Abb Digital Dido, Dx581-S - Data - Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Ordering data

DATA SHEET

DX581-S
Safety digital input/output module

1 Ordering data
Type Description Part no.
DX581-S Safety digital I/O module 8SDI/SDO 1SAP 284 100 R0001
DX581-S-XC Safety digital I/O module 8SDI/ 1SAP 484 100 R0001
SDO, extreme conditions

2020/07/06 3ADR010086, 1, en_US 1


Technical data

2 Dimensions
Dimensions

57.7
(2.27)

DX581-S

1.0 T0 PWR 2.0I0 3.0 T2 4.0I4

59 (2.32)
1.1 2.1I1 3.1 4.1I5

70.5 (2.78)
1.2 T1 2.2I2 3.2 T3 4.2I6

1.3 2.3I3 3.3 4.3I7

1.4 2.4O0 3.4 4.4O4


ADDR
1.5 x10H 2.5O1 3.5 4.5O5
45
23 6
1.6 1 7 2.6O2 3.6 4.6O6
0 8
F 9
1.7 ED A 2.7O3 3.7 4.7O7
CB
ADDR
1.8 UP x01H 2.8UP 3.8 UP 4.8UP
45
23 6
1.9 ZP 1 7 2.9ZP 3.9 ZP 4.9ZP
0 8
F 9
ED A
CB ERR1 ERR2

UP 24VDC 100W 8SDI 8SDO


Safety Digital Input 24VDC
Safety Digital Output 24VDC 0.5A

135 (5.31)
1.0 2.0 3.0 4.0 1.0 2.0 3.0 4.0

1.1 2.1 3.1 4.1 1.1 2.1 3.1 4.1

1.2 2.2 3.2 4.2 1.2 2.2 3.2 4.2

1.3 2.3 3.3 4.3 1.3 2.3 3.3 4.3

1.4 2.4 3.4 4.4 1.4 2.4 3.4 4.4

1.5 2.5 3.5 4.5 1.5 2.5 3.5 4.5

135 mm
1.6 2.6 3.6 4.6 1.6 2.6 3.6 4.6

1.7 2.7 3.7 4.7 1.7 2.7 3.7 4.7

1.8

1.9
2.8

2.9
3.8

3.9
4.8

4.9
1.8

1.9
2.8

2.9
3.8

3.9
4.8

4.9
(5.31) “

67.5 (2.66)

Fig. 1: Dimensions of DX581-S safety I/O module

3 Technical data
NOTICE!
DX581-S-XC version is available for usage in extreme environmental conditions
Ä Appendix A “System data for AC500-S-XC” on page 8.

Additional technical data is available in ABB PLC catalog at www.abb.com/plc.

Process supply Data Value Unit


voltage UP
Connections terminals 1.8 ... 4.8 (UP) +24 V
Connections terminals 1.9 ... 4.9 (ZP) 0 V
Rated value (-15 %, +20 %, without ripple) 24 V DC
Max. ripple 5 %
Protection against reversed voltage yes
Rated protection fuse for UP (fast) 10 A
Electrical isolation per module
Mechanisms in which I/Os are processed periodically refreshed
Current consumption from UP at normal operation with + 0.18 A
24 V DC (for module electronics)
Inrush current from UP at 30 V (at power up) 0.1 A2s
Inrush current from UP at 24 V (at power up) 0.06 A2s

2 3ADR010086, 1, en_US 2020/07/06


NOTICE!
All DX581-S channels (including test pulse outputs) are protected against reverse
polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.

Mounting posi- Horizontal or vertical with derating (output load reduced to 50 % at +40 °C per group and with max-
tion imal operating temperature reduced to +40 °C).

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switchgear
cabinet.

Allowed inter- Data Value Unit


ruptions of
power supply, DC supply interruptions < 10 ms
according to EN
Time between 2 DC supply interruptions, PS2 >1 s
61131-2

Environmental Data Value Unit


conditions
Operating temperature* 0 ... +60 °C
Storage temperature -40 ... +85 °C
Transport temperature -40 ... +85 °C
Humidity without condensation max. 95 %
Operating air pressure > 800 hPa
Storage air pressure > 660 hPa
Operating altitude < 2000 m above sea
level
Storage altitude < 3500 m above sea
level

* Extended temperature ranges (below 0 °C and above +60 °C) can be supported in special versions
of DX581-S Ä Appendix A “System data for AC500-S-XC” on page 8.

