Measurement
Measurement
Measurement
1 1 . 2
(a) 1 + 2 + (b)
3 3
(c) 1 + 2 − 3 (d) 1 + 2 + 3
04. Resistances R1 and R2 have, respectively nominal values 08. Suppose the resistors R and R are connected to in
1 2
of 10 and 5, and tolerances of 5% and 10%. The parallel to give an equivalent resistor R. If resistors
range of values for the parallel combination of R1 and R2 is
R and R have tolerance of 1% each, the equivalent
(a) 3.077 to 3.636 [2001] 1 2
(b) 2.805 to 3.371 resistor R for resistors R = 300 and R = 200 will
1 2
(c) 3.237 to 3.678
have tolerance of [2014-02]
(d) 3.192 to 3.435
(a) 0.5% (b) 1%
(c) 1.2% (d) 2%
05. The set-up in figure is used to measure resistance R.
The ammeter and voltmeter resistances are 0.01 and 09. The mean thickness and variance of silicon steel
2000, respectively. Their readings are 2A and 180V, laminations are 0.2mm and 0.02 respectively. The varnish
respectively, giving a measured resistance of 90Ω. The insulation is applied on both the sides of the laminations.
percentage error in the measurement is: [2005] The mean thickness of one side insulation and its variance
are 0.1mm and 0.01 respectively. If the transformer core is
made using 100 such varnish coated laminations, the mean
thickness and variance of the core respectively are
[2014-03]
(a) 30mm and 0.22
(b) 30mm and 2.44
(a) 2.25% (b) 2.35% (c) 40 mm and 2.44
(c) 4.5% (d) 4.71% (d) 40mm and 0.24
10. A capacitive voltage divider is used to measure the bus 13. A non-ideal Si-based pn junction diode is tested by
voltage Vbus in a high-voltage 50Hz AC system as shown in sweeping the bias applied across its terminals from –5 V to
+5 V. The effective thermal voltage, VT, for the diode is
figure. The measurement capacitors C1 and C 2 have
measured to be (29 ± 2) mV. The resolution of the voltage
tolerance of 10% on their nominal capacitance values. If source in the measurement range is 1 mV. The percentage
the bus voltage Vbus is 100kV rms, the maximum rms uncertainty (rounded off to 2 decimal places) in the
measured current at a bias voltage of 0.02 V is _______.
output voltage Vout (in kV), considering the capacitance
[2020]
tolerances, is _________ [2015-02]
14. The temperature of the coolant oil bath for a
transformer is monitored using the circuit shown. It
contains a thermistor with a temperature-dependent
resistance, Rthermistor = 2 (1+ T) k, where T is the
temperature in °C. The temperature coefficient, , is – (4 ±
0.25) %/°C. Circuit parameters: R1 = 1 k, R2 = 1.3 k, R3 =
2.6 k. The error in the output signal (in V, rounded off to
2 decimal places) at 150°C is __________. [2020]
2 2
R R
(a) R1 + R 2
R1 R 2
2 2
R R
(b) R1 + R 2
R 2 R1
2 2
R R
(c) R 2 + R1
R1 R 2
2 2
R R
(d) R1 + R 2
R1 R 2
Solutions
01. Ans: (d)
Solution:
V
R=
I
Maximum possible % error will be
R V I
= +
R V I
R
= 2.4 + 1 = 3.4%
R
121.2 − 120
Therefore, percentage error= 100 = 1%
120
11. Ans: 4
Solution:
W
The expression for pf is pf =
VI
The maximum error in pf is
%pf = %w+ %v + %I = 2% 1% 1% = 4%
ID ID ID VD
= =− ID
VD VT VT VT2
uncertainty in diode current
1/2
I 2
2 ID 2
2
I = D VD + VT
VD VT
1/2
2
I V V2
= D + D 2V
ID V2 V 4 T
T T
V = 2 mV V = 1 mV
T D
1/2
I 1 2 20 2
2
= + 2 = 0.0587 = 5.87%
ID 29 292
2.6 3 1 2.6
= −0.1 + 1 +
1.3 R th + 1 1.3
9
= −0.2 +
R th + 1
Case-1: = – (4 + 0.25)%/°C = – 0.0425
Rth = 2 (1 – 0.0425 × 150) = – 10.75 k
9
Vout = −0.2 + = −1.123 V
−10.75 + 1
Case-2: = – (4 – 0.25)%/°C = – 0.0375
Rth = 2 (1 – 0.0375 × 150) = – 9.25 k
9
Vout = −0.2 + = −1.291 V
−9.25 + 1
Vout = 0.168
error = 0.084 V
02. The current passing through a 10 Ohm resistor of 08. Four ammeters M1, M2, M3 and M4 with the following
figure (a) has the waveform in figure (b). The reading of the specifications are available.
