Axial Load and Moment Calculation in Column
Axial Load and Moment Calculation in Column
Axial Load and Moment Calculation in Column
Axial loads transferred from the first floor - to – the ground floor Column B2
Load from the First Floor Column = 326.2𝑘𝑁
Weight of the Beam on axis-2 = Factored combined load*Length of the beam on axis-2
= 54.5 𝑘𝑁⁄𝑚 ∗ 7𝑚 = 381.5𝑘𝑁
Weight of the Beam on axis-B = Factored combined load*Length of the beam on axis-B
= 30.8 𝑘𝑁⁄𝑚 ∗ 4𝑚 = 123.2𝑘𝑁
Self-weight of the Column = 1.35(0.275𝑚 ∗ 0.350𝑚 ∗ 5𝑚 ∗ 25 𝑘𝑁⁄𝑚3 ) = 16.242𝑘𝑁
∴ Total factored axial load on the Ground Floor Column = (326.2 + 381.5 + 123.2 +
16.242)𝑘𝑁 = 847.142𝑘𝑁
Axial loads transferred from the ground floor - to – the footing Column B2
Load from the Ground Floor Column = 847.142𝑘𝑁
Weight of the Beam on axis-2 = Factored combined load*Length of the beam on axis-2
= 10.5 𝑘𝑁⁄𝑚 ∗ 7𝑚 = 73.5𝑘𝑁
Weight of the Beam on axis-B = Factored combined load*Length of the beam on axis-B
= 10.5 𝑘𝑁⁄𝑚 ∗ 4𝑚 = 42𝑘𝑁
Self-weight of the Column = 1.35(0.275𝑚 ∗ 0.350𝑚 ∗ 1.5𝑚 ∗ 25 𝑘𝑁⁄𝑚3 ) = 5𝑘𝑁
∴ Total factored axial load on the Ground Floor Column = (847.142 + 73.5 + 42 + 5)𝑘𝑁 =
967.642𝑘𝑁
𝐸𝐼𝐵𝐶 𝐸∗(250∗5003 )
𝑘𝐵𝐶 = = = 3.26 ∗ 105 𝐸𝑚𝑚3
𝐿𝐵𝐶 12∗8000
𝐸𝐼𝑐 𝐸∗(275∗3503 )
For Columns: First Floor Column: 𝑘𝑐 = = = 2.46 ∗ 105 𝐸𝑚𝑚3
𝐿𝑐 12∗4000
𝐸𝐼𝑐 𝐸∗(275∗3503 )
Ground Floor Column: 𝑘𝑐 = = = 1.97 ∗ 105 𝐸𝑚𝑚3
𝐿𝑐 12∗5000
𝐸𝐼𝑐 𝐸∗(275∗3503 )
Footing Column: 𝑘𝑐 = = = 6.55 ∗ 105 𝐸𝑚𝑚3
𝐿𝑐 12∗1500
The arrangement of the design ultimate variable action should be such as that to cause
maximum moment in the column.
Bending Moments transferred from the roof level Beams- to – the first floor Column B2
Bending Moments transferred from the first floor Beams- to – the first floor and ground
floor Column B2
2.46 ∗ 105 𝐸
= 181 ∗ = 54.1𝑘𝑁𝑚
𝐸(2.46 ∗ 105 + 1.97 ∗ 105 + 0.5 ∗ 4.34 ∗ 105 + 0.5 ∗ 3.26 ∗ 105 )
Moment in Lower Column 𝑀𝑙𝑜𝑤𝑒𝑟
𝐾𝑐,𝑙
𝑀𝑙𝑜𝑤𝑒𝑟 = ∆𝐹𝐸𝑀 ∗ (𝐾
𝑐,𝑢 +𝐾𝑐,𝑙 +0.5𝐾𝑏1 +0.5𝐾𝑏2 )
1.97 ∗ 105 𝐸
= 181 ∗ = 43.3𝑘𝑁𝑚
𝐸(2.46 ∗ 105 + 1.97 ∗ 105 + 0.5 ∗ 4.34 ∗ 105 + 0.5 ∗ 3.26 ∗ 105 )
Bending Moments transferred from the ground floor Beams- to – the first floor and footing
Column B2
1.97∗105 𝐸
= 24.6 ∗ = 3.9𝑘𝑁𝑚
𝐸(6.55∗105 +1.97∗105 +0.5∗4.34∗105 +0.5∗3.26∗105 )
Moment in Lower Column 𝑀𝑙𝑜𝑤𝑒𝑟
𝐾𝑐,𝑙
𝑀𝑙𝑜𝑤𝑒𝑟 = ∆𝐹𝐸𝑀 ∗ (𝐾
𝑐,𝑢 +𝐾𝑐,𝑙 +0.5𝐾𝑏1 +0.5𝐾𝑏2 )
6.55 ∗ 105 𝐸
= 24.6 ∗ = 13.1𝑘𝑁𝑚
𝐸(6.55 ∗ 105 + 1.97 ∗ 105 + 0.5 ∗ 4.34 ∗ 105 + 0.5 ∗ 3.26 ∗ 105 )
𝐸𝐼𝐵𝐶 𝐸∗(250∗4003 )
𝑘23 = = = 3.33 ∗ 105 𝐸𝑚𝑚3
𝐿𝐵𝐶 12∗4000
𝐸𝐼𝑐 𝐸∗(350∗2753 )
For Columns: First Floor Column: 𝑘𝑐 = = = 1.52 ∗ 105 𝐸𝑚𝑚3
𝐿𝑐 12∗4000
𝐸𝐼𝑐 𝐸∗(350∗2753 )
Ground Floor Column: 𝑘𝑐 = = = 1.21 ∗ 105 𝐸𝑚𝑚3
𝐿𝑐 12∗5000
𝐸𝐼𝑐 𝐸∗(350∗2753 )
Footing Column: 𝑘𝑐 = = = 4.04 ∗ 105 𝐸𝑚𝑚3
𝐿𝑐 12∗1500
Bending Moments transferred from the roof level Beams- to – the first floor Column B2
Bending Moments transferred from the first floor Beams- to – the first floor and ground
floor Column B2
1.52∗105 𝐸
= 14 ∗ 𝐸(1.52∗105 +1.21∗105 +0.5∗3.33∗105 +0.5∗3.33∗105 ) = 3.5𝑘𝑁𝑚
1.21 ∗ 105 𝐸
= 14 ∗ = 2.8𝑘𝑁𝑚
𝐸(1.21 ∗ 105 + 1.52 ∗ 105 + 0.5 ∗ 3.33 ∗ 105 + 0.5 ∗ 3.33 ∗ 105 )
Bending Moments transferred from the ground floor Beams- to – the first floor and footing
Column B2
1.21 ∗ 105 𝐸
= 0∗ = 0𝑘𝑁𝑚
𝐸(1.21 ∗ 105 + 4.04 ∗ 105 + 0.5 ∗ 3.33 ∗ 105 + 0.5 ∗ 3.33 ∗ 105 )
Moment in Lower Column 𝑀𝑙𝑜𝑤𝑒𝑟
𝐾𝑐,𝑙
𝑀𝑙𝑜𝑤𝑒𝑟 = ∆𝐹𝐸𝑀 ∗ (𝐾
𝑐,𝑢 +𝐾𝑐,𝑙 +0.5𝐾𝑏1 +0.5𝐾𝑏2 )
4.04 ∗ 105 𝐸
= 0∗ = 0𝑘𝑁𝑚
𝐸(1.21 ∗ 105 + 4.04 ∗ 105 + 0.5 ∗ 3.33 ∗ 105 + 0.5 ∗ 3.33 ∗ 105 )