TAIE FY Series Manual
TAIE FY Series Manual
TAIE FY Series Manual
Operation Manual
FY101 FY100
90X90mm 175X110mm
February, 2007
FY_OPER_EN_V6
TAIE
CONTENT
1 Notice before start- up ……………………………………………………… Page 3
2 Specifications ………………………………………………………………… Page 4
3 Terminal arrangement
3.1 FY400 Terminals ……………………………………………………… Page 6
3.2 FY600 Terminals ……………………………………………………… Page 7
3.3 FY700 Terminals ……………………………………………………… Page 8
3.4 FY800 Terminals ……………………………………………………… Page 9
3.5 FY900 Terminals ……………………………………………………… Page 10
3.6 FY100 Terminals ……………………………………………………… Page 11
3.7 FY101 Terminals ……………………………………………………… Page 12
4 External dimension and panel cutout
4.1 FY100-FY101…………………………………………………………… Page 13
4.2 FY400-FY900…………………………………………………………… Page 14
5 Parts description…………… ………………………………………………… Page 15
6 Operations
6.1 Power On …………………………………………………………….. Page 16
6.2 Change the Set Value (SV) ………………………………………… Page 16
6.3 Change The Alarm Value…………………………………………… Page 16
6.4 Autotuning (AT) ……………..………………………………………… Page 17
6.5 Programmable RAMP / SOAK ……………………………………….. Page 18
7 Operation levels
7.1 Levels diagram ………………………………………………………. Page 19
7.2 Lock function ……………………………..……………………..…… Page 19
8 Parameters
8.1 Level 1 (User Level) ………………………………………………… Page 20
8.2 Level 2 (PID Level)
8.2.1 Level 2 parameters display / hiding condition…..……... Page 21
8.2.2 Description of parameters………………………………… Page 22
8.3 Level 3 (Input Level) ………………………………………………… Page 23
8.4 Level 4 (SET Level)
8.4.1 How to hide parameters (Use SET1~SET7) …………… Page 25
8.4.2 Special functions (Use SET8 / SET9 / SET0)………..… Page 26
8.4.3 Remote SV type selection…………………………………… Page 27
8.4.4 Output mode selection (Use OUTY) ……………………… Page 27
8.4.5 Modify caution……………………………………………… Page 27
1
8.5.2 Description of operation…………………………………… Page 29
9 Input type table ………………………………………………………………… Page 30
10 Alarm
10.1 Alarm time……………………………………………………………… Page 32
10.2 SETA …………………………………………………………………… Page 32
10.3 Alarm mode …………………………………………………………… Page 33
11 Heater Break Alarm(HBA) ……………………………………………….… Page 34
11.1 HBA Wiring Example……………………….…………………….….. Page 34
11.2 HBA Function Description………………………………………..….. Page 34
11.3 HBA setting procedure…………………………………………….…. Page 35
11.4 Parameters for HBA function………………………………....….….. Page 35
11.5 Activated conditions of HBA …………………………………….. Page 36
11.6 Remarks…………………………………………………………...….. Page 36
11.7 CT specifications
11.7.1 SC-80T Specifications………………………..….……….. Page 37
11.7.2 SC-100T Specifications……………………..…………… Page 37
11.7.3 SC-80T Linear Diagram.................................................... Page 38
12 Error codes ………………………………………………………………… Page 39
13 Modify input type: TC, RTD
13.1 FY400~FY900………………………………………………………… Page 40
13.2 FY100~FY101………………………………………………………… Page 41
14 Modify input type: Linear Input (mA ,V)
14.1 FY400~FY900 Hardware ……………………………………………… Page 43
14.2 FY100~FY101 Hardware……………………………………………… Page 44
14.3 Calibration ……………………………………………………………… Page 45
15 Modify output type: Relay, SSR, 4~20mA ………………………………… Page 46
16 Modify output mode: OUT1/ALARM, OUT1/OUT2 ……………………… Page 46
17 Applications
17.1 RAMP & SOAK ………………………..……………………………… Page 47
17.2 TTL Communication:SV output and RATE function……………… Page 48
17.3 1ψ Phase angle control (By SCR module) ………………………… Page 49
17.4 1ψPhase angle control (By TRIAC) …………...…………………… Page 50
17.5 3ψPhase angle control ( By DIODE/SCR module)……………….. Page 51
17.6 1ψZero crossing control (By SCR Module) ………………..……… Page 52
17.7 1ψZero crossing control (By TRIAC) ……………….……………… Page 53
17.8 3ψZero crossing control (By SCR module) ……………………… Page 54
17.9 3ψZero crossing control (By TRIAC) ……………………………… Page 55
17.10 3 wires proportional motor valve control ……………..………… Page 56
17.11 Wiring diagram of PC Communication …………………………. Page 57
2
1. Notice before start-up
FY series controller has got the CE approvals as below:
LVD: D/N EN61010-1
EMC: EN 55 022 1994 /A1:1995/ A2:1997
EN 61 000-3-2: 1995 / -3-3: 1995
EN 61 000-4-2: 1995 / -4-3: 1996 / -4-5: 1995 / -4-6
1996 / -4-8: 1993 / -4-11:1996/ EN 50 204: 1995
Please confirm the specification of controller is to totally with your requirement before
using it, also read this manual in detail.
