................................... 1-2
1.2 Warranty.............................................................................................................. 1-3
1.3 ATEX Documentation........................................................................................ 1-4
2. Handling Cautions..................................................................................... 2-1
2.1 Model and Specifications Check...................................................................... 2-1
2.2 Unpacking........................................................................................................... 2-1
2.3 Storage................................................................................................................ 2-1
2.4 Selecting the Installation Location ................................................................. 2-1
2.5 Pressure Connection......................................................................................... 2-2
2.6 Waterproofing of Cable Conduit Connections............................................... 2-2
2.7 Restrictions on Use of Radio Transceiver...................................................... 2-2
2.8 Insulation Resistance and Dielectric Strength Test....................................... 2-2
2.9 Installation of Explosion Protected Type........................................................ 2-3
2.9.1 FM Approval........................................................................................ 2-4
2.9.2 CSA Certification................................................................................. 2-5
2.9.3 IECEx Certification.............................................................................. 2-7
2.9.4 ATEX Certification............................................................................... 2-8
2.10 EMC Conformity Standards............................................................................ 2-11
2.11 PED (Pressure Equipment Directive)............................................................ 2-11
2.12 Low Voltage Directive...................................................................................... 2-12
3. Component Names................................................................................... 3-1
4. Installation.................................................................................................. 4-1
4.1 Precautions ....................................................................................................... 4-1
4.2 Mounting ............................................................................................................ 4-1
4.3 Rotating Transmitter Section............................................................................ 4-1
4.4 Changing the Direction of Integral Indicator ................................................. 4-2
4.5 Affixing the Teflon Film..................................................................................... 4-2
5. Installing Impulse Piping.......................................................................... 5-1
5.1 Impulse Piping Installation Precautions......................................................... 5-1
5.1.1 Connecting Impulse Piping to the Transmitter.................................... 5-1
5.1.2 Routing the Impulse Piping................................................................. 5-1
IM 01C21C01-01E
iii
(4) Output Signal Low Cut Mode Setup ................................................ 8-11
(5) Change Output Limits ...................................................................... 8-11
(6) Integral Indicator Scale Setup........................................................... 8-11
(7) Unit Setup for Displayed Temperature . ........................................... 8-13
(8) Unit Setup for Displayed Static Pressure ........................................ 8-13
(9) Operation Mode Setup . ................................................................... 8-13
(10) Output Status Display/Setup when a CPU Failure .......................... 8-14
(11) Output Status Setup when a Hardware Error Occurs ..................... 8-14
(12) Range Change while Applying Actual Inputs ................................... 8-14
(13) Zero Point Adjustment ..................................................................... 8-15
(14) Span Adjustment............................................................................... 8-16
(15) Test Output Setup ............................................................................ 8-17
(16) User Memo Fields............................................................................. 8-17
8.4 Displaying Data Using the BT200................................................................... 8-18
8.4.1 Displaying Measured Data............................................................... 8-18
8.4.2 Display Transmitter Model and Specifications.................................. 8-18
8.5 Self-Diagnostics............................................................................................... 8-18
8.5.1 Checking for Problems..................................................................... 8-18
8.5.2 Errors and Countermeasures........................................................... 8-20
9. Maintenance............................................................................................... 9-1
9.1 Overview............................................................................................................. 9-1
9.2 Calibration Instruments Selection................................................................... 9-1
9.3 Calibration.......................................................................................................... 9-1
9.4 Disassembly and Reassembly......................................................................... 9-3
9.4.1 Replacing the Integral Indicator.......................................................... 9-3
9.4.2 Replacing the CPU Board Assembly.................................................. 9-4
9.4.3 Replacing the Process Connector Gaskets........................................ 9-5
9.5 Troubleshooting................................................................................................. 9-5
9.5.1 Basic Troubleshooting........................................................................ 9-5
9.5.2 Troubleshooting Flow Charts.............................................................. 9-6
10. General Specifications........................................................................... 10-1
10.1 Standard Specifications.................................................................................. 10-1
10.2 Model and Suffix Codes.................................................................................. 10-3
10.3 Optional Specifications................................................................................... 10-5
10.4 Dimensions....................................................................................................... 10-8
Customer Maintenance Parts List
DPharp EJA Series Transmitter Section.........................................CMPL 01C21A01-02E
Model EJA210A and EJA220A
Flange Mounted Differential Pressure Transmitter........................CMPL 01C21C01-01E
Revision Information
IM 01C21C01-01E
<1. Introduction> 1-1
1. Introduction
Thank you for purchasing the DPharp electronic
pressure transmitter. NOTE
The DPharp Pressure Transmitters are precisely For FOUNDATION FieldbusTM, PROFIBUS PA
calibrated at the factory before shipment. To ensure and HART protocol versions, please refer to
correct and efficient use of the instrument, please IM 01C22T02-01E, IM 01C22T03-00E and IM
read this manual thoroughly and fully understand 01C22T01-01E respectively, in addition to this
how to operate the instrument before operating it. manual.
IM 01C21C01-01E
<1. Introduction> 1-2
1.1 For Safe Use of Product (c) Operation
For the protection and safety of the operator • Wait 10 min. after power is turned off, before
and the instrument or the system including the opening the covers.
instrument, please be sure to follow the instructions
(d) Maintenance
on safety described in this manual when handling
this instrument. In case the instrument is handled in • Please do not carry out except being written
contradiction to these instructions, Yokogawa does to a maintenance descriptions. When these
not guarantee safety. Please give your attention to procedures are needed, please contact nearest
the followings. YOKOGAWA office.
• Care should be taken to prevent the build up of
(a) Installation
drift, dust or other material on the display glass
• The instrument must be installed by an expert and name plate. In case of its maintenance, soft
engineer or a skilled personnel. The procedures and dry cloth is used.
described about INSTALLATION are not
permitted for operators. (e) Explosion Protected Type Instrument
• In case of high process temperature, care • Users of explosion proof instruments should
should be taken not to burn yourself because refer first to section 2.9 (Installation of an
the surface of body and case reaches a high Explosion Protected Instrument) of this manual.
temperature. • The use of this instrument is restricted to those
• The instrument installed in the process is under who have received appropriate training in the
pressure. Never loosen the process connector device.
bolts to avoid the dangerous spouting of • Take care not to create sparks when accessing
process fluid. the instrument or peripheral devices in a
• During draining condensate from the hazardous location.
pressuredetector section, take appropriate care
to avoid contact with the skin, eyes or body, or (f) Modification
inhalation of vapors, if the accumulated process • Yokogawa will not be liable for malfunctions or
fluid may be toxic or otherwise harmful. damage resulting from any modification made
• When removing the instrument from hazardous to this instrument by the customer.
processes, avoid contact with the fluid and the
interior of the meter.
• All installation shall comply with local installation
requirement and local electrical code.
(b) Wiring
• The instrument must be installed by an expert
engineer or a skilled personnel. The procedures
described about WIRING are not permitted for
operators.
• Please confirm that voltages between the
power supply and the instrument before
connecting the power cables and that the
cables are not powered before connecting.
IM 01C21C01-01E
<1. Introduction> 1-3
1.2 Warranty
• The warranty shall cover the period noted on
the quotation presented to the purchaser at the
time of purchase. Problems occurred during the
warranty period shall basically be repaired free
of charge.
• In case of problems, the customer should
contact the Yokogawa representative from
which the instrument was purchased, or the
nearest Yokogawa office.
• If a problem arises with this instrument,
please inform us of the nature of the problem
and the circumstances under which it
developed, including the model specification
and serial number. Any diagrams, data and
other information you can include in your
communication will also be helpful.
• Responsible party for repair cost for the
problems shall be determined by Yokogawa
based on our investigation.
• The Purchaser shall bear the responsibility for
repair costs, even during the warranty period, if
the malfunction is due to:
- Improper and/or inadequate maintenance by
the purchaser.
- Failure or damage due to improper handling,
use or storage which is out of design
conditions.
- Use of the product in question in a location
not conforming to the standards specified by
Yokogawa, or due to improper maintenance
of the installation location.
- Failure or damage due to modification or
repair by any party except Yokogawa or an
approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after
delivery.
- Reason of force majeure such as fires,
earthquakes, storms/floods, thunder/
lightening, or other natural disasters, or
disturbances, riots, warfare, or radioactive
contamination.
IM 01C21C01-01E
<1. Introduction> 1-4
1.3 ATEX Documentation
This procedure is only applicable to the countries in European Union.
GB SK
CZ
DK
I LT
E LV
EST
NL
PL
SF
SLO
P
BG
RO
S
M
GR
IM 01C21C01-01E
<2. Handling Cautions> 2-1
2. Handling Cautions
This chapter describes important cautions 2.2 Unpacking
regarding how to handle the transmitter. Read
carefully before using the transmitter. When moving the transmitter to the installation site,
keep it in its original packaging. Then, unpack the
The EJA-A Series pressure transmitters are transmitter there to avoid damage on the way.
thoroughly tested at the factory before shipment.
When the transmitter is delivered, visually check
them to make sure that no damage occurred during 2.3 Storage
shipment. The following precautions must be observed when
Also check that all transmitter mounting hardware storing the instrument, especially for a long period.
shown in Figure 2.1 is included. If the transmitter (a) Select a storage area which meets the following
was ordered without the mounting bracket or conditions:
without the process connector, the transmitter • It is not exposed to rain or water.
mounting hardware is not included. After checking • It suffers minimum vibration and shock.
the transmitter, repack it in the way it was delivered • It has an ambient temperature and relative
until installation. humidity within the following ranges.
Ambient temperature:
-40 to 85°C without integral indicator
-30 to 80°C with integral indicator
Relative humidity:
5% to 100% R.H. (at 40°C)
Process connector
Preferred temperature and humidity:
approx. 25°C and 65% R.H.
(b) When storing the transmitter, repack it as nearly
as possible to the way it was packed when
Bolt Process connector gasket delivered from the factory.
F0201.ai
(c) If storing a transmitter that has been used,
Figure 2.1 Transmitter Mounting Hardware
thoroughly clean the chambers inside the cover
flanges, so that no measured fluid remains
in it. Also make sure before storing that the
2.1 Model and Specifications pressure-detector and transmitter section are
Check securely mounted.
IM 01C21C01-01E
<2. Handling Cautions> 2-2
(b) Ambient Atmosphere 2.6 Waterproofing of Cable
Avoid installing the transmitter in a corrosive
atmosphere. If the transmitter must be installed
Conduit Connections
in a corrosive atmosphere, there must be Apply a non-hardening sealant to the threads
adequate ventilation as well as measures to to waterproof the transmitter cable conduit
prevent intrusion or stagnation of rain water in connections. (See Figure 6.7, 6.8 and 6.9.)
conduits.
(c) Shock and Vibration
Select an installation site suffering minimum 2.7 Restrictions on Use of Radio
shock and vibration (although the transmitter is Transceiver
designed to be relatively resistant to shock and
vibration). IMPORTANT
(d) Installation of Explosion-protected Transmitters
Explosion-protected transmitters can be Although the transmitter has been designed to
installed in hazardous areas according to the resist high frequency electrical noise, if a radio
types of gases for which they are certified. transceiver is used near the transmitter or its
See Subsection 2.9 “Installation of Explosion external wiring, the transmitter may be affected
Protected Type Transmitters.” by high frequency noise pickup. To test for such
effects, bring the transceiver in use slowly from a
distance of several meters from the transmitter,
2.5 Pressure Connection and observe the measurement loop for noise
effects. Thereafter, always use the transceiver
WARNING outside the area affected by noise.
IM 01C21C01-01E
<2. Handling Cautions> 2-3
• Insulation Resistance Test 2.9 Installation of Explosion
1) Short-circuit the + and – SUPPLY terminals in Protected Type
the terminal box.
In this section, further requirements and differences
2) Turn OFF the insulation tester. Then connect
and for explosionproof type instrument are
the insulation tester plus (+) lead wire to the
described. For explosionproof type instrument,
shorted SUPPLY terminals and the minus (–)
the description in this chapter is prior to other
leadwire to the grounding terminal.
description in this users manual.
3) Turn ON the insulation tester power and
measure the insulation resistance. The voltage For the intrinsically safe equipment and
should be applied short as possible to verify explosionproof equipment, in case the instrument
that the insulation resistance is at least 20 MΩ. is not restored to its original condition after any
4) After completing the test and being very careful repair or modification undertaken by the customer,
not to touch exposed conductors disconnect the intrinsically safe construction or explosionproof
insulation tester and connect a 100 kΩ resistor construction is damaged and may cause dangerous
between the grounding terminal and the short- condition. Please contact Yokogawa for any repair
circuiting SUPPLY terminals. Leave this resistor or modification required to the instrument.
connected at least one second to discharge any
static potential. Do not touch the terminals while NOTE
it is discharging.
For FOUNDATION Fieldbus and PROFIBUS
• Dielectric Strength Test PA explosion protected type, please refer to
1) Short-circuit the + and – SUPPLY terminals in IM 01C22T02-01E and IM 01C22T03-00E
the terminal box. respectively.
2) Turn OFF the dielectric strength tester. Then
connect the tester between the shorted
SUPPLY terminals and the grounding terminal. CAUTION
Be sure to connect the grounding lead of the
dielectric strength tester to the ground terminal. This instrument is tested and certified as
3) Set the current limit on the dielectric strength intrinsically safe type or explosionproof
tester to 10 mA, then turn ON the power and type. Please note that the construction of
gradually increase the test voltage from ‘0’ to the instrument, installation, external wiring,
the specified voltage. maintenance or repair is strictly restricted, and
4) When the specified voltage is reached, hold it non-observance or negligence of this restriction
for one minute. would result in dangerous condition.
