100% found this document useful (1 vote)
2K views19 pages

Operating Manual CSDPR-V2-200-N

This document provides instructions for setting up protection settings for a CSDPR-V2 relay. There are two groups of protection settings that can be selected as the active group. The first screen displays primary current measurements. Various protection parameters like CT ratio, overcurrent pickup, trip characteristics can be edited from the protection menu. Fault records and trip outputs can also be configured.

Uploaded by

JohnTP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views19 pages

Operating Manual CSDPR-V2-200-N

This document provides instructions for setting up protection settings for a CSDPR-V2 relay. There are two groups of protection settings that can be selected as the active group. The first screen displays primary current measurements. Various protection parameters like CT ratio, overcurrent pickup, trip characteristics can be edited from the protection menu. Fault records and trip outputs can also be configured.

Uploaded by

JohnTP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19




How to do Setting
Two group of Protection Setting are available in CSDPR-V2 relay. User can select One Group as Active Group. For setting below are
simple steps for configuration:

Default First Screen

MAIN DEFAULT SCREEN PAGE:


L1 : XXXX.X Amp
The very first Screen of the HMI shows the
Measured Primary Current for all the phases L2 : XXXX.X Amp
based on CT ratio.
L3 : XXXX.X Amp

Ie : XXXX.X Amp

<Menu 1>

“# EDIT/VIEW PARAMETER #"

<GROUP SEL> : For Active Group Selection of Parameter

<PROTECTION> : Protection Related Parameter Menu

E <FAULT RECORD> : Fault Record Menu


Press Key
<RELAY ASSIGN> : Programmable Relay Assignment Menu

<DI BLOCKING> : DI-Protection Blocking Menu

<TRIP TYPE> : Output Trip Type Configuration Menu

<RLY RESET MODE> : Programmable Relay Reset Menu

<RST TRIP COUNT> : TRIP COUNTER Reset Menu


By using the scroll keys
select the <TRIP TEST> : Output Trip Test Menu
desired menu and <COMM SETTING> : Communication RS485 Menu
press enter.
<EDIT RTC> : Clock Setting Menu

<CHNG PASSWORD>: Password Change Menu

< FACT SETTING > : Factory Setting Menu *

<RELAY VERSION> : Relay Version Menu

BACK

* Note: Factory setting menu is not for user. It is for factory setting purpose.
From Menu-1:
# GROUP SEL #
On Selecting <GROUP SEL> Menu, out
of two groups of setting, one group
ACT.GROUP: GROUP 1
[Group1 / group2] at a time can be
activated as ACTIVE GROUP & some will
be visible in parameters. ←BACK

“# EDIT/VIEW PARAMETER #"


From Menu-1:
On selecting <PROTECTION> List of all "CT_Ratio" : 0001 : CT Ratio for primary current display
the Editable parameter of protection will
appear by using the Scroll keys "CHAR-P" : DEFT : Phase over-current trip characteristic

select the desired Parameter & Press "CHAR-E" : DEFT : Earth over-current trip characteristic
Enter key to Edit the selected parameter.
"I>" : 0.30xIn : Over-current Pickup

"ti>" : 0.030 : TMS Over-current Setting

"t>" : 003.00s : DEFT Trip Time

"l>>" : 0.5 x In : Short Circuit Protection

"t>> : 00.05s : DEFT Trip timing for SC Protection

"le>" : 0.05 x In : Earth Over-current Pickup

"tie>" : 0.030 : TMS Over-current Setting

"te>" : 005.00s : DEFT Trip Time

"Ie>>" : 0.5x In : Earth High-set Pickup

"te>>" : 00.50s : DEFT Trip timing Earth High

“U0>" : 10% : Unbalance Pickup

“t0>" : 000.50s : Unbalance DEFT Trip time

“CBFP” : YES : CBFP Protection

“tCBFP” : 1.24s : CBFP Supervision Time

“TCS_DLY” : 0.50 : TCS supervision delay

←BACK
From Menu-1:
# FAULT RECORD #
On selecting <<FAULT RECORD>>
Menu, it will show the Fault number
<FAULT NUMBER>
(latest one as 1) & then it will show the
FAULT Current, Fault Type with date &
<ERASE FAULT>
Time & also the trip timing as per setting.
To erase all the fault record choose
“ERASE FAULT” selection.
←BACK
# RELAY ASSIGN #
*From Menu-1:
"OC_RELAY" : DISABLE
On Selecting <RELAY ASSIGN> user can
assign the Relay 1 & 2 on OC/SC E/EH "SC_RELAY" : RLY-1
/CBFP /U0>. By default it will be in
Disable Mode. These two relays will work "E_RELAY" : RLY-2
only in presence of Auxiliary supply.
"EH_RELAY" : DISABLE
Use the Scroll keys , to
"CBFP_RY" : DISABLE
select the desired Parameter & Press
Enter key to edit the selected parameter. “U0-RY" : DISABLE

“TCS-RY" : RLY-1
←BACK

* From Menu-1:
# DI BLOCKING #
On Selecting <DI BLOCKING> user can
program blocking of any of Protection, "I>" : BLOCK
based on applying Voltage to Blocking
"I>>" : UNBLOCK
DI. Protection will get block only when DI
Blocking will be assigned & Voltage will "Ie>" : BLOCK
be applied to BLOCKING-DI. By using
the Scroll keys select the desired "Ie>>" : BLOCK
Parameter & Press Enter key to Edit the
selected parameter
“U0>" : UNBLOCK

←BACK

From Menu-1: # TRIP TYPE #


On Selecting <TRIP TYPE> user can
select the required Trip Output i.e. MHT
"TripO/P: MHT
Coil OR Latch Relay OR DUAL.
←BACK

From Menu-1:

On selecting <RLY RESET MODE>


# RLY RESET MODE #

Use the Scroll keys , to RSET MODE : AUTO

select the desired Parameter & Press ←BACK


Enter key.