XF821A
XF821A
PRODUCT DATA
FEATURES
Plug-and-play functionality for easy maintenance.
Pluggable Panel Bus I/O modules can be exchanged
without rewiring. Further, the separate installation of
terminal sockets and electronic modules lower risk of
damage and theft in the construction phase.
Fast wiring with state-of-the-art push-in terminals (screw-
GENERAL type terminals also available) and bridge connectors.
The Honeywell Panel Bus I/O Modules communicate via the Wide range of sensors supported (NTC20kΩ, NTC10kΩ,
Panel Bus. PT1000-1/-2, Johnson A99 PTC, NI1000TK5000, PT3000,
The pluggable Honeywell Panel Bus I/O modules consist of a Balco500, 0/2…10 V, 0/4…20 mA). NOTE: The mixed
terminal socket and a removable electronic module, allowing Panel Bus I/O modules XF830A, XFU830A, and CPO-
the socket to be mounted and wired before the electronic IO830 feature inputs suitable for signals from NTC20kΩ
module is installed. All such electronic modules can be sensors and 0/2…10 V, 0/4…20 mA, only!
swapped out without disrupting the power and bus connec- Binary input LEDs of the pluggable Honeywell Panel Bus
tions: Simply unplug the “old” and insert the “new” module. I/O Modules can be configured for status display (off /
yellow) or alarm display (green / red) per channel. NOTE:
The mixed I/O modules XF830A, XFU830A, and CPO-
WARNING IO830 feature only non-configurable binary input LEDs!
Configurable safety position for outputs, in case of loss of
Risk of electric shock or equipment damage! communication with the controller.
► Do not touch any live parts in the cabinet. Max. wiring flexibility due to optional accessories like aux.
► Disconnect the power supply before you start to install terminals and cross-connectors.
the control system. More than one disconnect switch may Can be mounted in small installation housings
be required to de-energize the system. Flexible mix of Panel Bus I/O modules covering all your
► Do not reconnect the power supply until you have application requirements.
completed the installation.
► Unused terminals must be closed (by completely
screwing in the terminal screws), thus preventing the
accidental touching of “live” parts.
OVERVIEW
pluggable MIXED I/Os
pluggable pluggable pluggable pluggable
FLOATING
ANALOG INPUT ANALOG OUTPUT BINARY INPUT RELAY OUTPUT
OUTPUT (with integrated socket)
EN0B-0701GE51 R0218 2
PANEL BUS I/O MODULES – PRODUCT DATA
XS830 Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block consists of
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
two groups of nine internally-connected push-in terminals. For XF830A and XFU830A, only.
XS831 Ten Auxiliary Terminal Blocks (for connection of 0…20 mA signals). Each terminal block supports
A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B7 A8 B8 G2
up to 8 current inputs. For XF830A and XFU830A, only.
XS815 20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in
the Terminal Socket package. For pluggable I/O modules, only.
XS816 10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package.
XAL10 10 Swivel Labels Holders (for attaching the application-specific label printed with CARE). One
Swivel Label Holder is included in each Terminal Socket package. For pluggable I/O modules,
only.
XAL11 10 Swivel Label Holders for XF830A and XFU830A mixed Panel Bus I/O modules. One Swivel
Label Holder is included in each package of XF830A and XFU830A mixed Panel Bus I/O modules.
NOTE: All Honeywell Panel Bus I/O analog and binary I/O Modules are protected against short circuit, 24 VAC +20% and
40 VDC. The relay outputs of relay output modules, floating output modules, and mixed I/O modules should be
equipped with appropriate fusing to protect against short-circuiting of the load.
3 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
NOTE: When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
manual override switches and/or potentiometers.