PMMC voltmeter connected across the resistor [1991]
Instrument Type Full scale Accuracy
value (A) % of FS
1
3 digit ±0.10
M1 2 20
dual slope
M2 PMMC 10 ±0.20
Electro-
M3 5 ±0.50
dynamic
method. The watt meters used are similar and are of type 19. A moving coil galvanometer is made into a d.c.
of 400V, 5A, UPF, class 1 accuracy. [1995] ammeter by connecting [1998]
(i) Determine expected readings in W1, W2 (a) A low resistance across the meter
(ii) Compute the total power and (b) A high resistance in series with the meter
(iii) The possible worst case error in W1, W2 and the total (c) A pure inductance across the meter
(d) A capacitor in series with the meter
power
15. The scale of a voltmeter is uniform. Its type is measured with a thermocouple type, 5A full-scale, class 1
[1996] meter. The meter reading would lie in the range [1999]
(a) Moving iron
(b) Induction
(a) 5A 1% ( )
(b) 2 + 3 2 A 1%
34. A wattmeter reads 400 W when its current coil is 39. A moving coil of a meter has 100 turns, and a length
connected in the R phase and its pressure coil is and depth of 10 mm and 20 mm respectively. It is
connected between this phase and the neutral of positioned in a uniform radial flux density of 200mT. The
asymmetrical 3-phase system supplying a balanced star coil carries a current of 50mA. The torque on the coil is
connected 0.8p.f. inductive load. The phase sequence is [2004]
RYB. What will be the reading of this wattmeter if its (a) 200 µNm (b) 100 µNm
pressure coil alone is reconnected between the B and Y (c) 1000 µNm (d) 1µNm
phases all other connections remaining as before [2003]
(a) 400.0 (b) 519.6 40. A dc A-h meter is rated for 15 A, 250V. The meter
(c) 300.0 (d) 692.8 constant is 14.4 A-sec/rev. The meter constant at rated
voltage may be expressed as [2004]
35. The inductance of a certain moving-iron ammeter is (a) 3750 rev/kWh (b) 3600 rev/kWh
2 (c) 1000 rev/kWh (d) 960 rev/kWh
expressed as L = 10 + 3 − H , where is the deflection
4
41. A moving iron ammeter produces a full-scale torque of
in radians from the zero position. The control spring torque
240 µNm with a deflection of 120° at a current of 10 A. The
in 25×10-6 Nm/radian, the deflection of the pointer in
rate of change of self inductance (µH/radian) of the
radian when the meter carries a current of 5A, is [2003]
instrument at full scale is? [2004]
(a) 2.4 (b) 2.0
(a) 2.0µH/radian (b) 4.8µH/radian
(c) 1.2 (d) 1.0
(c) 12.0µH/radian (d) 114.6µH/radian
36. The voltage flux adjustment of a certain 1-phase 220 V
42. A single-phase load is connected between R and Y
induction watt hour meter is altered so that the phase
terminals of a 415 V, symmetrical, 3-phase, 4-wire system
angle between the applied voltage and the flux due to it is
with phase sequence RYB. A wattmeter is connected in the
85° (instead of 90°). The errors introduced in the reading of
system as shown in figure. The power factor of the load is
this meter when the current is 5A at power factors of unity
0.8 lagging. The wattmeter will read [2004]
and 0.5 lagging are respectively. [2003]
(a) 3.8mW, 77.4mW (b) −3.8mW, −77.4mW
(c) −4.2 W, −85.1 W (d) 4.2 W, 85.1 W
(a) 8 V (b) 16 V
(c) 24 V (d) 40 V
48. The pressure coil of a dynamometer type wattmeter is 52. Consider the following statements: [2011]
[2009] (i) The compensating coil of a low power factor wattmeter
(a) Highly inductive (b) Highly resistive compensates the effect of the impedance of the current
coil.
