Operating Manual CSDPR-V2-200-N
Operating Manual CSDPR-V2-200-N
How to do Setting
Two group of Protection Setting are available in CSDPR-V2 relay. User can select One Group as Active Group. For setting below are
simple steps for configuration:
Ie : XXXX.X Amp
<Menu 1>
BACK
* Note: Factory setting menu is not for user. It is for factory setting purpose.
From Menu-1:
# GROUP SEL #
On Selecting <GROUP SEL> Menu, out
of two groups of setting, one group
ACT.GROUP: GROUP 1
[Group1 / group2] at a time can be
activated as ACTIVE GROUP & some will
be visible in parameters. ←BACK
select the desired Parameter & Press "CHAR-E" : DEFT : Earth over-current trip characteristic
Enter key to Edit the selected parameter.
"I>" : 0.30xIn : Over-current Pickup
←BACK
From Menu-1:
# FAULT RECORD #
On selecting <<FAULT RECORD>>
Menu, it will show the Fault number
<FAULT NUMBER>
(latest one as 1) & then it will show the
FAULT Current, Fault Type with date &
<ERASE FAULT>
Time & also the trip timing as per setting.
To erase all the fault record choose
“ERASE FAULT” selection.
←BACK
# RELAY ASSIGN #
*From Menu-1:
"OC_RELAY" : DISABLE
On Selecting <RELAY ASSIGN> user can
assign the Relay 1 & 2 on OC/SC E/EH "SC_RELAY" : RLY-1
/CBFP /U0>. By default it will be in
Disable Mode. These two relays will work "E_RELAY" : RLY-2
only in presence of Auxiliary supply.
"EH_RELAY" : DISABLE
Use the Scroll keys , to
"CBFP_RY" : DISABLE
select the desired Parameter & Press
Enter key to edit the selected parameter. “U0-RY" : DISABLE
“TCS-RY" : RLY-1
←BACK
* From Menu-1:
# DI BLOCKING #
On Selecting <DI BLOCKING> user can
program blocking of any of Protection, "I>" : BLOCK
based on applying Voltage to Blocking
"I>>" : UNBLOCK
DI. Protection will get block only when DI
Blocking will be assigned & Voltage will "Ie>" : BLOCK
be applied to BLOCKING-DI. By using
the Scroll keys select the desired "Ie>>" : BLOCK
Parameter & Press Enter key to Edit the
selected parameter
“U0>" : UNBLOCK
←BACK
From Menu-1:
* Model dependent