Nomra Exxon Iluminación
Nomra Exxon Iluminación
Nomra Exxon Iluminación
INTERNATIONAL Page 1 of 6
PRACTICE Rev. 0 March 1998
Changes shown by
SCOPE
I 1.1 This practice covers lighting design.
I 1.2 An asterisk ( ) indicates that additional information is required. If a job is contracted, this additional
information is furnished in the Job Specification.
DEFINITIONS
I 2.1 In-service levels are defined as the levels required in service, averaged over the area involved and
averaged in time.
I 2.2 Maintenance factor is defined as a factor which must be included in the design calculations in order to
allow for the following:
a. Average loss of lamp lumens due to aging.
b. Decrease in lamp and luminaire output resulting from dust, dirt, insects, and chemical changes in
luminaire reflecting surface.
c. Increased absorption of the light output by dust, dirt, and chemical changes in the room or other
reflecting surfaces.
d. Known low voltage condition.
I 2.3 Acceptable and preferred practices. Where this practice lists more than one type of equipment or method
as acceptable, the contractor shall make the selection after determining whether reduced maintenance and
operating cost for one type provides sufficient cost benefit to offset an initial added investment. The Owner's
Engineer shall approve alternative choices.
DESIGN
S 3.1 Lighting shall be provided to obtain at least the in-service illumination levels specified in Table 1 at the
elevations indicated. They are on the horizontal plane except when labeled vertical. When high-pressure
sodium lighting is installed, initial lighting levels shall be 140% of the in service levels shown in Table 1, or
the initial level values shown in Table 1, whichever is less.
S 3.2 Lighting uniformity shall be such that the ratio of maximum to minimum level within the area does not
exceed the limit specified in Table 1.
C 3.3 Lighting is not required in the following areas unless otherwise specified:
a. Tank fields (specify if required for stairways and accessways).
b. Auxiliary or low traffic volume roads.
c. Refinery boundary fences.
R 3.4 For areas or equipment not covered by Table 1, where personnel are regularly required to perform
operating or maintenance duties, adequate lighting for tasks performed shall be provided.
S 3.5 Aviation obstruction lights shall be installed on structures and stacks as required by authorities having
jurisdiction.
S 3.6 Marine navigational lights shall be installed on piers as required by authorities having jurisdiction.
R 3.7 Where step-down transformers are used for lighting, these transformers shall be used for lighting only.
FIXTURE LOCATION
M,S 3.17 Fixture location shall allow safe and convenient relamping and cleaning. In no case shall lighting fixtures
be located directly over electrical equipment having exposed energized parts or equipment having exposed
moving parts.
M 3.18 All lighting fixtures mounted along platform handrails, shall have the stanchion mounted outside the
handrail and supported in such a manner that clearance between stanchion and handrail is a minimum of
3 in (75 mm). Fixtures shall be accessible for relamping or cleaning from the platform.
FLOODLIGHT POLES
I 3.19 For new work in existing plants having standardized pole types, the existing plant standard shall be
used.
LIGHTING CONTROL
O * 3.20 Street lighting and lighting for outdoor operating areas which are not continuously attended shall be
either of the following:
a. Automatically controlled (2-wire system) by photo-cell. An auto-on-off selector switch shall be
located at the controller location to permit manual control of the lighting.
b. When specified, remotely controlled (2-wire system) from an attended location.
O 3.21 Photo-cell units shall be located such that they:
a. Are readily accessible for cleaning and servicing
b. Are not activated by local artificial light sources
c. Are not obstructed by buildings or other structures, and
d. Activate only one lighting contactor per photocell.
S,O 3.22 Indoor lighting for substations and other normally unoccupied buildings shall be controlled by
switches located so that personnel can proceed from outdoor to indoor, and from room to room in the
unlighted building, lighting his way ahead by switches located within arms reach of the last lighted room or
outdoors.
EMERGENCY LIGHTING
S,O 3.27 Emergency lighting shall be provided for the following equipment and areas:
a. Instrument and operating consoles and panels in process and utility control rooms.
b. Switchgear control, relaying, metering, lighting panel, and alarm panels in:
1. Purchased power main substations.
2. Substations with two (2) or more supplies having manual or automatic switching between
supplies.
3. Radial substations with intertripping (transfer tripping) connections to their source substation
feeder breakers.
S c. Instrument & essential services equipment rooms.
S d. All other substations to the extent necessary for personnel to safely exit the building.
e. Other areas specified.
S 3.28 Emergency lighting illumination levels shall have an average value on the “seeing task" (surface
requiring emergency lighting) of 2 ft-candle (22 lx).
S 3.29 Emergency lighting for control rooms may be supplied from the instrument power supply if it includes a
backup battery. Lighting may be a-c, fed by and included in the sizing basis of an inverter. Alternatively, it
may be d-c, supplied from the battery. For d-c, the lighting shall be switched on automatically on loss of
normal lighting power, and have provision for testing. For a-c or d-c, the lighting load shall be included in
the sizing basis of battery and charger.
S 3.30 For control rooms without backup battery, emergency lighting shall be supplied by means of self-
contained battery operated units having integral trickle chargers which are supplied from the normal a-c
source. Self-contained battery units shall have the following features:
a. Units shall be mounted, wired, equipped with test provisions, and have an automatic switching device
to light unit when the normal lighting supply fails.
b. Units shall be capable of maintaining the illumination levels for at least four (4) hours.
S,R 3.31 Emergency lighting for substations may be supplied as follows:
a. From the switchgear control battery if one is installed, or
b. By self-contained units.
S,R 3.32 Emergency lighting from the switchgear control power battery shall conform to the following:
a Lighting shall not be switched automatically.
b. Lighting shall be switched manually at all doorways of the substation (or substation control room) with
switches located at each doorway.
c. Lighting shall be incandescent fixtures only.
WIRING
O 3.34 Neutral conductors of circuits supplying discharge type lighting shall be of the same size as the circuit line
conductors.
PANELBOARD DIRECTORIES
O 3.35 A circuit directory shall be installed at each lighting panelboard identifying each branch circuit. If
construction drawings do not indicate the specific fixtures on each of the circuits, then the panelboard
directory shall be in sufficient detail to give this information.
STROBOSCOPIC EFFECT
S 3.36 In locations with moving machinery, the lighting design shall avoid stroboscopic effect. Lead-lag ballasts
or division of load between phase shall be employed where necessary.
Revision Memo
9/68 Original Issue of Basic Practice
1/72 Revision 1
1/77 Revision 2
12/93 Revision 3
3/98 Revision 0 - Original Issue of International Practice
Complete editorial revision to rationalize this practice with the referenced standards and other IPs. Significant
changes include: The following paragraphs of IP 16-5-1 Revision 3 have been deleted: 2.3, 3.17, 3.19-3.21, 3.24,
3.26, 3.30, 3.42. Old Par 3.3 contents moved to Table 1 notes. Par. 3.13 removed voltage tap comment. Par. 3.20
made an asterisk paragraph and removed note.
Old Par. No. New Par. No. Old Par. No. New Par. No.
2.4 2.3 3.25 3.19
3.4 - 3.16 3.3 - 3.15 3.27 - 3.29 3.20 - 3.22
3.18 3.16 3.31 - 3.41 3.23 - 3.33
3.22, 3.23 3.17, 3.18 3.43 - 3.45 3.34 - 3.36