(c) Purely resistive (d) Purely inductive
(ii) The compensating coil of a low power factor wattmeter
compensates the effect of the impedance of the voltage
49. The figure shows a three-phase delta connected load
coil circuit.
supplied from a 400V, 50 Hz, 3-phase balanced source. The
pressure coil (PC) and current coil (CC) of a wattmeter are (a) (i) is true but (ii) is false
connected to the load as shown, with the coil polarities (b) (i) is false but (ii) is true
suitably selected to ensure a positive deflection. The (c) both (i) and (ii) are true
wattmeter reading will be [2009] (d) both (i) and (ii) are false
54. For the circuit shown in the figure, the voltage and
current expression are v ( t ) = E sin ( t ) + E sin (3t ) and
1 3
1( ) 1 3 ( 3 )
i ( t ) = I sin t − + I sin 3t − + I sin (5t )
5
The average power measured by the wattmeter is [2012]
V1 V2 V1 V2
(a) V = + (b) V = +
2 2 2 2
(c) V = V1 V2 (d) V = V2 − V1
61. While measuring power of a three-phase balanced load 67. A 3-phase balanced load which has a power factor of
by the two-wattmeter method, the readings are 100W and 0.707 is connected to a balanced supply. The power
250W. The power factor of the load is_____________. consumed by the load is 5kW. The power is measured by
[2014-02]
the two-wattmeter method. The reading of the two watt
meters are [2015-02]
62. Two
ammeters X and Y have resistances of
1.2 and 1.5 respectively and they give full-scale (a) 3.94 kW and 1.06 kW
deflection with 150 mA and 250 mA respectively. The (b) 2.50 kW and 2.50 kW
ranges have been extended by connecting shunts so as to (c) 5.00 kW and 0.00 kW
give full scale deflection with 15A. The ammeters along (d) 2.96 kW and 2.04 kW
with shunts are connected in parallel and then placed in a
circuit in which the total current flowing is 15A. The current 68. The coils of a wattmeter have resistance 0.01 and
in amperes indicated in ammeter X is_________. [2014-02] 1000 ; their inductances may be neglected. The
wattmeter is connected as shown in the figure, to measure
63. An LPF wattmeter of power factor 0.2 is having three
the power consumed by a load, which draws 25 A at power
voltage settings 300V, 150V and 75V, and two current
factor 0.8. The voltage across the load terminals is 30 V.
settings 5A and 10A. The full scale reading is 150. If the
The percentage error on the wattmeter reading is
wattmeter is used with 150V voltage setting and 10A
__________. [2015-02]
current setting, the multiplying factor of the wattmeter
is______________. [2014-03]
(a) W1 = 1732andW2 = W3 = 0
(b) W1 = 0,W2 = 1732andW3 = 0
(c) W1 = 866,W2 = 0,W3 = 866
(d) W1 = W2 = 0and W3 = 1732
Solutions
01. Ans: (1, 0.5)
Solution:
W1 − W2
Power factor angle = tan 3
−1
W1 + W2
( )
(a) = tan−1 0 = 00
Power factor Cos = 1
(b)
When W1=0
( )
= tan−1 − 3 = −600
Power factor Cos = 0.5
When W2=0
= tan−1 ( 3 ) = 60 0
02. Ans: 85
Solution:
As PMMC reads average voltage.
