TrueAlert ES Addressable Notification Appliances

UL, ULC, CSFM Listed; FM Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series
Approved* 49VO

Features BOCA, ICBO, or SBCCI; and the application guidelines of the Americans
with Disabilities Act (ADA).
Individually addressed and controlled multi-candela TrueAlert ES
V/O (visible only) notification appliances provide:
• Multi-candela xenon strobe with synchronized 1 Hz flash rate and with
intensity programmable from the control panel or jumper selected
as 15, 30, 75, 110, 135, or 185 cd
• Advanced addressable notification controlled by IDNAC SLCs providing
regulated 29 VDC allowing strobes to operate with lower current even
under battery backup
• Wiring supervision to each appliance allowing "T-tapped" connections
for Class B circuits to simplify wiring (Class A circuits require in/out
wiring)
• Self-Test Mode allows an on-board sensor to detect the strobe output
and then report its status to the control panel
• TrueAlert Device Reports at the control panel detailing appliance point
ID, custom label, type, and candela setting
• Magnet Test diagnostics to assist checkout and testing of appliances
and wiring and Electrical test point access without removing cover
• Compatibility with ADA requirements; (refer to Installation Reference)
• Compatibility with legacy TrueAlert addressable systems for upgrade
and replacement (see TrueAlert ES Strobe LEGACY Compatibility
Figure 1: TrueAlert ES Addressable
Reference)
Strobes are Available in Red with White
• Listed to UL Standard 1971 and ULC Standard S526 Lettering and White with Red Lettering

LED Indicator and Magnet Test feature:


• Appliance LED can be selected to display each polling cycle to indicate TrueAlert ES Operation Advantage
appliance supervision TrueAlert ES addressable appliances on IDNAC SLCs provide
• When the controller is in diagnostic mode, the Magnet Test pulses the separate visible (and audible) notification using a single two-wire circuit
LED to indicate appliance address and can be set to also briefly flash that also confirms connection to the individual notification appliance's
the strobe electronic circuit. This operation increases circuit supervision integrity
by providing supervision that extends beyond the appliance wiring
Mechanical design features include: connections.
• Rugged, high impact, flame retardant thermoplastic housing in red with Reduced current allows efficient IDNAC SLC operation. With
white letters or white with red letters, with clear lens, available with IDNAC SLCs, a constant 29 VDC source voltage is maintained, even
FIRE, ALERT, FEU, FEU/FIRE, or blank lettering during battery standby, allowing strobes to operate at higher voltage
• Separate covers are available to change appliance type on-site or for with lower current and ensuring a consistent current draw and voltage
replacement; covers can be easily removed without disturbing the drop margin under both primary power and secondary battery standby.
connected housing and avoiding trouble conditions Efficiencies include wiring distances up to 2 to 3 times farther than with
• A separate mounting plate allows wiring to be completed before conventional notification, or support for more appliances per IDNAC SLC,
appliance is mounted; use with single gang, double gang, or 4-inch or use of smaller gauge wiring, or combinations of these benefits, all
square box, flush or surface mount providing installation and maintenance savings with high assurance that
appliances that operate during normal system testing will operate during
• In/out wiring terminals for 18 AWG to 12 AWG
worst case alarm conditions.
• Optional mounting adapters are available to cover surface mounted
Reducing Installation and Testing Time. With separate controls on
electrical boxes and to adapt to Simplex, 2975-9145 boxes
the same two-wire SLC, installation time and expense for both retrofit
• Optional red wire guards (see Product Selection) and new construction can be significantly reduced. When Class B wiring
is used, wiring can be "T" tapped, allowing more savings in distance,
Description wire, conduit (size and utilization), and overall installation efficiency. Use
of Self-Test and Magnet Test features improves installation efficiency.
TrueAlert ES addressable strobes TrueAlert device reports conveniently identify information about each
TrueAlert ES addressable strobes are individually addressed visible connected appliance.
notification appliances that receive power, supervision, and control
signals from the Simplex fire alarm control panel providing IDNAC
Signaling Line Circuits (SLCs). (See IDNAC SLC Controller Compatibility
Reference.)

