SAP U

Job: 16152 Project: SULPHURIC ACID PLANT – SAP U

Plant: JORF LASFAR - MOROCCO Client: OCP S.A.

STATUS OF DOCUMENT

X A - Approved without comments D - Information

B - Approved with comments Z - Cancelled

C – Not Approved E - As-Built

DATE SIGNATURE

05.11.2020 JIL

NOTE: THE APPROVAL OF THIS DRAWING/DOCUMENT DOES NOT RELIEVE THE VENDOR/SUBCONTRACTOR OF HIS
RESPONSIBILITY IN THE PROJECT OBLIGATIONS AS SPECIFIED IN THE CONTRACTUAL DOCUMENTS.

DOCUMENT HISTORY & REVISION

10/05/2020 TDS 353 STEULER ACID Cement AE B353 CK DL YA 0

Date Description - Revision Subject Prepared by Checked by Approved by Rev

DOCUMENT DESCRIPTION & REFERENCES

CLIENT NAME: OCP

PROJECT LOCATION : JORF LASFAR

PROJECT DESCRIPTION : SULPHURIC ACID PLANT, SAP U

JE PROJECT NUMBER Q37100U1

PURCHASE ORDER REFERENCE : 6483 - 6485 - 6486

REQUISITION REFERENCE :

OTHER REFERENCE (tag, unit) :

DISCIPLINE CLASS DOCUMENT TITLE

Z 3 TECHNICAL DATA SHEET 353 STEULER ACID Cement AE B353

CONTRACTOR Document Number

Q3710-U-INT-GE-DSH-6111-2117

JESA Document Number

Imm. 5 - Zénith Millenium - Lot. Attaoufik Route Nouaceur - Sidi Mâarouf Casablanca -
20270 Tél: +212 (0)5 22 87 70 00 / +212 (0)5 22 87 71 50 Fax: +212 (0)5 22 87 72 34 Q37100U1-00-STG-Z-F02-02117

CLIENT Document Number ( if applicable)

Jacobs Engineering Group Inc.


Imm. 5 - Zénith Millenium - Lot. Attaoufik Route Nouaceur - Sidi Mâarouf Casablanca - 20270 Morocco Tél: +212 (0)5 22 87 70 00 / +212 (0)5 22 87
71 50 Fax: +212 (0)5 22 87 72 34

HELP JESA DOCUMENT NUMBERING SYSTEM Project Nbre Code of Sub-Project Sender Code Discipline Code Doc Type Sequence JESA Rev
Please Refer to Annex Q, L & DC Procedure . Shall you need help to
fill-in this cover page, please contact JESA Document Controller. Example (Trigram is unique to each contractor) Q37100U1 00 XXX XX XXX XXX 00
TI 353B Technical Information Surface Protection Linings
Issue 1 8.09.2019

STEULER ACID CEMENT AE B


Halogen-free water glass mortar for bedding and jointing of acid resistant tiles and bricks on floor areas

Base
Potassium water glass

Material Group
Mortars, Jointing Materials

Description
Halogen-free 2-component water glass mortar for the construction of filled joint- and hollow joint- applied acid resistant tile and brick
linings on floor areas.
In contrast to traditional silicate mortars, the mortar cannot only be applied in acidic areas but also in neutral areas, i.e. outdoors.

Use
Ceramic linings on floor areas, in channels, in pits – not for linings in vessels.