Danger
1. Danger! Electric Shock!
DON'T touch AC power wiring terminals when controller has been
powered!
Keep the power off until all of the wirings are completed!
Warning
1. Please confirm the AC power wiring to controller is correct, otherwise it would be
caused aggravated damage on controller. ( FY400 connecting with Pin 1 and 6,
FY100/FY101/FY600/700/800/900 with Pin 1 and 2).
2. Be sure to use the rated power supply (AC85~265V or DC24V), otherwise it would be
caused aggravated damage on controller.
3. Please confirm wires are connected with correct terminal (Input, Output).
4. Use M3 screw-compatible crimp-on terminals with an insulation sleeve, as shown
below
3.2mm 3.2mm
3
1. Specifications
z Standard spec.
Model FY400 FY600 FY700 FY800 FY900 FY100 FY101
Dimension 48X48mm 96X48mm 72X72mm 48X96mm 96X96mm 175X110mm 90X90mm
mA dc 4~20mA ,0~20mA
mV / V dc 0~1V,0~5V,0~10V,1~5V,2~10V
-10~10mV,0~10mV,0~20mV,0~50mV,10~50mV
Decimal point 0000 , 000.0 , 00.00 , 0.000
position Available for linear input (mA / mV / V)
Relay SPST type SPDT type SPST type SPDT type SPDT type SPDT type SPDT type
Voltage pulse For SSR drive. ON : 24V , OFF : 0V , max load current : 20mA
mA dc 4~20mA, 0~20mA. Maximum load resistance:560 Ω
Voltage dc 0~5V , 0~10V , 1~5V , 2~10V . Max load current:20mA
Alarm 1 3A , 220V , electrical life:100,000 times or more (under rated load)
Control algorithm PID,PI,PD,P,ON / OFF(P=0),FUZZY。
PID range P: 0.0 ~ 200.0 %,I: 0~3600s,D: 0~900s
Isolation Output terminals(control output , alarm , transmission) and input
terminals are isolated separately
Isolated resistance 10MΩ or more between input and case (ground) at DC 500 V
10MΩ or more between output and case (ground) at DC 500 V
Dielectric strength 1000V AC for 1 minute between input terminal and case (ground)
1500V AC for 1 minute between output terminal and case (ground)
Operating 0~50℃
temperature
Humidity range 20~90%RH
Weight 150g 225g 225g 225g 300g 130g 80g
Display Height PV:7mm PV:7mm PV:14mm PV:7mm PV:14mm
4
z Optional Spec.
Model FY400 FY600 FY700 FY800 FY900 FY100 FY101
Output 2 For heating and cooling control use.
Relay , SSR , 4~20mA , 0~20mA , 0~5V , 0~10V , 1~5V , 2~10V
Alarm 2 Available Available Available Available Available Available Not
SPST type SPDT type SPST type SPDT type SPDT type SPDT type available
Alarm 3 available SPST type SPST type SPST type SPST type SPST type available
Programmable RAMP/SOAK
Model PFY400 PFY600 PFY700 PFY800 PFY900 PFY100 PFY101
Programmable 2 patterns with 8 segments each.
RAMP/SOAK The 2 patterns can be linked together as 16 segments use.
