The Hot Bypass Pressure Control Rev. Agosto 2018
The Hot Bypass Pressure Control Rev. Agosto 2018
The Hot Bypass Pressure Control Rev. Agosto 2018
design review
Petrobras S.A.
[email protected]
The hot-vapor bypass pressure control of distillation column: a
design review
Abstract
The hot-vapor bypass has been designed for pressure control of distillation column for more than forty
years. The pressure balance between the top of the column and the overhead drum and the energy
balance into the overhead drum have been used to size the hot bypass valve. Nevertheless, the
overhead drum dimension has not been taken into consideration, even with the assumption that the hot
bypass vapor is totally condensed inside the overhead drum. The liquid surface area and the liquid
temperature inside the overhead drum determine the hot bypass vapor flow rate that is condensed inside
the drum and rule the energy balance into the overhead drum and the liquid temperature inside the
overhead drum. This paper describes the design criteria for sizing the hot bypass control system taking
into account the overhead drum size. Some problems are reported when these criteria have not been
considered.
Keywords
Pressure control
Distillation column
An optimum distillation column design minimizes total cost: the fixed capital cost of the equipment
plus the variable cost of operation. Capital costs are the total fixed project costs to design, construct, and
start-up the process. Variable costs are the operating costs of utilities, raw material, and workforce.
There are several shortcut methods for distillation column designing. Conventional method can
design the distillation column taking into account the degrees of freedom available for design. The
degrees of freedom are the total number of variables less the total number of equations describing the
problem. The design of the distillation column has five degrees of freedom. There are five more variables
than equations. Usually, the procedure to design a distillation column first determines which variables will
be set and what variables will be calculated by the design. The method must therefore set five variables
Typical production objectives require delivery of products that have compositions within certain
specifications. Column pressure will be set by utility considerations. The design procedure also fixes a
minimum approach temperature in the reboiler and condenser. Given these conditions, an optimization
step will be follow the design to find what reflux ratio and feed stage location produce the most
economical design of the distillation column system. As a result, the designer finds the number of trays,
To the process control engineer a two product single distillation column typically has also five
degrees of freedom:
The process control objective is to regulate the product compositions in this process on a desired
set point. The control engineer first step to determine the pairing of control and manipulative variables of
material in the overhead drum and column bottom. Therefore two degrees of freedom must be used for
Ideally we should measure and control compositions to meet these objectives. Compositions are
they can be difficult to maintain. For these reasons, composition analyzers sometimes are not preferred.
In general, the composition, temperature, and pressure of a boiling mixture are thermodynamically
related. Column pressure has a direct influence on the separation capability of the column. The pressure
control significantly affects the variable cost, and it is necessary to take into consideration the
controllability and stability of process during column design, because they have an effect on the
equipment sizes and consequently on the capital cost. If the pressure is difficult to control, it will require
additional labor to operate and create higher utility and raw material costs due to upsets. Therefore, it is
important to hold the column pressure constant when the column are being designed and operated.
Chin1 observed that column pressure is one of the most difficult distillation variables to control. In his
paper, Chin presented a description of 21 different pressure control methods showing advantages,
Among these pressure control methods, the hot-vapor bypass is one of the most used when the
overhead vapors from the column are totally condensed. The hot-vapor bypass has been designed for
pressure control of distillation column for more than forty years. Whistler 2 reported that in 1954 the hot-
vapor bypass was a recent design practice. Chin commented that this method has been controversial for
several reasons. First, the merits of locating the condenser at ground level versus higher are hard to
quantify, although for maintenance, it means that inspection, bundle pulling, cleaning are very much
easier; and there is an attractive savings in steelwork, platforms and trolleys. Second, it is not easy to
understand how the method works. Third, the design is empirical. And finally, some installations have
failed; yet others are operating successfully. Sloley 3 and Lieberman4 presented some case of study and
A typical arrangement for hot-vapor bypass on distillation column is shown in the figure 1. This
condenser is mounted at the ground level below the overhead drum. The condenser is submerged.
Flooding the condenser shell with condensate manipulates the heat transfer rate, in spite of the fact that it
requires more area than an elevated condenser of equal condensing capacity. This additional area
PCOL PIC
MBYPASS
MLCOND
PDRUM
MVAPOR T-1
H
x=0
P-1-- HDRUM
x
HCOND
TLCOND grade
level
THE CONVENTIONAL DESIGN METHOD FOR SIZE THE HOT-VAPOR BYPASS PRESSURE
SYSTEM
Durand4 described a method that determines the proper control valve size by estimating the amount
of vapors that must be bypassed in order to maintain the required pressure in the column. Basically, it
makes the energy balance in the overhead drum taking into account that the condensate is always
subcooled at the condenser outlet. Durand made the assumptions that the amount of vapor bypassed
must be enough to heat the subcooled condensate to the saturation temperature at overhead drum
pressure. Equation (1) reproduces the energy balance considering this assumptions:
The pressure balance arrives that the pressure drop across the bypass valve is principally the
difference in static head between the overhead drum and the condenser levels, assuming the condenser
Durand remarked that the distance between overhead drum liquid level and grade usually is defined
by NPSH (net positive suction head) requirements of distillate pumps. Moreover, although the sub-cooling
depends on heat transfer conditions at condenser, the sub-cooling temperature is assumed to be equal 5
oC above inlet water temperature at the condenser. These assumptions, which are the empirical design
rules mentioned by Chin, will yield a conservative system design, over-sizing the bypass valve.
