Installation and Maintenance: Sto Beg Iven To Use R

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

3972 en - 05.

2008 / e

Armature
+ 6-

Field
10 Yellow
11 Red
12 Black
9 Green

n to
b e give
is t o
m a nual nd user
This t he e F1 Slow fuse
250V 10 A
X2 Z1 X1 Z2 E+ E- 0V 110 22

ST5
with LAM without LAM

ST3
requency 50Hz 60Hz
R 448
ST10

R448 & R448 V50


A .V.R.
Installation and maintenance
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

This manual concerns the alternator A.V.R. which you have just purchased.

We wish to draw your attention to the contents of this maintenance manual. By


following certain important points during installation, use and servicing of your A.V.R.,
you can look forward to many years of trouble-free operation.

SAFETY MEASURES

Before using your machine for the first time, WARNING


it is important to read the whole of this
installation and maintenance manual.
Warning symbol for an operation
All necessary operations and interventions capable of damaging or destroying the
on this machine must be performed by a machine or surround-ing equipment.
qualified technician.

Our technical support service will be


pleased to provide any additional infor-
mation you may require.

The various operations described in this Warning symbol for general danger to
manual are accompanied by recommen- personnel.
dations or symbols to alert the user to
potential risks of accidents. It is vital that
you understand and take notice of the
following warning symbols.

Warning symbol for electrical danger to


personnel.

Note: LEROY-SOMER reserves the right to


modify the characteristics of its products at
any time in order to incorporate the latest
technological developments. The information
contained in this document may therefore be
changed without notice.

2
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

CONTENTS

1 - GENERAL INFORMATION................................................................................................5
1.1 - Description...................................................................................................................5
1.2 - Identification...................................................................................................................

2 - SUPPLY .............................................................................................................................5
2.1 - AREP excitation system ..............................................................................................5
2.2 - PMG excitation system ................................................................................................6
2.3 - SHUNT or separate excitation system.........................................................................7

3 - R448 A.V.R. .......................................................................................................................8


3.1 - Characteristics .............................................................................................................8
3.2 - Frequency compared with voltage (without LAM)........................................................8
3.3 - LAM (Load Acceptance Module) characteristics .........................................................8
3.4 - Typical effects of the LAM with a diesel engine with or without a LAM (U/F only).......9
3.5 - R448 A.V.R. options ....................................................................................................9

4 - INSTALLATION - COMMISSIONING ..............................................................................11


4.1 - Electrical checks on the AVR.....................................................................................11
4.2 - Settings......................................................................................................................11
4.3 - Electrical faults...........................................................................................................14

5 - SPARE PARTS ................................................................................................................15


5.1 - Designation................................................................................................................15
5.2 - Technical support service ..........................................................................................15

All such operations performed on the A.V.R. should be undertaken by personnel trained
in the commissioning, servicing and maintenance of electrical and mechanical
components.

Copyright 2005 : MOTEURS LEROY-SOMER


This document is the property of :
MOTEURS LEROY-SOMER
It may not be reproduced in any form without prior authorization.
All brands and models have been registered and patents applied for.

3
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

1 - GENERAL INFORMATION 1.2 - Identification


1.1 - Description These 2 A.V.R.s have strictly identical
The A.V.R. R 448 V50 is delivered in a box characteristics and dimensions, the
designed to be mounted on a panel with following details distinguish the V50:
suspension. - an adjuster dedicated to the alternator
Connexions are made with «Faston» LSA 50.2,
connectors. - the elimination of the ST6 jumper (A)
- Operating temperature: - 30°C to +70°C - a white serigraphy (B)
- Storage temperature: - 55°C to + 85°C (blue for R 448),
- Shocks on the base: 9g for the 3 axis - a label stipulating the type of alternator
- Vibrations: Less than 10Hz: 2mm half (C).
peak amplitude
10Hz to 100Hz: 100mm/s, above 100Hz:
8g

A
B

R 448

R 448 V50

4
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

2 - SUPPLY The first winding has a voltage in proportion


2.1 - AREP excitation system to that of the alternator (characteristic
Shunt), the second has a voltage in
For both AREP & PMG excitation systems, proportion to the stator current (compound
the alternator voltage regulator is the R characteristic: Booster effect).
448. The power supply voltage is rectified and
With AREP excitation, the R 448 electronic filtered before being used by the AVR
AVR is powered by two auxiliary windings monitoring transistor.
which are independent of the voltage
match circuit.