5
3. Terminal arrangement
3.1 FY400 Terminals ( 48mm x 48mm , DIN 1/16 )
A.Power Supply
AC 85~265V
DC 15 ~50V(Option)
H.CT Input
11
CT
12
D.Alarm
(Use OUT1 & OUT2)
(Option) AL 1 AL 2 (Proportional Motor
Valve Control)
OUT1 OUT1
2 13 11
(1ΦZero Cross (Proportional Motor AL 1
Control) Valve Control)
3 14 12
G1
K2 COM Dx+ SD 12
SD 12 12
SG 13 SG 13
6
3.2 FY600 Terminals ( 96mm x 48mm , DIN 1/8 )
A.Power Supply
1 11
2 12
AC 85~265V
DC 15 ~50V(Option) 3 13
4 14
5 15
6 16
H.CT Input
7 17
8 18 14
9 19 CT
10 20 15
D.Alarm E.Transmission
AL 1 AL 2 AL 3 TRS
(Option)
6 12
OUT1 OUT1 13
7
(Proportional Motor (1ΦPhase
Valve Control) Angle Control)
6 7 K2
7
3.3 FY700 Terminals ( 72mm x 72mm)
A.Power Supply
1 15 8
2 16 9
AC 85~265V
3 17 10
DC 15 ~50V(Option)
4 18 11 H.CT Input
5 19 12 15
6 20 13 CT
7 21 14 16
D.Alarm E.Transmission
AL 1 AL 2 TRS
(Option) COM
3 8 18
OUT1 OUT1 OUT1
(Proportional Motor (1ΦZero Cross (1ΦPhase Angle NO 19
Control) Control) 4 9
Valve Control)
3 15 G1 15 G1
NC 10
4 CLOSE 17 G2 16 K1
G.Communication F.Remote
5 OPEN 19 17 G2
RS232 RS485 TTL Remote SV
6 20 18 K2 RD 15 Dx- 15 RD 15 9
PROT
7 COM 20 SD 16 Dx+
16 SD 16 10
21 SG 17 SG 17
PROT
8
3.4 FY800 Terminals ( 48mm x 96mm , DIN 1/8 )
A.Power Supply
1 11
2 12
AC 85~265V
DC 15 ~50V(Option) 3 13
4 14
5 15
6 16
H.CT Input
7 17
8 18 14
9 19 CT
10 20 15
D.Alarm E.Transmission
AL 1 AL 2 AL 3 TRS
(Option)
6 12
OUT1 OUT1 13
7
(Proportional Motor (1ΦPhase
Valve Control) Angle Control)
6 7 K2
9
3.5 FY900 Terminals ( 96mm x 96mm , DIN 1/4 )
A.Power Supply
1 21 31 11 E.Transmission
TRS
2 22 32 12
39
AC 85~265V
DC 15 ~50V(Option) 3 23 33 13
40
4 24 34 14
5 25 35 15
6 26 36 16
15 10 30 40 20 15
31 G1 31 RG1 18 18 18
33 G2 33 RG2 19 19 19
39 35 TG1 20 20 20
10
3.6 FY100 Terminals ( 175mm x 110mm )
11
3.7 FY101 Terminals ( 90mm x 90mm )
12
4. External dimension and panel cutout〈Unit:mm〉
13
4.3 FY400-900
44.5+0.5
50
70 44.5+0.5
FY400
Y1
Y2
AT
AL1
AL2
PRO
50
65
90.5+0.5
96
FY600 50
70
44.5+0.5
111
68.5+0.5
74
68.5+0.5
FY700 94
74
89
44.5+0.5
50
90.5+0.5
FY800 96
116
65
90.5+0.5
96
90.5+0.5
116
FY900 96
111
14
5. Parts description
FY400 FY600 FY800 FY700 / FY900/ FY100/101
1 2 External Interface Unit
8 9 10 11 12 13 14 15
8 11 8 9 12 16 5 7 9 10
9
1
Y1
Y2
8 11 1
AT
10
AL1
12 15
2 11
AL2
PRO 13 14
2
12
16
15 7
4 16
3 5 6 7 1 2 13 10 15 14 4 3 6
3 5 6
3 4 5 6 7
All LED and 7 segment Display input type Display range Ready for use
displays will be lighted (K2) (0.0~400.0)
Press key. The SV Press key Press key Press SET key
number started to flash. to select the hundreds digit. to change the number to 1 to store the new
The flashing digit indicates set value.
which digit can be set.
* The are total 16 alarm mode types, please referred with “alarm mode” in page 30
* To change alarm mode, press SET + key 5 seconds to enter Level 3 (Input
Level) and then change ALD1/ALD2/ALD3 value.
16
6.4 Autotuning (AT)
Use AT function to automatically calculate and set the optimize PID value for your system.
Press SET key Press key Press key Press SET key
to display parameter AT. to change AT setting change AT to “YES" Start auto tuning
(AT lamp will be
lighted on)
Autotuning
Autotuning
ATVL=20
ATVL=0 *Set ATVL to prevent overshoot occurred during
autotuning process.
To set ATVL ,press SET key 5 seconds to enter
(Overshoot )
Level 2 (PID Level) and then change the value.
PV
SV SV
SV - 20
PV
100% 100%
Output% ON OFF ON OFF Output% ON OFF ON OFF
0% 0%
Autotuning failure
Possible cause 1: ATVL is too big. (If not sure,set ATVL=0)
Possible cause 2:Calculation time is too long.
(Set PID parameter manually)
17
6.5 Programmable RAMP / SOAK (Only available for PFY model)
*For detail of the programmable instruction, please refer with page 25.