Average current =
(12 T ) + (5 T ) =8.5Amp
2T
Reading of PMMC=8.5 10=85Volt
3VmIm
VRN ( I Y − IB ) = − sin ( 2t − ) + sin
2
Similarly,
(V YN ( ) ( )
− VBN ) iR = Vm sin t − 1200 − Vm sin t + 120 0 Im sin ( t − )
VmIm
(V YN
− VBN ) iR =
2
( ) ( )
2sin ( t − ) sin t − 1200 − 2sin ( t − ) sin t + 1200
VmIm
(V YN
− VBN ) iR =
2
( ) ( ) ( ) (
cos 1200 − − cos 2t − 1200 − − cos 1200 + + cos 2t + 1200 −
)
( )
( VYN − VBN ) iR = VmIm sin 120 sin + sin (2t − ) sin120
0 0
3VmIm
(V YN
− VBN ) iR =
2
sin + sin ( 2t − )
09. Ans: 15
Solution:
I= IR2 + IL2
From phasor diagram
(12 ) + ( 9 )
2 2
A1 = = 225 =15Amp
1
(I )
fsd 2
=
20k V
= 0.05mA
Rm 5
Value of Shunt Resistance Required, R sh = = = 7.501 10−4
m−1 6666.667 − 1
Due to 100C change in Temperature, the meter and shunt resistance will be modified.
R 'm = R m (1 + m T ) = 5 (1 + 0.004 10 ) = 5.2
R 'sh = R sh (1 + sh T ) = 7.5 10 −4 (1 + 0.00015 10 ) = 7.51125 10 −4
For 100A current, the current in meter resistance is,
R sh 7.51125 10−4
Im = I = 100 = 0.0144A
R sh + Rm 7.51125 10 + 5.2
−4
0.0144 − 0.015
%error = 100 = −3.7%
0.015
RMS = 22 + (1 ) + ( 2 ) = 3Amp
2 2
230 2
Ouput current Peak value = = 7.07A
46
Hence
7.07
A 1 = rms value of Irms = = 3.53A
2
230 2
A 2 = Average value of Iavg = = 2.25A
46
V1 = peak value of Vout = 230 2 = 325.24 V
230 2
V2 = Average value of Vavg = = 103.53V
W = I2rms R= 573.20W
Hence reading of the wattmeter is proportional to the reactive power drawn by the load.
2Im
Average current through meter =
For FSD
2Im
IDC= 1mA =
Im = 1.57 mA
1.57
rms supply current IC = = 1.11 mA.
2
Now supply current
Vs 100
Is = = Rs + Rm
R s + Rm 1.11 mA
Rs + Rm = 90.07 K ( Rm = 0.1 K )
Rs = 89.97 K
dL
100 = 480 10 −6
d
dL
= 4.8 H rad
d
4 50 106
1000
Voltmeter reading =
( 4 10 3
+ 50 ) 8.16Volt
4 50 106
+ 6 10
6
( )
4 10 + 50
3
For a sampling wattmeter, average power of load for a given current and voltage
Rm 0.2
R sh = = =0.05ohm
m−1 5 −1
V
Let z be the impedance of pressure coil I p =
Z
As Ip 0 Hence produce additional magnetic field BP
Wattmeter reading = load power + losses in PC
Hence error produce due to magnetic field BP
Now compensating coil provided along with current coil IP is in opposite direction. The compensating coil produce
magnetic field (Bp) in opposite direction.
Hence compensating coil compensates the effect of impedance of voltage coil circuit.
V2 = 2 j I
V = V1 + V2 = j I
V1 = | V1 | = I and V2 = | V2 | = 2I
V 2 – V1 = I = V
V = |V| = I
Hence V = V2 − V1
Time Period, T = 20 ms
Amplitude, V = 100 V
V
Equation of line = t
T
2 T
T T
1 Vt 1 V2 2 V2 t 3 V2 T3 V
T 0 T T T2 0
Vrms = dt = t dt = = =
T3 3
0 T3 3 3
V 100
Vrms = = = 57.73V
3 3
Note: The expression for rms value of sawtooth waveform can be directly memorized.