STATOR : 6 wires (marked T1 to T6)


MAIN FIELD STATOR : 12 wires (marked T1 to T12)
AREP SYSTEM Aux. windings
T1 T7 T2 T8 T3 T9
Varistor

Armature
5+ 6-
T4 T10 T5 T11 T6 T12
Field
10 Yellow
11 Red
12 Black
9 Green

according voltage

140 mm 4 x holes Ø 5.8


(175 x 115 mm)

X2 Z1 X1 Z2 E+ E- 0V 110 220 380


Slow fuse
200 mm

F1 250V 10 A Quad
P1 droop

ST5
with LAM without LAM AREP/SHUNT
ST9 PMG

ST3
Frequency 50Hz 60Hz T.I. S2 P2

R 448 S1
Option
Ph.1
ST10 P1

LAM 13 % 25 %

Excitation
ST4 Option

P5 ceiling External potentiometer


for adjusting the voltage

open
ST11 knee-point: 65 Hz
Option

Response normal R731 3-ph. detection


ST2 time fast ST6
46.2/47.2
ST1 in 3-ph. detection ST1 open
49.1
Single-
No ST6 jumper phase
P3 Stability
for R448 V50 detection P2 Voltage

5
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

2.2 - PMG excitation system jumper must be disconnected.


These two principles provide the machine
With PMG excitation, a permanent magnet
with a short-circuit current capacity of 3 IN
generator (PMG) added to the alternator
for 10 s, and good immunity to distortions
supplies the AVR with voltage which is
generated by the load.
independent of the main alternator winding.
The AVR monitors and corrects the
This is fitted at the rear of the machine and
alternator output voltage by adjusting the
connected to the R 448 AVR, and the ST9
excitation current.
STATOR : 6 wires (marked T1 to T6)
MAIN FIELD STATOR : 12 wires (marked T1 to T12)
PMG SYSTEM
T1 T7 T2 T8 T3 T9

Varistor
PMG

Armature
5+ 6-
T4 T10 T5 T11 T6 T12
Field

according voltage
14 15 16
140 mm 4 x holes Ø 5.8
(175 x 115 mm)

X2 Z1 X1 Z2 E+ E- 0V 110 220 380


Slow fuse
200 mm

F1 250V 10 A Quad
P1 droop

ST5
with LAM without LAM AREP/SHUNT
ST9 PMG

ST3
Frequency 50Hz 60Hz T.I. S2 P2

R 448 S1
Option
Ph.1
ST10 P1

LAM 13 % 25 %

Excitation
ST4 Option

P5 ceiling External potentiometer


for adjusting the voltage

open
ST11 knee-point: 65 Hz
Option

Response normal R731 3-ph. detection


ST2 time fast ST6
46.2/47.2
ST1 in 3-ph. detection ST1 open
49.1
Single-
No ST6 jumper phase
P3 Stability
for R448 V50 detection P2 Voltage

6
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

2.3 - SHUNT or separate excitation - 3-phase sensing (R 731 module)


system - LAM function integrated in the R 448 AVR.
In SHUNT excitation, R 448 A.V.R. is In this case of LSA 42.2, A.V.R. and
supplied by main windings (140V - 50/60 module(s) must be installed in the
Hz) to X1, X2. external control panel.
The new functions are :
- Parallel operation between alternators
with C.T.
- Parallel operation with the mains with C.T.
and R 726 module

MAIN FIELD STATOR : 12 wires (marked T1 to T12)


SHUNT SYSTEM T8
T1 T7 T2 T3 T9
Varistor

Armature
5+ 6-
T4 T10 T5 T11 T6 T12
Field

according voltage

140 mm 4 x holes Ø 5.8


(175 x 115 mm)

