Panel Bus I/O Modules

PRODUCT DATA
FEATURES
 Plug-and-play functionality for easy maintenance.
 Pluggable Panel Bus I/O modules can be exchanged
without rewiring. Further, the separate installation of
terminal sockets and electronic modules lower risk of
damage and theft in the construction phase.
 Fast wiring with state-of-the-art push-in terminals (screw-
GENERAL type terminals also available) and bridge connectors.
The Honeywell Panel Bus I/O Modules communicate via the  Wide range of sensors supported (NTC20kΩ, NTC10kΩ,
Panel Bus. PT1000-1/-2, Johnson A99 PTC, NI1000TK5000, PT3000,
The pluggable Honeywell Panel Bus I/O modules consist of a Balco500, 0/2…10 V, 0/4…20 mA). NOTE: The mixed
terminal socket and a removable electronic module, allowing Panel Bus I/O modules XF830A, XFU830A, and CPO-
the socket to be mounted and wired before the electronic IO830 feature inputs suitable for signals from NTC20kΩ
module is installed. All such electronic modules can be sensors and 0/2…10 V, 0/4…20 mA, only!
swapped out without disrupting the power and bus connec-  Binary input LEDs of the pluggable Honeywell Panel Bus
tions: Simply unplug the “old” and insert the “new” module. I/O Modules can be configured for status display (off /
yellow) or alarm display (green / red) per channel. NOTE:
The mixed I/O modules XF830A, XFU830A, and CPO-
WARNING IO830 feature only non-configurable binary input LEDs!
 Configurable safety position for outputs, in case of loss of
Risk of electric shock or equipment damage! communication with the controller.
► Do not touch any live parts in the cabinet.  Max. wiring flexibility due to optional accessories like aux.
► Disconnect the power supply before you start to install terminals and cross-connectors.
the control system. More than one disconnect switch may  Can be mounted in small installation housings
be required to de-energize the system.  Flexible mix of Panel Bus I/O modules covering all your
► Do not reconnect the power supply until you have application requirements.
completed the installation.
► Unused terminals must be closed (by completely
screwing in the terminal screws), thus preventing the
accidental touching of “live” parts.

The mixed Honeywell Panel Bus I/O modules offer a mix of


34 inputs and outputs in a compact housing.
Software updates, configuration, and commissioning are all
done automatically by the controller for all Panel Bus I/O
Modules.
The Panel Bus I/O Modules are addressed manually by
adjusting their HEX switches.
The Panel Bus I/O Modules may be used with any CPU
supporting Panel Bus communication (e.g., the XL800, CPO-
PC-6A, etc.).

® U.S. Registered Trademark


Copyright © 2018 Honeywell Inc. • All Rights Reserved EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

OVERVIEW
pluggable MIXED I/Os
pluggable pluggable pluggable pluggable
FLOATING
ANALOG INPUT ANALOG OUTPUT BINARY INPUT RELAY OUTPUT
OUTPUT (with integrated socket)

PANEL XFR822A XFR824A XFR825A XF830A, XFU830A


BUS MODULES
Binary Inputs Analog Inputs GND Analog Outputs 24V Relays
Honeywell B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
TM
ComfortPoint Open 7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
1 2 3 4 5 6 13 14 15 16 G1 G2 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 41 42 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
!
Install. Instr. 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
MU1B-0463GE51 DI DO

