V90 Firmware Update Process For End User
V90 Firmware Update Process For End User
Unrestricted
2. Copy all the files to the root directory of the SD card as figure 2
3. Plug SD card into the SD card slot on V90 drive, and then power on 24 VDC supply
of V90 as figure 3.
Insert SD “RDY”,
Card “COM”
Provide
24V
Unrestricted
4. After step 3, the RDY and COM LEDs can indicate you the update process as figure
4.
Normally, firmware update process is that RDY LED is in red and COM LED flashes
at 2 Hz in orange.
If the RDY and COM LEDs come to abnormal display, please check the files in the
SD card and check the SD card itself. Maybe the following circumstance occurs.
(1) The SD card is not supported by V90.
(2) The firmware version on the SD card is the same as current version in drive.
(3) Files in SD card are missing, corrupt or not in the root directory.
5. When both RDY and COM LEDs are flashing at 0.5 Hz, firmware update is finished.
Please power off V90 drive and un-plug the SD card from V90.
6. Power on V90 and check the version with parameter r29018 to see whether the
version is correct.
Unrestricted
7. Implement the “Default” and “Save” operations for the drive to complete the update
process.
Note: Please make commission again because the drive is set to factory default, and all
the parameters except for the field bus (USS/Modbus) related parameters are recovered to
their factory default values.
Unrestricted