X2 Z1 X1 Z2 E+ E- 0V 110 220 380


Slow fuse
200 mm

F1 250V 10 A Quad
P1 droop

ST5
with LAM without LAM AREP/SHUNT
ST9 PMG

ST3
Frequency 50Hz 60Hz T.I. P2
S2
R 448 Option
Ph.1
ST10 S1
P1

LAM 13 % 25 %

Excitation
ST4 Option

P5 ceiling External potentiometer


for adjusting the voltage

open
ST11 knee-point: 65 Hz
Option

Response normal R731 3-ph. detection


ST2 time fast ST6
46.2/47.2
ST1 in 3-ph. detection ST1 open
49.1
Single-
No ST6 jumper phase
P3 Stability
for R448 V50 detection P2 Voltage

7
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

3 - R448 A.V.R. 3.1.1 - Configuration jumpers function


3.1 - Characteristics Delivrery
Pot. config. Position Function
- Shunt power supply: max 150V - 50/60 Hz Open Closed
- Rated overload current: 10A - 10s Open for module
ST1 3-ph. Mono
- Electronic protection: (in the event of installation tri detection
overload, short-circuit, loss of voltage sensing) ST2 Fast Normal Response time
this acts to restore the value of the excitation ST3 50 ou 60 Hz Frequency selection
current to 1A after 10 s. The alternator must be External
stopped (or the power switched off) in order to ST4 potentio- Without Potentiometer
meter
reset the protection.
ST5 Without With LAM
- Fuse: F1 on X1, X2. 10A ; slow - 250V
Alternator LSA 46.2 and
- Voltage sensing : 5 VA isolated via trans- closed
LSA 472
former ST6 With open Alternator LSA 49.1
• 0-110 V terminals = 95 to 140 V no jumper Alternator LSA 50.2
• 0-220 V terminals = 170 to 260 V Others AREP
• 0-380 V terminals = 340 to 520 V ST9 Supply
(PMG...) SHUNT
for other voltages, a transformer should be ST10
LAM voltage drop
13% or 25%
used. amplitude
- Voltage regulation ± 0.5% ST11 65 Hz
48 or U/f function bend
58 Hz position
- Normal or rapid response time via jumper
ST2 (see below) 3.1.2 - Setting potentiometers function
- Voltage adjustment via potentiometer P2 or
apply a DC voltage of ± 1 V on the terminals of Delivrery
Pot. Function
the external potentiometer position
- Current sensing: (parallel operation): input 0 P1 Quadrature droop ; // operation with C.T.
S1, S2 intended for 1 C.T. Š 2.5 VA cl1, 400V P2 Voltage
secondary 1A (optional)
- Quadrature droop adjustment via potentio- Centre P3 Stability
meter P1 Maxi P5 Excitation current ceiling
- Max. excitation current adjustment via P5:
4.5 to 10A (see below)
- 50/60 Hz selection via ST3 jumper
- ST11: Knee-point at 65 Hz for Tractelec
application and variable speed.

8
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

3.2 - Frequency compared with


Voltage
voltage (without LAM) Underspeed and LAM
ST5 disconnected
UN Voltage
Voltage Bend 57.5 Hz P2
48 Hz
100 %
U/UN 50 Hz U/f
0.85 UN LAM
60 Hz

Frequency
50 Hz 60 Hz Hz
48 or 57.5 Hz 50 or 60 Hz
0 ST3 fC fN
3.3 - LAM (Load Acceptance
Module) characteristics 3.3.2 - Gradual voltage return function
3.3.1 - Voltage drop During load impacts, the function helps the
The LAM system is integrated in the genset to return to its rated speed faster
regulator, as standard it is active (ST5 with thanks to a gradual increase in voltage
bridge). It can be deactivated by removing according to the principle:
the ST5 bridge. It can be adjusted to 13% - If the speed drops between 46 and 50 Hz,
or 25% by means of the ST10 jumper. the rated voltage follows a fast gradient as
- Role of the “LAM” (Load Acceptance it is restored.
Module): - If the speed drops below 46 Hz, since the
On application of a load, the rotation speed engine needs more help, the voltage
of the generator set decreases. When it follows a slow gradient as it returns to the
passes below the preset frequency reference value.
threshold, the LAM causes the voltage to
drop by approximately 13% or 25% and
consequently the amount of active load
applied is reduced by approximately 25% U
to 45%, until the speed reaches its rated
value again. Drop N ≤ 46 Hz
Hence the LAM can be used either to
reduce the speed variation (frequency) and Drop N > 46 Hz
Time
its duration for a given applied load, or to 0
increase the applied load possible for one
speed variation (turbo-charged engine).
To avoid voltage oscillations, the trip
threshold for the LAM function should be
set approximately 2 Hz below the lowest
frequency in steady state.
It is advisable to use the LAM at 25% for
load impacts Š 70% of the genset rated
power.
- LAM : action eliminated by cutting the ST5
jumper.