XF821A XF822A XF823A XF824A CPO-IO830A

XS821-22 XS823 XS824-25


XF830A, XFU830A, CPO-IO830A
CONTROLLER XSU821-22 XSU823 XSU824-25
PANEL BUS I/O MODULES
Panel Bus
Fig. 1. Overview of Honeywell Panel Bus I/O Modules
Table 1. Overview of Honeywell Panel Bus I/O Modules
order number description
Pluggable Panel Bus I/O Modules
XF821 Pluggable Panel Bus Analog Input Module (with 8 analog inputs)
XF822 Pluggable Panel Bus Analog Output Module (with 8 analog outputs)
XFR822 Pluggable Panel Bus Analog Output Module (with 8 analog outputs and manual overrides)
XF823 Pluggable Panel Bus Binary Input Module (with 12 binary inputs)
XF824 Pluggable Panel Bus Relay Output Module (with 6 relay outputs)
XFR824 Pluggable Panel Bus Relay Output Module (with 6 relay outputs and manual overrides)
XFR825 Pluggable Panel Bus Floating Output Module (with 3 floating outputs and manual overrides)
Mixed Panel Bus I/O Modules with integrated socket
Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with
XF830A
push-in terminals (incl. bridge connector and swivel label); housing matches XL800 design
Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with
XFU830A
screw terminals (incl. bridge connector and swivel label); housing matches XL800 design
Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with
CPO-IO830
push-in terminals (incl. bridge connector); housing matches CPO-PC-6A design
Terminal Sockets (not needed for the mixed I/O modules XF830A, XFU830A, and CPO-IO830)
XS821-22 Push-in terminal socket for pluggable AI/AO modules (incl. bridge connector, swivel label)
XSU821-22 Screw-type terminal socket for pluggable AI/AO modules (incl. bridge connector, swivel label)
XS823 Push-in terminal socket for pluggable BI modules (incl. bridge connector, swivel label)
XSU823 Screw-type terminal socket for pluggable BI modules (incl. bridge connector, swivel label)
Push-in terminal socket for pluggable relay/floating output modules (incl. bridge connector, cross connector, swivel
XS824-25
label)
Screw-type terminal socket for pluggable relay/floating output modules (incl. bridge connector, cross connector,
XSU824-25
swivel label)

EN0B-0701GE51 R0218 2
PANEL BUS I/O MODULES – PRODUCT DATA

Table 2. Overview of auxiliary parts and spare parts


order number description
XS814 Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two
groups with seven internally-connected push-in terminals. For pluggable I/O modules, only.

XS830 Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block consists of
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
two groups of nine internally-connected push-in terminals. For XF830A and XFU830A, only.
XS831 Ten Auxiliary Terminal Blocks (for connection of 0…20 mA signals). Each terminal block supports
A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B7 A8 B8 G2
up to 8 current inputs. For XF830A and XFU830A, only.
XS815 20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in
the Terminal Socket package. For pluggable I/O modules, only.

XS816 10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package.

XAL10 10 Swivel Labels Holders (for attaching the application-specific label printed with CARE). One
Swivel Label Holder is included in each Terminal Socket package. For pluggable I/O modules,
only.

XAL11 10 Swivel Label Holders for XF830A and XFU830A mixed Panel Bus I/O modules. One Swivel
Label Holder is included in each package of XF830A and XFU830A mixed Panel Bus I/O modules.

NOTE: All Honeywell Panel Bus I/O analog and binary I/O Modules are protected against short circuit, 24 VAC +20% and
40 VDC. The relay outputs of relay output modules, floating output modules, and mixed I/O modules should be
equipped with appropriate fusing to protect against short-circuiting of the load.

3 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

Table 3. Pluggable Panel Bus I/O Module specifications


Analog Input Analog Output Binary Input Relay Output Floating Output
Module
XF821 XF822, XFR822 XF823 XF824, XFR824 XFR825
no. of I/Os 8 analog inputs 8 analog outputs 12 binary inputs 6 relay outputs 3 floating outputs
requiring a gold
contact or open
collector
charac- Linear Graph, 0..10 VDC with 0…11 VDC /  1 mA static binary input, relay outputs (default) floating outputs
teristics pull-up, 0(2)…10 VDC without Also configurable as: (default: dry Features:
pull-up contact)  Changeover relays Features:
floating outputs or
NTC20kΩ (-50…+150 °C,
binary outputs (0 V / Also configurable  Voltage:  2 relays per
default)
NTC10kΩ (-30…+100 °C) 10 V) as: 19…250 VAC, floating output
PT1000-1 (-50…150 °C) totalizers (20 Hz) 1…29 VDC, P>50 mW  Voltage:
PT1000-2 (0…400 °C) Features: Features:  max. total current: 19…250 VAC,
Johnson A99 (-40…+120 °C)  8-bit resolution  1 LED per input 12 A 1…29 VDC,
NI1000TK5000 (-30…+130 °C) (default)  Color mode can  current per relay: P>50 mW
PT3000 (-50…150 °C)  Safety position be set per input N.O.: 4(4) A (AC) or  max. total current:
BALCO500 (-30…120 °C)
(remain, 0%, 50%, to OFF/yellow 4(1) A (DC), 12 A
Also configurable as: 100%) or green/red N.C.: 2(1) A (AC) or  current per relay:
binary inputs  red LED per output using CARE 4(1) A (DC) N.O.: 4(4) A (AC)
 Linear graph (0…10 V with  light intensity follows  ON: < 1.6 kΩ to  Safety position or 4(1) A (DC),
pull-up) output level in auto GND or < 2.5 V (remain, 0%, 100%) N.C.: 2(1) A (AC)
to GND,  yellow LED per output or 4(1) A (DC)
Features: Version with manual OFF: > 90 kΩ to With man. override (R):  1 potentiometer per
 16-bit resolution GND or > 4 V to  1 switch per output floating output
 configurable offset per input
override (R):
 1 potentiometer per GND  auto feedback signal  2 LEDs per output:
 auxiliary voltage: 10 VDC, Imax
= 5 mA output (mode + value) green: relay 1
 auto feedback signal  blinking in manual closed, red: relay 2
(mode + value) override position closed
 blinking in manual  blinking in manual
override position override position
 auto feedback sig-
nal (mode + value)