120
Press SET key Set SV_1 to 200.0 Set TM_1 to 01.00 Set OUT1 to 100.0
to display SV_1 (1 hour)
Press key
Set SV_4 to 120.0 Set TM_4 to 01.20 Set OUT4 to 100.0 to run program
(1 hour and 20 minutes) (PRO LED start lighting)
18
7. Operation levels
7.1 Levels diagram
Level 1
(User Level)
LCK = 0000
Press SET Key 5 seconds Press SET Key+ 5 seconds
Level 2 Level 3
Press SET (PID Level) (Input Level) Press SET Key+ 5 seconds
Key 5 seconds
LCK = 1111
Press SET Key+ 5 seconds
19
8. Parameters
8.1 Level 1 (User Level)
PV Process Value
SV Set Value
Set
Output Limt
Set
Autotuning
Set
Alarm 1 set value
Set
20
8.2 LEVEL 2 (PID Level)
To enter level 2, press SET key 5 seconds in level 1
Set Set
Set
Set
Set
Set
21
8.2.2 Description of parameters
Proportional band 1 Range:0.0~200.0%
(For output 1) ON/OFF control if set to 0 (0.0)
Set
Integral time 1 Range:0~3600 seconds
(For output 1) PD control if set to 0
Set
Derivative time 1 Range:0~900 seconds
(For output 1) PI control if set to 0
Set
Reserved Reserved
Set
Auto tuning offset value Range:0~USPL
Set
Range:0~150 seconds
Output 1 cycle time Relay output : 10
Display Set Voltage pulse output : 1 , mA output: 0
If P1=0.0 Hysteresis for output 1
ON/OFF control Range:0~1000
Set
Proportional band 2
(For output 2) The same with P1
Set
Integral time 2
The same with I1
(For output 2)
Display if output2 is provided
Set
Derivative time 2
The same with D1
(For output 2)
Set
Output 2 Cycle time The same with CYT1
Display Set
If P2=0.0
Hysteresis for output 2
The same with HYS1
ON/OFF control
Set
Control gap 1 Set point of output 1 (Heating side)
(For output 1) =SV - GAP1
Set
Control gap 2
(For output 2) =SV + GAP2
Set
Function lock
Return to “P1"
22
8.3 LEVEL 3 (Input Level)
To enter level 3 , set LCK to ”0000”and then press SET key + Shift( ) key 5 seconds.
23
Output 2 low limit calibration
The same with CLO1
(Used for mA and V output)
Set
Output 2 high limit calibration The same with CHO1
(Used for mA and V output)
Set
Retransmission low limit calibration The same with CLO1
Set
Retransmission high limit calibration The same with CHO1
Set
Full run time of proportional motor
( Used for proportional motor valve Range:5~200 seconds
control output)
Set
Used for programmable controller 0=Not wait
to wait continued operation Others=Wait value
Set
Frequency 50 / 60HZ
Set
Return to “INP1"
24
8.4 Level 4 (SET level)
To enter level 4, set LCK to ”1111”and then press SET key + Shift( ) key 5 seconds.
SET 1_ 1
SET 1_ 2
SET 1_ 3
SET 1_ 4
*For the description of Level 1 parameters, please refer with page 17.
*For the description of Level 3 parameters, please refer with page 20.
SET Display / hiding Level SET Display / hiding Level
1_ 1 Level 1 5_ 1 , Level 3
1_ 2 Level 1 5_ 2 , Level 3
1_ 3 Level 1 5_ 3 , , Level 3
1_ 4 Level 1 5_ 4 , , , Level 3
2_ 1 Level 1 6_ 1 Level 3
2_ 2 , , Level 3 6_ 2 Level 3
2_ 3 , Level 3 6_ 3 Level 3
2_ 4 , Level 3 6_ 4 Level 3
3_ 1 Level 3 7_ 1 Level 3
3_ 2 Level 3 7_ 2 Level 3
3_ 3 Level 3 7_ 3 Level 3
3_ 4 Level 3 7_ 4 Level 3
4_ 1 Level 3
4_ 2 Level 3
4_ 3 Level 3
4_ 4 , Level 3
25
8.4.2 Special functions (Use SET8 / SET9 / SET0)
SET 8 Remark
8_ 1 0 : Program not repeat
1 : Program repeat
8_ 2 0 : No power failure option Only available for
1 : With power failure option programmable
8_ 3 0 : Program starts from 0 controller
1 : Program starts from PV
8_ 4 0 : Reserved (Don’t change it)
SET 9 Remark
9_ 1 0 : Reserved (Don’t change it)
9_ 2 0 : Timer Unit = “Hour : Minute” Only available for
programmable
1 : Timer Unit = “Minute : Second”
controller
9_ 3 0 : Disable transmission Used for transmission
1 : SV Transmission output
9_ 4 0 : Disable transmission
1 : PV Transmission
SET 0 Remark
0_ 1 0 : TTL Communication (Slave) Used for TTL
1 : TTL Communication (Master) communication
26
Please don't operate SET 8_4,otherwise the controller's process will be in confusion.