5) After completing this test, slowly decrease the
voltage to avoid any voltage surges.
WARNING
To preserve the safety of explosionproof
equipment requires great care during mounting,
wiring, and piping. Safety requirements also
place restrictions on maintenance and repair
activities. Please read the following sections very
carefully.
IM 01C21C01-01E
<2. Handling Cautions> 2-4
2.9.1 FM Approval Note 3. Installation
• Barrier must be installed in an enclosure that
a. FM Intrinsically Safe Type meets the requirements of ANSI/ISA S82.01.
Caution for FM intrinsically safe type. (Following • Control equipment connected to barrier must
contents refer “DOC. No. IFM012-A12 P.1 and not use or generate more than 250 V rms or
2.”) V dc.
• Installation should be in accordance with
Note 1. Model EJA Series pressure transmitters ANSI/ISA RP12.6 “Installation of Intrinsically
with optional code /FS1 are applicable for Safe Systems for Hazardous (Classified)
use in hazardous locations. Locations” and the National Electric Code
• Applicable Standard: FM3600, FM3610, (ANSI/NFPA 70).
FM3611, FM3810, ANSI/NEMA250 • The configuration of associated apparatus
• Intrinsically Safe for Class I, Division 1, must be FMRC Approved.
Groups A, B, C & D. Class II, Division 1, • Dust-tight conduit seal must be used when
Groups E, F & G and Class III, Division 1 installed in a Class II, III, Group E, F and G
Hazardous Locations. environments.
• Nonincendive for Class I, Division 2, Groups • Associated apparatus manufacturer’s
A, B, C & D. Class II, Division 2, Groups E, installation drawing must be followed when
F & G and Class III, Division 1 Hazardous installing this apparatus.
Locations. • The maximum power delivered from the
• Outdoor hazardous locations, NEMA 4X. barrier must not exceed 0.9 W.
• Temperature Class: T4 • Note a warning label worded
• Ambient temperature: –40 to 60°C “SUBSTITUTION OF COMPONENTS MAY
Note 2. Entity Parameters IMPAIR INTRINSIC SAFETY,” and “INSTALL
• Intrinsically Safe Apparatus Parameters IN ACCORDANCE WITH DOC. No. IFM012-
[Groups A, B, C, D, E, F and G] A12 P.1 and 2.”
Vmax = 30 V Ci = 22.5 nF Note 4. Maintenance and Repair
Imax = 165 mA Li = 730 µH • The instrument modification or parts
Pmax = 0.9 W replacement by other than authorized
* Associated Apparatus Parameters representative of Yokogawa Electric
(FM approved barriers) Corporation is prohibited and will void
Factory Mutual Intrinsically safe and
Voc ≤ 30 V Ca > 22.5 nF
Nonincendive Approval.
Isc ≤ 165 mA La > 730 µH
Pmax ≤ 0.9W [Intrinsically Safe]
Hazardous Location Nonhazardous Location
• Intrinsically Safe Apparatus Parameters
[Groups C, D, E, F and G] Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G General
Vmax = 30 V Ci = 22.5 nF
EJA Series Pressure Purpose
Imax = 225 mA Li = 730 µH Transmitters Safety Barrier Equipment
Pmax = 0.9 W + + + +
Supply – – – –
* Associated Apparatus Parameters
(FM approved barriers)
Voc ≤ 30 V Ca > 22.5 nF
Isc ≤ 225 mA La > 730 µH [Nonincendive]
Pmax ≤ 0.9 W Hazardous Location Nonhazardous Location
Class I, II, Division 2,
• Entity Installation Requirements Groups A, B, C, D, E, F, G
Vmax ≥ Voc or Vt, Imax ≥ Isc or It, Class III, Division 1. General
Pmax (IS Apparatus) ≥ Pmax (Barrier) EJA Series Pressure Purpose
Ca ≥ Ci + Ccable, La ≥ Li + Lcable Transmitters Equipment
+ +
Supply – –
Not Use
Safety Barrier
F0203.ai
IM 01C21C01-01E
<2. Handling Cautions> 2-5
b. FM Explosionproof Type Note 1. For the installation of this transmitter,
once a particular type of protection is
Caution for FM explosionproof type.
selected, any other type of protection
Note 1. Model EJA Series differential, gauge, cannot be used. The installation must be in
and absolute pressure transmitters with accordance with the description about the
optional code /FF1 are applicable for use in type of protection in this instruction manual.
hazardous locations.
Note 2. In order to avoid confusion, unnecessary
• Applicable Standard: FM3600, FM3615,
marking is crossed out on the label other
FM3810, ANSI/NEMA250
than the selected type of protection when
• Explosionproof for Class I, Division 1,
the transmitter is installed.
Groups B, C and D.
• Dust-ignitionproof for Class II/III, Division 1, 2.9.2 CSA Certification
Groups E, F and G.
• Outdoor hazardous locations, NEMA 4X. a. CSA Intrinsically Safe Type
• Temperature Class: T6 Caution for CSA Intrinsically safe type.
• Ambient Temperature: –40 to 60°C (Following contents refer to “DOC No. ICS003-
• Supply Voltage: 42 V dc max. A12 P.1-1 and P.1-2.”)
• Output signal: 4 to 20 mA
Note 1. Model EJA Series differential, gauge,
Note 2. Wiring and absolute pressure transmitters with
• All wiring shall comply with National Electrical optional code /CS1 are applicable for use
Code ANSI/NEPA70 and Local Electrical in hazardous locations
Codes. Certificate: 1053843
• When installed in Division 1, “FACTORY • Applicable Standard: C22.2 No.0, No.0.4,
SEALED, CONDUIT SEAL NOT No.25, No.30, No.94, No.142, No.157,
REQUIRED.” No.213
Note 3. Operation • Intrinsically Safe for Class I, Division 1,
• Keep the “CAUTION” nameplate attached to Groups A, B, C & D. Class II, Division 1,
the transmitter. Groups E, F & G and Class III, Division 1
CAUTION: OPEN CIRCUIT BEFORE Hazardous Locations.
REMOVING COVER. FACTORY SEALED, • Nonincendive for Class I, Division 2, Groups
CONDUIT SEAL NOT REQUIRED. A, B, C & D, Class II, Division 2, Groups F &
INSTALL IN ACCORDANCE WITH THE G, and Class III, Hazardous Locations. (not
INSTRUCTION MANUAL IM 1C22. use Safety Barrier)
• Take care not to generate mechanical • Encl. “Type 4X”
sparking when accessing to the instrument • Temperature Class: T4
and peripheral devices in a hazardous • Ambient temperature: –40* to 60°C
location. * –15°C when /HE is specified.
• Process Temperature: 120°C max.
Note 4. Maintenance and Repair
• The instrument modification or parts Note 2. Entity Parameters
replacement by other than authorized • Intrinsically safe ratings are as follows:
representative of Yokogawa Electric Maximum Input Voltage (Vmax) = 30 V
Corporation is prohibited and will void Maximum Input Current (Imax) = 165 mA
Factory Mutual Explosionproof Approval. Maximum Input Power (Pmax) = 0.9 W
Maximum Internal Capacitance (Ci) = 22.5nF
c. FM Intrinsically Safe Type/FM
Maximum Internal Inductance (Li) = 730 µH
Explosionproof Type
* Associated apparatus (CSA certified barriers)
Model EJA Series pressure transmitters with Maximum output voltage (Voc) ≤ 30 V
optional code /FU1 can be selected the type Maximum output current (Isc) ≤ 165 mA
of protection (FM Intrinsically Safe or FM Maximum output power (Pmax) ≤ 0.9 W
Explosionproof) for use in hazardous locations.
IM 01C21C01-01E
<2. Handling Cautions> 2-6
Note 3. Installation Note 2. Wiring
• All wiring shall comply with Canadian • All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical Electrical Code Part I and Local Electrical
Codes. Codes.
• The instrument modification or parts • In hazardous location, wiring shall be in
replacement by other than authorized conduit as shown in the figure.
representative of Yokogawa Electric CAUTION: SEAL ALL CONDUITS WITHIN
Corporation and Yokogawa Corporation 50 cm OF THE ENCLOSURE.
of America is prohibited and will void UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
Canadian Standards Intrinsically safe and MOINS DE 50 cm DU BîTIER.
nonincendive Certification. • When installed in Division 2, “SEALS NOT
REQUIRED.”
[Intrinsically Safe]
Hazardous Location Nonhazardous Location Note 3. Operation
Class I, II, III, Division 1, • Keep the “CAUTION” label attached to the
Groups A, B, C, D, E, F, G General transmitter.
EJA Series Pressure Purpose CAUTION: OPEN CIRCUIT BEFORE
Transmitters Safety Barrier Equipment
REMOVING COVER.
+ + + +
OUVRIR LE CIRCUIT AVANT D´NLEVER
Supply – – – –
LE COUVERCLE.
• Take care not to generate mechanical
sparking when accessing to the instrument
[Nonincendive] and peripheral devices in a hazardous
Hazardous Location Nonhazardous Location location.
Class I, II, Division 2,
Note 4. Maintenance and Repair
Groups A, B, C, D, E, F, G
Class III, Division 1. General • The instrument modification or parts
EJA Series Pressure Purpose replacement by other than authorized
Transmitters Equipment representative of Yokogawa Electric
+ + Corporation and Yokogawa Corporation of
Supply – – America is prohibited and will void Canadian
Not Use
Safety Barrier
Standards Explosionproof Certification.
F0204.ai
IM 01C21C01-01E
<2. Handling Cautions> 2-7
c. CSA Intrinsically Safe Type/CSA Note 2. Entity Parameters
Explosionproof Type • Intrinsically safe ratings are as follows:
Maximum Input Voltage (Ui) = 30 V
Model EJA Series pressure transmitters with
Maximum Input Current (Ii) = 165 mA
optional code /CU1 can be selected the type
Maximum Input Power (Pi) = 0.9 W
of protection (CSA Intrinsically Safe or CSA
Maximum Internal Capacitance (Ci) = 22.5nF
Explosionproof) for use in hazardous locations.
Maximum Internal Inductance (Li) = 730 µH
Note 1. For the installation of this transmitter, • Type “n” ratings are as follows:
once a particular type of protection is Maximum Input Voltage (Ui) = 30 V
selected, any other type of protection Maximum Internal Capacitance (Ci) = 22.5nF
cannot be used. The installation must be in Maximum Internal Inductance (Li) = 730 µH
accordance with the description about the • Installation Requirements
type of protection in this instruction manual. Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
Note 2. In order to avoid confusion, unnecessary Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
marking is crossed out on the label other Uo, Io, Po, Co, and Lo are parameters of
than the selected type of protection when barrier.
the transmitter is installed. Note 3. Installation
2.9.3 IECEx Certification • In any safety barreir used output current
must be limited by a resistor 'R' such that
Model EJA Series differential, gauge, and absolute Io=Uo/R.
pressure transmitters with optional code /SU2 • The safety barrier must be IECEx certified.
can be selected the type of protection (IECEx • Input voltage of the safety barrier must be
Intrinsically Safe/type n or flameproof) for use in less than 250 Vrms/Vdc.
hazardous locations. • The instrument modification or parts
replacement by other than authorized
Note 1. For the installation of this transmitter, representative of Yokogawa Electric
once a particular type of protection is Corporation and will void IECEx Intrinsically
selected, any other type of protection safe and type n certification.
cannot be used. The installation must be in • The cable entry devices and blanking
accordance with the description about the elements for type n shall be of a certified type
type of protection in this instruction manual. providing a level of ingress protection of at
Note 2. In order to avoid confusion, unnecessary least IP54, suitable for the conditions of use
marking is crossed out on the label other and correctly installed.
than the selected type of protection when • Electrical Connection:
the transmitter is installed. The type of electrical connection is stamped
near the electrical connection port according
a. IECEx Intrinsically Safe Type / type n
to the following marking.
Caution for IECEx Intrinsically safe and type n.
Screw Size Marking
Note 1. Model EJA Series differential, gauge, M
ISO M20 × 1.5 female
and absolute pressure transmitters with
ANSI 1/2 NPT female A
optional code /SU2 are applicable for use
in hazardous locations.
• No. IECEx KEM 06.0007X
• Applicable Standard: IEC 60079-0:2004,
IEC 60079-11:1999, IEC 60079-15:2005,
IEC 60079-26:2004 Location of the marking
IM 01C21C01-01E
<2. Handling Cautions> 2-8
Note 4. Operation • Ambient Temperature: –40 to 75°C (T4),
• WARNING: –40 to 80°C (T5), –40 to 75°C (T6)
WHEN AMBIENT TEMPERATURE ≥ 55°C, • Supply Voltage: 42 V dc max.
USE THE HEAT-RESISTING CABLES ≥ • Output Signal: 4 to 20 mA dc
90°C.
Note 2. Wiring
Note 5. Special Conditions for Safe Use • In hazardous locations, the cable entry
• WARNING: devices shall be of a certified flameproof
IN THE CASE WHERE THE ENCLOSURE type, suitable for the conditions of use and
OF THE PRESSURE TRANSMITTER IS correctly installed.
MADE OF ALUMINUM, IF IT IS MOUNTED • Unused apertures shall be closed with
IN AN AREA WHERE THE USE OF ZONE suitable flameproof certified blanking
0 IS REQUIRED, IT MUST BE INSTALLED elements. (The plug attached is certificated
SUCH, THAT, EVEN IN THE EVENT OF as the flame proof IP67 as a part of this
RARE INCIDENTS, IGNITION SOURCES apparatus.)