P2 + P1 250 + 100
pf = cos 0.8
63. Ans: 2
Solution:
Power setting VIcos 150 10 0.2
Multiplying factor = = = =2
Power for maximum deflection PFS 150
2 3
(RMS) = 2 3 =
2 2
( )
Reading of second watt meter = VLIL cos 30 − = 4.083 cos15 = 3.943kW
70. Ans: 2
Solution:
Meter constant of energy meter = 1200 revolutions/KWh
Number of revolutions = 20
30
Time = 30 sec = hours
60 60
Let P be the load in Watts.
Revolutions
Meter constant =
KWh
20
1200 =
P 30
1000 60 60
20 2 60 1000
1200 =
P
20 2 60 1000
P= = 2000 Watts = 2KW
1200
71. Ans: (d)
Solution:
Total real power = 3 577.35 = 1732.05W
Apparent power = 3467VA
1732
pf = P = = 0.5
S 3464
When switch is move to Y, the potential coil of second wattmeter gets shorted
Hence W2 = 0
W1 : VPC = VRY ; ICC = IR
W1 = VRY IR cos ( 30 + 60 ) = 0
W3 : VPC = VBY ;ICC = IB
S
W3 = VL IL cos30 = cos30 = S = 1732W
3 2
(b) L = R R / R , R = C R R
2 3 4 4 2 3
(c) R = R
4 (
/R R , L =1 C R R
2 3 4 2 3 )
(d) L = R /R R , R = 1 (C R R )
4 2 3 4 2 3
(a) 56.02 (b) 40.83
10. The bridge circuit shown in the figure below is used for (c) 29.85 (d) 10.02
the measurement of an unknown element Z x . The bridge
14. The reading of the voltmeter (rms) in volts, for the
circuit is best suited when Z x is a [2011]
circuit shown in the figure is ____________. [2014-01]
15. In the Wien bridge oscillator circuit shown in figure, the (a) [123.50, 136.50]
bridge is balanced when [2014-01]
R R
(a) (1 + x )
1
(a) 3 = 1 , =
R R (b) (1 + x)
4 2 R C R C
1 1 2 2
R C 1
(c) 1 / (1 + x )
(b) 2 = 2, =
R C R C R C
1 1 1 1 2 2 (d) (1 − x )
R R C 1
(c) 3 = 1 + 2, =
R R C R C R C
4 2 1 1 1 2 2
19. Inductance is measured by [2021]
R R C 1 (a) Schering bridge (b) Maxwell bridge
(d) 3 + 1 = 2 , =
R R C R C R C (c) Kelvin bridge (d) Wien bridge
4 2 1 1 1 2 2
20. A balanced Wheatstone bridge ABCD has the following
16. In the bridge circuit shown, the capacitors are loss free. arm resistances: RAB = 1 k 2.1%; RBC = 100 0.5%; RCD
At balance the value of capacitance C in microfarad is is an unknown resistance; RDA = 300 0.4%. The value
1
of RCD and its accuracy is [2022]
_________________. [2014-03]
(a) 30 3 (b) 30 0.9
(c) 3000 90 (d) 3000 3
Solutions
01. Ans: A-S, B-R, C-P, D-Q
Solution:
L1 1
Q= =
R1 C 4R 4
For high Q coil
L1 = R2R3C4
R1 = 2R2R3C24R 4
Hence R 4 appear in only one equation. First R 2 is varied as it appears in both then equations to obtain minimum
deflection in detector. At minimum deflection L1 is balanced now R 4 varied to balance R 1 equation
So first R 2 is adjusted and then R 4 is adjusted
Z=
(300 − j200 )(300 + j200 ) = 260
500
R 2R 3
R=
R4
L = R2R3C4
1
Due to open circuit the inductor and capacitor are connected in series and impedance of each branch, Z = j + = 0
j
Hence, both parallel branches are shorted.