If SET8.4 is set to “1”, the controller will enter into “Single Display” mode, the PV LED will
not display any values. The SV LED will display both the parameter value and the setting
value alternately as shown in the diagram below.
Displayed alternately
PV EMPTY
SV
To rectify the problem please press the SHIFT KEY ( ) and change the setting value to
“0000”.
27
8.5 Program Level (Only displayed in programmable controller)
8.5.1 Description of parameters
LEVEL 1
Set
Program Pattern Setting value of Seg.5
Range:0~2
Set Set
Program Segment display
Set time for Seg.5
( Pattern _ Segment )
Set Set
Program countdown display
Output Limit of Seg.5
Range:0~99 hour 59 min
Set Set
Setting value of Seg.1
Setting value of Seg.6
Range:LSPL~USPL
Set Set
Set time for Seg.1
Set time for Seg.6
Range:0~99 hour 59 min
Set Set
Output Limit of Seg.1
Range:0~100% Output Limit of Seg.6
If OUT=0,program will end.
Set Set
Set Set
Set Set
Set Set
Set Set
Set Set
Set Set
Setting value of Seg.4 Return LEVEL 1
Set
Set
Set
28
8.5.2 Description of operation
1. There are 2 patterns can be used,each pattern contains 8 segments.
2. Terminologies
Pattern :A program consists of some steps.
Ramp status:The status with changing SV.
Soak status :The status with fixed SV.
3. Operating
I. "KEY" function (no changing parameter)
(RUN) :Start program procedure,PRO LED in panel start flicking.
(HOLD) :Suspend program procedure,PRO LED in panel will stop
flicker but still light on.
+ SET(JUMP) :Jump to previous segment.
+ SET (RESET):Reset program procedure,PRO LED in panel will off.
II. Alarm Function:
ALD1 = “07”(Segment end alarm),
AL1 =“2”(It means when segment 2 end,AL1 will act),
ALT1 =“00:10”(Relay on time is 10 seconds).
* In this case,when program proceeds to segment 2 end,the relay of AL1 will
be on 10 seconds.
III. END function:
The Controller doesn’t have END order, so if program procedure is less than 8
segments, please set the last segment’s OUT to “0”. Program will end in this
segment. Otherwise,it will proceed 8 or 16 segments.
IV. Linking Function:
PTN=1 proceed pattern 1,contains 8 segments.
PTN=2 proceed pattern 2,contains 8 segments.
PTN=0 linking proceed pattern 1 and 2 totally 16 segments.
(Please set PTN1 and PTN2 at first,and then set PTN to 0)
V. Other function(*refer to LEVEL 4)
SET 8_1=1 Program repeats.
SET 8_2=0 No power failure function.
SET 8_2=1 Enable power failure function.
(When power shut down and on again,the controller will start from the
segment which is near PV)
SET 8_3=0 Program starts from 0.
SET 8_3=1 Program starts from PV.
29
9. Input type table (INP1 selection)
TYPE CODE RANGE
0.0 ~ 200.0℃ / 0.0 ~392.0℉
0.0 ~ 400.0℃ / 0.0 ~752.0℉
0 ~ 600℃ / 0 ~1112℉
K 0 ~ 800℃ / 0 ~1472℉
0 ~ 1000℃ / 0 ~1832℉
0 ~ 1200℃ / 0 ~2192℉
0.0 ~ 200.0℃ / 0.0 ~392.0℉
0.0 ~ 400.0℃ / 0.0 ~752.0℉
0 ~ 600℃ / 0 ~1112℉
J 0 ~ 800℃ / 0 ~1472℉
0 ~ 1000℃ / 0 ~1832℉