DUE TO IMPACT AND FRICTION SPARKS • In case of ANSI 1/2 NPT plug, ANSI
ARE EXCLUDED. hexagonal wrench should be applied to
screw in.
[Intrinsically Safe]
Hazardous Location Nonhazardous Location Note 3. Operation
Group I/IIC, Zone 0 • WARNING:
General AFTER DE-ENERGIZING, DELAY 10
EJA Series Pressure IECEx certified Purpose MINUTES BEFORE OPENING.
Transmitters Safety Barrier Equipment
• WARNING:
+ + + +
WHEN AMBIENT TEMPERATURE ≥ 70°C,
Supply – – – –
USE THE HEAT-RESISTING CABLES ≥
90°C.
• Take care not to generate mechanical
[type n] sparking when accessing to the instrument
Hazardous Location Nonhazardous Location and peripheral devices in a hazardous
Group IIC, Zone 2 location.
Note 1. Model EJA Series differential, gauge, a. ATEX Intrinsically Safe Type
and absolute pressure transmitters with
optional code /SU2 are applicable for use Caution for ATEX Intrinsically safe type.
in hazardous locations: Note 1. Model EJA Series differential, gauge,
• No. IECEx KEM 06.0005 and absolute pressure transmitters with
• Applicable Standard: IEC60079-0:2004, optional code /KS2 for potentially explosive
IEC60079-1:2003 atmospheres:
• Type of Protection and Marking Code: • No. KEMA 02ATEX1030 X
Ex d IIC T6...T4 • Applicable Standard: EN 50014:1997,
• Enclosure: IP67 EN 50020:1994, EN 50284:1999
• Maximum Process Temperature:
120°C (T4), 100°C (T5), 85°C (T6)
IM 01C21C01-01E
<2. Handling Cautions> 2-9
• Type of Protection and Marking code: b. ATEX Flameproof Type
EEx ia IIC T4
Caution for ATEX flameproof type.
• Temperature Class: T4
• Enclosure: IP67 Note 1. Model EJA Series differential, gauge,
• Process Temperature: 120°C max. and absolute pressure transmitters
• Ambient Temperature: –40 to 60°C with optional code /KF21 for potentially
explosive atmospheres:
Note 2. Electrical Data
• No. KEMA 02ATEX2148
• In type of explosion protection intrinsic
• Applicable Standard: EN 60079-0:2006,
safety EEx ia IIC only for connection to a
EN 60079-1:2004
certified intrinsically safe circuit with following
• Type of Protection and Marking Code:
maximum values:
Ex d IIC T6...T4
Ui = 30 V
• Temperature Class: T6, T5, and T4
Ii = 165 mA
• Enclosure: IP67
Pi = 0.9 W
• Maximum Process Temperature:
Effective internal capacitance; Ci = 22.5 nF
85°C (T6), 100°C (T5), and 120°C (T4)
Effective internal inductance; Li = 730 µH
• Ambient Temperature:
Note 3. Installation T4 and T6; –40* to 75°C, T5; –40* to 80°C
• All wiring shall comply with local installation * –15°C when /HE is specified.
requirements. (Refer to the installation
Note 2. Electrical Data
diagram)
• Supply voltage: 42 V dc max.
Note 4. Maintenance and Repair • Output signal: 4 to 20 mA
• The instrument modification or parts
Note 3. Installation
replacement by other than authorized
• All wiring shall comply with local installation
representative of Yokogawa Electric
requirement.
Corporation is prohibited and will void KEMA
• The cable entry devices shall be of a certified
Intrinsically safe Certification.
flameproof type, suitable for the conditions of
Note 5. Special Conditions for Safe Use use.
• In the case where the enclosure of the
Note 4. Operation
Pressure Transmitter is made of aluminium,
• Keep the “CAUTION” label to the transmitter.
if it is mounted in an area where the use of
CAUTION: AFTER DE-ENERGIZING,
category 1 G apparatus is required, it must
DELAY 10 MINUTES BEFORE OPENING.
be installed such, that, even in the event of
WHEN THE AMBIENT TEMP. ≥ 70°C, USE
rare incidents, ignition sources due to impact
HEAT-RESISTING CABLES ≥ 90°C.
and friction sparks are excluded.
• Take care not to generate mechanical
[Installation Diagram] sparking when accessing to the instrument
Hazardous Location Nonhazardous Location
and peripheral devices in a hazardous
location.
Transmitter Note 5. Maintenance and Repair
+ + • The instrument modification or parts
Supply Safety Barrier *1
– – replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void KEMA
Flameproof Certification.
F0208.ai
IM 01C21C01-01E
<2. Handling Cautions> 2-10
(2) Electrical Connection (6) Name Plate
The type of electrical connection is stamped Name plate
near the electrical connection port according to
the following marking.
Screw Size Marking
ISO M20 × 1.5 female M
: Refer to USER'S MANUAL
(3) Installation
F0211.ai
WARNING
The instrument modification or parts replacement
by other than authorized Representative of
Yokogawa Electric Corporation is prohibited and
will void the certification.
IM 01C21C01-01E
<2. Handling Cautions> 2-11
2.10 EMC Conformity Standards
PS*1 PS-V
Model V(L) Category*2
EN 61326-1 Class A, Table 2 (For use in industrial (bar) (bar-L)
locations) Article 3, paragraph 3
EJA110A 160 0.01 1.6
(SEP)
EN 61326-2-3 EJA120A 0.5 0.01 0.005
Article 3, paragraph 3
(SEP)
EN 61326-2-5 (for Fieldbus) Article 3, paragraph 3
EJA130A 420 0.01 4.2
(SEP)
EJA130A
CAUTION With code /PE3
420 0.01 4.2 III
Article 3, paragraph 3
This instrument is a Class A product, and it is EJA310A 160 0.01 1.6
(SEP)
designed for use in the industrial environment. Article 3, paragraph 3
EJA430A 160 0.01 1.6
Please use this instrument in the industrial (SEP)
environment only. Article 3, paragraph 3
EJA440A 500 0.01 50
(SEP)
EJA440A
500 0.01 50 III
With code /PE3
Article 3, paragraph 3
NOTE EJA510A 500 0.01 50
(SEP)
EJA510A With
YOKOGAWA recommends customer to apply 500 0.01 50 III
code /PE3
the Metal Conduit Wiring or to use the twisted Article 3, paragraph 3
EJA530A 500 0.01 50
pair Shield Cable for signal wiring to conform the (SEP)
EJA530A
requirement of EMC Regulation, when customer 500 0.01 50 III
With code /PE3
installs the EJA Series Transmitters to the plant.
*1: PS is maximum allowable pressure for vessel itself.
*2: Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 97/23/EC
IM 01C21C01-01E
<2. Handling Cautions> 2-12
2.12 Low Voltage Directive
Applicable standard: EN 61010-1
IM 01C21C01-01E
<3. Component Names> 3-1
3. Component Names
Terminal box cover
Tramsmitter sedtion
CPU assembly
Zero-adjustment screw
Integral
indicator (Note 1)
Mounting screw
Process connection
(low pressure side)
Setting pin
(CN4)
Cover flange Process connector
Range-setting
(Note 1)
switch (Note 1)
(See Subsection 7.6) Pressure-detector section
Note 1: See Subsection 10.2, “Model and Suffix Codes,” for details.
Note 2: Insert the pin (CN4) as shown in the figure above to set the burn-out direction. The pin is set to the H side for delivery (unless
option code /C1 is specified in the order).
The setting can be confirmed by calling up parameter D52 using the BRAIN TERMINAL. Refer to Subsection 8.3.3 (11).
Figure 3.1 Component Names
IM 01C21C01-01E
<4. Installation> 4-1
4. Installation
4.1 Precautions 4.3 Rotating Transmitter Section
Before installing the transmitter, read the cautionary The DPharp transmitter section can be rotated in
notes in Section 2.4, “Selecting the Installation 90° segments.
Location.” For additional information on the ambient
1) Remove the two Allen screws that fasten the
conditions allowed at the installation location, refer
transmitter section and pressure-detector
to Subsection 10.1 “Standard Specifications.”
section, using the Allen wrench supplied with
the transmitter.
IMPORTANT 2) Rotate the transmitter section slowly in 90°
• When welding piping during construction, segments.
take care not to allow welding currents to 3) Tighten the two Allen screws.
flow through the transmitter.
• Do not step on this instrument after IMPORTANT
installation.
Do not rotate the transmitter section more than
• Never loosen the four screws securing the
180°.
cover flanges (if the seal liquid leaks, the
transmitter cannot be used).
Rotate 90° or 180° segments
Transmitter section
4.2 Mounting
The transmitter is mounted on a process using its
highpressure side flange as shown in Figure 4.1. Conduit connection
The customer should prepare the mating flange,
gasket, stud bolts and nuts. Zero-adjustment screw
Gasket
Pressure-detector section
F0402.ai
Stud bolt
Nut
F0401.ai
IMPORTANT
Please use a gasket which has a bigger inside
diameter than that of gasket facing (Ød) on
diaphragm seal. In case a gasket which has a
smaller inside diameter than that of gasket facing
is used, it may cause an error as the gasket
prevents diaphragm from working correctly.
(Refer to Subsection 10.4 ‘Dimensions’)
IM 01C21C01-01E
<4. Installation> 4-2
4.4 Changing the Direction of Teflon film
Integral Indicator
IMPORTANT
Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area
Fluorinated oil
before disassembling and reassembling an [PART No. : F9145YN]
Diaphragm
indicator.
F0403.ai
F9347YD 2 inch (50mm)
IM 01C21C01-01E
<5. Installing Impulse Piping> 5-1
5.1.1 Connecting Impulse Piping to the 5.1.2 Routing the Impulse Piping
Transmitter
(1) Impulse Piping Slope
(1) Check the High and Low Pressure The impulse piping must be routed with only an
Connections on the Transmitter (Figure 5.1) upward or downward slope. Even for horizontal
Symbols “H” and “L” are shown on a capsule routing, the impulse piping should have a slope of
assembly to indicate high and low pressure side. at least 1/10 to prevent condensate (or gases) from
For liquid level measurement in an open tank, the ‘L’ accumulating in the pipes.
(low pressure) side is used to refer atmosphere. For
(2) Preventing Freezing
a closed tank, connect the impulse line to the low
pressure side of the transmitter. This will refer the If there is any risk that the process fluid in the
pressure in the tank. impulse piping or transmitter could freeze, use a
steam jacket or heater to maintain the temperature
of the fluid.
“H” and “L” are shown
NOTE
Low pressure
connection After completing the connections, close the
Process connector
valves on the process pressure taps (main
valves), the valves at the transmitter (stop
Bolt
valves), and the impulse piping drain valves,
F0501.ai so that condensate, sediment, dust and other
extraneous material cannot enter the impulse
Figure 5.1 “H” and “L” Symbols on a Capsule
Assembly
piping.
IM 01C21C01-01E
<5. Installing Impulse Piping> 5-2
5.2 Impulse Piping Connection
Examples
Figure 5.2 shows examples of typical impulse
piping connections. Before connecting the
transmitter to the process, study the transmitter
installation location, the process piping layout,
and the characteristics of the process fluid
(corrosiveness, toxicity, flammability, etc.), etc. and
make appropriate changes and additions to the
connection configurations.
Open Tank
Closed Tank
Tap valve
Union or flange
Vent plug
Tee
Drain valve
Drain plug
F0502.ai
IM 01C21C01-01E
<6. Wiring> 6-1
6. Wiring
6.1 Wiring Precautions 6.3 Connections of External
Wiring to Terminal Box
IMPORTANT
• Lay wiring as far as possible from electrical
6.3.1 Power Supply Wiring Connection
noise sources such as large capacity Connect the power supply wiring to the SUPPLY +
transformers, motors, and power supplies. and – terminals.
• Remove electrical connection dust cap
Transmitter terminal box
before wiring. +
• All threaded parts must be treated with Power supply
waterproofing sealant. (A non-hardening –
and power cables through the same ducts. Figure 6.1 Power Supply Wiring Connection
• Explosion-protected instruments must
be wired in accordance with specific 6.3.2 External Indicator Connection
requirements (and, in certain countries,
legal regulations) in order to preserve the Connect wiring for external indicators to the CHECK
effectiveness of their explosion-protected + and – terminals.
features. (Note) Use a external indicator whose internal resistance is 10Ω
or less.
• The terminal box cover is locked by an Allen
head bolt (a shrouding bolt) on CENELEC External indicator
Power supply
and IECEx flameproof type transmitters. +
When the shrouding bolt is driven clockwise
–
by an Allen wrench, it is going in and cover
lock is released, and then the cover can
be opened by hand. See Subsection 9.4
Transmitter terminal box
“Disassembly and Reassembly” for details. F0602.ai
(a) Use stranded leadwires or cables which are Connect the BT200 to the SUPPLY + and
the same as or better than 600 V grade PVC – terminals (Use hooks). The communication line
insulated wire (JIS C3307) or equivalent. requires a reception resistor of 250 to 600Ω in
(b) Use shielded wires in areas that are susceptible series.
to electrical noise. Transmitter terminal box Power supply
(c) In areas with higher or lower ambient +
temperatures, use appropriate wires or cables. –
(d) In environment where oils, solvents, corrosive
Ignore the polarity
gases or liquids may be present, use wires or since the BT200 is
cables that are resistant to such substances. AC-coupled to the
BT200 terminal box.
(e) It is recommended that crimp-on solderless
F0603.ai
terminal lugs (for 4 mm screws) with insulating
Figure 6.3 BT200 Connection
sleeves be used for leadwire ends.