1000
Supply Current, Is = = 2000A
0.5
This current would be equally divided in the two parallel branches. So, current in each branch
2000
I= = 1000A
2
Voltage across inductor in 1st branch = 1000 j = 10090V
Voltage across capacitor in 2nd branch = 1000 − j = 100 − 90V
Voltage across voltmeter = 10090 − 100 − 90 = 20090 V
Peak Voltage = 200V
200
RMS Voltage = = 141.42V
2
65 95
R = = 123.5
x 50
If R = 105 ,
3
65 105
R = = 136.5
x 50
Therefore, R = 123.5, 136.5
x
(1 + p )2 − 2 (1 + p ) − x = 0
p2 + 2p + 1 − 2 − 2p − x = 0
p2 = 1 + x
p = 1+x
R CD =
RBCRDA
=
(100 0.5% ) (300 0.4% )
R AB (1k 2.1% )
= 30 3% = 30 3/100 × 30 = 30 0.9
Chapter 4 – CRO
01. A CRO screen has ten divisions on the horizontal scale. (c)
(
If a voltage signal 5sin 314t + 45 ) is examined with a (R) fy=125
(S) fy=150
line base setting of 5msec/div, the number of cycles of
signal displayed on the screen will be [1993] (T) fy=200
(a) 0.5 cycles (b) 2.5 cycles (U) fy=300
(c) 5 cycles (d) 10 cycles
02. A Lissajous pattern, as shown in figure, is observed on 06. Fig shows the electrostatic vertical deflection system of
the screen of a CRO when voltages of frequencies CRT. Given that VA is the accelerating voltage, the
fx and fy are applied to the x and y plates respectively.
deflection sensitivity (deflection/volt) is proportional to: [1998]
fx : fy is then equal to [1994]
(a) 3:2
(b) 1:2
(c) 2:3
(d) 2:1
Group II
(a) A, B, C, A (b) A, B, C, B
(c) C, B, A, B (d) B, A, B, C
( )
13. Two sinusoidal signals p 1 t = A sin 1t and q 2 t( )
(a) 3.53 V (b) 4.37 V
(c) 4.54 V (d) 5.00 V are applied to X and Y inputs of a dual channel CRO. The
Lissajous figure displayed on the screen is shown below:
10. The simultaneous application of signals x(t) and y (t ) to The signal q 2 t( ) will be expressed as [2008]
the horizontal and vertical plates, respectively, of an
oscilloscope, produces a vertical figure-of - 8 display. If P
and Q are constants, and x(t)=P sin(4t+30) , then y (t ) is ( )
(a) q 2t = A sin 2t, 2 = 21
equal to [2005]
1
(a) Q sin(4t − 30) (b) Q sin(2t + 15)
( )
(b) q 2t = A sin 2t, 2 =
2
(c) Q sin(8t + 60) (d) Q sin(4t + 30)
( )
(c) q 2t = A cos 2t, 2 = 21
11. The time/div and voltage/div axes of an oscilloscope
1
have been erased. A student connects a 1 kHz, 5V p-p
square wave calibration pulse to channel 1 of the scope
( )
(d) q 2t = A cos 2t, 2 =
2
and observes the screen to be as shown in the upper trace
of the figure. An unknown signal is connected to channel 2
14. The two inputs of a CRO are fed with two stationary (b)
periodic signals. In the X-Y mode, the screen shows a figure
which changes from ellipse to circle and back to ellipse
with its major axis changing orientation slowly and
repeatedly. The following inference can be made from this.
[2009]
(a) The signals are not sinusoidal
(b) The amplitudes of the signals are very close but not
equal
(c) The signals are sinusoidal with their frequencies very
close but not equal
(d) There is a constant but small phase difference between (c)
the signals
(a)
Solutions
01. Ans: (b)
Solution:
10 divisions= 50m/sec
1 division= 5msec
314
Frequency f = = 50Hz
2
Period= 1/50= 20ms
50
In 10 divisions → = 2.5 cycles
20
fy 6
(c) = =3
fx 2
fy = 300Hz
(c) → (U)
(P) = 0 ⎯⎯
→
(Q) = ⎯⎯
→
2
(S) = 3 ⎯⎯
→
2
(R) 3 ⎯⎯
→
2
VAB = Vin 1 − e L
−Rt
So, S1 is connected to A
G1 is connected to B
So, S 2 is connected to C.