Strobe Application Reference


Proper selection of visible notification is dependent on occupancy,
location, local codes, and proper applications of: the National Fire Alarm
Code (NFPA 72), ANSI A117.1; the appropriate model building code:

* These products have been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125-0026:0373 for allowable
values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals
under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

S49VO-0001 Rev. 7 3/2018


Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series 49VO

TrueAlert ES Diagnostics
Test Features. When IDNAC SLCs are in diagnostic mode, Self-Test and Magnet Test features provide individual appliance testing. With the Self-Test
feature, appliance operation can be confirmed without leaving the control panel. Additionally, each appliance’s LED can be selected to pulse when it
receives a supervision poll during normal operation.
Self-Test Details. Selecting Self-Test Mode from the control panel allows on-board sensors, depending on the device type, to detect its own strobe
and/or horn output and then report their status to the control panel. Operation is by selected VNAC appliance groups and is either automatic (all
briefly simultaneously activated) or individually activated by applying a magnet (Refer to control panel data sheet for more Self-Test information, see
IDNAC SLC Controller Compatibility Reference).
Silent Appliance Magnet Test. In this test mode, in response to application of a magnet, the appliance LED pulses sequentially to conveniently
indicate the appliance’s address.
Operational Appliance Magnet Test. In this test mode, after the address is indicated by pulsing the appliance LED, the strobe will briefly flash to
indicate proper operation.
TrueStart Instrument Two (TSIT). The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert
ES appliances to its ability to test IDCs, NACs, and IDNet communications before connection to the control panel. Please contact your local Simplex
representative for additional information.

TrueAlert Addressable Wiring Isolator


Isolator Model 4905-9929 is available for remote mounting on TrueAlert addressable circuits to isolate short circuited wiring from functioning wiring.
(See data sheet S4905-0001 .)

Page 2 S49VO-0001 Rev. 7 3/2018


Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series 49VO

Installation Reference

Figure 2: Installation Reference

Adapter Plate and Surface Mount Installation Reference

Figure 3: Adapter Plate and Surface Mount Installation Reference

The 2975-9145 box is shown mounted to the 4905-9931 Adapter Plates. Also shown is the optional surface mount adapter skirt (available in red
4905-9937 or white 4905-9940)., as well as the 4905-9961 optional wire guard.

Page 3 S49VO-0001 Rev. 7 3/2018


Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series 49VO

Product Selection
Table 1: TrueAlert ES Wall Mount Addressable Strobes

SKU* Cover Color Wording Lens Color


49VO-WRF
Red
49VO-WRF-BA
FIRE
49VO-WWF
White
49VO-WWF-BA
49VO-WRA
Red
49VO-WRA-BA
ALERT
49VO-WWA
White Clear
49VO-WWA-BA
49VO-WRQ Red
FEU
49VO-WWQ White
49VO-WRS
Red
49VO-WRS-BA
Simplex logo only
49VO-WWS
White
49VO-WWS-BA
49VO-APPLW
Select cover and mounting plate separately
49VO-APPLW-BA
TrueAlert ES addressable VO (strobe) appliances include cover and matching mounting plate except as noted; Dimensions with Cover = 5 ⅛" H x 5" W
x 2 ⅝" D (130 mm x 127 mm x 67 mm)

Table 2: Separate Mounting Plate

Model Color Note


49MP-AVVOWR Red
Mounting Plate is required when ordering model 49VO-APPLW(-BA)
49MP-AVVOWW White

Table 3: Separate Covers (Required when ordering model 49VO-APPLW(-BA))

SKU* Color Wording


49VOC-WRFIRE Red
FIRE
49VOC-WWFIRE White
49VOC-WRALT Red
ALERT
49VOC-WWALT White
49VOC-WRFEU Red
FEU
49VOC-WWFEU White
49VOC-WRBLNG Red
FEU/FIRE
49VOC-WWBLNG White
49VOC-WRS Red
Simplex logo only
49VOC-WWS White

