49VO-0001 Visible Notification Appliances
49VO-0001 Visible Notification Appliances
49VO-0001 Visible Notification Appliances
UL, ULC, CSFM Listed; FM Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series
Approved* 49VO
Features BOCA, ICBO, or SBCCI; and the application guidelines of the Americans
with Disabilities Act (ADA).
Individually addressed and controlled multi-candela TrueAlert ES
V/O (visible only) notification appliances provide:
• Multi-candela xenon strobe with synchronized 1 Hz flash rate and with
intensity programmable from the control panel or jumper selected
as 15, 30, 75, 110, 135, or 185 cd
• Advanced addressable notification controlled by IDNAC SLCs providing
regulated 29 VDC allowing strobes to operate with lower current even
under battery backup
• Wiring supervision to each appliance allowing "T-tapped" connections
for Class B circuits to simplify wiring (Class A circuits require in/out
wiring)
• Self-Test Mode allows an on-board sensor to detect the strobe output
and then report its status to the control panel
• TrueAlert Device Reports at the control panel detailing appliance point
ID, custom label, type, and candela setting
• Magnet Test diagnostics to assist checkout and testing of appliances
and wiring and Electrical test point access without removing cover
• Compatibility with ADA requirements; (refer to Installation Reference)
• Compatibility with legacy TrueAlert addressable systems for upgrade
and replacement (see TrueAlert ES Strobe LEGACY Compatibility
Figure 1: TrueAlert ES Addressable
Reference)
Strobes are Available in Red with White
• Listed to UL Standard 1971 and ULC Standard S526 Lettering and White with Red Lettering
* These products have been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:0373 for allowable
values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals
under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
TrueAlert ES Diagnostics
Test Features. When IDNAC SLCs are in diagnostic mode, Self-Test and Magnet Test features provide individual appliance testing. With the Self-Test
feature, appliance operation can be confirmed without leaving the control panel. Additionally, each appliance’s LED can be selected to pulse when it
receives a supervision poll during normal operation.
Self-Test Details. Selecting Self-Test Mode from the control panel allows on-board sensors, depending on the device type, to detect its own strobe
and/or horn output and then report their status to the control panel. Operation is by selected VNAC appliance groups and is either automatic (all
briefly simultaneously activated) or individually activated by applying a magnet (Refer to control panel data sheet for more Self-Test information, see
IDNAC SLC Controller Compatibility Reference).
Silent Appliance Magnet Test. In this test mode, in response to application of a magnet, the appliance LED pulses sequentially to conveniently
indicate the appliance’s address.
Operational Appliance Magnet Test. In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash to
indicate proper operation.
TrueStart Instrument Two (TSIT). The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert
ES appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex
representative for additional information.
Installation Reference
The 2975-9145 box is shown mounted to the 4905-9931 Adapter Plates. Also shown is the optional surface mount adapter skirt (available in red
4905-9937 or white 4905-9940)., as well as the 4905-9961 optional wire guard.
Product Selection
Table 1: TrueAlert ES Wall Mount Addressable Strobes
Specification Rating
Typical Operating Voltage Range 23 VDC to 31 VDC, Special Application (see below for 17 VDC rating)
Supervisory Requirements 1 unit load (= 0.8 mA control panel current)
IDNAC SLC Loading Maximum of 127 addresses per SLC, 139 unit loads
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without
notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are
registered trademarks of the National Fire Protection Association (NFPA).
S49VO-0001 Rev. 7 3/2018