Cummins 220 KW

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

INTRODUCTION

Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and
continuous duty applications. All generator sets are factory build, and production tested.

Power (kVA) 3 Phase,50 Hz, PF 0.8


STANDBY RATING (ESP) PRIME RATING (PRP)
Standby Amper
VOLTAGE
kW kVA kW kVA

400/231 220,00 275,00 200,00 250,00 396,94

STANDBY RATING (ESP) Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility
source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 %
overload capability is available for a period of 1 hour within 12-hour perod of operation.

General Characteristics
Model Name APD 275 C
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model CUMMINS 6LTAA8.9-G2
Alternator Made and Model AK 4200
Control Panel Model DSE 7320
Canopy MS 60 CK

ENGINE SPECIFICATIONS
Engine CUMMINS
Engine Model 6LTAA8.9-G2
Number of Cylinder (L) 6 cylinders - in line
Bore (mm.) 114
Stroke (mm.) 145
Displacement (lt.) 8,90
Aspiration Turbo Charged and Charge Air Cooled
Compression Ratio 16.6:1
RPM (d/dk) 1500
Oil Capacity (Total With Filter) (lt) 21
Standby Power (kW/HP) 240/322
Prime Power 220/295
Block Heater QTY 1
Block Heater Power (Watt) 1500
Fuel Type Diesel
Injection Type and System Direct
Type of Fuel Pump BYC P7100
Governor System Electronic
Operating Voltage (Vdc) 24 Vdc

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (21.08.2023)
Battery and Capacity (Qty/Ah) 2x85
Charge Alternator (A) 70
Cooling Method Water Cooled
Cooling Fan Air Flow (m3/min) 475
Coolant Capacity (engine only / with radiator) (lt) 12.3/46.1
Air Filter Dry Type
Fuel Cons. Prime With %100 Load (lt/hr) 53
Fuel Cons. Prime With %75 Load (lt/hr) 39
Fuel Cons. Prime With %50 Load (lt/hr) 27

ALTERNATOR CHARACTERISTICS
Manufacturer Aksa
Alternator Made and Model AK 4200
Frequency (Hz) 50
Power (kVA) 250
VOLTAGE (V) 400
Phase 3
A.V.R. SX440
Voltage Regulation (+/-)1%
Insulation System H
Protection IP22
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 727
COOLING AIR (m³/min) 34.8

Open Gen.Set Dimensions (mm)


LENGTH 2600
WIDTH 1250
HEIGHT 1684
DRY WEIGHT (kg.) 1950
TANK CAPACITY (lt.) 473

Gen.Set Canopy Dimensions (mm)


LENGTH 3963
WIDTH 1356
HEIGHT 2171
DRY WEIGHT (kg.) 2700
TANK CAPACITY (lt.) 470
1. Steel structures.
2. Emergency stop push button.
3. Control panel is mounted on the baseframe . Located
at the right side of the generator set.

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (21.08.2023)
4. Corrosion-resistant locks and hinges.
5. Oil could be drained via valve and a hose
6. Exhaust system in the canopy.
7. Special large access doors for easy maintanance
8. In front and back side special large access doors for
easy maintanance
9. Base frame -fuel tank.
10. Lifting points similar to ISO container , located on
each top corner of the canopy.
11. The cap on the canopy provides easy accsess to
radiator cap.
12. Sound proofing materials
13. Plastic air intake pockets.
INTRODUCTION
Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements
and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our
modular designed sound insulated canopies provide ease of access for servicing and general maintenance and
interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance,
providing you with confidence that genset ratings and ambient capability.

Control Panel
Control Module DSE
Control Module Model DSE 7320
Communication Ports MODBUS
1. Menu navigation buttons
2. Close mains button
3. Main Status and instrumentation display
4. Alarm LED's
5. Close generator button
6. Status LED's
7. Operation selecting buttons
Devices
DSE 7320 Auto Mains Failure control module
Static battery charger
Emergency stop push button and fuses for control circuits
CONSTRUCTION and FINISH
Components installed in a sheet steel enclosure.
Phosphate chemical, pre-coating of steel provides corrosion resistant surface
Polyester composite powder topcoat forms a high gloss and extremely durable finish
Lockable hinged panel door provides for easy component access
INSTALLATION
Control panel is mounted to gen-set baseframe on robust steel stand or power module. Located on the side of generating
set with proper panel visibility.
GENERATING SET CONTROL UNIT
The DSE 7320 control module is a standard addition to our generator sets from 220 kVA upwards and it has been
designed to start and stop diesel and gas generating sets that include electronic and non-electronic engines.
The DSE 7320 includes the additional capability of being able to monitor a mains (utility) supply and is, therefore, suitable
for controlling a standby generating set in conjunction with an automatic transfer switch.
The DSE7320 also indicates operational status and fault conditions, automatically shutting down the generating set and
indicating faults by means of its LCD display on the front panel.