Creepage dis- The creepage distances and clearances meet the overvoltage category II, pollution degree 2.
tances and
clearances
Power supply For the supply of modules, power supply units according to PELV/SELV specifications must be used.
units

Electromagnetic For information on electromagnetic compatibility refer to the latest TÜV SÜD Report.
compatibility

Mechanical Data Value Unit


properties
Degree of protection IP 20
Housing according to UL 94
Vibration resistance acc. to EN 61131-2 (all three axes), 2 ... 15 Hz
continuous 3.5 mm
Vibration resistance acc. to EN 61131-2 (all three axes), 15 ... 150 Hz
continuous 1 g *

2020/07/06 3ADR010086, 1, en_US 3


Technical data of safety digital inputs

Data Value Unit


Shock test (all three axes), 11 ms half-sinusoidal 15 g
MTBF 73 years

* Higher values on request

Self-test and Start-up and runtime tests: Program flow control, RAM, CPU, cross-talk, stuck-at-1, etc.
diagnostic func-
tions
Dimensions, Data Value Unit
weight
WxHxD 67.5 x 76 x 62 mm
Weight ~ 130 g

Certifications CE, cUL (further certifications at www.abb.com/plc)

3.1 Technical data of safety digital inputs


Data Value Unit
Number of input channels per module 8
Terminals of the channels I0 to I3 2.0 ... 2.3
Terminals of the channels I4 to I7 4.0 ... 4.3
Terminals of reference potential for all inputs (minus pole of 1.9 ... 4.9
the process supply voltage, signal name ZP)
Electrical isolation from the rest of the module (I/O bus) Yes
Input type acc. to EN 61131-2 Type 1
Input delay (0 ➔ 1 or 1 ➔ 0), configurable 1 ... 500 ms

Input signal One yellow LED per channel, the LED is ON when the input signal is high (signal 1).
indication

Signal voltage Data Value Unit


Input signal voltage 24 V DC
Signal 0 -3 ... +5 V
Undefined signal > +5 ... < +15 V
Signal 1 +15 ... +30 V

Input current Data Value Unit


per channel
Input voltage +24 V, typically 7 mA
Input voltage +5 V > 1 mA
Input voltage +15 V > 4 mA
Input voltage +30 V < 8 mA

4 3ADR010086, 1, en_US 2020/07/06


Technical data of safety digital outputs

Cable length Data Value Unit


Max. cable length, shielded 1000 m
Max. cable length, unshielded 600 m

3.2 Technical data of safety digital outputs

DANGER!
Exceeding the permitted process or supply voltage range (< -35 V DC or > +35 V DC)
could lead to unrecoverable damage of the system.

Data Value Unit


Number of channels per module (transistor outputs) 8
Terminals of reference potential for all outputs (minus pole 1.9 ... 4.9
of the process supply voltage, signal name ZP)
Terminals of common power supply voltage for all outputs 1.8 ... 4.8
(plus pole of the process supply voltage, signal name UP)
Output voltage for signal 1 UP - 3 V
Output delay (0 ➔ 1 or 1 ➔ 0): 5 mA output current 1 ms
Output delay (0 ➔ 1 or 1 ➔ 0): 500 mA output current 4 ms
Ability to switch a capacitive load of at least 300 µF
Ability to switch an inductive load of at least 1 H

Output current Data Value Unit


Rated value, per channel at UP = 24 V 500 mA
Maximum value (all channels together) 4 A
Leakage current with signal 0 < 0.5 mA
Short-circuit proof/overload proof yes
Overload message (channel passivation), I > 0.7 A yes
Output current limitation (automatic reactivation after short- yes
circuit/overload)
Resistance to feedback against 24 V signals yes
Demagnetization by internal suppressor diodes when yes
switching off inductive loads
Rated protection fuse on UP 4.5 A

