Interoperability Test On IED
Interoperability Test On IED
net/publication/326047207
CITATION READS
1 997
2 authors:
All content following this page was uploaded by Mayada Daboul on 18 March 2019.
Abstract—Over the last years, the standard IEC 61850 related the switchyard are usually connected to the control
to automation systems within electrical substation has been room via fibre optic cables.
considered as a promising solution to provide better quality of
power supply and to cope the issue of increasing energy demand. The fundamental objective of this standard is to define
IEC 61850 as a communication protocol in the substation functional architecture, communication structure and the
automation provides efficient performance through the exchange substation requirements. Furthermore, it allow the
information in real-time. Moreover, one of the main motivations communication between IEDs and the operation centre
of using this standard is interoperability. However, connecting (vertical communication), between two or more IEDs
several IEDs manufactured by different vendors which are (horizontal communication), and between the process level and
compliant with IEC 61850 standard is not a trivial task. This the IEDs.
paper presents a method for interoperability testing of
multivendor IEDs based on the IEC61850 standard and includes Achieving substation level interlocking, protection / control
the laboratory results of the testing. functions are the most relevant items to ensure interoperability
between IEDs that can be provided by that standard. However,
Keywords— IEC61850; SAS; GOOSE; interoperability connecting several IEDs manufactured by different vendors
which are compliant with IEC 61850 standard is not a trivial
I. INTRODUCTION task.
International Electrotechnical Commission (IEC) issued This paper demonstrates the influencing factors on
IEC 61850 in 2003 as a communication standard for a interoperability between IEDs, also describes the need for
substation automation system. IEC 61850 used firstly in wind interoperability testing. It also presents a method for
power and then on hydroelectric power plants and on interoperability testing of multivendor IEDs and includes the
Distributed Energy Resources (DERs) [1]. Substations used hardware and software.
Automation Systems (SAS) has been used in modern
substation based on communication protocol standard IEC II. GOOSE MESSAGES
61850 that facilitates the interoperability among third-party
IEC61850 defined generic substation events (GSE) model
IEDs. Moreover, IEC 61850 has used in protection schemes to
to transfer event data between connected IEDs over substation
enhance the stability and the power quality of the system by
networks. GSE ensure that the same event message will be
very fast fault clearing for different faults.
received by single or multiple IEDs through multicast Ethernet
Electrical substation have developed thanks to this standard services. The GSE control model can be presented by two
features which can mention some of them: types of events. First is generic object oriented substation
events (GOOSE) that composed of status and analogue data
Low project costs including installation, and (dataset) directly embedded into Ethernet data packets. Second
maintenance of automation systems and is generic substation state events (GSSE), which involves only
protection/control schemes. status data that included directly into Ethernet packets [2].
Increasing the system reliability through direct access GOOSE messages allow the communication between IEDs and
to all local and remote substation control points and the process level. In another words, Current Transformers
replacing the centralized Remote terminal unit (RTU). (CTs) and Voltage Transformers (PTs) located at process level
can be associated with merging units that publish GOOSE
Simplification the communication infrastructure messages including voltage and current samples to the devices
between IEDs. at bay level. GOOSE messages have replaced the hard wired
signals exchanged between IEDs for interlocking and
Getting rid of electromagnetic interference in the
protection purposes. GOOSE message delivers the IEDs
control room in case of utilising a merging unit or
indication that a new event has occurred and the time of event
optical transducer technologies; where merging units in
This research work has been carried out in the Centre for Research and
Utilization of Renewable Energy (CVVOZE). Authors gratefully
acknowledge financial support from the Ministry of Education, Youth and
Sports of the Czech Republic under NPU I programme (project No. LO1210
Energy for Sustainable Development) and BUT specific research
programme (project No. FEKT-S-17-4784 New Technologies for
Sustainable Power Engineering II).
CONCLUSION
Fig. 3. System configuration IEC 61850 is widely used today, with hundreds of
Network analyser is used to sniff the network and capture substations already in service; this standard is accompanied
the network messages as is displayed if Fig. 4. with some of challenges arising from lack of knowledge about
this standard. Wherefore, it is important to understand the
basics of IEC 61850 and also learn each IED’s configuration
tools in order to reduce the IEC 61850 issues during
configuring process into protection schemes.
Some of IEC 61850 challenges has discussed. It was
figured out that differences in IED configuration tools lead to
many configuration issues such as import or export errors of a
specific SCL type file.
Lastly, it has been shown the timing test comparison
between a hardwired relays contacts and GOOSE messages
and it has been concluded that GOOSE is faster than traditional
wiring as expected.
REFERENCES
Fig. 4. Captured GOOSE messages in the network [1] A. Hadbah, T. S. Ustun and A. Kalam, “Using IEDScout software for
managing multivendor IEC61850 IEDs in substation automation
GOOSE communication time delay has measured to verify systems,” 2014 IEEE International Conference on Smart Grid
Communications (SmartGridComm), Venice, 2014, pp. 67-72.
the compatibility of each relay with IEC 61850.
[2] G. Manassero, E. L. Pellini, E. C. Senger and R. M. Nakagomi,
After several attempts of changing the initial status of the “IEC61850–Based Systems—Functional Testing and Interoperability
data (Tab. 1), the delay time of GOOSE message had an Issues,” in IEEE Transactions on Industrial Informatics, vol. 9, no. 3, pp.
1436-1444, Aug. 2013.
average value 2.7 ms.
[3] M. Daboul, J. Orsagova, T. Bajanek and V. Wasserbauer, “Testing
protection relays based on IEC 61850 in Substation Automation
TABLE I. DELAY COMMUNICATION TIME FOR GOOSE AND WIRED SIGNAL Systems,” 2015 16th International Scientific Conference on Electric
Delay GOOSE Time Delay Wired Connection Time Power Engineering (EPE), Kouty nad Desnou, 2015, pp. 335-340.
(ms) (ms) [4] A. Apostolov, “Impact of IEC 61850 on the interoperability and
reliability of protection schemes,” 2013 IEEE Power & Energy Society
1 2.1 32
General Meeting, Vancouver, BC, 2013, pp. 1-5.
2 3.4 32 [5] R. Aguilar and J. Ariza, “Testing and configuration of IEC 61850
multivendor protection schemes,” IEEE PES T&D 2010, New Orleans,
3 3.1 32.5 LA, USA, 2010, pp. 1-8.
4 2.8 21 [6] J. C. Tan, C. Zhang and Z. Q. Bo, “The importance of IEC 61850
interoperability testing,” 2008 43rd International Universities Power
5 2 20 Engineering Conference, Padova, 2008, pp. 1-5.
[7] J. C. Tan, V. Green and J. Ciufo, “Testing IEC 61850 based multi-
VIII. COMPARISON OF WIRED AND GOOSE SIGNAL vendor substation automation systems for interoperability,” 2009
IEEE/PES Power Systems Conference and Exposition, Seattle, WA,
As a result of the fact that many customers have a reticence 2009, pp. 1-5.
of to switch over to GOOSE messaging for tripping or even B. Stojcevski and A. Kalam, “Multi-vendor portable IEC61850 testing
performing control functions, many installations of substations unit,” 2011 IEEE PES Innovative Smart Grid Technologies, Perth,
WA, 2011, pp. 1-8
that are based on IEC 61850 are also hardwired. This section