48 N-S MWP SOLAR PlANT - Project - VC0-Report
48 N-S MWP SOLAR PlANT - Project - VC0-Report
48 N-S MWP SOLAR PlANT - Project - VC0-Report
Author
Saatvik Green Energy Pvt Ltd (India)
Signature
___________________
Project: 48MWp SOLAR PlANT
Variant: 48 MWp SOLAR PlANT 2
Project summary
Geographical Site Situation Project settings
55MWp SOLAR PLANT Latitude 15.14 °N Albedo 0.20
India Longitude 76.77 °E
Altitude 539 m
Time zone UTC+5.5
Meteo data
Haraganadona
Meteonorm 8.1 (1996-2015), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
Simulation for year no 1
System information
PV Array Inverters
Nb. of modules 84224 units Nb. of units 109 units
Pnom total 48.01 MWp Pnom total 38.15 MWac
Pnom ratio 1.258
User's needs
Unlimited load (grid)
Results summary
Produced Energy 97454613 kWh/year Specific production 2030 kWh/kWp/year Perf. Ratio PR 81.03 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 5
Loss diagram 6
Predef. graphs 7
P50 - P90 evaluation 8
06/11/23 PVsyst Licensed to Saatvik Green Energy Pvt Ltd (India) Page 2/8
Project: 48MWp SOLAR PlANT
Variant: 48 MWp SOLAR PlANT 2
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Tracking algorithm Trackers configuration
Tracking plane, horizontal N-S axis Irradiance optimization
Axis azimuth 0°
Models used
Transposition Perez
Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer JINKO SOLAR Manufacturer Sungrow
Model JKM570N-72HL4-BDV Model SG350-HX
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 570 Wp Unit Nom. Power 350 kWac
Number of PV modules 84224 units Number of inverters 109 units
Nominal (STC) 48.01 MWp Total power 38150 kWac
Modules 3008 string x 28 In series Operating voltage 500-1450 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.26
Pmpp 44.41 MWp Power sharing within this inverter
U mpp 1083 V
I mpp 40995 A
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 2.0 % Module temperature according to irradiance Global array res. 0.43 mΩ
Uc (const) 29.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 1.0 % Loss Fraction 1.0 % Loss Fraction 1.0 % at MPP
06/11/23 PVsyst Licensed to Saatvik Green Energy Pvt Ltd (India) Page 3/8
Project: 48MWp SOLAR PlANT
Variant: 48 MWp SOLAR PlANT 2
System losses
Unavailability of the system Auxiliaries loss
Time fraction 0.8 % constant (fans) 100.0 kW
3.0 days, 0.0 kW from Power thresh.
3 periods Proportionnal to Power 15.0 W/kW
0.0 kW from Power thresh.
AC wiring losses
Inv. output line up to MV transfo
Inverter voltage 800 Vac tri
Loss Fraction 1.20 % at STC
Inverter: SG350-HX
Wire section (109 Inv.) Alu 109 x 3 x 240 mm²
Average wires length 134 m
MV line up to Injection
MV Voltage 33 kV
Wires Alu 3 x 1000 mm²
Length 500 m
Loss Fraction 0.07 % at STC
AC losses in transformers
MV transfo
Medium voltage 33 kV
Transformer parameters
Nominal power at STC 47.62 MVA
Iron Loss (24/24 Connexion) 71.44 kVA
Iron loss fraction 0.15 % at STC
Copper loss 713.40 kVA
Copper loss fraction 1.50 % at STC
Coils equivalent resistance 3 x 0.20 mΩ
06/11/23 PVsyst Licensed to Saatvik Green Energy Pvt Ltd (India) Page 4/8
Project: 48MWp SOLAR PlANT
Variant: 48 MWp SOLAR PlANT 2
Main results
System Production
Produced Energy 97454613 kWh/year Specific production 2030 kWh/kWp/year
Perf. Ratio PR 81.03 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
06/11/23 PVsyst Licensed to Saatvik Green Energy Pvt Ltd (India) Page 5/8
Project: 48MWp SOLAR PlANT
Variant: 48 MWp SOLAR PlANT 2
Loss diagram
1955 kWh/m² Global horizontal irradiation
+28.1% Global incident in coll. plane
06/11/23 PVsyst Licensed to Saatvik Green Energy Pvt Ltd (India) Page 6/8
Project: 48MWp SOLAR PlANT
Variant: 48 MWp SOLAR PlANT 2
Predef. graphs
Daily Input/Output diagram
06/11/23 PVsyst Licensed to Saatvik Green Energy Pvt Ltd (India) Page 7/8
Project: 48MWp SOLAR PlANT
Variant: 48 MWp SOLAR PlANT 2
Probability distribution
06/11/23 PVsyst Licensed to Saatvik Green Energy Pvt Ltd (India) Page 8/8