0 ~ 1200℃ / 0 ~2192℉
0 ~ 1600℃ / 0 ~2912℉
R 0 ~ 1769℃ / 0 ~3216℉
0 ~ 1600℃ / 0 ~2912℉
S 0 ~ 1769℃ / 0 ~3216℉
B 0 ~ 1820℃ / 0 ~3308℉
0 ~ 800℃ / 0 ~1472℉
E 0 ~ 900℃ / 0 ~1652℉
0 ~ 1200℃ / 0 ~2192℉
N 0 ~ 1300℃ / 0 ~2372℉
-199.9 ~ 400.0℃ /-199.9 ~752.0℉
T -199.9 ~ 200.0℃ / -199.9 ~392.0℉
0.0 ~ 350.0℃ / 0.0 ~662.0℉
0 ~ 2000℃ / 0 ~3632℉
W5Re/W26Re 0 ~ 2320℃ / 0 ~4208℉
0 ~ 1300℃ / 0 ~2372℉
PLⅡ 0 ~ 1390℃ / 0 ~2534℉
-199.9 ~ 600.0℃ / -199.9 ~999.9℉
U -199.9 ~ 200.0℃ / -199.9 ~392.0℉
0.0 ~ 400.0℃ / 0.0 ~752.0℉
0 ~ 400℃ / 0 ~752℉
L 0 ~ 800℃ / 0 ~1472℉
30
TYPE CODE RANGE
-199.9 ~ 600.0℃ / -199.9 ~999.9℉
JIS -199.9 ~ 400.0℃ / -199.9 ~752.0℉
-199.9 ~ 200.0℃ / -199.9 ~392.0℉
PT100 0 ~ 200℃ / 0 ~392℉
0 ~ 400℃ / 0 ~752℉
0 ~ 600℃ / 0 ~1112℉
-199.9 ~ 600.0℃ / -199.9 ~999.9℉
DIN -199.9 ~ 400.0℃ / -199.9 ~752.0℉
-199.9 ~ 200.0℃ / -199.9 ~392.0℉
PT100 0 ~ 200℃ / 0 ~392℉
0 ~ 400℃ / 0 ~752℉
0 ~ 600℃ / 0 ~1112℉
-199.9 ~ 600.0℃ / -199.9 ~999.9℉
JIS -199.9 ~ 400.0℃ / -199.9 ~752.0℉
-199.9 ~ 200.0℃ / -199.9 ~392.0℉
PT50 0 ~ 200℃ / 0 ~392℉
0 ~ 400℃ / 0 ~752℉
0 ~ 600℃ / 0 ~1112℉
AN1 -10 ~ 10mV / -1999~9999
AN2 0 ~ 10mV / -1999~9999
AN3 0 ~ 20mV / -1999~9999
AN4 0 ~ 50mV / -1999~9999
AN5 10 ~ 50mV /-1999~9999
*The initial setting in factory is “K2”.
31
10. Alarm
10.1 Alarm time (ALT1/ALT2/ALT3)
ALT1=0 Flicker alarm
ALT1=99.59 Continued alarm
ALT1=00.01 ~ 99.58 Alarm on delay time
10.2 SETA
*SETA is in Level 3 (Input level)
}
When "b" contact
If SETA_2=1,AL2 relay will be action reversely (normal close) is
If SETA_3=1,AL3 relay will be action reversely needed
32
10.3 Alarm mode (ALD1 / ALD2 / ALD3)
( :SV :Alarm set value)
Deviation high alarm Process low alarm
with hold action* with hold action*
01 OFF ON 06 ON OFF
HIGH PV PV
LOW HIGH
*Hold action:
When Hold action is ON ,the alarm action is suppressed at start-up until the measured
value(PV) enters the non-alarm range.
*System failed:
It means that the controller display error message with one of following :
”UUU1” or “NNN1” or “CJCE”
33
11. Heater Break Alarm (HBA)
(CT Input)
AL1
(HBA Relay)
(Sensor Input)
OUT1
+ -
SSR
Sensor
AC POWER
Heater
CT
(CT), and compares the CT input value and HBA set value. When OUT1 is ON and CT
input value is less than HBA set value during 5 seconds , AL1 is activated. Otherwise, AL1
is not activated.
The AC current flowing through heater can also be monitored in HBA setting mode.
34
11.3 HBA setting procedure
SV
SV
Heater Current
※ Means current
To store new
HBA set value
Press SET Key
ALD1 9 Level 3
INP2 4 Level 4
¾ How to enter Level 3:Set parameter “LCK”to 0000 in Level 2 , and then press “SET”
¾ How to enter Level 4:Set parameter “LCK”to 1111 in Level 2 , and then press “SET”
35
11.5 Activated conditions of HBA
Condition
1. OUT1 is ON
11.6 Remarks
¾ Available output(OUT1) type for HBA
I. Relay
¾ Since HBA function uses AL1 as alarm relay, please set temperature alarms in AL2 or
AL3.