Cable length Data Value Unit


Max. cable length, shielded 1000 m
Max. cable length, unshielded 600 m

2020/07/06 3ADR010086, 1, en_US 5


Technical data of non-safety test pulse outputs

3.3 Technical data of non-safety test pulse outputs


Data Value Unit
Number of test pulse channels per module (transistor test 4
pulse outputs)
Terminals of the channels T0, T1 1.0, 1.2
Terminals of the channels T2, T3 3.0, 3.2
Terminals of reference potential for all test pulse outputs 1.9 ... 4.9
(minus pole of the process supply voltage, signal name ZP)
Terminals of common power supply voltage for all outputs 1.8 ... 4.8
(plus pole of the process supply voltage, signal name UP)
Output voltage for signal 1 UP - 0.8 V
Length of test pulse 0 phase 1 ms

Output current Data Value Unit


Rated value, per channel 10 mA
Maximum value (all channels together) 40 mA
Short-circuit proof / overload proof yes
Output current limitation 65 mA
Resistance to feedback against 24 V signals yes

Cable length Data Value Unit


Max. cable length, shielded 1000 m
Max. cable length, unshielded 600 m

6 3ADR010086, 1, en_US 2020/07/06


Appendix

2020/07/06 3ADR010086, 1, en_US 7


A System data for AC500-S-XC
A.1 Environmental conditions
Process and Data Value Unit
supply voltages
Process and supply voltage (-25 %, +30 % inclusive ripple) 24 V DC
Absolute limits inclusive ripple 18 ... 31.2 V
Ripple < 10 %
Protection against reverse polarity yes
Allowed interruptions of DC power supply < 10 ms
Time between 2 interruptions, PS2 >1 s

DANGER!
Exceeding the permitted process or supply voltage range (< -35 V DC or > +35 V DC)
could lead to unrecoverable damage of the system.

DANGER!
For the supply of the modules, power supply units according to PELV or SELV specifi-
cations must be used.

NOTICE!
The creepage distances and clearances meet the requirements of the overvoltage
category II, pollution degree 2.

Temperature Data Value Unit


Operating temperature* -40 ... +70 °C
Operating temperature (vertical mounting of module output -40 ... +40 °C
load limited to 50 % per group)
Storage temperature -40 ... +85 °C
Transport temperature -40 ... +85 °C

* +60 ... +70 °C with the following deratings:


● Terminal bases: Maximum 2 communication modules allowed
● Digital inputs: Maximum number of simultaneously switched on input channels limited to 50 % per
group (e.g. 8 channels => 4 channels)
● Digital outputs: Output current maximum value (all channels together) limited to 50 % per group
(e.g. 4 A => 2 A)
● Analog inputs: No limitations

DANGER!
The average temperature (MTBF calculation base) for both the extended temperature
range (-40 ... +70 °C) as well as for normal temperature range (0 ... +60 °C) is defined
to +40 °C.
Ensure that average operating temperature for used AC500-S-XC modules does not
exceed +40 °C.

8 3ADR010086, 1, en_US 2020/07/06


Humidity Data Value Unit
Relative humidity with condensation (operating/storage) 100 %

Air pressure Data Value Unit


Operating air pressure 1080 ... 620 hPa
Operating altitude -1000 ... 4000 m
Reduction of operating temperature at an air pressure of < 10 (e.g. +70 °C to K
795 hPa (or > 2000 m above sea level) +60 °C)

Immunity to cor- Data Value


rosive gases
Operating: according to ISA S71.04.1985 harsh group A, G3/GX yes
IEC 60721-3-3 3C2 / 3C3

Immunity to salt Data Value


mist
Operating: horizontal mounting only, according to IEC 60068-2-52 severity yes
level 1

Electromagnetic Data Value


compatibility
Radiated emission (radio disturbance) according to CISPR 16-2-3 yes
Conducted emission (radio disturbance) according to CISPR 16-2-1, CISPR yes
16-1-2
Electrostatic discharge (ESD) according to IEC 61000-4-2, zone B, criterion yes
B
Fast transient interference voltages (burst) according to IEC 61000-4-4, zone yes
B, criterion B
High energy transient interference voltages (surge) according to yes
IEC 61000-4-5, zone B, criterion B
Influence of radiated disturbances according to IEC 61000-4-3, zone B, crite- yes
rion A
Influence of line-conducted interferences according to IEC 61000-4-6, zone yes
B, criterion A
Influence of power frequency magnetic fields according to IEC 61000-4-8, yes
zone B, criterion A

NOTICE!
In order to prevent malfunctions, it is recommended that the operating personnel dis-
charge themselves prior to touching communication connectors or perform other suit-
able measures to reduce effects of electrostatic discharges.