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (21.08.2023)
STANDARD SPECIFICATIONS
Microprocessor controlled
- 132 x 64 pixel LCD display makes information easy to read
- Front panel programming and also via PC software
- Soft touch membrane keypad and five key menu navigation
- Remote communications via RS232, RS485 and ethernet.
- Event logging (50) showing date and time
- Multiple date and time engine exercise mode and maintenance scheduler
- Engine block heater control.
- Controls; stop, manual, auto, test, start, mute lamb test/transfer to generator, transfer to mains, menu navigation.
Instruments
ENGINE
Engine speed
Oil pressure
Coolant temperature
Run time Battery volts
Engine maintenance due
GENERATOR
Voltage (L-L, L-N)
Current (L1-L2-L3)
Frequency
Earth current
kW
Pf
kVAr
kWh, kVAh, kVArh
Phase sequence
MAINS
Voltage (L-L, L-N)
Frequency
WARNING
Charge failure
Battery under voltage
Fail to stop
Low fuel level (opt.)
kW overload
Negative phase sequence
Loss of speed signal

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (21.08.2023)
PRE-ALARMS
Low oil pressure
High engine temperature
Low engine temperature
Over /Under speed
Under/over generator frequency
Under/over generator voltage
ECU warning
SHUTDOWNS
Fail to start
Emergency stop
Low oil pressure
High engine temperature
Low coolant level
Over /Under speed
Under/over generator frequency
Under/over generator voltage
Oil pressure sensor open
Phase rotation
ELECTRICAL TRIP
Earth fault
kW overload
Generator over current
Negative phase sequence
Options
High oil temperature shut down
Low fuel level shut down
Low fuel level alarm
High fuel level alarm
EXPANSION MODULES
Additional LED module (2548)
Expansion relay module (2157)
Expansion input module (2130)
Standards
Elecrical Safety / EMC compatibility
BS EN 60950 Electrical business equipment
BS EN 61000-6-2 EMC immunity standard
BS EN 61000-6-4 EMC emission standard

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (21.08.2023)
STATIC BATTERY CHARGER
Battery charger is manufactured with switching-mode and SMD technology and it has high efficiency.
Battery charger models' output V-I characteristic is very close to square
2405 has fully output short circuit protection and ıt can be used as a current source.
2405 charger has high efficiency, long life, low failure rate, lightweight and low heat radiated in accordance with linear
alternatives.
The charger is fitted with a protection diode across the output.
Charge fail output is available.
Connect charge fail relay coil between the positive output and CF output.
Input: 196-264V.
Output: 27,6V 5A or 13,8V 5A.

STANDARD SPECIFICATIONS
- Water cooled, Diesel engine
- Radiator with mechanical fan
- Protective grille for rotating and hot parts
- Electric starter and charge alternator
- Starting battery (with lead acid) including rack and cables
- Engine coolant heater
- Base frame design incorporates an integral fuel tank and anti-vibration isolators
- Flexible fuel connection hoses
- Single bearing, class H alternator
- Industrial exhaust silencer and steel bellows supplied separately(for open sets)
- Static battery charger
- Manual for application and installation

OPTIONAL EQUIPMENTS
ENGINE

Fuel-Water Seperator Filter

Oil heater

ALTERNATOR

Anti-Condensation Heater

Main line circuit breaker

CONTROL SYSTEM

Charge Ammeter

TRANSFER SWITCH

Three or four pole contactor

Three or four pole motor operated circuit breaker

OTHER ACCESSORIES

Main Fuel Tank

Manual oil drain pump

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (21.08.2023)
Residential silencer

Enclosure: weater protective or sound attenuated

Trailer

Tool kit for maintenance

AKSA CERTIFICATES
- ISO 14001-2004
- TS ISO 8528
- TS ISO 9001-2008
- CE
- SZUTEST
- 2000/14/EC

Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (21.08.2023)

You might also like