IM 01C21C01-01E
<6. Wiring> 6-2
6.3.4 Check Meter Connection (2) Intrinsically Safe Type
Connect the check meter to the CHECK + and For intrinsically safe type, a safety barrier must be
– terminals (use hooks). included in the loop.
• A 4 to 20 mA DC output signal from the CHECK Hazardous Location Nonhazardous Location
+ and – terminals.
(Note) Use a check meter whose internal resistance is 10Ω or Transmitter terminal box
less. Distributor
(Power supply unit)
Power supply
+ Receiver
instrument
– +
–
Check meter
Transmitter terminal box Safety barrier
F0604.ai F0606.ai
Figure 6.4 Check Meter Connection Figure 6.6 Connection between Transmitter and
Distributor
Apply a non-hardening
Hazardous Location Nonhazardous Location
Wiring metal sealant to the threads
conduit for waterproofing.
Transmitter terminal box
Distributor Tee
(Power supply unit)
Drain plug
F0607.ai
IM 01C21C01-01E
<6. Wiring> 6-3
(2) Flameproof Type 6.5 Grounding
Wire cables through a flameproof packing adapter, Grounding is always required for the proper
or using a flameproof metal conduit. operation of transmitters. Follow the domestic
■ Wiring cable through flameproof packing adapter. electrical requirements as regulated in each
• Apply a nonhardening sealant to the terminal country. For a transmitter with built-in lightning
box connection port and to the threads on the protector, grounding should satisfy ground
flameproof packing adapter for waterproofing. resistance of 10Ω or less.
Ground terminals are located on the inside and
outside of the terminal box. Either of these terminals
Flameproof packing adapter may be used.
Drain plug
F0608.ai
IM 01C21C01-01E
<7. Operation> 7-1
7. Operation
7.1 Preparation for Starting Confirming that Transmitter is Operating
Properly
Operation
The Model EJA210A and EJA220A flange mounted Using the BT200
differential pressure transmitter measures the levels
• If the wiring system is faulty, ‘communication
or densities of liquids. This section describes the
error’ appears on the display.
operation procedure for the EJA210A as shown in
• If the transmitter is faulty, ‘SELF CHECK
Figure 7.1 when measuring a liquid level in an open
ERROR’ appears on the display.
tank.
PARAM
C60:SELF CHECK
(a) Confirm that there is no leak in the connecting ERROR
part of the transmitter mounting flange. communication error
Open tank
Self-diagnostic error on
the integral indicator
(Faulty transmitter)
F0703.ai
NOTE
If any of the error indications above appears on
the display of the integral indicator or BT200,
refer to Subsection 8.5.2 for corrective action.
IM 01C21C01-01E
<7. Operation> 7-2
7.2 Zero Point Adjustment 7.2.1 When you can obtain Low Range
Value from actual measured value of
Adjust the zero point after operating preparation is
0% (0 kPa, atmospheric pressure);
completed.
IM 01C21C01-01E
<7. Operation> 7-3
7.2.2 When you cannot obtain Low Range 7.3 Starting Operation
Value from actual measured value of
After completing the zero point adjustment, follow
0%;
the procedure below to start operation.
Convert the actual measured value obtained by a
1) Confirm the operating status.
glass gauge into %.
The output signal may widely fluctuate (hunting
[Example] state) due to process pressure periodic
variation. In such case, BT200 operation can
The measuring range of 0 to 2 m and the actual dampen the transmitter output signal. Confirm
measured value of 0.8 m. the hunting state using a receiving instrument
0.8 or the integral indicator and set the optimum
Actual measured value = x 100 = 40.0% damping time constant. See Subsection 8.3.3
2
(3) “Damping time constant setup.”
2) After confirming the operating status, perform
Using the Transmitter Zero-Adjustment the following:
Screw
Turn the screw to match the output signal to the IMPORTANT
actual measured value in %.
• Remove the BT200 from the terminal box,
Using the BT200 and confirm that none of the terminal screws
are loosened.
Select the parameter J10: ZERO ADJ. Change • Close the terminal box cover and the
the set point (%) displayed for the parameter to the amplifier cover. Screw each cover in tightly
actual measured value (%), and press the ENTER until it will not turn further.
key twice. • Two covers are required to be locked on
See Subsection 8.3.3 (12) for operation details. the CENELEC and IECEx Flameproof type
SET A display at J10 transmitters. An Allen head bolts (shrouding
J10:ZERO ADJ
-0.0 % bolts) are provided under edge of the
+ 000.0
each cover for locking. When a shrouding
bolts are driven counterclockwise by an
CLR ESC
Allen wrench, it is coming out and locks
up a cover. (See page 9-3) After locking,
the covers should be confirmed not to be
SET Change setting to the actually
J10:ZERO ADJ opened by hand.
-0.0 % measured value (40.0%). • Tighten the zero-adjustment cover mounting
+ 040.0
Press key twice screw to fix the cover in position.
for 40% output 10.4 mA DC.
CLR ESC
F0706.ai
IM 01C21C01-01E
<7. Operation> 7-4
7.4 Shutting Down Operation 7.5.2 Venting Gas
Turn off the power. 1) Gradually open the vent screw to vent gas from
the transmitter pressur-detector section. (See
NOTE Figure 7.2)
2) When the transmitter is completely vented,
Whenever shutting down the transmitter for a close the vent screw.
long period, detach the transmitter from the tank. 3) Tighen the vent screw to a torque of 10 N·m.
will be required if the impulse piping is configured When you loosen the drain plug or the vent screw, the
accumulated liquid (or gas) will be expelled in the direction
appropriately for self-draining or self-venting of the arrow.
operation. F0707.ai
IM 01C21C01-01E
<7. Operation> 7-5
4) Turn the external zero-adjustment screw in the Integral indicator
desired direction. The integral indicator displays
the output signal in %. (Note 2) Note : Use a thin bar which
has a blunt tip, e.g.,
5) Adjust the output signal to 0% (1 V DC) by a hexagonal wrench,
rotating the external zero-adjustment screw. to press the range-
setting push-button
Doing so completes the LRV setting.
6) Press the range-setting push-button. The
integral indicator then displays “HSET.”
Range-setting switch
7) Apply a pressure of 3 MPa to the transmitter. (Push-button)
(Note 1) F0708.ai
8) Turn the external zero-adjustment screw in the Figure 7.3 Range-setting Switch
desired direction. The integral indicator displays
the output signal in %. (Note 2)
9) Adjust the output signal to 100% (5 V DC) by
rotating the external zero-adjustment screw.
Doing so completes the HRV setting.
10) Press the range-setting push-button. The
transmitter then switches back to the normal
operation mode with the measurement range of
0 to 3 MPa.
Note 1: Wait until the pressure inside the pressure-detector
section has stabilized before proceeding to the next step.
Note 2: If the pressure applied to the transmitter exceeds the
previous LRV (or HRV), the integral indicator may display
error number “Er.07” (In this case, the output signal
percent and “Er.07” are displayed alternately every two
seconds).
Although “Er.07” is displayed, you may proceed to the
next step. However, should any other error number be
displayed, take the appropriate measure in reference to
Subsection 8.5.2, “Errors and Countermeasures.”
IMPORTANT
• Do not turn off the power to the transmitter
immediately after completion of the change
in the LRV and/or HRV setting(s). Note
that powering off within thirty seconds after
setting will cause a return to the previous
settings.
• Changing LRV automatically changes HRV
to the following value.
HRV =
previous HRV + (new LRV – previous LRV)
• If the range-setting push-button and external
zero-adjustment screw are not touched
during a range-change operation, the
transmitter automatically switches back to
the normal operation mode.
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-1
Power
supply
cc
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-2
8.2 BT200 Operating Procedures 8.2.2 Operating Key Functions
8.2.1 Key Layout and Screen Display (1) Alphanumeric Keys and Shift Keys
Figure 8.3 shows the arrangement of the operating You can use the alphanumeric keys in conjunction
with the shift keys to enter symbols, as well as
keys on the BT200 keypad, and Figure 8.4 shows
alphanumeric keys.
the BT200 screen component.
1 –9
Alphanumeric keys F0806.ai
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-3
symbol command
l/m
(I) (/) (m)
F0809.ai
Function keys
F0810.ai
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-4
8.2.3 Calling Up Menu Addresses Using the Operating Keys
PARAM
01:MODEL
EJA210A-DM
INITIAL 02:TAG NO. FUNC
DATA YOKOGAWA 1.MENU
SCREEN 03:SELF CHECK (ESC) 2.UPLOAD TO BT200
GOOD 3.DOWNLOAD TO INST
OK 4.PRINT ALL DATA
(SET) (ADJ)
(HOME MENU SCREEN) (SET MENU SCREEN) (ADJ MENU SCREEN)
MENU MENU MENU
A.DISPLAY C.SETTING J.ADJUST
B.SENSOR TYPE D.AUX SET 1 K.TEST
MENU E.AUX SET 2 M.MEMO
SCREEN H:AUTO SET P:RECORD
HOME SET ADJ ESC HOME SET ADJ ESC HOME SET ADJ ESC
PARAM PARAM
A60:SELF CHECK C60:SELF CHECK
GOOD GOOD
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-5
8.3 Setting Parameters Using the BT200
8.3.1 Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters EJA110A, EJA120A, and EJA130A
P: Pressure transmitters EJA310A, EJA430A, EJA440A, EJA510A, and EJA530A
L: Liquid level transmitters EJA210A and EJA220A
Applica-
Rewrita- bility
No. Item Description Remarks Default Value
bility
F P L
01 MODEL Model+capsule type –
02 TAG NO. Tag number – 16 alphanumerics
03 SELF CHECK Self-diagnostic result – GOOD/ERROR
A DISPLAY Measured data display – Menu name
A10 OUTPUT (%) Output (in %) – –5 to 110%*3
A11 ENGR. OUTPUT Output (in engineering units) – –19999 to 19999
A20 AMP TEMP Amplifier temperature – Unit specified in D30
A21 CAPSULE Capsule temperature – Unit specified in D30
TEMP
A30 STATIC PRESS Static pressure – Unit specified in D31*1 –
A40 INPUT Input (indicated as the value – –32000 to 32000
after zeroing)
A60 SELF CHECK Self-diagnostic messages – GOOD/ERROR, CAP MODULE FAULT, AMP
MODULE FAULT, OUT OF RANGE, OUT OF SP
RANGE*1, OVER TEMP (CAP), OVER TEMP (AMP),
OVER OUTPUT, OVER DISPLAY, ILLEGAL LRV,
ILLEGAL HRV, ILLEGAL SPAN, and ZERO ADJ OVER
B SENSOR TYPE Sensor type – Menu name
B10 MODEL Model+span – 16 uppercase alphanumerics
B11 STYLE NO. Style number –
B20 LRL Lower range-limit – –32000 to 32000
B21 URL Upper range-limit – –32000 to 32000
B30 MIN SPAN Minimum span – –32000 to 32000
B40 MAX STAT.P. Maximum static pressure*6 – –
B60 SELF CHECK Self-diagnostic messages – Same as A60
C SETTING Setting data – Menu name
C10 TAG. NO. Tag number 16 alphanumerics As specified when
ordered.
C20 PRESS UNIT Measurement range units Selected from mmH2O, As specified when
mmAq, mmWG, mmHg, Torr, ordered.
Pa, hPa, kPa, MPa, mbar, bar,
gf/cm2, kgf/cm2, inH2O, inHg,
ftH2O, psi, or atm
C21 LOW RANGE Measurement range, lower –32000 to 32000(but within As specified when
range value measurement range) ordered.
C22 HIGH RANGE Measurement range, higher –32000 to 32000(but within As specified when
range value measurement range) ordered.
C30 AMP DAMPING Damping time constant Selected from 0.2*2, 0.5, 1.0, 2.0 s
2.0, 4.0, 8.0, 16.0, 32.0, or
64.0 sec.
C40 OUTPUT MODE Output mode and integral Selected from OUT:LIN; DSP: As specified when – –
indicator mode LIN, OUT:LIN; DSP:SQR, ordered.
OUT:SQR; DSP:SQR If not specified, OUT:
LIN; DSP: LIN.
C60 SELF CHECK Self-diagnostic messages – Same as A60
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-6
Applica-
Rewrita- bility
No. Item Description Remarks Default Value
bility
F P L
D AUX SET 1 Auxiliary setting data 1 – Menu name
D10 LOW CUT Low cut 0.0 to 20.0% 10.0%
D11 LOW CUT Low cut mode LINEAR/ZERO LINEAR
MODE
D15 OUT LIMIT(L) Lower output range-limit –5.0 to 110.0% –5.0%*7
D16 OUT LIMIT(H) Upper output range-limit –5.0 to 110.0% 110.0%
D20 DISP SELECT Display selection NORMAL %/USER SET, As specified when
USER & %/INP PRES, PRES ordered.
&%
D21 DISP UNIT Engineering unit for display 8 uppercase alphanumerics
D22 DISP LRV Engineering range, lower –19999 to 19999 As specified when
range value ordered.
D23 DISP HRV Engineering range, higher –19999 to 19999 As specified when
range value ordered.
D30 TEMP UNIT Temperature setting units deg C/deg F deg C
D31 STAT. P. UNIT Static pressure setting units Selected from mmH2O, As specified when –
mmAq, mmWG, mmHg, Torr, ordered. If not
Pa, hPa, kPa, MPa, mbar, bar, specified, MPa.
gf/cm2, kgf/cm2, inH2O, inHg,
ftH2O, psi, or atm
D40 REV OUTPUT Output reversal NORMAL/REVERSE If not specified,
NORMAL.