Table 4. Mixed Panel Bus I/O module specifications (XF830A, XFU830A, and CPO-IO830)
Analog Inputs Analog Outputs Binary Inputs Relay Outputs
Number: 8 Number: 8 Number: 12 (requiring a gold Number: 6
contact or open collector)
Configurable types: Configurable types: Configurable types:
NTC20kΩ (-30…+110 °C) 0…11 VDC / 1 mA (default) Configurable types: Relay outputs (default)
(default) Static binary inputs (default:
Linear Graph static, dry contact); ON: < 1.6 Features:
0..10 VDC with pull-up kΩ to GND or < 2.5 V to GND, Voltage: 24 VAC/DC,
0(2)…10 VDC without pull-up OFF: > 90 kΩ to GND or > 4 V P>50 mW
to GND max. total current: 3 A
Also configurable as: Also configurable as: (AC/DC)
binary inputs (static, dry binary outputs (0 V / 10 V) current per relay: 500 mA
contact, only) normally-open contacts: P >
Features: Also configurable as: 50 mW, voltage: 24 V (AC/DC)
Features: 10-bit resolution (default) totalizers (15 Hz) 1 yellow LED per output
10-bit resolution Safety position (remain, 0%,
configurable offset per input 50%, 100%)
Features:
1 yellow LED per input
EN0B-0701GE51 R0218 4
PANEL BUS I/O MODULES – PRODUCT DATA
depends upon
3:ABCDFERTAQWESDERT3
4:ABCDFERTAQWESDERT4
5:ABCDFERTAQWESDERT5
6:ABCDFERTAQWESDERT6
S1 S2
PRESS
7:ABCDFERTAQWESDERT7
PRESS
71 COM a
controller type
45
67
01
72 COM b
89
EF
AB
CD
73 24V~
74 24V~0
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12
Max. no. of I/O modules per row 10
Honeywell Honeywell
21 22 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12
VAUX AI/AO BI
5
S1 S2 S1 S2 S1 S2
Max. current (F3) 12 A
PRESS
PRESS
PRESS
PRESS
71 COM a 71 COM a
45 45 45
23 23 23
67
67
67
01
01
01
72 COM b 72 COM b
89
89
89
EF
EF
EF
AB AB AB
CD CD CD
74 24V~0 74 24V~0
A A A
0
AUTO
100
A A A A A A A A
0
AUTO
100
--1
--0
--AUTO
Max. distance between rows 40 m
! ! !
11 21 31 41 51 61 21 22 1 2 3 4 5 6 7 8 11 21 31 41 51 61
13 23 33 43 53 63 13 23 33 43 53 63
GND GND
6 7
Fig. 2. Panel Bus I/O Modules on DIN rails
Legend
1 Controller (e.g., XL800, XL Web II, CPO-PC-6A, etc.)
2 Cable (power and LONWORKS) connection from controller
to Panel Bus I/O Modules
3 Swivel label holder
4 Cable connection between Panel Bus I/O Modules on
separate DIN rails
5 Bridge connectors between Panel Bus I/O Modules on
same DIN rail
6 Stopper (from 3rd-party supplier)
7 Auxiliary terminal packages
LEDs
Each Honeywell Panel Bus I/O Module is equipped with:
one green power LED
one yellow service LED
Overvoltage Protection
All Honeywell Panel Bus I/O analog and binary I/O Modules
are protected against short circuit, 24 VAC +20% and
40 VDC. The relay outputs of relay output modules, floating
output modules, and mixed I/O modules should be equipped
with appropriate fusing to protect against short-circuiting of
the load.
Service LED
Each Panel Bus I/O Module is equipped with a yellow service
LED (status: yellow/OFF) for easy diagnosis of failures.
Microprocessor
Each Panel Bus I/O Module is equipped with its own
microprocessor.
System Constraints
Depending upon the given controller, up to 64 I/O modules in
any combination of models may be connected.
Addressing
Addressing is performed using the HEX switch.
5 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
1 10 VDC
24.9 kOHM
AI
Vi 199.9 kOHM
(8.9 VDC IF
CONNECTION
INTERRUPTED)
GND
71 COM
A
COM
A 75
2 3 72 COM
B
COM
B 76
24 24
73 V~ V~ 77
24 24
74 V~0 V~0 78
Fig. 3. XF821 Panel Bus AI Module (shown with terminal
socket)
VAUX VAUX AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
Legend 21 22 1 2 3 4 5 6 7 8
1 Hex switch S2
2 Service LED
3 Power LED
GND GND GND GND GND GND GND GND GND GND
The pluggable Honeywell Panel Bus Analog Input Module,
with 8 analog inputs, is installed with the XS821-22 or 9 10 11 12 13 14 15 16 17 18 25 26
XSU821-22 Terminal Socket.
EN0B-0701GE51 R0218 6
PANEL BUS I/O MODULES – PRODUCT DATA
72 COM
B
COM
B 76 72 COM
B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0
VAUX VAUX AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
21 22 1 2 3 4 5 6 7 8
XF...
SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL
GND GND GND GND GND GND GND GND GND GND GND GND
9 10 11 12 13 14 15 16 17 18 25 26 9 10
A1 A2 A3 A4 A5 A6 A7 B1 B
F2
1 2 3 1 2 3
ACTIVE SENSOR AUX. VOLTAGE + POT.