36
11.7 CT specifications
11.7.1 SC-80T Specifications
Rated Primary Current(Amp.):0.1A~80.0A
Turns Ratio: 800:1
D.C.Resistance Max.at 20 ℃(Ω):45Ω
Accuracy ( Linearity ):3%
Dielectric Withstanding Voltage(Hi-pot):2500Vrms / 1 minute
Approx.Weight:12g
15.0
6.0
5.9
b K
Vout
L
Epoxy
30.0
40.0
38 MAX 15MAX
Ep oxy
39.5MAX
6 .0+1
0
1 .0
25 .2±0 .3
1 3±0 .3
32 .8± 0 .3
1 2
4 3
37
11.7.3 SC-80T Linear Diagram
80
75
70
65
60
55
FY900 Controller Current Value(A)
50
45
40
35
Japan CTL-6-S
30
TAIE-1
25
TAIE-2
20
TAIE-3
15
TAIE-4
10 TAIE-5
0
5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80
Current Generator(A)
38
12. Error codes
DISPLAY DESCRIPTION
Open circuit of main control sensor.(INP1)
* A/D convert failed.
* Cold junction compensation failed.
Open circuit of sub control sensor.(Remote SV)
PV exceeds USPL.
PV under LSPL.
Input signal of sub control exceeds the upper limit.
(Remote SV)
Input signal of sub control under the lower limit.
(Remote SV)
* RAM failed.
Interface failed.
Auto tuning failed.
NOTE:If the “*” marked error comes up,the controller needs to be repaired.
Please send it to the nearest sales office or retail dealer.
39
13. Modify input type (“TC” “RTD”)
If the controller needs to modify input type from TC or mV to RTD ,please make PAD
short on the back side of PC board as following diagram and change input selection(INP1).
On the contrary,modify from RTD to TC or mV,make PAD open.
13.1 FY400~FY900
FY900,FY800,FY600
RTD : Short pads TC or mV : Open pads
FY700
RTD : Short pads TC or mV : Open pads
FY400
RTD : Short pads TC or mV : Open pads
40
13.2 FY100~FY101
If the controller needs to modify input type from TC or mV to RTD ,please make PAD
short on the back side of PC board as following diagram and change input selection(INP1).
On the contrary,modify from RTD to TC or mV,make PAD open.
FY100
No short Pin is
TC(mV)
RTD TC or mV
41
If the controller needs to modify input type from TC or mV to RTD ,please make PAD
short on the back side of PC board as following diagram and change input selection(INP1).
On the contrary,modify from RTD to TC or mV,make PAD open.
FY101
TC or mV RTD
42
14. Modify input type : Linear Input (mA ,V)
FRONT BACK
R1
R4 R2 S1
S2 S4
R5 R3
S3 S5
20 19 ................ 11 11 ............ 19 20
72×72 72×72
( PC Board ) ( PC Board )
FRONT BACK
R1
S1
R4 R2 S2 S4
R5 R3 S3 S5
14 13 .... 8 8 .... 13 14
48×48 48×48
( PC Board ) ( PC Board )
FRONT BACK
R1
S1
R4 R2 S2 S4
R5 R3 S3 S5
10 9 .... 6 6 .. 9 10
43
14.2 FY100/101 Hardware:
FY100 FY101
INPUT ( + ) PIN 14 PIN 10
INPUT ( - ) PIN 11 PIN 8
0~20mA (INP1=AN4):(R3 use 100Ω,R5 use 2.4Ω, S3&S5 SHORT)
4~20mA (INP1=AN5):(R3 use 100Ω,R5 use 2.4Ω, S3&S5 SHORT)
0 ~ 1V (INP1=AN4):(R1 use 2KΩ,R4 use 100Ω,S1&S4 SHORT)
0 ~ 5V (INP1=AN4):(R2 use 10KΩ,R4 use 100Ω,S2&S4 SHORT)
1 ~ 5V (INP1=AN5):(R2 use 10KΩ,R4 use 100Ω,S2&S4 SHORT)
0 ~ 10V (INP1=AN4):(R3 use 22KΩ,R4 use 100Ω,S3&S4 SHORT)
2 ~ 10V (INP1=AN5):(R3 use 22KΩ,R4 use 100Ω,S3&S4 SHORT)
44
14.3 Calibration:
To display ANL1 &
SET 2.2 = 1 ANH1
ANL1=0
ANH1=5000 at INPUT Level
LSPL=0
USPL=5000
Return User Level to view
the changing of PV
Inputs 4mA
Inputs 20mA
NO
OK ?
YES
45
Modify Output type : Relay , SSR , 4~20mA
15. It just needs to change a module at the same position,
and modify parameter CYT1 in LEVEL 2 .