D45 H/L SWAP Impulse piping accessing NORMAL/REVERSE*4 NORMAL – –
direction
D52 BURN OUT CPU error – HIGH/LOW, –5 to 110%*3 HIGH
D53 ERROR OUT Hardware error HOLD/HIGH/LOW, HIGH
–5 to 110%*3
D60 SELF CHECK Self-diagnostic messages – Same as A60
E AUX SET 2 Auxiliary setting data 2 – Menu name
E10 DFS MODE DFS mode OFF/ON*5 ON –
E14 TEMP SELECT Reference temperature AMP. TEMP/CAP. TEMP*5 CAP. TEMP –
sensor
E15 TEMP ZERO Zero shift conpensation ±10.00*5 0.00 –
setup
E30 BI DIRE MODE Bidirectional mode OFF/ON OFF – –
E50 AUTO Auto-recover from sensor OFF/ON ON
RECOVER error
E60 SELF CHECK Self-diagnostic messages – Same as A60
H AUTO SET Automatic setup – Menu name
H10 AUTO LRV Automatic measurement –32000 to 32000 Displays the same
range lower range value data as C21.
setup
H11 AUTO HRV Automatic measurement –32000 to 32000 Displays the same
range higher range value data as C22.
setup
H60 SELF CHECK Self-diagnostic messages – Same as A60
J ADJUST Adjustment data – Menu name
J10 ZERO ADJ Automatic zero adjustment –5 to 110.0%*3
J11 ZERO DEV. Manual zero adjustment
J15 SPAN ADJ Manual span adjustment –10.00 to 10.00% 0.00%
J20 EXT. ZERO ADJ External zero-adjustment ENABLE/INHIBIT
screw permission
J30 AOUTPUT 4mA 4mA adjustment –10.00 to 10.00% 0.00%
J31 OUTPUT 20mA 20mA adjustment –10.00 to 10.00% 0.00%
J60 ASELF CHECK Self-diagnostic messages – Same as A60
K TEST Tests – Menu name
K10 OUTPUT in % Test output % setting –5 to 110.0%*3 Displays
‘ACTIVE’ while executing
K60 SELF CHECK Self-diagnostic messages – Same as A60
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-7
Applica-
Rewrita- bility
No. Item Description Remarks Default Value
bility
F P L
M MEMO Memo – Menu name
M10 MEMO 1 Memo 8 uppercase alphanumerics
M20 MEMO 2 Memo 8 uppercase alphanumerics
M30 MEMO 3 Memo 8 uppercase alphanumerics
M40 MEMO 4 Memo 8 uppercase alphanumerics
M50 MEMO 5 Memo 8 uppercase alphanumerics
M60 SELF CHECK Self-diagnostic messages – Same as A60
P RECORD History of the errors –
P10 ERROR REC 1 Last error Display the error
P11 ERROR REC 2 One time before Display the error
P12 ERROR REC 3 Two time before Display the error
P13 ERROR REC 4 Three time before Display the error
P60 SELF CHECK Self-diagnostic messages – Same as A60
*1: In case of Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
*2: When Optional code /F1 is specified, substitute the value with 0.1.
*3: When Optional code /F1 is specified, substitute the value –5 with –2.5.
*4: Not applicable for Model EJA115.
*5: Applicable only for Model EJA118W, EJA118N, EJA118Y, EJA438W, and EJA438N.
*6: See MWP(max. working pressure) on the nameplate. B40 shows an approximate value of maximum pressure for the capsule.
*7: Unless otherwise specified by order. When optional code /F1 is specified, substitute the value –5 with –2.5.
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-8
8.3.2 Parameter Usage and Selection
IMPORTANT
Before describing the procedure for setting
parameters, we present the following table showing If the transmitter is turned off within 30 seconds
how the parameters are used and in what case. after parameters have been set, the set data
will not be stored and the terminal returns to
previous settings.
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-9
8.3.3 Setting Parameters SET Set TAG NO. and press the
C10:TAG NO.
Set or change the parameters as necessary. After YOKOGAWA key.
FIC-1a _
completing these, do not fail to use the “DIAG” key
to confirm that “GOOD” is displayed for the self- CODE caps CLE ESC
F0812-1.ai kPa
MPa
mbar
bar
gf/cm2
kgf/cm2
inH2O
inHg
ftH2O
psi
atm
F0813.ai
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-10
b. Setting Calibration Range Lower Range
Value and Higher Range Value • Example 2: With present settings of 0 to
(C21: LOW RANGE, C22: HIGH RANGE) 30 kPa, set the Higher range
value to10 kPa.
These range values are set as specified in the
order before the instrument is shipped. Follow the
SET
C22:HIGH RANGE
Set 10.
30 kPa Press the key twice
procedure below to change the range. + 10
to enter the setting.
• The measurement span is determined by DEL CLR ESC
the high and low range limit values. In this
SET Press the (OK) key.
instrument, changing the low range value also C22:HIGH RANGE
10 kPa
automatically changes the high range value,
keeping the span constant.
FEED NO OK
SET
C20:PRESS UNIT
The higher range value is • Example: Change from 2.0 sec to 4.0 sec.
kPa
C21:LOW RANGE changed while the span remains
SET
0.5 kPa
constant. C30:AMP DAMPING Use the or
C22:HIGH RANGE
2.0 sec
30.5 kPa
DATA DIAG PRNT ESC < 2.0 sec > key to select 4.0 sec.
< 4.0 sec >
< 8.0 sec > Press the key twice
(Span = Higher range value – Lower range value ) < 16.0 sec >
ESC to enter the setting.
F0814.ai
SET
C30:AMP DAMPING Press the (OK) key.
• Note, however, that changing the higher range 4.0 sec
2.0sec
any decimal point) for low or high range limits
within the range of −32000 to 32000. 4.0sec
8.0sec
16.0sec
32.0sec
64.0sec
F0816.ai
Note: The damping time constant set here is the damping time
constant for the amplifier assembly. The damping time
constant for the entire transmitter is the sum of the values
for the amplifier assembly and for the capsule assembly.
For the capsule assembly damping time constant (fixed),
see the “General Specifications” found at the end of this
manual. (See Chapter 10.)
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-11
(4) Output Signal Low Cut Mode Setup (5) Change Output Limits
(D10: LOW CUT, D11: LOW CUT MODE) (D15: OUT LIMIT(L), D16: OUT LIMIT(H))
Low cut mode can be used to stabilize the output The range of normal output is preset at the factory
signal near the zero point. The low cut point can be from −5.0% to 110.0% unless otherwise specified,
set in a range from 0 to 20% of output. (Hysteresis: and the output is limited with these upper and lower
±1%) values. This output range can be changed, for
example, to meet the requirements of NAMUR, etc.
Either “ZERO” as the low cut mode.
within the settable range. Set the lower limit with
Low cut mode “ZERO” D15: OUT LIMIT(L) and upper limit with D16: OUT
(%) LIMIT(H).
50
Settable range: −5.0 to 110.0 (%)
Output
Lower limit < Upper limit
20
(6) Integral Indicator Scale Setup
The following 5 displays are available for integral
0 50 (%)
Input indicators.
F0817.ai
A40:INPUT
FEED NO OK 456 kPa
PARAM
PRES & % Indicates input pressure and %
D10:LOW CUT alternately in 3 second intervals.
20.0 %
D11:LOW CUT MODE
ZERO A10:OUTPUT (%)
D20:DISP SELECT
NORMAL % 45.6 %
DATA DIAG PRNT ESC
A40:INPUT
456 kPa
F0818.ai
F0819.ai
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-12
b. Setting User-set Engineering Unit
% indication and User-set engineering
(D21: DISP UNIT)
input pressure unit display
indication This parameter allows entry of the engineering units
to be displayed on the BT200. When the instrument
D20: DISP SELECT D20: DISP SELECT is shipped, this is set as specified in the order.
NORMAL % USER SET
INP PRES USER & % Follow the procedure below to change this setting.
PRES & %
This parameter need not be set for % display.
Set for user-set
Transmitter is set engineering unit display.
• Example: Set an engineering unit M.
for “% display” when
shipped. SET Set “M.”
D21:DISP UNIT
D21: DISP UNIT
M_ Press the key twice to
Set a unit to be
enter the setting.
displayed on the BT200.
CODE CAPS CLR ESC
FEED NO OK
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-13
c. Lower and Higher Range Value Setup in (8) Unit Setup for Displayed Static Pressure
Engineering Unit (D31: STAT.P.UNIT)
(D22: DISP LRV, D23: DISP HRV)
Follow the procedure below to change the static
These parameter items are used to set the lower pressure units.
and higher range values for the engineering unit
Changing this parameter changes the unit for the
display.
A30: STATIC PRESS (static pressure) display.
When the instrument is shipped, these are set
as specified in the order. Follow the procedure • Example: Change the static pressure unit
below to change these settings. Note that these from kgf/cm2 to MPa.
parameters need not be set for % display. SET Use the or key
D31:STAT.P.UNIT
kgf/cm^2
< MPa > to select MPa.
• Example: Set lower range value (LRV) to –50 < mbar >
< bar > Press the key twice
and higher range value (HRV) to 50. < gf/cm^2 >
ESC
to enter the setting.
Setting LRV mmH2O
mmAq
SET Set “–50.” mmWG
D22:DISP LRV
0M mmHg
- 50 Press the key twice to Torr
kPa
enter the setting. MPa
DEL CLR ESC mbar
bar
gf/cm2
Setting HRV kgf/cm2
SET Set “50.” inH2O
D23:DISP HRV
100M inHg
+ 50 Press the key twice to ftH2O
psi
enter the setting. atm
DEL CLR ESC
F0825.ai
F0823.ai
SET Use the or key
D40:REV OUTPUT
NORMAL
< NORMAL > to select REVERSE.
< REVERSE>
(7) Unit Setup for Displayed Temperature Press the key twice to
(D30: TEMP UNIT) ESC
enter the setting.
When the instrument is shipped, the temperature F0826.ai
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-14
(10) Output Status Display/Setup when a CPU (12) Range Change while Applying Actual
Failure Inputs
(D52: BURN OUT) (H10: AUTO LRV, H11: AUTO HRV)
This parameter displays the status of 4 to 20 mA This feature allows the lower and higher range
DC output if a CPU failure occurs. In case of a values to be set up automatically with the actual
failure, communication is disabled. input applied. If the lower and higher range values
are set, C21: LOW RANGE and C22: HIGH
Setting of HIGH or LOW is enabled. This is done
RANGE are changed at this same time.
with the pin (CN4) on the CPU assembly. See
Chapter 3 for details. Follow the procedure in the figure below.
The measurement span is determined by the higher
Standard specifications
and lower range values. Changing the lower range
The parameter is set to HIGH. If a failure, the value results in the higher range value changing
transmitter outputs the signal of 110% or higher. auto-matically, keeping the span constant.
The parameter D53: ERROR OUT is set to HIGH
from the factory. • Example 1: When changing the lower range
value to 0.5 kPa for the present
Optional code/C1
setting of 0 to 30 kPa, take the
The parameter is set to LOW. If a failure, output following action with input pressure
which is −5% or lower is generated. The parameter of 0.5 kPa applied.
D53: ERROR OUT is set to LOW from the factory.
SET Press the key twice.
H10:AUTO LRV
0 kPa
• Example: Standard specifications + 0 The lower range value is
F0827.ai PARAM
H10:AUTO LRV
The higher range value is
0.5000 kPa
H11:AUTO HRV changed keeping the span
(11) Output Status Setup when a Hardware 30.500 kPa
H60:SELF CHEC constant.
Error Occurs GOOD
DATA DIAG PRNT ESC
Parameters C21 and C22 are
(D53: ERROR OUT)
changed at the same time.
This parameter allows the setting of the output F0829.ai
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-15
(a) Follow the procedure below when setting the
• Example 2: When the higher range value is to
present output to 0% (4 mA).
be changed to 10 kPa with the
present setting of 0 to 30 kPa, take Output is 0.5%.
A10:OUTPUT (%)
the following action with an input 0.5 %
FEED NO OK
FEED NO OK
PARAM The lower range value is not A10:OUTPUT (%) Output is 0%.
H10:AUTO LRV 0.0 %
0 kPa
H11:AUTO HRV changed, so the span changes.
10.000 kPa
H60:SELF CHECK Parameter C22 is changed at the F0831.ai
GOOD
DATA DIAG PRNT ESC
same time. (b) In tank level measurement, if the actual level
F0830.ai cannot be brought to zero for zero adjustment,
then the output can be adjusted to correspond
(13) Zero Point Adjustment to the actual level obtained using another
(J10: ZERO ADJ, J11: ZERO DEV, J20: EXT measuring instrument such as a glass gauge.
ZERO ADJ)
Present level: 45%
The DPharp supports several adjustment methods. Present output: 41%
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-16
(b)-2 Follow the procedure below to use J11: • Zero point adjustment using external zero-
ZERO DEV. adjustment screw on the transmitter
A10:OUTPUT (%)
Present output is 41.0%. Turn the zero-adjustment screw on the outside of
41.0 %
Output error = 45.0 – 41.0 = 4.0%. the transmitter case using a slotted screwdriver.
Turn the screw to the right to increase the zero point
SET Since “J11: ZERO DEV.” contains
J11:ZERO DEV.
2.50 %
or to the left to decrease the zero output; the zero
0 the previous correction, obtain the adjusts in increments of 0.01% of the range setting.
correction value by adding 4.0% Note that the amount of adjustment to the zero point
ESC
to it. (2.50% + 4.0% = 6.50%) changes according to the speed at which the screw
is turned. To make fine adjustments, turn the screw
SET Set the correction value, 6.50.
J11:ZERO DEV.