1: 24V~ POWER 1: SIGNAL
2: 0...10 VDC SIGNAL 2: GND
3: GND (24V~0) 3: 10 VDC AUX.
LEGEND:
F1 MAX. 4 A
F2 MAX. 12 A
Fig. 8. XF821 Panel Bus AI Module, wiring example 1: Active sensor and potentiometer
7 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
VAUX VAUX AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
21 22 1 2 3 4 5 6 7 8
XF... XF...
SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL
GND GND GND GND GND GND GND GND GND GND GND GND
9 10 11 12 13 14 15 16 17 18 25 26 9 10
EXTERNAL
DC POWER EXTERNAL 499 OHM
SUPPLY RESISTOR WITH
TWIN WIRE-END
FERRULES
REQUIRED.
1 2 1 2 1 2
DRY CONTACT
1: SIGNAL 0(4)...20 mA
2: GND
DRY 1: IN
TEMP. SENSOR 2: OUT
CONTACT (NTC20k or Pt1000)
LEGEND:
F1 MAX. 4 A
F2 MAX. 12 A
Fig. 9. XF821 Panel Bus AI Module, wiring example 2: Passive sensor and 0 (4) … 20 mA signal
EN0B-0701GE51 R0218 8
PANEL BUS I/O MODULES – PRODUCT DATA
2 21 22 1 2 3 4 5 6 7 8
GND GND GND GND GND GND GND GND GND GND
9 10 11 12 13 14 15 16 17 18 25 26
3 4 5
Fig. 10. XFR822 Panel Bus AO Module (shown with Fig. 11. Terminal assignment and internal connections
terminal socket)
Features
Legend 0…11 VDC, +/-1 mA
1 Hex switch S2 Floating actuator (requires MCD3)
2 Manual overrides Binary output (0 V / 10 V)
3 Status LEDs red LED per output (brightness according to signal level)
4 Service LED
Optional versions with manual override potentiometers
5 Power LED
(Auto, 0…100%; LED flashes in override mode)
Feedback on manual override signal
The pluggable Honeywell Panel Bus Analog Output Modules,
with 8 analog outputs, are available in the following models: 8-bit resolution
XF822 Panel Bus Analog Output Module (without manual Configurable safety position for outputs in case of
overrides) communication problems (remain, 0%, 50%, 100%)
XFR822 Panel Bus Analog Output Module (with manual
overrides)
9 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
72 COM
B
COM
B 76 72 COM
B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0
NC NC AO1AO2AO3AO4AO5AO6AO7AO8
21 22 1 2 3 4 5 6 7 8 XF...
SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL
GND GND GND GND GND GND GND GND GND GND GND GND
9 10 11 12 13 14 15 16 17 18 25 26 9 10
A1 A2 A3 A4 A5 A6 A7 B1 B A1 A
EXT. GROUND
REQUIRED
TO POWER (24 VAC)
EXT. DEVICES
F1
F2
1 2 3
24V~ DRIVE WITH
0...10 VDC SIGNAL
1: 24V~ POWER
2: GND (24V~0) M
3: 0...10 VDC SIGNAL
LEGEND:
F1 MAX. 4 A
F2 MAX. 12 A
EN0B-0701GE51 R0218 10
PANEL BUS I/O MODULES – PRODUCT DATA
72 COM
B
COM
B 76 72 COM
B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0
NC NC AO1AO2AO3AO4AO5AO6AO7AO8
21 22 1 2 3 4 5 6 7 8 XF...
SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL
GND GND GND GND GND GND GND GND GND GND GND GND
9 10 11 12 13 14 15 16 17 18 25 26 9 10
A1 A2 A3 A4 A5 A6 A7 B1 B A1 A
EXT. GROUND
REQUIRED
TO POWER (24 VAC)
EXT. DEVICES
F1
F2
1 2 3
24V~ DRIVE WITH
0...10 VDC SIGNAL 11 12 13 14 15 16 17 18
1: 24V~ POWER
2: GND (24V~0) M
3: 0...10 VDC SIGNAL MCD 3
LEGEND:
K1 K2 K3
F1 MAX. 4 A
F2 MAX. 12 A 1 2 3 4 5 6 7 8
Fig. 13. XF822 Panel Bus AO Module, wiring example 2: Relay Module MCD 3
The relay module facilitates the control of peripheral devices with high load via the analog outputs.
Input terminal 17 of MCD3 controls changeover contact K3.