NOTICE!
Unused sockets for communication modules on terminal bases must be covered with
TA524 dummy communication module. I/O bus connectors must not be touched
during operation.

2020/07/06 3ADR010086, 1, en_US 9


Radiation Data Value
Radio disturbance according to IEC 55011, group 1, class A yes

10 3ADR010086, 1, en_US 2020/07/06


A.2 Mechanical data
Data Value
Wiring method spring terminals
Degree of protection IP 20
Vibration resistance according to IEC 61131-2, IEC 60068-2-6, yes
IEC 60068-2-64
Shock resistance according to IEC 60068-2-27 yes
Horizontal assembly position yes
Vertical assembly position (no application in salt mist environment) yes

Assembly on Data Value Unit


DIN rail
according to DIN rail type 35 mm
IEC 60715
DIN rail type depth 7.5 or 15 mm

Assembly with Data Value Unit


screws
Screw diameter 4 mm
Fastening torque 1.2 Nm

2020/07/06 3ADR010086, 1, en_US 11


A.3 Environmental tests
Storage IEC 60068-2-1 test Ab: cold withstand test -40 °C / 16 h
IEC 60068-2-2 test Bb: dry heat withstand test +85 °C / 16 h
Humidity IEC 60068-2-30 test Dd: Cyclic (12 h / 12 h) damp-heat test +55 °C, 93 %
relative humidity / +25 °C, 95 % relative humidity, 6 cycles
IEC 60068-2-78, stationary humidity test: +40 °C, 93 % relative humidity,
240 h
Insulation test IEC 61131-2
Vibration resistance IEC 61131-2 / IEC 60068-2-6: 5 Hz ... 500 Hz, 2 g (with SD memory card
inserted in non-safety CPU)
IEC 60068-2-64: 5 Hz ... 500 Hz, 4 g rms
Shock resistance IEC 60068-2-27: all 3 axes 15 g, 11 ms, half-sinusoidal

EMC immunity
Electrostatic discharge (ESD)

Data Value Unit


Electrostatic voltage in case of air discharge 8 kV
Electrostatic voltage in case of contact discharge 6 kV

Fast transient interference voltages (burst)

Data Value Unit


Supply voltage units (DC) 4 kV
Digital inputs/outputs (24 V DC) 2 kV
Analog inputs/outputs 2 kV
Communication lines, shielded 2 kV
I/O supply (DC-out) 2 kV

High energy transient interference voltages (surge) - common mode (CM)

Data Value Unit


Supply voltage units (DC) 1 kV
Digital inputs/outputs (24 V DC) 1 kV
Analog inputs/outputs 1 kV
Communication lines, shielded 1 kV
I/O supply (DC-out) 0.5 kV

High energy transient interference voltages (surge) - differential mode (DM)

Data Value Unit


Supply voltage units (DC) 0.5 kV
Digital inputs/outputs (24 V DC) 0.5 kV
Analog inputs/outputs 0.5 kV
I/O supply (DC-out) 0.5 kV

Data Value Unit


Influence of radiated disturbances: test field strength 10 V/m
Influence of line-conducted interferences: test voltage 10 V

12 3ADR010086, 1, en_US 2020/07/06


Data Value Unit
Power frequency magnetic fields at 30 A/m 50 and 60 Hz

NOTICE!
Extreme environmental conditions and relevant requirements for used non-safety
CPUs and I/O modules from AC500-XC family shall be taken into account.

— —
ABB Automation Products GmbH © Copyright 2020 ABB.
Eppelheimer Str. 82 We reserve all rights in this document and in the information contained
69123 Heidelberg, Germany therein. Reproduction, use or disclosure to third parties without express
Telephone: +49 (0)6221 701 1444 authority is strictly forbidden.
Fax: +49 (0)6221 701 1382
E-mail: [email protected]
abb.com/plc

2020/07/06 3ADR010086, 1, en_US 13