Properties
● halogen-free
● thermal resistance up to 450 °C

Physical Data
Property (unit), Test method Value
Density [g/cm³], DIN EN ISO 1 183-1, ASTM D 792 2.15
Compressive strength [MPa], DIN EN ISO 604, ASTM C 579 70
Modulus of elasticity [MPa], DIN EN ISO 178, ASTM C 580 3 x 1 04
Adherence to concrete / screed [MPa], DIN EN ISO 4624 > inherent strength of concrete
Adherence to ceramic bricks [MPa], DIN EN ISO 4624 > inherent strength of ceramic
Bricks
The thermal coefficient of linear expansion [1/K], ISO 11 359-2, ASTM C 531 1 .5 x 10-6
Thermal conductivity [W/mK], ISO DIS 22007 ≈ 1 .2
Tensile Strength [MPa], DIN EN ISO 527, ASTM C 307 7
Lowest working temperature [°C] 10
3602879871 3792651 • V 5 • en

Maximum working temperature [C] 40


Data are mean values

Chemical Resistance
For detailed information about the chemical resistance please refer to Technical Information TI 350.
Please contact our application engineering for approval of the project-specific possible application.
+ = resistant at 20 °C

STEULER-KCH GmbH│ Berggarten 1 │ D-56427 Siershahn│ GERMANY FOCUS ON PROGRESS 1 /4


Telefon:/Phone: +49 2623 600-0│ [email protected]│ www.steuler-linings.com
Technical Information Surface Protection Linings
STEULER ACID CEMENT AE B │ TI 353B │ Issue 1 8.09.2019

(+) = short time resistant


− = not resistant
Substances
Acids
Formic/acetic/lactic acid +
Chromic acid 30 % +
Hydrofluoric acid -
Oleum +
Nitric acid 65 % +
Hydrochloric acid up to 37 % +
Sulfuric acid up to 98 % +
Alkalis
Ammonia solution 25 % (+)
Chlorine bleaching -
Sodium hydroxide solution, potassium hydroxide solution -
Solvents
Aldehyde +
Alcohols +
Benzene / Toluene / Xylene +
Ester / Ketones +
Formaldehyde +
Methylene chloride +
Mineral oils +
Petrol +
Trichlorethylene +
Other
Amines +
Vegetable/animal oils and fats +

Substrate
● Concrete, screed, plaster (solid, clean, free of oil, grease or other separating substances). Before application preferably moisten
the substrate. Do not saturate it.
● Impervious sealing layer (sanded)
● Lead linings, ceramic brick and tile linings (clean, dry)
Use in any case for sanding SKC-Filler 16. Please contact our application engineering for approval of the project-specific possible
application.
Concrete / screed
Refer to DIN EN 14879-1 as well as to STEULER-KCH-Formsheet 010.
To attain a sufficient adhesive tensile strength, the substrate is generally to be pretreated in such a way that it is free of cement
slurry, cement skin, loose and crumbly particles, structure imperfections and separating substances.
The residual moisture of cementitious substrates must not exceed 4 %.
3602879871 3792651 • V 5 • en

Steel
Refer to DIN EN 14879-1 as well as to STEULER-KCH-Formsheet 020.
The steel surface shall be sandblasted to a metallic bright finish. A preparation degree of SA 2 ½ as specified in DIN EN ISO
1 2944-4 and a roughness grade “medium (G)” as specified in DIN EN ISO 8503-1 must be achieved; minimum surface roughness Rz
= 70 μm. After blasting, the formation of new rust must be prevented by suitable measures, e. g. priming directly.

STEULER-KCH GmbH│ Berggarten 1 │ D-56427 Siershahn│ GERMANY FOCUS ON PROGRESS 2/4


Telefon:/Phone: +49 2623 600-0│ [email protected]│ www.steuler-linings.com
Technical Information Surface Protection Linings
STEULER ACID CEMENT AE B │ TI 353B │ Issue 1 8.09.2019

Moisture
During application, the substrate must be kept absolutely dry. Uncured material has to be protected from any kind of moisture (con-
densation, fog, precipitation or other water source). Distance to dew point has to be at least 3 K, at a relative humidity of above 70 %
at least 5 K.