Table 4: Mounting Adapters and Wire Guard

Model Color Description Dimensions


4905-9937 Red 5 ⅜" H x 5 ¼" W x 1 ⅝" D (136 mm x 133 mm x 41 mm)
Surface Mount Adapter Skirt
4905-9940 White Total depth with strobe = 4 ⅜" (111 mm)
Red Adapter Plate for mounting to Simplex, 2975-9145 Box (typically
4905-9931 8 5⁄16" x 5 ¾" x 0.060" Thick (211 mm x 146 mm x 1.5 mm)
for retrofit, mount vertical or horizontal)
2975-9145 Red Mounting Box, requires 4905-9931 Adapter Plate 7 ⅞" x 5 ⅛" x 2 ¾" D (200 mm x 130 mm x 70 mm)
Red wire guard with mounting plate, compatible with semi-flush or
4905-9961 6 1⁄16" H x 6 1⁄16" W x 3 ⅛" D (154 mm x 154 mm x 79 mm)
surface mount boxes

Page 4 S49VO-0001 Rev. 7 3/2018


Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series 49VO

IDNAC SLC Controller Compatibility Reference


Data Sheet IDNAC SLC Output Appliance Voltage
Compatible Controllers Controller Output
Reference Voltage Design Reference
4100ES with EPS+ or EPS Power Supply S4100-0100
4009 IDNAC Repeater S4009-0004 23 VDC
IDNAC SLC 29 VDC (regulated)
4007ES with IDNAC Notification S4007-0002 (with 6 VDC drop)
4010ES with ESS Enhanced System Supply S4010-0011

TrueAlert ES Strobe Specifications


Table 5: Electrical Ratings

Specification Rating
Typical Operating Voltage Range 23 VDC to 31 VDC, Special Application (see below for 17 VDC rating)
Supervisory Requirements 1 unit load (= 0.8 mA control panel current)
IDNAC SLC Loading Maximum of 127 addresses per SLC, 139 unit loads

Table 6: Candela Setting

Candela 15 cd 30 cd 75 cd 110 cd 135 cd 185 cd


23 VDC RMS Current Ratings, for typical design
47 mA 57 mA 100 mA 132 mA 160 mA 208 mA
of IDNAC Addressable SLCs (6 VDC drop)

Table 7: General Specifications

Temperature Range 32° to 122° F (0° to 50° C)


Humidity Range 10% to 93%, non-condensing @ 104° F (40° C)
UTP, unshielded twisted pair recommended
IDNAC SLC Wiring Specifications (refer to control Maximum wire length allowed with "T-Taps" for Class B wiring per SLC = 10,000 ft (3048
panel installation instructions for more information) m)
Maximum wire length to any appliance = 4000 ft (1219 m)
Terminal blocks on mounting plate for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two
Connections
wires per terminal for in/out wiring
Installation Instructions 579-1031
Note: Refer to compatibility table above for fire alarm control panel and power supply operation type.

Page 5 S49VO-0001 Rev. 7 3/2018


Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series 49VO

TrueAlert ES Strobe LEGACY Compatibility Reference


Table 8: Compatibility Reference

Data Sheet Appliance Voltage


Compatible Controller Controller Output Available Strobe Intensity
Reference Minimum
4100ES or 4100U with TrueAlert
S4100-0031
Power Supply
4009 TPS, Remote TrueAlert
S4100-0037 TrueAlert Addressable SLC 15, 30, 75, and 110 cd 17 VDC
Power Supply
TrueAlert Addressable
S4009-0003
Controller (4009T)

Table 9: Electrical Ratings Reference for Retrofit Applications

Voltage Range 17 VDC to 31 VDC, Special Application


Candela Setting 15 cd 30 cd 75 cd 110 cd
17 VDC RMS Current Ratings, use when
connected to TrueAlert Addressable SLCs per 62 mA 75 mA 133 mA 178 mA
above

© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without
notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are
registered trademarks of the National Fire Protection Association (NFPA).
S49VO-0001 Rev. 7 3/2018

You might also like