Abb Digital Dido, Dx581-S - Data - Sheet
Abb Digital Dido, Dx581-S - Data - Sheet
Abb Digital Dido, Dx581-S - Data - Sheet
DATA SHEET
DX581-S
Safety digital input/output module
1 Ordering data
Type Description Part no.
DX581-S Safety digital I/O module 8SDI/SDO 1SAP 284 100 R0001
DX581-S-XC Safety digital I/O module 8SDI/ 1SAP 484 100 R0001
SDO, extreme conditions
2 Dimensions
Dimensions
57.7
(2.27)
DX581-S
59 (2.32)
1.1 2.1I1 3.1 4.1I5
70.5 (2.78)
1.2 T1 2.2I2 3.2 T3 4.2I6
135 (5.31)
1.0 2.0 3.0 4.0 1.0 2.0 3.0 4.0
135 mm
1.6 2.6 3.6 4.6 1.6 2.6 3.6 4.6
1.8
1.9
2.8
2.9
3.8
3.9
4.8
4.9
1.8
1.9
2.8
2.9
3.8
3.9
4.8
4.9
(5.31) “
67.5 (2.66)
3 Technical data
NOTICE!
DX581-S-XC version is available for usage in extreme environmental conditions
Ä Appendix A “System data for AC500-S-XC” on page 8.
Mounting posi- Horizontal or vertical with derating (output load reduced to 50 % at +40 °C per group and with max-
tion imal operating temperature reduced to +40 °C).
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switchgear
cabinet.
* Extended temperature ranges (below 0 °C and above +60 °C) can be supported in special versions
of DX581-S Ä Appendix A “System data for AC500-S-XC” on page 8.
Creepage dis- The creepage distances and clearances meet the overvoltage category II, pollution degree 2.
tances and
clearances
Power supply For the supply of modules, power supply units according to PELV/SELV specifications must be used.
units
Electromagnetic For information on electromagnetic compatibility refer to the latest TÜV SÜD Report.
compatibility
Self-test and Start-up and runtime tests: Program flow control, RAM, CPU, cross-talk, stuck-at-1, etc.
diagnostic func-
tions
Dimensions, Data Value Unit
weight
WxHxD 67.5 x 76 x 62 mm
Weight ~ 130 g
Input signal One yellow LED per channel, the LED is ON when the input signal is high (signal 1).
indication
DANGER!
Exceeding the permitted process or supply voltage range (< -35 V DC or > +35 V DC)
could lead to unrecoverable damage of the system.
DANGER!
Exceeding the permitted process or supply voltage range (< -35 V DC or > +35 V DC)
could lead to unrecoverable damage of the system.
DANGER!
For the supply of the modules, power supply units according to PELV or SELV specifi-
cations must be used.
NOTICE!
The creepage distances and clearances meet the requirements of the overvoltage
category II, pollution degree 2.
DANGER!
The average temperature (MTBF calculation base) for both the extended temperature
range (-40 ... +70 °C) as well as for normal temperature range (0 ... +60 °C) is defined
to +40 °C.
Ensure that average operating temperature for used AC500-S-XC modules does not
exceed +40 °C.
NOTICE!
In order to prevent malfunctions, it is recommended that the operating personnel dis-
charge themselves prior to touching communication connectors or perform other suit-
able measures to reduce effects of electrostatic discharges.
NOTICE!
Unused sockets for communication modules on terminal bases must be covered with
TA524 dummy communication module. I/O bus connectors must not be touched
during operation.
EMC immunity
Electrostatic discharge (ESD)
NOTICE!
Extreme environmental conditions and relevant requirements for used non-safety
CPUs and I/O modules from AC500-XC family shall be taken into account.
— —
ABB Automation Products GmbH © Copyright 2020 ABB.
Eppelheimer Str. 82 We reserve all rights in this document and in the information contained
69123 Heidelberg, Germany therein. Reproduction, use or disclosure to third parties without express
Telephone: +49 (0)6221 701 1444 authority is strictly forbidden.
Fax: +49 (0)6221 701 1382
E-mail: [email protected]
abb.com/plc