0% found this document useful (0 votes)
15 views8 pages

Systems Input Data

This document provides input data for the MECH ROOM air system of the 1088-HAQL RECREATIONAL project. It includes details on the single zone, a fan coil terminal unit, thermostat settings, and sizing values. The terminal unit is a ceiling supply/ceiling return fan coil serving the MECH ROOM zone. Sizing was performed with a cooling supply temperature of 13°C, heating supply of 35°C, and safety factors of 10% for cooling and heating loads.

Uploaded by

comekib310
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views8 pages

Systems Input Data

This document provides input data for the MECH ROOM air system of the 1088-HAQL RECREATIONAL project. It includes details on the single zone, a fan coil terminal unit, thermostat settings, and sizing values. The terminal unit is a ceiling supply/ceiling return fan coil serving the MECH ROOM zone. Sizing was performed with a cooling supply temperature of 13°C, heating supply of 35°C, and safety factors of 10% for cooling and heating loads.

Uploaded by

comekib310
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

ELECTRICAL Input Data

Project Name: 1088-HAQL RECREATIONAL 09/25/2023


Prepared by: orion 12:58PM

1. General Details:
Air System Name ELECTRICAL
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Dedicated Outdoor Air System Components:


(Dedicated Outdoor Air System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
ELECTRICAL x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 21.0 25.0 20.0 18.3 2.00

Thermostat Schedule Fan/Thermostat Schedule


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temp. 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temp. 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 150 Pa 65 % -
ceiling return

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates

Hourly Analysis Program 5.10 Page 1 of 8


ELECTRICAL Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 133.1 - - 4.8

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) Rating Units (°C)
1 1.6 35.0 Auto-Sized 1.6 0 - 3.224 EER -17.8

Hourly Analysis Program 5.10 Page 2 of 8


MECH ROOM Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

1. General Details:
Air System Name MECH ROOM
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Dedicated Outdoor Air System Components:


(Dedicated Outdoor Air System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
MECH ROOM x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 21.0 25.0 20.0 18.3 2.00

Thermostat Schedule Fan/Thermostat Schedule


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temp. 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temp. 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 150 Pa 65 % -
ceiling return

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Hourly Analysis Program 5.10 Page 3 of 8


MECH ROOM Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 123.7 - - 4.2

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) Rating Units (°C)
1 1.4 35.0 Auto-Sized 1.4 0 - 3.224 EER -17.8

Hourly Analysis Program 5.10 Page 4 of 8


PACU1 Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

1. General Details:
Air System Name PACU1
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:


Supply Temperature 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 250 Pa
Overall Efficiency 65 %
Fan Control 1-speed fan, cooling and heating

Duct System Data:


Supply Duct Data:
Duct Heat Gain 2 %
Duct Leakage 1 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RECREATIONAL x1
LOBBY ENTRANCE x1
CORRIDOR x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 22.0 25.0 21.1 18.3 1.00 100 0.0 0.0

Thermostat Schedule Fan/Thermostat Schedule


Unoccupied Cooling is Available

Supply Terminals Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Diffuser (no Ceiling supply /
1 Not Used - 0.00 L/s/person - - -
reheat) ceiling return

Hourly Analysis Program 5.10 Page 5 of 8


PACU1 Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Zone Heating Units:

Zone Unit Heat Source Electric Resistance


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 13.0 °C
Supply Fan Airflow 3077.8 L/s
Ventilation Airflow 338.4 L/s
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 5 %
Heating 5 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 3047.0 - -

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load 52.7 kW
Design OAT 35.0 °C
Equipment Sizing (Auto-Sized) 52.7 kW
Capacity Oversizing Factor 0 %
ARI Performance Rating 3.224 EER
DX System Configuration 1-stage compression, 1 circuit
Conventional Cutoff OAT 12.8 °C
Low Temperature Operation Used
Low Temperature Cutoff OAT -17.8 °C

Hourly Analysis Program 5.10 Page 6 of 8


TELECOM Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

1. General Details:
Air System Name TELECOM
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Dedicated Outdoor Air System Components:


(Dedicated Outdoor Air System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
TELECOM x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 21.0 25.0 20.0 18.3 2.00

Thermostat Schedule Fan/Thermostat Schedule


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temp. 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temp. 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 150 Pa 65 % -
ceiling return

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Hourly Analysis Program 5.10 Page 7 of 8


TELECOM Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 145.0 - - 5.2

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) Rating Units (°C)
1 1.7 35.0 Auto-Sized 1.7 0 - 3.224 EER -17.8

Hourly Analysis Program 5.10 Page 8 of 8