Relay terminal 18 of MCD3 controls the N.O. contacts (floating outputs) K1, K2.
11 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
72 COM
B
COM
B 76 72 COM
B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0
NC NC AO1AO2AO3AO4AO5AO6AO7AO8
21 22 1 2 3 4 5 6 7 8 XF...
SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL
GND GND GND GND GND GND GND GND GND GND GND GND
9 10 11 12 13 14 15 16 17 18 25 26 9 10
A1 A2 A3 A4 A5 A6 A7 B1 B A1
EXT. GROUND
REQUIRED
TO POWER (24 VAC)
EXT. DEVICES
F1
F2
1 2 3
24V~ DRIVE WITH
0...10 VDC SIGNAL 11 12 13 14 15 16 17 18
1: 24V~ POWER
2: GND (24V~0) M
3: 0...10 VDC SIGNAL MCE 3
LEGEND:
K1 K2 K3
F1 MAX. 4 A
F2 MAX. 12 A 1 2 3 4 5 6 7 8
Fig. 14. XF822 Panel Bus AO Module, wiring example 3: Relay Module MCE 3
The relay module facilitates the control of peripheral devices with high load via the analog outputs.
Input terminal 16 of MCE3 controls the N.O. contact K3.
Input terminal 17 of MCE3 controls the changeover contact K2.
Input terminal 18 of MCE3 controls the changeover contact K1.
EN0B-0701GE51 R0218 12
PANEL BUS I/O MODULES – PRODUCT DATA
Pulse ON min. 25 ms
Bounce max. 5 ms
Fig. 15. XF823 Panel Bus BI Module (shown with XS823
terminal socket)
+V
Legend
1 Hex switch S2 18 VDC (NOT STABILIZED)
2 Status LEDs
3 Service LED 10 kOHM
4 Power LED
The pluggable Honeywell Panel Bus Binary Input Module, 150 kOHM
with 12 binary inputs, is installed with the XS823 or XSU823
BI
Terminal Socket.
DRY CONTACT
4 ... 40 VDC = OPEN
71 COM
A
COM
A 75 0 ... 2 VDC = CLOSED
72 COM
B
COM
B 76
24 24
73 V~ V~ 77 GND
24
74 V~0 24
78 FAST
V~0
TOTALIZER
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12
Fig. 17. Configuration of binary input as fast totalizer
1 2 3 4 5 6 7 8 9 10 11 12
GND GND GND GND GND GND GND GND GND GND GND GND
13 14 15 16 17 18 19 20 21 22 23 24 25 26
13 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
72 COM
A
COM
76
A
72 COM
B B B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11BI12
1 2 3 4 5 6 7 8 9 10 11 12
XF...
SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL
GND GND GND GND GND GND GND GND GND GND GND GND
13 14 15 16 17 18 19 20 21 22 23 24 25 26
1 2 1 2
DRY CONTACT TOTALIZER
1: SIGNAL 1: SIGNAL
2: GND 2: GND
DRY MIN. 25 ms
CONTACT TOTALIZER
LEGEND:
F1 MAX. 4 A
Fig. 18. XF823 Panel Bus BI Module, wiring example: Dry contact and totalizer
EN0B-0701GE51 R0218 14
PANEL BUS I/O MODULES – PRODUCT DATA
2
REMOVABLE CROSS CONNECTOR (FACTORY-MOUNTED)
25
15 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
72 COM
A
COM
76
A
72 COM
B B B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0
NO 11 NO 21 NO 31 NO 41 NO 51 NO 61
NC 12 NC 22 NC 32 NC 42 NC 52 NC 62 XF...
COM 13 COM 23 COM 33 COM 43 COM 53 COM 63
SHIELD
INTERNALLY
CROSS CONNECTOR XS815 (FACTORY-MOUNTED) CONNECTED
TO DIN RAIL
25
A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B7
F3
LN FIELD DEVICE
1 2
FIELD DEVICE
1 2
POWER SUPPLY 1: 230 V (N) 1: 230 V (N)
230 VAC
2: 230 V (L) M 2: 230 V (L) M
230 V 230 V
LEGEND:
F1 MAX. 4 A
F3 MAX. 12 A
Fig. 21. XF824 Panel Bus RO Module, wiring example 1: Both relay blocks with line voltage
EN0B-0701GE51 R0218 16
PANEL BUS I/O MODULES – PRODUCT DATA
72 COM
A
COM
76
A
72 COM
B B B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0
NO 11 NO 21 NO 31 NO 41 NO 51 NO 61
NC 12 NC 22 NC 32 NC 42 NC 52 NC 62 XF...