9
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

3.4 - Typical effects of the LAM with 3.5 - R448 A.V.R. options
a diesel engine with or without a - Current transformer for parallel operation
LAM (U/F only) of....../ 1A Š 2.5 VA CL 1 (See the diagram
in this manual).
- Voltage transformer (adaptation)
3.4.1 - Voltage
470 Ω, 0.5 W min : adjustment range ± 5%
- Remote voltage adjustment potentiometer:
Transient voltage drop
UN (range limited by internal voltage

the potentiometer. (A 1 k Ω potentiometer


potentiometer P2). Remove ST4 to connect
0,9
can also be used to extend the adjustment
(U/f)
with without LAM
range).
0,8 - R 731 module: detection of 200 to 500V 3-
LAM
Time
phase voltage, compatible with parallel
0 1s 2s 3s operation. Disconnect ST1 to connect the
3.4.2 - Frequency module; set the voltage via the
potentiometer.
Max speed drop with - R 734 module: detection of 3-phase
fN LAM current and voltage for parallel operation on
unbalanced installations (imbalance > 15%)
- R 726 module: regulation system changed
0,9
without
to "4-function". (See the maintenance

• PF regulationϕ (2F)
LAM manual and connection diagram.)
0,8 Time

0 1s 2s 3s • voltage matching before paralleling (3 F)


• mains connection of alternators already
3.4.3 - Power running in parallel (4F)
- R 729 module: same as R 726 with
LAM additional functions
• detection of a diode fault
Load on the

• 4/20 mA input
shaft (kW)

Variation in the load


• possibility of kVAR regulation
- Control through DC voltage used
Load shedding due to "LAM" monitoring apply to the terminals for

• internal impedance 1,5 kΩ


connection of a potentiometer DC voltage :
Time
0 1s 2s 3s
• ± 0,5V enable a voltage setting of 10%.

10
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

4 - INSTALLATION - COMMISSIONING a) Initial potentiometer settings (see table


4.1 - Electrical checks on the AVR below)
- Remote voltage adjustment potentiometer
- Check that all connections have been : centre (ST4 jumper removed).
made properly as shown in the attached
wiring diagram. Action Factory setting Pot.
- Check that the ST3 frequency selection
400V - 50 Hz
jumper is on the correct frequency setting. Voltage
(Input
- Check whether the ST4 jumper or the minimum fully anti-clockwise P2
0 - 380 V)
remote adjustment potentiometer have
been connected. Not set
- Optional operating modes.
Stability
(centre position)
P3
• ST1 jumper : open to connect the R 731
Voltage quadrature droop Not set
or R 734 3-phase (// operation with C.T.) (fully anti-
sensing module. - 0 quadrature loop fully clockwise) P1
• ST2 jumper : open if rapid response time anti-clockwise.
used Excitation ceiling
• ST5 jumper : open to suppress the LAM Limit of excitation and 10 A
function. short-circuit current, maximum P5
• ST9 jumper : closed with AREP, open minimum fully anti-clockwise.
with PMG.
Stability adjustments in standalone
4.2 - Settings operation

b) Install a D.C. analogue voltmeter (needle


dial) cal. 100V on terminals E+, E- and an
A.C. voltmeter cal 300 - 500 or 1000V on the
alternator output terminals.