2.50 % slowly; to make coarse adjustments, turn the screw
6.50 Press the key twice.
quickly.
ECS Note: When a zero point adjustment has been made, do not turn
off the transmitter less than 30 seconds after adjustment.
A10:OUTPUT (%) The output is changed to 45%.
45.0 % (14) Span Adjustment
F0834.ai Each DPharp EJA series transmitter is factory
When the zero point is adjusted, the displayed characterized according to the specification.
value of A40 is as follows. Mounting position effects or zero shifts caused by
static pressure are typically compensated by a zero
[Example] adjustment.
When the zero point is shifted by 20 kPa for the A span adjustment is a function to correct the slope
actual pressure, the parameter of A40 indicates 50 error from a zero point in characterizing 100% point
kPa. (HRV). This function can be used when span drifts
may be caused or characterization to the specific
pressure standard is required.
70 kPa
Therefore, the zero point adjustment should always
50 kPa
be performed before the upper point adjustment in
order to maintain the pitch between zero and 100%
Zero
20 kPa adjustment points within the calibration range.
Zero adjustment
volume(J11)
0 kPa 0 kPa You can manually perform the trimming procedure
Actual differential Input value
pressure/pressure of A40
by using J15: SPAN ADJ.
F0835.ai
• Span adjustment value
(c) Zero Point Adjustment Using the External Zero The span adjustment value is calculated as
Adjustment Screw follows.
• Enabling/inhibiting of zero point adjustment
P – A40 ×100
using the external zero-adjustment screw on Span adjustment value (%) = 1
P1
the transmitter (J20: EXT ZERO ADJ)
P1: Actual differential pressure/pressure value
Follow the procedure below to enable or inhibit zero A40: Input (indicated as the value after zeroing)
point adjustment from the zero-adjustment screw
Measurement pressure
on the transmitter.
This is set to “ENABLE” when the instrument is
shipped. A40
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-17
F0839.ai
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-18
8.4 Displaying Data Using the 8.5 Self-Diagnostics
BT200 8.5.1 Checking for Problems
8.4.1 Displaying Measured Data
(1) Identifying Problems with BT200
The BT200 can be used to display measured data.
The following four areas can be checked.
The measured data is updated automatically every
(a) Whether connections are good.
7 seconds. In addition, the display can be updated
(b) Whether BT200 was properly operated.
to the present data value at any time by pressing
(c) Whether settings were properly entered.
the [F1] (DATA) key. For parameters associated
(d) History of the errors.
with the display of measured data, see Subsection
See examples below.
8.3.1, “Parameter Summary.”
• Example 1: Connection errors
• Example: Display output.
--WELCOME--
BRAIN TERMINAL
Press the key.
MENU
A:DISPLAY ID: BT200
B:SENSOR TYPE
When the panel shown on the left
check connection
push ENTER key appears, press the key.
UTIL FEED
HOME SET ADJ ESC
Since communications will be
PARAM
A10:OUTPUT (%)
Display “A10: OUTPUT (%).”
XX.X % communication error unsuccessful if there is a problem
A11:ENGR.OUTPUT
YY.Y % in the connection to the BT200,
A20:AMP TEMP
ZZ deg C ESC the display at the left will appear.
DATA DIAG PRNT ESC
Data is updated automatically
Recheck the connection.
PARAM communi
at 7-second intervals.
A10:OUTPUT (%) Press the (OK) key.
A11:ENGR.OUTPUT
F0843.ai
A20:AMP TEMP
F0844.ai
PARAM
B10:MODEL For the associated
EJA210A-DM parameters, see
B11:STYLE NO.
S1.01 Subsection 8.3.1,
B20:LRL Parameter Summary.
- 98.07 kPa
DATA DIAG PRNT ESC
F0842.ai
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-19
(2) Checking with Integral Indicator
• Example 3: Checking the history of the errors
MENU
J:ADJUST
Connect the BT200 to the NOTE
K:TEST
M:MEMO
transmitter, and call item “P.”
P:RECORD If an error is detected in the self-diagnostic,
HOME SET ADJ ESC
an error number is displayed on the integral
indicator. If there is more than one error, the error
PARAM
P10:ERROR REC 1 number changes at two-second intervals. See
ERROR
P11:ERROR REC 2
ERROR
Table 8.2 regarding the error numbers.
P12:ERROR REC 3
GOOD
DATA DIAG PRNT ESC
<
ERROR
ERROR >
press the key to
< ILLEGAL LRV > display the error message.
< ILLEGAL HRV >
ESC
IM 01C21C01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-20
8.5.2 Errors and Countermeasures
The table below shows a summary of error messages.
Table 8.2 Error Message Summary
Integral
Output Operation during
Indicator BT200 Display Cause Countermeasure
Error
Display
None GOOD
--- ERROR
Er.01 CAP MODULE FAULT Capsule problem.*1 Outputs the signal (Hold, Replace the capsule when
High, or Low) set with error keeps appearing even
parameter D53. after restart.*2
Er.02 AMP MODULE FAULT Amplifier problem. Outputs the signal (Hold, Replace amplifier.
High, or Low) set with
parameter D53.
Er.03 OUT OF RANGE Input is outside Outputs high range limit Check input.
measurement range value or low range limit
limit of capsule. value.
Er.04 OUT OF SP RANGE Static pressure exceeds Displays present output. Check line pressure (static
specified range.*3 pressure).
Er.05 OVER TEMP (CAP) Capsule temperature is Displays present output. Use heat insulation or make
outside range lagging to keep temperature
(–50 to 130°C). within range.
Er.06 OVER TEMP (AMP) Amplifier temperature is Displays present output. Use heat insulation or make
outside range lagging to keep temperature
(–50 to 95°C). within range.
Er.07 OVER OUTPUT Output is outside high or Outputs high or low range Check input and range
low range limit value. limit value. setting, and change them as
needed.
Er.08 OVER DISPLAY Displayed value is Displays high or low range Check input and display
outside high or low limit value. conditions and modify them
range limit value. as needed.
Er.09 ILLEGAL LRV LRV is outside setting Holds output immediately Check LRV and modify as
range. before error occurrence. needed.
Er.10 ILLEGAL HRV HRV is outside setting Holds output immediately Check HRV and modify as
range. before error occurrence. needed.
Er.11 ILLEGAL SPAN SPAN is outside setting Holds output immediately Check SPAN and change as
range. before error occurrence. needed.
Er.12 ZERO ADJ OVER Zero adjustment is too Displays present output. Readjust zero point
large.
*1: This error code appears at a capsule problem or when an illegal overpressure is applied to the pressure sensor.
*2: If the normal pressure is regained, the Er.01 will disappear according to the setting of the parameter of E50: AUTO RECOVER.
When the E50: AUTO RECOVER is set to ON(defalut setting), the Er.01 will disappear automatically. When the E50: AUTO
RECOVER is set to OFF, restart the transmitter to cancel Er.01. If no error code appears then, perform necessary adjustment such
as zero-adjustment to continue the operation. If the error code still exists, replace the capsule assembly.
*3: For Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
IM 01C21C01-01E
<9. Maintenance> 9-1
9. Maintenance
9.1 Overview 9.2 Calibration Instruments
Selection
WARNING Table 9.1 shows the instruments required for
Since the accumulated process fluid may be calibration. Select instruments that will enable
toxic or otherwise harmful, take appropriate care the transmitter to be calibrated or adjusted to the
to avoid contact with the body, or inhalation of required accuracy.
vapors during draining condensate or venting The calibration instruments should be handled
gas in transmitter pressure-detector section and carefully so as to maintain the specified accuracy.
even after dismounting the instrument from the
process line for maintenance.
9.3 Calibration
Maintenance of the transmitter is easy due to its Use the procedure below to check instrument
modular construction. This chapter describes the operation and accuracy during periodic
procedures for calibration, adjustment, and the maintenance or troubleshooting.
disassembly and reassembly procedures required
1) Connect the instruments as shown in Figure 9.1
for component replacement.
and warm up the instruments for at least five
Since the transmitters are precision instruments, minutes.
carefully and thoroughly read the following sections
for proper handling during maintenance.
IMPORTANT
• To adjust the transmitter for highest
IMPORTANT accuracy, make adjustments with the
power supply voltage and load resistance
• As a rule, maintenance of this transmitter
including leadwire resistances set close to
should be implemented in a maintenance
the conditions under which the transmitter is
service shop where the necessary tools are
installed.
provided.
• If the measurement range 0% point is
• The CPU assembly contains sensitive parts
0 kPa or shifted in the positive direction
that may be damaged by static electricity.
(suppressed zero), the reference pressure
Exercise care so as not to directly touch
should be applied as shown in the figure
the electronic parts or circuit patterns on
(low pressure side open to atmosphere). If
the board, for example, by preventing static
the measurement range 0% point is shifted
electrification by using grounded wrist straps
in the negative direction (elevated zero), the
when handling the assembly. Also take
reference pressure should be applied on the
precautions such as placing a removed
low pressure side (high pressure side open
CPU assembly into a bag with an antistatic
to atmosphere).
coating.
• Do not perform the calibration procedures
until the transmitter is at room temperature.
IM 01C21C01-01E
<9. Maintenance> 9-2
Table 9.1 Instruments Required for Calibration
Name Yokogawa-recommended Instrument Remarks
Power supply Model SDBT or SDBS distributor 4 to 20 mA DC signal
Load resistor Model 2792 standard resistor [250 Ω ±0.005%, 3 W]
Load adjustment resistor [100 Ω ±1%, 1 W]
Voltmeter Model 2501 A digital multimeter
Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)
Digital Model MT220 precision digital manometer Select a manometer having a
manometer 1) For 10 kPa class pressure range close to that of
Accuracy: ± (0.015% of rdg + 0.015% of F.S.) · · for 0 to 10 kPa the transmitter.
± (0.2% of rdg + 0.1% of F.S.) · · · · · · for −10 to 0 kPa
2) For 130 kPa class
Accuracy: ± 0.02% of rdg · · · · · · · · · · · · · · · · · · for 25 to 130 kPa
± 5 digits · · · · · · · · · · · · · · · · · · · · · · · for 0 to 25 kPa
± (0.2% of rdg + 0.1% of F.S.) · · · · · · for −80 to 0 kPa
3) For 700 kPa class
Accuracy: ± (0.02% of rdg + 3 digits) · · · · · · · · · for 100 to 700 kPa
± 5 digits · · · · · · · · · · · · · · · · · · · · · · · for 0 to 100 kPa
± (0.2% of rdg + 0.1% of F.S.) · · · · · · for −80 to 0 kPa
4) For 3000 kPa class
Accuracy: ± (0.02% of rdg + 10 digits) · · · · · · · · for 0 to 3000 kPa
± (0.2% of rdg + 0.1% of F.S.) · · · · · · for −80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ± (0.03% of rdg + 6 digits) · · · · · · · · · for 0 to 130 kPa abs
Pressure Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, Requires air pressure supply.
generator 25 kPa {2500 mmH2O}
Accuracy: ± 0.05% of F.S.
Dead weight gauge tester 25 kPa {2500 mmH2O} Select the one having a
Accuracy: ±0.03% of setting pressure range close to that of
the transmitter.
Pressure Model 6919 pressure regulator (pressure pump) Prepare the vacuum pump for
source Pressure range: 0 to 133 kPa {1000 mmHg} negative pressure ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
level, there are difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa representatives
from which the instrument was purchased or the nearest Yokogawa office.
Terminal box
Power
Load resistance, 250Ω supply
E
Rc R (Note) For Model EJA220A transmitter
Load adjusting (diaphragm-extended type), prepare a
resistance, 100Ω V mating calibration flange to match
the diaphragm extension length and
Digital voltmeter outer diameter.
Model MT220
Model 7674 precision Mating (Note)
pneumatic digital manometer calibration
pressure standards flange
Supply pressure P P
Pressure source
Reference pressure
F0901.ai
IM 01C21C01-01E
<9. Maintenance> 9-3
9.4 Disassembly and
Reassembly
This section describes procedures for disassembly
and reassembly for maintenance and component Shrouding Bolt
replacement.
Shrouding Bolt
Always turn OFF power and shut off and release
pressures before disassembly. Use proper tools for F0902.ai
all operations. Table 9.2 shows the tools required. Figure 9.2 Shrouding Bolts
Table 9.2 Tools for Disassembly and Reassembly
Tool Quantity Remarks 9.4.1 Replacing the Integral Indicator
Phillips 1 JIS B4633, No. 2
screwdriver
Slotted 1
CAUTION
screwdriver
Cautions for Flameproof Type Transmitters
Allen wrenches 2 JIS B4648
One each, nominal 3 and
Users are prohibited by law from modifying the
5 mm Allen wrenches construction of a flameproof type transmitter.
Wrench 1 Width across flats, 17 mm This would invalidate the agency approval and
Torque wrench 1 the transmitter’s use in such rated area.
Adjustable 1 Thus the user is prohibited from using a
wrench flameproof type transmitter with its integral
Socket wrench 1 Width across flats, 16 mm indicator removed, or from adding an integral
Socket driver 1 Width across flats, 5.5 mm
indicator to a transmitter. If such modification is
Tweezers 1
absolutely required, contact Yokogawa.
IM 01C21C01-01E
<9. Maintenance> 9-4
Attaching the Integral Indicator 3) Disconnect the output terminal cable (cable
Integral indicator can be installed in the following with brown connector at the end). When doing
three directions. this, lightly press the side of the CPU assembly
connector and pull the cable connector to
disengage.
4) Use a socket driver (width across flats, 5.5mm)
to loosen the two bosses.
5) Carefully pull the CPU assembly straight
forward to remove it.