One of Durand premises is that the overhead vapors bypassed are totally condensed into the
overhead drum. Thus, the vapors bypassed enter the drum above the liquid level. The liquid surface in
the drum is cooler than the vapor saturation temperature. The method described by Durand does not take
into consideration the physical mechanisms of heat transfer and condensation that occur at the vapor-
liquid interface.
Condensation occurs when the temperature of a vapor is reduced below the dew point. The latent
energy of the vapor is released; heat is transferred to the liquid surface. There may be several
complicating features associated with this condensation. The liquid condensed at the top of the liquid
surface flows downward under the influence of gravity. A thin layer of condensed liquid is formed at liquid-
vapor interface, and the temperature, which is at this interface, is the saturation temperature TSAT.
However, the liquid under this layer is maintained at a temperature below the saturation temperature.
Despite the difficulties of the condensation at overhead drum, Tundidor8 showed that it guards
similarities with turbulent film condensation on a vertical plate described by Bayazitoglu 6. Tundidor noted
that the similarities come from the fact that the condensation takes place continuously over the vertical
plate which is kept cooled, the plate is covered with a thin layer of liquid, and the condensed liquid is
removed from the plate surface by the force of gravity. This situation is known as filmwise condensation.
Incropera7 wrote that Nusselt was the first that had analyzed the laminar filmwise condensation over a
vertical plate at a constant temperature. Bayazitoglu also underlined that Kirkbride had proposed the
empirical correlation valid for Re>1800 for film condensation on a vertical plate after start of turbulence,
1/ 3
L2
h m 2
= 0.0077 (Re)0.4 (3)
kL L g
2
Departing from equation (3) Tundidor showed that the total mass flow rate of condensate at liquid-
From equations (3), (4) and (5), Tudidor arrived in equation (6).
g L2 A L (TSAT − TDRUM )
1/ 3
kL
M 0,6
= 0,0134 (6)
VAPOR ( L )0 ,4 2 VAPOR
L L
Where:
AL = L D (7)
The equation (6) indicates that the mass flow rate of condensate at liquid-vapor interface depends
on the area of the interface, the sub-cooling temperature of the liquid inside the overhead drum and
physical properties of the condensate. One of the assumptions adopted by Durand was that the
temperature of the liquid inside the overhead drum would be at the saturation temperature. However, the
equation (6) would result that there would be no mass flow rate of condensate at liquid-vapor interface,
since T is equal zero. This contradiction leads us that the temperature of the liquid inside the overhead
drum must be subcooled. When the temperature of drum is at saturation temperature; the bypass valve
In other words, Tudidor showed that the overhead drum has one important role in hot-vapor bypass
system design, because the size and the temperature liquid inside the overhead drum determines the
So far, The equations (1) to (6), which are utilized for hot-vapor bypass system design, were
obtained by using the formulas commonly used for steady pipe flows. But, its dynamic response is
sometimes of interest. In fact, we are interested in how the pressures of column and overhead drum vary
with time.
In the hot-vapor bypass configuration, the column pressure PCOL and drum pressure PDRUM are
exerted by a gas whose inertia and viscosity may be considered negligible compared with those of liquid
into pipe and condenser. If the pressures vary with time, the flow of liquid and the pressure drop due to
friction across the pipe and condenser vary with time. The variation of liquid flow rate in the pipe and
condenser is caused by action of various forces. Equation (8) represents the force balance considering
the liquid in the pipe and condenser as free body and taking into account the following forces:
1. The gravity force (weight) distributed uniformly over the whole body of fluid.
2. The force due to the wall shearing stress related to the motion of the liquid.
3. The forces on the two ends of the free body due to pressures PCOL and PDRUM.
4. The effective mass of moving liquid. Based on the kinetic energy we can arrive that the effective
mass of moving liquid is four-thirds of the actual mass in the pipe and condenser.