Packaging / Shelf life


All components must be stored and transported dry and frost-free. The minimum storage life applies to a storage temperature of 20
°C, unless otherwise specified. Higher temperatures reduce, lower temperatures increase the shelf life.
Components Item number Package Content Shelf life
Acid-Cement-AE-Solution 1 5021001001 Drum 25 kg 24 Months (at min. 5 °C)
Acid-Cement-AE-Powder 50211 37001 Bag 25 kg 24 Months
For handling, transport and storage observe the relevant material safety data sheets.

Mixing Ratio / Consumption


STEULER Acid cement AE-B
Part by weight Part by volume
Acid-Cement-AE-Solution 1 1.0 1.0
Acid-Cement-AE-Powder 8.8 6.9
Consumption 2,150 kg/litre mortar mass
Bed / bed joint thickness 5 - 8 mm
Joint width 5 - 8 mm
Joint width (hollow joint laying) 5 - 8 mm
Joint depth (bumpy joint installation) min. 15 mm
Consumption of mortar by filled-joint laying (bed joint 5 mm / butt joints 7 mm):
Split tiles 240 x 11 5 x 20 mm approx. 7.5 l 16.3 kg/m²
Split tiles 240 x 11 5 x 40 mm approx. 9.5 l 20.5 kg/m²
Bricks 240 x 1 15 x 65 mm approx. 11.5 l 24.8 kg/m²
Bricks 240 x 1 15 x 80 mm approx. 13 l 28 kg/m²
The joints must always be acidified. Acidification should take place approximately 24 hours after application. This can be used for
this purpose:
● Sulfuric acid 20 % or
● alcoholic sulphuric acid 20 %

Pot Life
Pot life depends on temperature:
20 °C approx. 30 - 60 minutes

Curing times
To support foot traffic at 20 °C at least 24 hours.
To achieve full chemical resistance: at least 8 days at 20 °C.
Joints are to be acidified always approx. 24 hours after application.
3602879871 3792651 • V 5 • en

For an acidification following media can be used: sulphuric acid 20 % or alcoholic sulphuric acid 20 %.

STEULER-KCH GmbH│ Berggarten 1 │ D-56427 Siershahn│ GERMANY FOCUS ON PROGRESS 3/4


Telefon:/Phone: +49 2623 600-0│ [email protected]│ www.steuler-linings.com
Technical Information Surface Protection Linings
STEULER ACID CEMENT AE B │ TI 353B │ Issue 1 8.09.2019

Safety and Disposal


● Sufficient aeration and de-aeration (especially in tanks and pits).
● No smoking/no fire
● Refer to the Safety Data Sheets
● Observe danger references and safety recommendation labels.
● Wear required personal protective equipment (avoid skin contact with materials)
● Clean and protect hands with skin protective soap and skin protection cream (no solvents)
● Wear a dust mask when sanding (e.g. for repairs).
● Instructions as per § 14 of GefahrstoffV (Toxic Substances Act) and TRGS 507 (Technical regulations for Hazardous Sub-
stances - Germany)
● Accident precautions issued by the Liability Insurance Association for the Chemical Industries (Germany)
Do not expose materials to heat or open flame, this applies in particular to welding works (weld beads).
Preferably consume residual quantities. Do not pour into a spout or dustbin! Collect separately for disposal in durable, lockable and
labeled containers.

Cleaning of Equipment
Tools can be cleaned with water. During application the mortar must not come into contact with water!
3602879871 3792651 • V 5 • en

All information contained in this Technical Information is based on the present state of our knowledge and practical experience. All
data are approximate values for guidance only. A legally binding warranty of certain characteristics or the suitability for a certain pur-
pose of use cannot be derived from this.
The information given in this Technical Information is our intellectual property. The Technical Information may neither be copied nor
used by unauthorized parties, nor professionally distributed or otherwise made accessible to third parties without our prior consent.
This issue replaces all previous versions.

STEULER-KCH GmbH│ Berggarten 1 │ D-56427 Siershahn│ GERMANY FOCUS ON PROGRESS 4/4


Telefon:/Phone: +49 2623 600-0│ [email protected]│ www.steuler-linings.com

You might also like