The machine is tested and set at the c) Make sure that the ST3 jumper is
factory. When first used with no load, positioned on the desired frequency (50 or
make sure that the drive speed is 60 Hz).
correct and stable (see the nameplate).
After operational testing, replace all d) Voltage potentiometer P2 at minimum,
access panels or covers. fully anti-clockwise.
The only possible adjustments to the
machine should be made on the AVR. e) Stability potentiometer P3 to around 1/3 of
the anti-clockwise limit.
4.2.1 - R448 settings (AREP or PMG
system) f) Start the engine and set its speed to a
frequency of 48 Hz for 50 Hz, or 58 for 60
WARNING Hz.

g) Set the output voltage to the desired


Before any intervention on the A.V.R., value using P2.
make sure that the ST9 jumper is closed - Rated voltage UN for solo operation (eg.
with AREP / SHUNT excitation and 400 V)
disconnected with PMG or separate - Or UN + 2 to 4% for parallel operation with
excitation. C.T. (eg. 410 V)
If the voltage oscillates, use P3 to make
adjustments (try both directions) observing

11
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

the voltage between E+ and E- (approx. 10V 4.2.2 - Max. excitation setting (excitation
D.C.). The best response times are obtained ceiling)
at the limit of the instability. If no stable
Max. excitation depending on the mains frequency
position can be obtained, try disconnecting
or replacing the ST2 jumper (normal/fast). ST3
100V...140V
X2
P5
h) Check LAM operation : ST5 closed. 50Hz 60Hz Z1
A
X1
i) Vary the frequency (speed) around 48 or Z2
E+ Field
58 Hz according to the operating frequency, P3 R 448 - + ~ 10 ohms
and check the change in voltage from that E- A
10A DC
0V
observed previously (~ 15%).
110 V
P2 220V
j) Readjust the speed of the unit to its rated ST4
380V
no-load value. 110/220/380V D

Voltage
Adjustments in parallel operation
Before any intervention on the alternator,
make sure that the speed droop is - static adjustment of the current limit ,
identical for all engines. potentiometer P5 (fuse rating : 8 A - 10
seconds).
k) Preset for parallel operation (with C.T. The maximum factory setting corresponds
connected to S1, S2) to that of the excitation current required to
- Potentiometer P1 (quadrature droop) in obtain a 3-phase short-circuit current of

Apply the rated load (cos ϕ = 0.8 inductive).


centre position. approximately 3 IN at 50 Hz for industrial
power, unless otherwise specified(*).
The voltage should drop by 2 to 3%. If it A static method can be used to reduce this
increases, check that V and W and also S1 value or adapt the Isc to the actual operating
and S2 have not been reversed. power (derated machine), which is safer for
the alternator and the installation.
l) The no-load voltages should be identical - Disconnect power supply wires X1,X2 and
for all the alternators intended to run in Z1,Z2 and the voltage reference (0-110V-
parallel. 220V-380V) on the alternator.
- Couple the machines in parallel. Connect the mains power supply using a
- By adjusting the speed, try to obtain 0 KW transformer (200-240V) as indicated
power exchange. (X1,X2) : 120V).
- By altering the voltage setting P2 on one of - Apply the corresponding voltage to the
the machines, try to cancel (or minimise) the voltage reference input used
current circulating between the machines. - Supply the AVR with a voltage of 120V
- From now on, do not touch the voltage max. on the X1, X2 input.
settings. - Install a 10A D.C. ammeter in series with
the exciter field.
m) Apply the available load (the setting is - Turn P5 fully anti-clockwise and activate
only correct if a reactive load is available) the power supply. If there is no output
- By altering the speed, match the KW (or current from the AVR, turn potentiometer P2
divide the rated power of the units (voltage) clockwise until the ammeter
proportionally) indicates a stable current.
- By altering the quadrature droop - Switch the power supply off, then on again,
potentiometer P1, match or divide the turn P5 clockwise until the required max.
currents. current is obtained (no more than 10 A).
Checking the internal protection :

12
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

Open switch (D) : the excitation current The exciter is switched off by disconnecting

at that level for ≥ 1 second in AREP or 10


should increase to its preset ceiling, remain the AVR power supply (1 wire on each
auxiliary winding) - contact rating 16 A -
seconds in PMG and then drop to < 1A. 250V A.C.
To reset, switch off the power supply by Connection is identical for resetting the
opening switch (A). Reconnect the AVR to AVR internal protection.
the alternator and adjust the reference
voltage via P2 to obtain the rated voltage.
(*): In some countries it is a legal
requirement to have a short-circuit current,
so as to offer discriminating protection.
In case of using the de-excitation,
4.2.3 - Special type of use provide a forced excitation.

