(Week 9) Transformers Analysis
(Week 9) Transformers Analysis
Transformers Analysis
IDEAL TRANSFORMER
Ideal Transformer
• Winding resistances are zero, no leakage inductance and iron
loss
• Magnetization current generates a flux that induces voltage in
both windings
𝑁!∅" 𝜔 Im Fm
𝐸! =
2
𝑁#∅" 𝜔 V1 E1 N1 N2 E2 = V2
𝐸# =
2
= 4.44𝑁#∅" 𝑓
Im + I I2
1 Fm
V1 E1 F1 F2 E2 V2
Load
N1 E1 I 2
a= = =
N 2 E 2 I1
In-Class Activity 2:
As an in-charge person in an electrical plant, you are required to analyze
and design a transformer with specific application for your plant. It is a
single-phase transformer (ideal with unity power factor) with 15 kVA
power rating. You only have AC source of 40 A and you are required to
generate 10 A of AC current.
I1 I2
T
Vac V1 V2 Zload
Ideal Transformer
• Equivalent circuit when I1
secondary impedance is
transferred to primary side Vac V1 a2Zload
and ideal transformer
eliminated.
PRACTICAL TRANSFORMER
Practical Transformer
Equivalent Circuit
• In a practical magnetic core having finite
permeability, a magnetizing current Im is
required to establish a flux in the core.
– This effect can be represented by a magnetizing
inductance Lm.
• The core loss can be represented by a
resistance Rc.
Equivalent Circuit
N1 E1 I 2 I1 = I 0 + I1 '
= =
N 2 E 2 I1 '
Equivalent Circuit
• Winding resistance and leakage flux
R2 ' = a R22
V2 ' = aV2
X 2 ' = a2 X 2 I1 ' = I 2 / a
Approximate Equivalent
Circuit
• Phasor diagram of a loaded transformer
(primary)
Approximate Equivalent
Circuit
• For convenience, the turns is usually not shown
TRANSFORMER TEST
Transformer Test
• The equivalent circuit model for the actual transformer can be
used to predict the behavior of the transformer.
• The parameters Rc, Xm, R1, X1, R2, X2 and N1/N2 must be
known so that the equivalent circuit model can be used.
• These parameters can be directly and more easily determined
by performing tests:
– No load test (or open circuit test)
– Short circuit test
Transformer Test
• No load/Open circuit test
– Provides magnetizing reactance (Xm) and core loss
resistance (Rc)
– Obtain components are connected in parallel
• Short circuit test
– Provides combined leakage reactance and winding
resistance
– Obtain components are connected in series
Transformer Test – Open Circuit
• Equivalent circuit for open circuit test, measurement at the primary side
P oc
X1 R1 X2 R2
A W
I oc
V X Rc
m
V oc
#
𝑉"!
–. %&
𝑃"!
𝑅! = 𝜃$ = 𝑐𝑜𝑠
𝑃"! 𝑉"! 𝐼"!
#
𝑉"!
𝑄 = 𝑉"! 𝐼"! sin 𝜃$ 𝑋' =
𝑄
–.
Transformer Test – Short Circuit
• Short circuit test
– Secondary (normally the LV winding) is shorted, that
means there is no voltage across secondary terminals; but a
large current flows in the secondary.
– Test is done at reduced voltage (about 5% of rated voltage,
with full-load current in the secondary.
• Hence the induced flux are also 5%. The core losses is negligible
since it is approximately proportional to the square of the flux.
• So, the ammeter reads the full-load current; the wattmeter reads the
winding losses, and the voltmeter reads the applied primary
voltage.
Transformer Test – Short Circuit
• Equivalent circuit for short circuit test, measurement at the primary side
P sc R1 X1 R2 X2
A W
V I sc
V sc
V I sc
V sc
Transformer Test – Short Circuit
• Simplified circuit for calculation of series impedance
P sc
Re1 X e1
A W
V I sc
V sc
2
Re1 = R1 + a R2
2
X e1 = X 1 + a X 2
Transformer Test – Short Circuit
• Short circuit test evaluation
– . 𝑃)! 𝑉)!
𝑅(& = # 𝑍(& =
𝐼)! 𝐼)!
– . # #
𝑋(& = 𝑍(& − 𝑅(&
Transformer Test
• Equivalent circuit for a real transformer
resulting from the open and short circuit tests.
X e1 R e1
Xm Rc
Transformer Test
Example 5
• Obtain the equivalent circuit of a 200/400V,
50Hz 1-phase transformer from the following
test data:-
– O/C test : 200V, 0.7A, 70W - on L.V. side(LV
data)
– S/C test : 15V, 10A, 85W - on H.V. side(HV
data)
(Rc = 571.4 Ω, Xm = 330 Ω, Re = 0.21 Ω, Xe = 0.31 Ω)
VOLTAGE REGULATION
Voltage Regulation
• Most loads connected to the secondary of a transformer are
designed to operate at essentially constant voltage. However,
as the current is drawn through the transformer, the load
terminal voltage changes because of voltage drop in the
internal impedance.
• To reduce the magnitude of the voltage change, the
transformer should be designed for a low value of the internal
impedance Zeq
• The voltage regulation is defined as the change in magnitude
of the secondary voltage as the load current changes from the
no-load to the loaded condition.
Voltage Regulation
• The voltage regulation is expressed as follows:
𝑉!"# − 𝑉!$#
𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 (%) = ×100%
𝑉!$#
– V1 = no-load voltage
– V2’ = secondary voltage referred to the primary (full-load condition)
Voltage Regulation
• Consider the equivalent circuit referred to the
secondary,
I2' R1' X1' X2 R2 I2
V2NL V2 Z2
I 2 Re 2 cosθ 2 ± I 2 X e 2 sin θ 2
Voltage regulation =
V2 NL
– (-) : leading power factor
– (+) : lagging power factor
Voltage Regulation
• Consider the equivalent circuit referred to the
primary,
I1 R1 X1 X2' R2' I1'
V1 V2' Z’2
EFFICIENCY
Efficiency
• Losses in a transformer
– Copper losses in primary and secondary windings
– Core losses due to hysteresis and eddy current. It
depends on maximum value of flux density, supply
frequency and core dimension. It is assumed to be
constant for all loads
Efficiency
• Equipment is desired to operate at a high efficiency.
• Efficiency is defined as