CCC Load Sharing For Parallel Compressor Networks - AN21
CCC Load Sharing For Parallel Compressor Networks - AN21
Hot Recycle
PIC
PT TT TIC FY CRIC FY
Hot Recycle
AM FY FT PT PT
Analog Input
Station CV
and Load-Sharing Controllers
Controller
to/from all other Antisurge
Capacity
SP
Control
Pressure CRSC
SP Override
Ssel and Lsel CRPOC
Load Balancing
Lavg
CRPOC Lavg Lsel A Ssel CRPOC
A A
CRSC CRSC Analog Inputs
Ssel Ssel
Controllers for same compressor
Capacity Load fA
L L
to/from any other Antisurge
compressors will usually have different surge limits, due largely to inter-
nal leakage. As a result, this approach also fails to keep the compressors
equidistant from surge. While this strategy is better than sequential load-
ing, there is still a high likelihood that one compressor will be more apt to
surge or will go into recycle before the others.
CCC Parallel As shown in Figure 1, a CCC load-sharing system for compressors oper-
Load-Sharing ating in parallel consists of one station pressure or flow controller (PIC),
Systems one load-sharing performance controller (LSIC) per compressor, and one
antisurge controller (UIC) per compressor or compressor section. They
use a unique combination of protection and control methods (see Figure
2) to cooperatively maintain the desired pressure or flow while keeping
the compressors the same distance from their surge limits:
• Primary Capacity Control regulates the header flow or pressure.
• Load Balancing keeps the compressors the same distance from
surge to avoid unnecessary recycling or blow-off.
• Pressure Override Control provides accelerated capacity control
when the header pressure or flow exceeds a user-defined limit.
• Recycle Balancing equalizes the recycle rates of the compressors
when recycling is unavoidable.
Primary The station controller calculates its PID control response from the devia-
Capacity tion of its capacity control variable. Any change in the resulting station
Control control response (CRSC) is transmitted to the load-sharing and antisurge
controllers, which make appropriate changes in their own output signals.
Because this feature is the primary means of controlling the header flow
or pressure, it is called the primary capacity control response. Depending
on the controlled variable, it can also be more specifically referred to as
primary pressure or primary flow control.
When the compressors are recycling and less throughput is needed,
each antisurge controller multiplies the change in the station control
response by its own load-sharing gain and adds the resulting primary
capacity control response to its surge control response. This raises the
recycle rate, thus reducing net flow without hindering surge protection.
Under these conditions, the primary capacity control responses of the
load-sharing performance controllers will be zero.
When the compressors are not recycling or more throughput is needed,
each load-sharing controller multiplies the change in the station control
response by its own load-sharing gain, and adds the resulting primary
capacity control response to its own accumulated integral response.
Under these conditions, the primary capacity control responses of the
antisurge controllers are zero. This increases the compressor speed and
throughput without directly changing the recycle rate.
The overall effect is to throttle the compressor network by manipulating
the most appropriate control elements (speed set points or recycle
valves). This minimizes recycling without compromising surge protection.
Pressure Our load-sharing control systems also offer a pressure override control
Override (POC) feature that can raise the recycle flow to help control excessively
Control large or rapid changes in the capacity control variable. When controlling
the discharge pressure or net flow, POC is initiated when that variable
rises too high or too fast. When controlling suction pressure, it is initiated
when that variable falls too far or too quickly.
The station controller uses two separate algorithms to calculate the POC
response. One responds to the deviation of the control variable, the other
to its rate of change:
• The one-sided proportional-integral (PI) response counters excessive
deviations of the capacity control variable from the POC set point.
Depending on your application, this set point can be either an abso-
lute threshold or an offset from the capacity control set point.
• The pressure override predictor (POP) counters rapid changes in the
capacity control variable by comparing its instantaneous value (CV)
to a filtered average value (CVavg) and subtracting a user-defined
control threshold (SPPOP). When the objective is to limit the rate of
increase, this deviation is calculated as:
dev POP = ( CV – CV avg – SP POP ) ≥ 0
When the objective is to limit the capacity control variable’s rate of
decrease, this deviation is calculated as:
dev POP = ( CV avg – CV – SP POP ) ≥ 0
If this deviation is positive, which can only occur if the control variable
is changing rapidly in the limited direction, the POC response will
include a term proportional to the predictive deviation:
CR POC = CR PI + CR POP
CR POP = K POP ⋅ dev POP
Otherwise, the predictive response will be zero.
The POC response is sent to the antisurge controllers, which compare it
to their own control responses and use the higher of the two. Thus, this
feature never reduces the recycle rate below that needed to prevent
surge. If the POC response is higher than the surge protection response,
it will increase the recycle flow rate and suction pressure while lowering
the net flow rate and discharge pressure.
When appropriate, the POC response can alternately be used to control
large or rapid deviations of any single-input process variable measured
by the Station Controller.
Recycle In the event that recycling becomes unavoidable, this feature equalizes
Balancing the recycle rates of the various compressors. When it is enabled, the
Antisurge Controllers monitor each other to determine which of them has
the highest recycle rate.
If the compressors are moving away from surge, the controller with the
highest output will close its valve at an accelerated rate, while the others
slow the rate at which they close their antisurge valves. The furthest open
valve will thus “catch up” with the others.
If the outputs diverge while the compressors are moving toward surge,
the controller with the highest output (presumably closest to surging)
operates normally (so adequate surge protection is not imperilled). The
others then slowly open their valves, thus enabling them to catch up to
the furthest open valve.
The impeller and TTC logos, Total Train Control, TTC, Recycle Trip, Safety On, Air Miser, TrainView, and
WOIS are registered trademarks and COMMAND is a trademark of Compressor Controls Corporation.