THT/CL-40-2T-1.5-F-400 IE3: Code: 1139561

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

TECHNICAL DATA REPORT

THT/CL-40-2T-1.5-F-400 IE3
Code: 1139561
400 ºC/2h and 300 ºC/2h tubular axial extractor fans with long casing and external
terminal boxes
Tubular axial extract fans with long casing for immersed operation in fire risk zones.

Fan:
• Tubular casing in sheet steel with external terminal box (Cable box) and inspection hatch.
• Variable angle impeller made of cast aluminium.
• Approved in accordance with standard EN 12101-3, with certifications no.: 0370-CPR-
0305 (F400) and 0370-CPR-0973 (F300).
• Airflow direction from motor to impeller.

Motor:
• Class H motors for S1 continuous operation and S2 emergency use. With ball bearings,
IP55 protection and 1 or 2 speeds, depending on model.
• Motors with IE3 efficiency for powers equal to or greater than 0.75 kW, except single-
phase, 2-speed and 8-pole.
• Three-phase 230/400 V 50 Hz (up to 3 kW) and 400/690 V 50 Hz (powers greater than 3
kW).
• Maximum temperature of air to be carried: S1 -25 ºC +40 ºC continuous service, also
suitable for warm climates with temperatures up to 50 ºC. S2 operation, 300 ºC/2h, 400
ºC/2h.

Finish:
• Anti-corrosive finish in polyester resin, polymerised at 190 ºC, after degreasing with
phosphate-free nanotechnology treatment.

Available versions:
• THT: Tubular axial fans with short casing.

On request:
• Airflow direction from impeller to motor.
• 100% reversible impellers.

CHARACTERISTIC CURVE AND ACOUSTICS AT 1.2KG/M³


Design Point
Q (m³/h) 1800
Ps (Pa) 200

Service Point (SP)


Q (m³/h) 2846
Ps (Pa) 500.1
Pd (Pa) 23.75
Pt (Pa) 523.9
Impeller (rpm) 2880
Blade Inclination (º) 20
Max. Temp. (ºC) 40
Outlet air speed (m/s) 6.292
Mechanical efficiency 41.24
(Pt) (%)
SFP (kW/m³/s) 1.53
Mechanical power (kW) 1.004

v2.16.0.0
www.sodeca.com DB v2.16.0.0 Data in this report can change without notice 1/3
TECHNICAL DATA REPORT

Acoustics: Radiated, 3 (m), Free field Band Lw dB(A) Lp dB(A)


63 Hz 43 22
125 Hz 59 38
250 Hz 71 50
500 Hz 79 58
1000 Hz 84 63
2000 Hz 82 61
4000 Hz 78 57
8000 Hz 71 50
TOTAL 88 67

TECHNICAL CHARACTERISTICS

Airflow maximum (m³/h) 7032


Speed (rpm) 2880
Maximum static pressure (Pa) 687.8
Maximum total pressure (Pa) 695

ERP

Efficiency 38.0% Pressure (Pa) 338


Efficiency grade N 43.6 Input power (kW) 1.280
Measurement category A Speed (rpm) 2902
Efficiency category Static Variable speed drive VSD not necessary
Specific ratio 1.00 ErP compliance 2015
Flowrate (m³/h) 5180

Data established at point of optimum efficiency

MOTOR DATA

Rated Mechanical Power (kW) 1.1


Hz/phases 50/3
Motor (rpm) 2870
Poles 2P
Max. current (A) 380-400 V Y 2.26
Max. current (A) 220-240 V D 3.93
Motor protection IP55
Motor class F400
Motor frame size 80M

Data can change, please check motor plate

v2.16.0.0
www.sodeca.com DB v2.16.0.0 Data in this report can change without notice 2/3
TECHNICAL DATA REPORT

DIMENSIONS

ØA ØB ØD E F ØJ N
490 450 410 400 - 12 8x45º

Dimensions without explicitly defined units are shown in millimeters (mm). Dimensions depending on the motor are approximate

Approx. weight (kg) 33

AVAILABLE ACCESSORIES

INT-KG- IAT CABLE BOX C2V VSD3/A-RFT- VSD1/A-RFM- VSD3/A-RFT- VSD1/A-RFM- AET P-400 RT-40 R/THT-40
20/3CA 2 2 2-IP66 2-IP66

BTUB BAC-400 PS-35/40 ACE/400-400 S CENTRAL CO SC PV-40

It must be checked that the accessory is suitable for the fan model

v2.16.0.0
www.sodeca.com DB v2.16.0.0 Data in this report can change without notice 3/3