F0903.ai
6) Disconnect the flat cable (cable with black
Figure 9.3 Installation Direction of Indicator connector at the end) that connects the CPU
assembly and the capsule.
1) Align both the LCD board assembly and CPU
assembly connectors and engage them. NOTE
2) Insert and tighten the two mounting screws.
Be careful not to apply excessive force to the
3) Replace the cover.
CPU assembly when removing it.
Output terminal cable
Mounting the CPU Assembly
1) Connect the flat cable (with black connector)
Press between the CPU assembly and the capsule.
forward
2) Connect the output terminal cable (with brown
connector).
LCD board
assembly
Integral
NOTE
indicator
Make certain that the cables are free of pinching
Boss Zero-adjustment between the case and the CPU assembly edge.
Flat cable screw pin
Mounting CPU assembly 3) Align and engage the zero-adjustment screw
screw
Bracket
pin with the groove on the bracket on the CPU
Cover
(for zero-adjustment assembly. Then insert the CPU board assembly
screw pin)
F0904.ai straight onto the post in the amplifier case.
Figure 9.4 Removing and Attaching LCD Board 4) Tighten the two bosses. If the transmitter is
Assembly and CPU Assembly
equipped with an integral indicator, refer to
Subsection 9.4.1 to mount the indicator.
9.4.2 Replacing the CPU Board Assembly
This subsection describes the procedure for NOTE
replacing the CPU assembly. (See Figure 9.4) Confirm that the zero-adjustment screw pin is
placed properly in the groove on the bracket prior
Removing the CPU Assembly
to tightening the two bosses. If it is not, the zero-
1) Remove the cover. If an integral indicator is adjustment mechanism will be damaged.
mounted, refer to Subsection 9.4.1 and remove
the indicator. 5) Replace the cover.
2) Turn the zero-adjustment screw to the position
(where the screw head slot is horizontal) as
shown in Figure 9.4.
IM 01C21C01-01E
<9. Maintenance> 9-5
9.4.3 Replacing the Process Connector 9.5.1 Basic Troubleshooting
Gaskets
First determine whether the process variable
This subsection describes the procedure for is actually abnormal or a problem exists in the
replacing the process connector gasket. (See measurement system.
Figure 9.5.)
If the problem is in the measurement system,
1) Loosen the two bolts and remove the process isolate the problem and decide what corrective
connector. action to take.
2) Replace the process connector gasket.
This transmitter is equipped with a self-diagnostic
3) Mount the process connector. Tighten the bolts
function which will be useful in troubleshooting; see
securely and uniformly to a torque of 39 to 49
Section 8.5 for information on using this function.
N·m{4 to 5 kgf·m}, and verify that there are no
pressure leaks. : Areas where self-diagnostic offers support
Process connector
gasket Inspect the NO
Measurement system problem
process system.
Process connector
YES Does problem exist in
F0905.ai
receiving instrument?
Figure 9.5 Replacing the Process Connector
Gasket
NO
Inspect receiver.
9.5 Troubleshooting
Environmental conditions Transmitter itself
If any abnormality appears in the measured values,
use the troubleshooting flow chart below to isolate
and remedy the problem. Since some problems Check/correct
Check transmitter.
environmental conditions.
have complex causes, these flow charts may
Operating conditions
not identify all. If you have difficulty isolating or
correcting a problem, contact Yokogawa service
personnel. Check/correct operating
conditions.
F0906.ai
IM 01C21C01-01E
<9. Maintenance> 9-6
9.5.2 Troubleshooting Flow Charts Output travels beyond 0% or 100%.
Is power supply NO
polarity correct? NO
Are valves opened or
closed correctly?
YES
Refer to Section 6.3 to check/correct
polarity at each terminal from power
YES Fully open the low pressure valve.
supply to the terminal box.
Are power
NO
supply voltage and load
resistance correct? YES
Is there any pressure leak?
Is there
continuity through the NO
transmitter loop wiring?
Do the loop numbers
match?
IM 01C21C01-01E
<9. Maintenance> 9-7
Is impulse piping NO
connected correctly?
Is transmitter
installed where there is YES
marked variation in
temperature?
Were appropriate NO
instruments used for
calibration?
NO
Is output adjusted correctly?
IM 01C21C01-01E
<10. General Specifications> 10-1
IM 01C21C01-01E
<10. General Specifications> 10-2
Communication Requirements “◊”: Housing;
BRAIN Low copper cast-aluminum alloy with
Communication Distance; polyurethane paint (Munsell 0.6GY3.1/2.0)
Up to 2 km (1.25 miles) when using CEV Degrees of Protection
polyethylene-insulated PVC-sheathed IP67, NEMA4X
cables. Cover O-rings;
Communication distance varies depending Buna-N, Fluoro-rubber (option)
on type of cable used. Data plate and tag;
Load Capacitance; SUS304 or SUS316(optional)
0.22 μF or less (see note) Fill Fluid;
Load Inductance; Silicone or Fluorinated oil (optional)
3.3 mH or less (see note) Weight:
Input Impedance of communicating device; EJA210A with 150# flange 11 kg(25 lb)
10 kΩ or more at 2.4 kHz. EJA220A with 150# flange 16 kg(35 lb)
Note: For general-use and Flameproof type. For Connections:
Intrinsically safe type, please refer to ‘Optional
Specifications.’ Refer to the ‘Model and Suffix Codes’ to
specify the process and electrical connection
HART
type.
Communication Distance;
The high pressure side is a flange
Up to 1.5 km (1 mile) when using multiple
connected, and low side is threaded.
twisted pair cables. Communication distance
varies depending on type of cable used. Atmospheric
100{14.5} pressure
Use the following formula to determine cable
length for specific applications: Working
pressure
65 x 106 (Cf + 10,000) kPa abs
L= − {psi abs}
(R x C) C Applicable range
Where: 10{1.4}
Model EJA210A
Model Suffix Codes Description
EJA210A .............................. Flange-mounted differential pressure transmitter
(Flush diaphragm type)
Output -D . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
Signal -E . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol, see IM 01C22T01-01E)
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol, see IM 01C22T02-01E)
-G . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, see 01C22T03-00E)
Measurement M . . . . . . . . . . . . . . . . . . . . . . . . . 1 to 100 kPa {100 to 10000 mmH2O}
span (capsule) H . . . . . . . . . . . . . . . . . . . . . . . . . 5 to 500 kPa {0.05 to 5 kgf/cm2}
High pressure [Diaphragm] [Others]
side (Process S*2 . . . . . . . . . . . . . . . . . . . . . . SUS316L SUS316
flange side) H*2 . . . . . . . . . . . . . . . . . . . . . . Hastelloy C-276 Hastelloy C-276
Wetted parts T*2 . . . . . . . . . . . . . . . . . . . . . . Tantalum Tantalum
material *1 W*3 . . . . . . . . . . . . . . . . . . . . . Hastelloy C-276 SUS316
Process flange rating J1 . . . . . . . . . . . . . . . . . . . JIS10K
J2 . . . . . . . . . . . . . . . . . . . JIS20K
A1 . . . . . . . . . . . . . . . . . . . ANSI Class 150
A2 . . . . . . . . . . . . . . . . . . . ANSI Class 300
P1 . . . . . . . . . . . . . . . . . . . JPI Class150
P2 . . . . . . . . . . . . . . . . . . . JPI Class 300
D2 . . . . . . . . . . . . . . . . . . . DIN PN10/16
D4 . . . . . . . . . . . . . . . . . . . DIN PN25/40
Process flange D . . . . . . . . . . . . . . . . . 3-inch (80 mm) /S25C
size/material E . . . . . . . . . . . . . . . . . 3-inch (80 mm) /SUS304
F . . . . . . . . . . . . . . . . . 3-inch (80 mm) /SUS316
A . . . . . . . . . . . . . . . . . 2-inch (50 mm) /SU25C
B . . . . . . . . . . . . . . . . . 2-inch (50 mm) /SUS304
C . . . . . . . . . . . . . . . . . 2-inch (50 mm) /SUS316
Low pressure side process 0 . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
connection 1 . . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . with 1/2 NPT female process connector
5 . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts material A . . . . . . . . . . . . SCM435
B . . . . . . . . . . . . SUS630
C . . . . . . . . . . . . SUH660
Installation -9 . . . . . . . . . Horizontal impulse piping type, left side high pressure
Electrical connection 0 . . . . . . . G1/2 female, one electrical connection
2 . . . . . . . 1/2 NPT female, two electrical connections without blind plug
3 . . . . . . . Pg 13.5 female, two electrical connections without blind plug
4 . . . . . . . M20 female, two electrical connections without blind plug
5 . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
8 . . . . . . . Pg 13.5 female, two electrical connections and a blind plug
9 . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . G1/2 female, two electrical connections and a SUS316 blind plug
C . . . . . . . 1/2 NPT female, two electrical connections and a SUS316 blind plug
D . . . . . . . M20 female, two electrical connections and a SUS316 blind plug
Integral indicator D . . . Digital indicator
E . . . Digital indicator with the range setting switch
N . . . (None)
— N Always N
Optional codes / Optional specification
Example: EJA210A-DMSA1D5A-92NN/
*1: Low pressure side wetted parts material: Cover flange; SCS14A, Process connector; SCS14A, Capsule; SUS316L (Diaphragm;
Hastelloy C-276), Vent plug; SUS316
*2: Applicable only for 3-inch (80 mm) flange size (Process flange size/material codes D and E)
*3: Applicable only for 2-inch (50 mm) flange size (Process flange size/material codes A and B)
IM 01C21C01-01E
<10. General Specifications> 10-4
Model EJA220A
Model Suffix Codes Description
EJA220A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flange-mounted differential pressure transmitter
(Extended diaphragm type)
Output -D . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
Signal -E . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol, see IM 01C22T01-01E)
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol, see IM 01C22T02-01E)
-G . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, see 01C22T03-00E)
Measurement M . . . . . . . . . . . . . . . . . . . . . . . . . 1 to 100 kPa {100 to 10000 mmH2O}
span (capsule) H . . . . . . . . . . . . . . . . . . . . . . . . . 5 to 500 kPa {0.05 to 5 kgf/cm2}
High pressure [Diaphragm] [Pipe] [Others]
side (Process S*2 . . . . . . . . . . . . . . . . . . . . . . SUS316L SUS316 SUS316
flange side) W*3 . . . . . . . . . . . . . . . . . . . . . Hastelloy C-276 SUS316 SUS316
Wetted parts
material *1
Process flange rating J1 . . . . . . . . . . . . . . . . . . JIS10K
J2 . . . . . . . . . . . . . . . . . . JIS20K
A1 . . . . . . . . . . . . . . . . . . ANSI Class 150
A2 . . . . . . . . . . . . . . . . . . ANSI Class 300
P1 . . . . . . . . . . . . . . . . . . JPI Class150
P2 . . . . . . . . . . . . . . . . . . JPI Class 300
D2 . . . . . . . . . . . . . . . . . . DIN PN10/16
D4 . . . . . . . . . . . . . . . . . . DIN PN25/40
Diaphragm extension 2 . . . . . . . . . . . . . . . . . X2=50 mm
length (X2) 4 . . . . . . . . . . . . . . . . . X2=100 mm
6 . . . . . . . . . . . . . . . . . X2=150 mm
Process flange G . . . . . . . . . . . . . . . 4-inch (100 mm) / S25C
size/material H . . . . . . . . . . . . . . . 4-inch (100 mm) / SUS304
J . . . . . . . . . . . . . . . 4-inch (100 mm) / SUS316
D . . . . . . . . . . . . . . . 3-inch (80 mm) / S25C
E . . . . . . . . . . . . . . . 3-inch (80 mm) / SUS304
F . . . . . . . . . . . . . . . 3-inch (80 mm) / SUS316
Low pressure side process 0 . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
connection 1 . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . with 1/2 NPT female process connector
5 . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts material A . . . . . . . . . SCM435
B . . . . . . . . . SUS630
C . . . . . . . . . SUH660
Installation -9 . . . . . . . Horizontal impulse piping type, left side high pressure
Electrical connection 0 . . . . . . G1/2 female, one electrical connection
2 . . . . . . 1/2 NPT female, two electrical connections without blind plug
3 . . . . . . Pg 13.5 female, two electrical connections without blind plug
4 . . . . . . M20 female, two electrical connections without blind plug
5 . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . 1/2 NPT female, two electrical connections and a blind plug
8 . . . . . . Pg 13.5 female, two electrical connections and a blind plug
9 . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . G1/2 female, two electrical connections and a SUS316 blind plug
C . . . . . . 1/2 NPT female, two electrical connections and a SUS316 blind plug
D . . . . . . M20 female, two electrical connections and a SUS316 blind plug
Integral indicator D . . . Digital indicator
E . . . Digital indicator with the range setting switch
N . . . (None)
— N.. Always N
Optional codes / Optional specification
Example: EJA220A-DMSA12G5A-92NN/
*1: Low pressure side wetted parts material: Cover flange; SCS14A, Process connector; SCS14A, Capsule; SUS316L (Diaphragm,
Hastelloy C-276), Vent plug ; SUS316
*2: Applicable only for 4-inch (100 mm) flange size (Process flange size/material codes G and H).
*3: Applicable only for 3-inch (80 mm) flange size (Process flange size/material codes D and E).
IM 01C21C01-01E
<10. General Specifications> 10-5
10.3 Optional Specifications
For FOUNDATION Fieldbus explosion protected type, see IM 01C22T02-01E.
For PROFIBUS PA explosion protected type, see IM 01C22T03-00E.