4.2.3.3 - R448 field forcing


WARNING
(400V - 10A) Diode
X2
Excitation circuit E+, E- must not be left
open when the machine is running : Z1 t - +
AVR damage will occur. X1 Battery (B Volt)
Z2
4.2.3.1 - R448 field weakening (SHUNT) E+
E-
Exciter field
X2
Forced excitation
Z1 B Volt
X1
t
Z2
E+ Time

E-
Applications B volts Time t
The exciter is switched off by disconnecting Guaranteed voltage build-up 12 (1A) 1-2 s
the AVR power supply (1 wire - X1 or X2).
Contact rating 16 A - 250V A.C. Parallel operation, de-energized 12 (1A) 1-2 s

Parallel operation, at standstill 12 (1A) 5 - 10 s


4.2.3.2 - R448 field weakening (AREP/
PMG) Frequency starting 12 (1A) 5 - 10 s

Sustained voltage on overload 12 (1A) 5 - 10 s

X2
Z1
X1
Z2
E+
E-

13
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

4.3 - Electrical faults


Fault Action Effect Check/Cause
The alternator builds up and its voltage is - Lack of residual magnetism
still correct when the battery is removed.
The alternator builds up but its voltage - Check the connection of the voltage reference to
No voltage at Connect a new battery of 4
does not reach the rated value when the AVR
no load on to 12 volts to terminals E-
the battery is removed. - Faulty diodes
start-up and E+, respecting the - Armature short-circuit
polarity, for 2 to 3 seconds
The alternator builds up but its voltage - Faulty AVR
disappears when the battery is - Field windings disconnected
removed - Main field winding open circuit - check the
resistance
Check the AVR connections (AVR may be faulty)
- Field windings short-circuited
Correct speed - Rotating diodes burnt out
Voltage too low Check the drive speed - Main field winding short-circuited - Check the
resistance
Increase the drive speed
Speed too low (Do not touch the AVR voltage pot. (P2) before
running at the correct speed.)
Voltage too Adjust AVR voltage Adjustment ineffective Faulty AVR
high potentiometer
Voltage Adjust AVR stability If no effect : try normal / fast recovery - Check the speed : possibility of cyclic irregularity
oscillations potentiometer modes (ST2) - Loose connections
- Faulty AVR
- Speed too low when on load (or U/F bend set too
high)
Voltage between E+ and E-
Voltage correct Run at no load and check SHUNT < 20 V - AREP / PMG < 10V - Check the speed (or U/F bend set too high)
at no load and the voltage between E+ Voltage between E+ and E- - Faulty rotating diodes
too low when and E- on the AVR SHUNT > 30V - AREP / PMG > 15V - Short-circuit in the main field. Check the
on load (*) resistance
- Faulty exciter armature.
(*) Caution : For single-phase operation, check that the sensing wires coming from the AVR are correctly connected to the operating terminals
Voltage Check the AVR, the surge The voltage does not return to the rated - Exciter winding open circuit
disappears suppressor, the rotating value. - Faulty exciter armature
during diodes, and replace any - Faulty AVR
operation (**) defective components - Main field open circuit or short-circuited
(**) Caution : Internal protection may be activated (overload, open circuit, short-circuit)

Warning : after operational testing,


replace all access panels or covers.

14
LEROY-SOMER Installation and maintenance 3972 en - 05.2008 / e

R448 & R448 V50


A.V.R.

5 - SPARE PARTS
5.1 - Designation
Description Type Code
A.V.R. R 448 AEM 110 RE 016

A.V.R. R 448 V50 AEM 110 RE 022

5.2 - Technical support service


Our technical support service will be happy
to provide any information you require.

When ordering spare parts, you should in-


dicate the complete machine type, its serial
number and the information indicated on
the nameplate.

Part numbers should be identified from


the exploded views and their description
in the parts list.
Our extensive network of "service stations"
can dispatch the necessary parts without
delay.
To ensure correct operation and the safety
of our machines, we recommend the use of
original manufacture spare parts.
In the event of failure to comply with this ad-
vice, the manufacturer cannot be held res-
ponsible for any damage.

15
MOTEURS LEROY-SOMER 16015 ANGOULÊME CEDEX -
FRANCE
338 567 258 RCS ANGOULÊME
S.A. au capital de 62 779 000 euro

You might also like