ÎRelay: CYT1=10, Voltage pulse: CYT1=1, 4~20mA:CYT1=0
PAD of OUT2:
PAD of OUT2:OPEN
SHORT
PAD of AL3:SHORT
PAD of AL3:OPEN
11 12 13 14 15 16 17 18 19 20 11 12 13 14 15 16 17 18 19 20
FY700
72×72 FY700
72×72
( CPU Board ) ( CPU Board )
8 9 10 11 12 13 14 8 9 10 11 12 13 14
FY400 FY400
48×48 48×48
( CPU Board ) ( CPU Board )
PAD of AL1:
PAD of AL1:
SHORT
OPEN
6 7 8 9 10 6 7 8 9 10
46
17. Applications
17.1 RAMP & SOAK
z RAMP:
I. SET2.1=1ÎTo display AL3
II. SET4.1=1ÎTo display ALD3
III. ALD3=9ÎOpen RAMP option
IV. Then, AL3 will not display. It was replaced by RAMP.
z SOAK:
I. ALD1 / ALD2=19 Î To use Sock Timer.
II. AL1 / AL2 will display as below:
AL1
Range:00.00 ~ 99.59(Hour.Minute)
00.00
z Example:
SV=100℃,RAMP=10.00 (℃/min),AL1=00.10 min,PV=25℃
℃
Time on Time up
if PV > = SV(100℃) AL1 on
100℃
AL1 00.01 Sock Timer
00.10 00.10 counts
1sec.
SV=SV+RAMP
t
Power on 5 seccons(Start RAMP function)
47
17.2 TTL Communication:SV output and RATE function
z Open RATE function (use for slave controller)
Display AL3 :SET2.1=1
Display ALD3:SET4.1=1
Display RATE(AL3 will be replaced) :SET0.2=1
Set ALD3 to 0. (In Level 3)
Slave SV = (RATE÷9999)×master SV
z Example:
Connection Diagram
RD
RD
SD
SG
SG
SG
PFY900 FY900 FY900
Master Slave 1 Slave 2
SV OUT (SET0.1=1) IDNO=1 (SET5.4=1) IDNO=1 (SET5.4=1)
IDNO=0 (SET5.4=1) BAUD=2400 BAUD=2400
BAUD=2400(SET5.4=1) (SET5.4=1) (SET5.4=1)
open RATE function open RATE function
Time Chart
48
17.3 1ψ Phase angle control (By SCR module)
S R
FAST
FUSE CONTROLLER
K2
G1
G2
SCR
Module K1
G1
G2
K1
K2
Short
PROT
U V
LOAD
** Controller source phase must be same as load source phase
49
17.4 1ψ Phase angle control (By TRIAC)
S R
FAST
FUSE CONTROLLER
G1
T2
TRIAC
K1
Module
G1
G2
T1
K2
Short
PROT
U V
LOAD
U V
1/2W
100Ω 0.1uf/630V
A
C
50
17.5 3ψ Phase angle control (By DIODE/SCR module)
R S T
CONTROLLER
FAST G1
FUSE
K1
K1 K2 K3 DIODE/SCR
G1 G2 G3 Module G2
K2
G3
K3
U V W
PROT
Short
3φ LOAD
51
17.6 1ψZero crossing control (By SCR module)
R S
FAST
FUSE CONTROLLER
G1
G1
SCR
Module
G2
G2
Short
PROT
U V
TIME CHART:
OFF
ON
52
17.7 1ψZero crossing control (By TRIAC)
S R
T2
G1
TRIAC
T1
G1 G2
Short
U V PROT
Load
53
17.8 3ψZero crossing control (By SCR module)
R S T CONTROLLER
FAST RG 1
FUSE
SCR RG 2
Module
RG 1 TG 1
TG 1
RG 2 TG 2
TG 2
U V W
WE CAN SUPPLY
HEATER SINK
PROT
Short
TIME CHART:
OFF
ON
54
17.9 3ψZero crossing control (By TRIAC)
R S T Controller
(RG 1)
Fast Fuse
T2 T2
(RG 1) (TG 1) (RG 2)
(TG 2)
U V W
Short
PROT
55
17.10 3 wires proportional motor valve control
MOTOR VALVE
COM
R CONTROLLER
CLOSE OUT2
Relay
CLOSE
OPEN
OPEN
COM OUT1
Relay
56
17.11 Wiring diagram of PC communication
RS232 Connection Diagram
COM PORT :
9PIN ( DTE ) Controller
Pin 3 (T)
RD
Pin 2 (R)
SD
Pin 5 (G)
SG
PC
COM PORT :
25PIN ( DTE ) Controller
Pin 2 (T)
RD
Pin 3 (R) SD
Pin 7 (G) SG
PC
NOTE:
1.The length of cable be connected between controller and PC can't exceed 15 meter.
3.Ensure that the controller's IDNO and BAUD settings are the same with PC software's settings.
DCE DX -
(Cable) 1 (T+) DX +
2 (T-)
TxON 3 (R-)
PC RxO 4 (R+)
N
NOTE:
1.The length of cable be connected between Converter and Controller can't exceed 1.2 KM.
Suggestion:choose "Shielded Cable".
3.Ensure that the Controller's IDNO and BAUD settings are the same with PC software's settings.
57