COM 13 COM 23 COM 33 COM 43 COM 53 COM 63
SHIELD
INTERNALLY
CROSS CONNECTOR XS815 (FACTORY-MOUNTED) CONNECTED
TO DIN RAIL
25
A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B7
F3
L N FIELD DEVICE
1 2
FIELD DEVICE
1 2
FIELD DEVICE
1 2
POWER SUPPLY 1: 230 V (N) 1: 230 V (N) 1: 230 V (N)
230 VAC
2: 230 V (L) M 2: 230 V (L) M 2: 230 V (L) M
230 V 230 V 230 V
LEGEND:
F1 MAX. 4 A
F3 MAX. 12 A
Fig. 22. XF824 Panel Bus RO Module, wiring example 2: Relay blocks with low and line voltage
17 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
25
EN0B-0701GE51 R0218 18
PANEL BUS I/O MODULES – PRODUCT DATA
72 COM
A
COM
76
A
72 COM
B B B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0
NO 11 NO 21 NO 31 NO 41 NO 51 NO 61
NC 12 NC 22 NC 32 NC 42 NC 52 NC 62 XF...
COM 13 COM 23 COM 33 COM 43 COM 53 COM 63
CON 14 CON 24 CON 34 CON 44 CON 54 CON 64
SHIELD
INTERNALLY
CROSS CONNECTOR XS815 (FACTORY-MOUNTED) CONNECTED
TO DIN RAIL
25
A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B7
F3
L N 3 2 1 FLOATING ACTUAOR WITH 230VAC
POWER SUPPLY (REQUIRES TWO RELAYS)
230 VAC 1:
M 2:
3: N
LEGEND:
F1 MAX. 4 A
F3 MAX. 12 A
Fig. 25. XFR825 Panel Bus FO Module, wiring example: Floating actuator
19 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
67
S2
8 9A
EF
Honeywell
Binary Inputs Analog Inputs GND Analog Outputs 24V Relays
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
1 2 3 4 5 6 13 14 15 16 G1 G2 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4
1 2 3 4 5 6 7 8 9 10 11 12
41 42 AO1 AO2 AO3 AO4 NO1 NO2
1 2 3 4 5 6
NO3 NO4 NO5 NO6
!
Permissible Loads
DO
Table 7. Permissible loads of mixed Panel Bus I/O
Install. Instr.
EN1B-0375GE51 DI
XF830A modules
12 BI / 8 AI / 8 AO / 6 RO 7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
24V, 15VA, T50
0706AX0001-XFU830A max. load min. load
8 Made in Germany
0532
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34
per module 19…29 VAC, 1…29 VDC –
A1 A2 A3 A4 A5 A6 A7 A8 A9
1
B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 A2 A3 A4 A5 A6 A7 A8 A9
2
B1 B2 B3 B4 B5 B6 B7 B8 B9 (total for all 3 A resistive or inductive,
3 4
relay cos φ ≥ 0.6,
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B7 A8 B8 G2
contacts) no capacitive load,
Fig. 27. XF830A mixed Panel Bus I/O module, shown with protected by fuse F4
4 optional aux. terminal blocks (top view)
per nor- 19…29 VAC, 1…29 VDC >50 mW,
71 COM a External COM a 75
mally open 0.5 A resistive or inductive, 0.05 A res./ind.,
cos φ ≥ 0.6, cos φ ≥ 0.6
40
72
73
COM b
24V~
24V
COM b
24V~
76
77
contact
74 24V~0
34 5
24V for relay 1...5 24V~0 78 no capacitive load
012
67
S2
8 9A
EF
BCD
J1 J2 J3 J4 J5
Honeywell
Binary Inputs Analog Inputs GND Analog Outputs 24V Relays
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
1 2 3 4 5 6 13 14 15 16 G1 G2 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 41 42 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
!
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
Install. Instr.