d2 d2 1
P − g x − d Z 0 = d 2 Z x (8)
4 2 3
Where:
The force per unit area is known as the shear stress (). The turbulent wall shearing stress is
shear stress and liquid velocity in pipe and condenser. When the force due to wall shearing stress is
substituted in equation (8) results is a nonlinear differential equation because of the term x
1, 75
. This
nonlinear equation cannot be solved analytically. Nevertheless, Doebelin 8 reported that engineers
have developed a useful and practical method of analysis, which have been verified in experimental
tests. This approach is based on the observation that the linearization of term x
1, 75
does not result
in a form of oscillation radically different from the nonlinear approach if the pressure disturbances
X(s ) 1 (2 g )
=
P(s )
(14)
2 0,107 0, 25 Z VAV 0,75
s2 + s +1
(3 g Z) d 1,25 g 0, 25
systems. The shape of the transient response can generally be characterized satisfactorily by two
parameters, a frequency and a damping coefficient. Equation (14) can be rewrite as a second-order
form:
X(s ) K
=
P(s )
(15)
1 2
s2 + s +1
n2 n
Thus, the gain, frequency and damping coefficient are:
1
K= (16)
2 g
3 g
n =
2 Z (17)
0,0655 0, 25 VAV0,75
Z
= (18)
d
1,25 0 , 25
g
The significance of n and becomes apparent after considering a step change in pressures input
P. With a damping coefficient less than 1, the output (x), which means the submerged tube of
condenser, overshoots the final value and oscillates before coming to equilibrium. The system is known
as an underdamped system. The equations (17) and (18) show us that the hot-vapor bypass system can
easily be underdamped. To avoid oscillations, we can change two parameters in equations (17) and (18),
Z and VAV. Z is the distance between overhead drum and condenser liquid level, and as Durand remarked
VAV is the average velocity of the liquid in pipe and condenser shell. Therefore, it is related to
pressure drop across the pipe and condenser shell. In others words, if the pressure drop across the pipe
and condenser shell increase, which implies that VAV also increase, the damping coefficient will increase,
which means that the hot-vapor bypass system will have a dynamic response with less oscillations. As a
result, the pressure drop across the pipe and condenser shell is an important variable to sizing the hot-
Furthermore, lets examine the hot-bypass system at minimum required capacity. Minimum capacity
means that more tubes of the condenser are submerged. So, Z increases. The pressure across the
condenser would decrease, and the temperature at condenser outlet and in the overhead drum would be
lower because the condenser has more tubes submerged. Thus when the condenser operates at
minimum capacity the hot-vapor bypass becomes more underdamped. Moreover, the equation (06)
indicates that the flow rate of vapor bypassed would increase because the temperature and in the
CONCLUSIONS
Many assumptions were made in the above analysis. The formulas for steady state were
employed for an unsteady situation. Turbulent equations were used for the analysis and the nonlinear
differential equation actually has no analytical solution. Thus what is the meaning of n and attached to
the hot-vapor bypass process? A more complete theory and some supporting data shall be made.
Despite the fact of the simplified analysis, some important conclusion can be taken from the
above appraisal:
• The size and subcooled temperature of liquid of the overhead drum determines the mass flow rate
• The liquids inside the overhead drum and at condenser outlet are not in equilibrium with vapor, but
they are subcooled. The temperature at condenser outlet is lower than temperature in the overhead
drum.
• The pressure drop across the pipe and condenser shell is an important parameter. It shall be as
• It is important to examine the hot-bypass system at minimum required capacity, as well as in nominal
capacity, since at minimum capacity the hot-vapor bypass becomes more underdamped than at
nominal capacity.
NOMENCLATURE
Re Reynolds number.
s Laplace variable.
n Frequency, rad/s.
Damping coefficient.
REFERENCES
1. WHISTLER, Arthur M. Locate condenser at ground level. Petroleum Refiner, Vol. 33, No. 3, March
1954, p. 173-174.
2. CHIN, T. G. Guide to distillation pressure control methods. Hydrocarbon Processing, October 1979,
p. 145-153.
3. SLOLEY, Andrew W. Troubleshooting with exchanger liquid levels. AIChE Spring Meeting:
Symposium on Industrial Applications in Process Heat Transfer, New Orleans - Louisiana – 8-12
March 1998.
4. LIEBERMAN, Norman P and LIEBERMAN, Elizabeth T. A working guides to process equipment: How
process equipment works. 1 ed. McGraw-Hill, Inc: New York, 1997. Cap. 13. p. 147-161.
5. Durand, Alejandro A. Sizing hot-vapors bypass valve. Chemical Engineering, August 25, 1980, p.
111-112.
6. BAYAZITOGLU, Yildiz and Özisik, M. N. Elements of heat transfer. International edition. McGraw-Hill,
7. INCROPERA, Frank P. and DeWITT, David P. Fundamental of heat and mass transfer. 3a ed. John
8. TUNDIDOR, Miguel A. Modelo para cálculo do “hot bypass”. Unpublished report. Revisão 0.
Petrobrás/CENPES. 07/02/1996.
9. HOLLAND, F. A. Fluid flow for chemical engineers. 2a ed. Edward Arnold Publishers Ltd. London,
1980.