Item Description Code
FM Explosionproof Approval *1
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
FF1
Hazardous (classified) locations, indoors and outdoors (NEMA 4X)
Temperature class: T6
Amb. Temp.: –40 to 60°C (–40 to 140°F)
FM Intrinsically safe Approval *1
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1 Hazardous Locations.
Factory Mutual (FM)
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
Groups E, F & G, and Class III, Division 1 Hazardous Locations.
Enclosure: “NEMA 4X”, Temp. Class: T4, Amb. Temp.: –40 to 60°C (–40 to 140°F) FS1
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 µH
[Groups C, D, E, F and G]
Vmax=30 V, Imax=225 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 µH
Combined FF1 and FS1 *1 FU1
ATEX Flameproof Approval *2
Certificate: KEMA 02ATEX2148
II 2G Exd IIC T4, T5, T6 KF21
Amb. Temp.: T5; –40 to 80°C (–40 to 176°F), T4 and T6; –40 to 75°C (–40 to 167°F)
ATEX Max. process Temp.: T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F)
ATEX Intrinsically safe Approval *2
Certificate: KEMA 02ATEX1030X
KS2
II 1G EEx ia IIC T4, Amb. Temp.: –40 to 60°C (–40 to 140°F)
Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 µH
CSA Explosionproof Approval *1
Certificate: 1089598
Explosionproof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
Division2 ‘SEALS NOT REQUIRED’ , Temp. Class: T4, T5, T6 Encl Type 4x
Max. Process Temp.: T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F) CF1
Amb. Temp.: –40 to 80°C (–40 to 176°F)
Process Sealing Certification
Dual seal certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required. Primary seal failure annunciation : at the zero
adjustment screw
Canadian Standards
CSA Intrinsically safe Approval *1
Association (CSA)
Certificate: 1053843
Intrinsically Safe for Class I, Groups A, B, C and D Class II and III, Groups E, F and G
Nonincendive for Class I, Division 2, Groups A, B, C and D Class II, Division 2,
Groups F and G and Class III (not use Safety Barrier)
Encl Type 4x, Temp. Class: T4, Amb. Temp.: –40 to 60°C (–40 to 140°F) CS1
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 µH
Process Sealing Certification
Dual seal certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required. Primary seal failure annunciation : at the zero
adjustment screw
Combined CF1 and CS1 *1 CU1
IM 01C21C01-01E
<10. General Specifications> 10-6
Item Description Code
IECEx Intrinsically safe, type n and Flameproof Approval *3
Intrinsically safe and type n
Certificate: IECEx KEM 06.0007X
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP67
Amb. Temp.: –40 to 60°C (–40 to 140°F), Max. Process Temp.: 120°C (248°F)
Electrical Parameters:
[Ex ia] Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 µH
IECEx Scheme SU2
[Ex nL] Ui=30 V, Ci=22.5 nF, Li=730 µH
Flameproof
Certificate: IECEx KEM 06.0005
Ex d IIC T6...T4 Enclosure: IP67
Max.Process Temp.: T4;120°C (248°F), T5;100°C (212°F), T6; 85°C (185°F)
Amb.Temp.: –40 to 75°C (–40 to 167°F) for T4, –40 to 80°C (–40 to 176°F) for T5,
–40 to 75°C (–40 to 167°F) for T6
*1: Applicable for Electrical connection code 2 and 7 (1/2 NPT female).
*2: Applicable for Electrical connection code 2, 4, 7 and 9 (1/2 NPT and M20 female).
*3: Applicable for Electrical connection code 2, 4 and 7 (1/2 NPT and M20 female).
IM 01C21C01-01E
<10. General Specifications> 10-7
Item Description Code
Amplifier cover only P
Color change
Painting Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Epoxy resin-baked coating X1
Exterior parts on the amprifier housing (name plates, tag plate, zero-adjustment
316 SST exterior parts HC
screw, stopper screw) will become 316 or 316L SST.
Fluoro-rubber O-ring All O-rings of amplifier housing. Lower limit of ambient temperature : –15 °C (5 °F) HE
Transmitter power supply voltag: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically
safe type, 9 to 32 V DC for FOUNDATION Fieldbus and PROFIBUS PA communication
Lightning protector A
type.)
Allowable current: Max. 6000 A (1×40 µs), Repeating 1000 A (1×40 µs), 100 times
Degrease cleansing treatment K1
Oil-prohibited use Degrease cleansing treatment with fluorinated oil filled capsule.
K2
Operating temperature –20 to 80 °C
Degrease cleansing and dehydrating treatment K5
Oil-prohibited use with
dehydrating treatment Degrease cleansing and dehydrating treatment with fluorinated oil filled capsule.
K6
Operating temperature –20 to 80 °C
P calibration (psi unit ) D1
(See Table for Span and Range
Calibration units bar calibration (bar unit ) D3
Limits.)
M calibration (kgf/cm2 unit ) D4
Sealing treatment to Sealant (liquid silicone rubber) is coated on SUS630 cover flange mounting nuts
Y
SUS630 nuts against stress corrosion cracking.
No serration No serration work on the flange gasket surface ( for ANSI flange only ) Q
With FEP film and fluorinated oil.
Teflon film Working range: 20 to 120 °C, 0 to 2 MPa {0 to 20 kgf/cm2} T
(Not usable under vacuum )
Fast response *2 Update time: 0.125 sec or less, see GS for response time F1
Failure alarm
Output status at CPU failure and hardware error is –5%, 3.2 mA or less. C1
down-scale *1
Failure alarm down-scale: output status at CPU failure and
C2
NAMUR NE43 Output signal limits: hardware error is –5%, 3.2 mA or less.
compliant *1 3.8 mA to 20.5 mA Failure alarm up-scale: output status at CPU failure and
C3
hardware error is 110%, 21.6 mA or more.
Data configuration at
Description into “Descriptor” parameter of HART protocol CA
factory
Stainless steel amplifier Amplifier housing material: SCS14A stainless steel
E1
housing (equivalent to SUS316 cast stainless steel or ASTM CF-8M)
Gold-plate Gold-plated diaphragm for high pressure side (process flange side) A1
Stainless steel tag plate SUS 304 stainless steel tag plate wired onto transmitter N4
High pressure side: Process flange, Block
M03
Low pressure side: Cover flange For model
High pressure side: Process flange, Block EJA210A
M13
Low pressure side: Cover flange, Process connector
Mill Certificate
High pressure side: Process flange, Block, Pipe, Base
M04
Low pressure side: Cover flange For model
High pressure side: Process flange, Block, Pipe, Base EJA220A
M14
Low pressure side: Cover flange, Process connector
( Flange rating ) ( Test Pressure )
JIS 10K 2 MPa {20 kgf/cm2 } T31
Pressure test/Leak test JIS 20K 5 MPa {50 kgf/cm2 } T32
Certificate Nitrogen(N2) Gas
ANSI/JPI class 150 3 MPa {29.8 kgf/cm2 } T36
Retention time: 10 minutes
ANSI/JPI class 300 7.7 MPa {77 kgf/cm2 } T37
ANSI/JPI class 300 7 MPa {70 kgf/cm2 } T38
*1: Applicable for Output signal code D and E. The hardware error indicates faulty amplifier or capsule. When combining with Optional
code F1, output status for down-scale is –2.5%, 3.6 mA DC or less.
* 2: Applicable for Output signal code D and E. Write protection switch is attached for Output code E.
IM 01C21C01-01E
<10. General Specifications> 10-8
10.4 Dimensions
Model EJA210A
Unit: mm (approx. inch)
174 (6.85) 30 (1.18)
110 (4.33)
External indicator
conduit connection 133 (5.24) Conduit Zero 35
connection adjustment (1.38)
Blind plug
(Optional) 25 Internal Terminal side
(0.98) indicator ø78
t (Optional) (3.07)
163 146
(6.42) (5.75)
Ground
Shrouding bolt *2 terminal
øD øC øg ød *1
Vent plug
46 Drain plug
Process
(1.81) connector n- øh
(Optional) 54
Process flange (2.13)
IM 01C21C01-01E
<10. General Specifications> 10-9
Model EJA220A
Unit: mm (approx. inch)
174 (6.85) 30 (1.18)
110 (4.33)
External indicator
conduit connection 133 (5.24) Conduit Zero 35
connection adjustment
Blind plug (1.38)
(Optional) Internal Terminal side
indicator
ø78
(Optional) (3.07)
163 146
(6.42) (5.75)
IM 01C21C01-01E
Customer DPharp EJA Series
Maintenance Transmitter Section
Parts List
2 5
4
11
A 10
12
13 1
2 2
1
14
A
6
7-2
7-1 5
8 9
F9341AR SCS14A stainless steel for 1/2 NPT (two electrical connections)
4 — 1 Name Plate
5 Bellow 4 Screw
F9900RG For cast-aluminum alloy case assembly
F9900RR For SCS14A stainless steel case assembly
F9342AM For HART protocol version with write protection switch (Optional code /F1)
7-2 F9342BF 1 For FOUNDATION Fieldbus protocol version
F9342BG For FOUNDATION Fieldbus protocol version with PID/LM function (Optional code /LC1)
8 F9900RP 2 Cap Screw
9 Y9612YU 2 Screw
10 Below 1 Plug
F9340NW For Pg13.5
F9340NX For M20
G9330DP For G1/2
G9612EB For 1/2 NPT
(Note 1) Applicable for BRAIN and HART protocol versions (Output signal code D and E). For FOUNDATION Fieldbus protocol version (Output
signal code F), consult Yokogawa local office.
EJA210A EJA220A
8
5
3
9
4
2 6
10
7
1 F9300AJ 1 O-Ring
2 Below 1 Gasket
D0114RB PTFE Teflon
U0102XC PTFE Teflon (degreased)
3 Below 1 Process Connector, SCS14A Stainless Steel (Note 1)
F9340XY Rc 1/4
F9340XW Rc 1/2
F9340XZ 1/4 NPT
F9340XX 1/2 NPT
4 Below 2 Bolt
IM 01C21C01-01E
Edition Date Page Revised Item
6th July 2001 2-10 2.10 Change EMC Conformity number.
8-4, 8-5 8.3.1 Add footnote (*4) to B40, Maximum static pressure in Parameter
Summary.
CMPL CMPL 1C21A1-02E 6th → 7th(Manual Change)
Change Part No. of 7-1 CPU Assembly for BRAIN protocol.
F9342BB → F9342AB
CMPL 1C21A1-02E 7th → 8th(Manual Change)
Change Part No. of 7-1 CPU Assembly for HART protocol.
F9342BH → F9342AL
CMPL 1C21A1-02E 8th → CMPL 01C21A01-02E 9th
Delete Part No. of 4 Name Plate.
Change Part No. of 5 Screw.
F9303JU → Y9303JU
CMPL 1C21C1-01E 3rd → CMPL 01C21C01-01E 4th
7th May 2002 1-2 1.1 Add “1.1 For Safety Using.”
2-7 2.9.4 Add descriptions based on ATEX directive.
10-5 10.3 Add Optional code K2.
10-6 Add Optional code C2 and C3.
8th Apr. 2003 2-8 2.9.4 Add Option code KU2.
2-10 2.11 Add PED (Pressure Equipment Directive).
10-5 10.3 Add Option code KU2.
9th Apr. 2006 1-2 1.1 Add (e) Explosion Protected Type Instrument and (f) Modification
1-3 1.3 Add “1.3 ATEX Document”
2-6 2.9.3 Add “IECEx Certification” and delete “SAA Certification”
2-11 2.12 Add Low Voltage Directive
10-5, 10-6 10.3 Add Certificate numbers and Applicable standards
10-6 Add option code /SU2 and delete option code /SU1
10-7 Add option code /PR
10th Jan. 2008 1-1 Add direct current symbol.
1-4 Add 11 European languages for ATEX documentation.
2-3+ 2.9.1 Add applicable standard and certificate number for appovals.
2-10 2.10 Add EMC caution note.
4-2 4.4 Add section of changing the direction of integral indicator.
8-14 8.3.3(12) Add figure for A40.
9-3 9.4.1 Add figure of integral indicator direction.
10-1+ 10.1, 10.2 Add PROFIBUS PA communication type.
10-5,10-6 10.3 Delete applicable standard from the table.
CMPL CMPL 01C21A01-02E 9th → 10th
Delete logo from the tag plate.
11th Oct. 2008 2-9 2.9.4 Change explosion protection marking for type n from EEx to Ex.
2-10 2.10 Update EMC conformity standards.
8-4, 8-5 8.3.1 Add new parameters.
8-6 8.3.2 Add items in table 8.3.1.
8-9 and later 8.3.3 Add (5)Change Output Limits and (14)Span Adjustment.
Re-number the items.
8-18 8.5.2 Modify descriptions and notes for Er.01.
9-1 9.3 Add note for calibration.
9-5 9.4.3 Add note for cleaning.
10-3, 10-4 10.2 Add new suffix codes.
10-6, 10-7 10.3 Add sealing statement for CSA standards. Add /HC.
CMPL CMPL 01C21A01-02E 10th → 11th
Change Part No. of items 5 and 8.
12th July 2015 2-5, 2-6 2.9.2 Add temperature limitation for /HE.
2-9 to 2-10 2.9.4 b Change /KF2 to /KF21 and modify descriptions. Delete c. Replace
tag plate.
2-11 2.10 Add standards.
2-12 2.12 Add (3) and (4).
8-1 8.1.1 Add note. 8.1.2 Add descriptions.
10-1 10.1 Add information to “EMC Conformity Standards”.
10-5 to 10-7 10.3 Delete codes KU2 and KF2. Add KF21. Add Codes HE and CA.
IM 01C21C01-01E