EN1B-0375GE51 DI DO
XFU830A
12 BI / 8 AI / 8 AO / 6 RO 7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
24V, 15VA, T50
0706AX0001-XFU830A
8 Made in Germany
0532
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34
EN0B-0701GE51 R0218 20
PANEL BUS I/O MODULES – PRODUCT DATA
+V
18 VDC (NOT STABILIZED)
AI
10 kOHM
150 kOHM
Vi 199.9 kOHM BI
DRY CONTACT
GND 16 ... 22 VDC = OPEN
0 ... 2 VDC = CLOSED
24.9 kOHM
AI
Vi 199.9 kOHM
(8.9 VDC IF
CONNECTION
INTERRUPTED)
GND
21 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
71 COM
A
XF830 Mixed I/O Module COM
A 75
F1 72 COM
B
24
COM
B 76
73 V~ 24
24 V~ 77
74 V~0 24
V~0 78
BINARY INPUTS ANALOG INPUTS ANALOG OUTPUTS 24V RELAYS
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 G1 G2 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34
1 2 1 2 1 2 1 2 1 2 3 1 2 3 1 2
F4 MAX. 3 A
Fig. 33. XF830A mixed Panel Bus I/O Module, wiring example 1: Actuators
EN0B-0701GE51 R0218 22
PANEL BUS I/O MODULES – PRODUCT DATA
ACTIVE
4...20 mA
SENSOR
1: GND (24V~0)
2: 24V~ POWER
OPT. AUX. TERM. MODULE XS831 3: 4...20 mA
A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B7 A8 B8 G2
1 2 3
OPT. AUX. TERM. MODULE XS830 OPT. AUX. TERM. MODULE XS830
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
F2
71 COM
A
CPO-IO830 Mixed I/O Module COM
A 75
F1 72 COM
B
24
COM
B 76
73 V~ 24
24 V~ 77
74 V~0 24
V~0 78
BINARY INPUTS ANALOG INPUTS ANALOG OUTPUTS 24V RELAYS
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 G1 G2 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34
23 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
Mechanical
Housing Dimensions (H x W x D)
The pluggable Panel Bus I/O Modules (mounted on Terminal
Sockets) all have the dimensions: 110 X 90 X 93 mm (see
also Fig. 35 on page 25).
The XF830A and XFU830A mixed Panel Bus I/O Modules
have the dimensions: 216 X 110 X 93 mm (see also Fig. 36
on page 25).
The CPO-IO830 mixed Panel Bus I/O Module has the
dimensions: 216 X 110 X 61 mm (see also Fig. 37 on page
26).
Housing Material
Plastic, flame-retardant
EN0B-0701GE51 R0218 24
PANEL BUS I/O MODULES – PRODUCT DATA
Dimensions
89.5 94.1
TERMINAL
SOCKET
LOCK
REMOVABLE
110
45
ELECTRONIC
MODULE
67.5
SCREW-TYPE
30.6 TERMINALS
83
28
38
14
SWIVEL LABEL HOLDER
XS814 Aux. Terminal Package (optional)
51.5
Fig. 35. Pluggable Honeywell I/O Modules (example with manual overrides), incl. terminal socket, dimensions (in mm)
216 92.5
71 COM a External COM a 75
40 24V
72 COM b COM b 76
73 24V~ 24V~ 77
345
74 24V~0 24V for relay 1...5 24V~0 78
01 2
67
S2
8 9A
EF
BCD
J1 J2 J3 J4 J5
Honeywell
Binary Inputs Analog Inputs GND Analog Outputs 24V Relays
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
110
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
45
1 2 3 4 5 6 13 14 15 16 G1 G2 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 41 42 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
!
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
Install. Instr.
EN1B-0375GE51 DI DO
CLEARANCE
XF830A
69
12 BI / 8 AI / 8 AO / 6 RO 7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
24V, 15VA, T50
0706AX0001-XFU830A
8
28 38
100
Made in Germany
0532
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34
A1 A2 A3 A4 A5 A6 A7 A8 A9
A
B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 A2 A3 A4 A5 A6 A7 A8 A9
B
B1 B2 B3 B4 B5 B6 B7 B8 B9 15 SCREW-TYPE TERMINALS
(XFU830A)
SWIVEL LABEL HOLDER
C D
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B7 A8 B8 G2
51.5
A, B, and C = XS830 Aux. Terminal Packages (optional) D = XS831 Aux. Terminal Package (optional)
Fig. 36. XF830A (shown) and XFU830A mixed Honeywell I/O Module (example with 4 auxiliary terminal packages),
dimensions (in mm)
25 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA
216 54.4
44
110
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
ComfortPoint Open
TM
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
1 2 3 4 5 6 13 14 15 16 G1 G2 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 41 42 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
!
Install. Instr. 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
MU1B-0463GE51 DI DO
61.1
Fig. 37. CPO-IO830 Mixed Honeywell I/O Modules, dimensions (in mm)
Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: