Three Phase Transformer (2) - 1
Three Phase Transformer (2) - 1
Equipments
Three phase transformer
3 Watt meters
3 AC Ammeters
2 AC voltmeter
Connecting cables
1 Power cable
Transformation Ratio
The transformation ratio is defined as the ratio of output voltage to the input voltage of the
transformer. It gives the information about the change in voltage level by the transformer.
Calculate the transformation ratio of the transformer at the rated voltage
PROCEDURE:
1. Connect the circuit as shown in figure with the 3pole switch(Icc) in closed position and
make sure the high voltage side corresponds to the left side of connection diagram.
2. Keep the three phase variac at its zero position.
3. Switch on the main supply and turn on the variac
4. Turn on the variac slowly until the current Isc reaches the rated current value.
5. Repeat the previous steps by reducing the voltage at intervals and record the values in the
table.
6. Turn off the variac.
The characteristic curve for a short circuit test of a three phase transformer
Plot the copper losses Wsc Vsc and power factor cossc against the current Isc.
The short circuit test is used to determine the values Req and Xeq of the series branch of the
equivalent circuit. These impedances are usually very low, but appear higher in value when
referred to the high voltage side. This test is consequently performed on high voltage side of the
transformer in order to keep the current drawn by these impedances at a manageable level.
The open circuit test is used to determine the values of the shunt branch of the equivalent
circuit Ro and Xo
With the secondary winding left open, the only part of the equivalent circuit that affects our
measurement is the parallel branch. The impedance of the parallel branch is usually very high but
appears lower when referred to the low voltage side. This test is therefore performed on the low
voltage side of the transformer to increase the current drawn by the parallel branch to a readily
measurable level. Besides, the rated voltage on the low voltage side is lower and therefore more
manageable
The characteristic curve for an open circuit test of a three phase transformer
VOLTS(V) I1(A) I2(A) I3(A) I0(A) P1(W) P2(W) P(W) coso
50
100
150
200
250
300
350
400
415
415
Plot the characteristic curves of no-load current I0, core loss W0, against the applied
voltage V0 on the same graph paper.
The practical transformer has two types of major losses namely copper and core losses. The
temperature of the transformer rises due to these losses which are dissipated as heat. Due to these
losses, input power drawn by the primary no longer equal to the output delivered at secondary.
Therefore, the efficiency of the transformer is given as
Efficiency of the transformer is defined as:
η = output power/ input power
In terms of losses,
η = output power /output power+ iron losses + copper losses
consider
power output= the KVA rating of the transformer
Assume the power factor =0.8
Report
-Calculate the transformation ratio of the transformer at the rated voltage
-Plot the characteristic curves from the test results
-Determine the equivalent circuit parameters at the rated values from the test results.
Question
1.Which winding (LV or HV) should be kept open while conducting OC test? Justify your
answer.
2.Why are transformers rated in kVA and not in kW?