And G2 is connected to B
Hence control input signal will have a frequency equal to the frequency of the time base (Sweep) oscillator.
02. Precautions are essential for ensuring that the 06. A 50 Hz, bar primary CT has a secondary with 500 turns.
secondary of a CT is not open circuited when the primary The secondary supplies 5A current into a purely resistive
circuit carries a current because [1991] burden of 1Ω. The magnetizing ampere-turns is 200. The
(a) Dangerously high voltage might develop across the phase angle between the primary and secondary current is
secondary [2004]
(b) The ferromagnetic core may develop residual (a) 4.6° (b) 85.4°
magnetism (c) 94.6° (d) 175.4°
(c) The reflected impedance may prevent the flow of
current in the primary circuit 07. A 50 Hz, bar primary CT has a secondary with 500 turns.
(d) None of the above The secondary supplies 5A current into a purely resistive
burden of 1W. The magnetizing ampere-turns is 200. The
03. The primary current in a current transformer is dictated core flux in the CT, under the given operating condition is
by [1997] [2004]
(a) The secondary burden (a) 0 (b) 45.0µWb
(b) The core of the transformer (c) 22.5mWb (d) 100.0mWb
(c) The load current
(d) None of the above 08. A 200/1 current transformer (CT) is wound with 200
turns on the secondary on a toroidal core. When it carries
04. Instrument transformers are known to introduce a current of 160 A on the primary, the ratio and phase
magnitude and phase errors in measurements. These are errors of the CT are found to be -0.5% and 30 minutes
primarily due to [2000] respectively. If the number of secondary turns is reduced
(a) Improper connections on the primary side by 1 the new ratio error (%) and phase error (min) will be
(b) Measurement errors inherent in the meter connected to respectively [2006]
the transformer secondary (a) 0.0, 30 (b) −0.5, 35
(c) Open and short circuit parameters of the instrument (c) −1.0, 30 (d) −1.0, 25
transformers
(d) None of the above
Solutions
01. Ans: (b)
Solution:
Using strip wound core reduces the number of joints and hence the reluctance reduces so that the no-load current drawn
by Transformer reduces. This reduces the ratio and phase errors in CT.
(nI )
2
IP = S
+ Im2 = 559.017
559.017
Actual ratio = = 111.803
5
100 − 111.803
Ratio error = 100% = −10.56%
111.803
(a) 1V
(b) 150V
(c) 120V
(d) 147V
Solutions
01. Ans: (c)
Solution:
Reversing polarities method is used to eliminate the effect of thermal EMF.
1
02. A 4 digit DMM has the error specification as: 0.2% of
2
reading + 10 counts. If a dc voltage of 100V is read on its
200V full scale, the maximum error that can be expected in
the reading is [2011]
(a) ±0.1% (b) ±0.2%
(c) ±0.3% (d) ±0.4%
Solutions
01. Ans: (c)
Solution:
Since the wave is symmetric about real axis we can only compute half cycle average.
Vm
which is equal to = 10 = Vm = 20V
2
rms reading meter reads rms value.
V
For triangular wave rms value = m (standard result)
3
RMS=
20 V
3
1
Maximum count on 4 digital display = 19999
2
Full scale voltage = 200 V.
Hence full count 19999 = 200V
200
10 counts = 10
19999
10 counts = 0.1 Volt
To measure 100 V DC
Reading has error of 0.2 % + 10 count
0.2 % of 100 V = 0.2V
Total error = 0.2 + 0.1 = 0.3 Volt
Reading = 100 ± 0.3 V
Error = ±0.3%
Chapter 8 – Transducers
01. A metal strain gauge has factor of two. Its nominal
resistance is 120 ohms. If it undergoes a strain of 10−5 , the
value of change of resistance in response to the strain is
[1993]
Solutions
01. Ans: (b)
Solution:
R
= Gauge factor ×
R
= strain
R
= 2 × 10–5
120
R = 240 × 10–5