Manual Overrides as per EN ISO 16484-2:2004


The manual override switches and potentiometers of the output modules (…R822, …R824, and XFR825) support direct
operation as per EN ISO 16484-2:2004, section 5.4.3 "Local Priority Override/Indicating Units."
Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently of the
controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the corresponding
output LED will blink continuously, and the output module will send a feedback signal with the status "manual override" and the
given override position to the controller (which will then also store this information in its alarm memory).

NOTE: When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
manual override switches and/or potentiometers.

Table 4. Mixed Panel Bus I/O module specifications (XF830A, XFU830A, and CPO-IO830)
Analog Inputs Analog Outputs Binary Inputs Relay Outputs
Number: 8 Number: 8 Number: 12 (requiring a gold Number: 6
contact or open collector)
Configurable types: Configurable types: Configurable types:
 NTC20kΩ (-30…+110 °C)  0…11 VDC /  1 mA (default) Configurable types:  Relay outputs (default)
(default)  Static binary inputs (default:
 Linear Graph static, dry contact); ON: < 1.6 Features:
 0..10 VDC with pull-up kΩ to GND or < 2.5 V to GND,  Voltage: 24 VAC/DC,
 0(2)…10 VDC without pull-up OFF: > 90 kΩ to GND or > 4 V P>50 mW
to GND  max. total current: 3 A
Also configurable as: Also configurable as: (AC/DC)
 binary inputs (static, dry  binary outputs (0 V / 10 V)  current per relay: 500 mA
contact, only)  normally-open contacts: P >
Features: Also configurable as: 50 mW, voltage: 24 V (AC/DC)
Features:  10-bit resolution (default)  totalizers (15 Hz)  1 yellow LED per output
 10-bit resolution  Safety position (remain, 0%,
 configurable offset per input 50%, 100%)
Features:
 1 yellow LED per input

EN0B-0701GE51 R0218 4
PANEL BUS I/O MODULES – PRODUCT DATA

GENERAL FEATURES System Constraints


1 2 3 4
1:ABCDFERTAQWESDERT1
Table 5. System constraints
Max. no. of I/O modules (any
2:ABCDFERTAQWESDERT2

depends upon
3:ABCDFERTAQWESDERT3
4:ABCDFERTAQWESDERT4
5:ABCDFERTAQWESDERT5
6:ABCDFERTAQWESDERT6
S1 S2

PRESS
7:ABCDFERTAQWESDERT7

PRESS
71 COM a

controller type
45

combination) per controller


23
8:ABCDFERTAQWESDERT8

67
01
72 COM b

89
EF
AB
CD

73 24V~

74 24V~0

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12
Max. no. of I/O modules per row 10
Honeywell Honeywell

Max. current (F1) 4A


! !

21 22 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12

VAUX AI/AO BI

GND GND GND

Max. current (F2) 12 A


9 10 11 12 13 14 15 16 17 18 25 26 13 14 15 16 17 18 19 20 21 22 23 24 25 26

5
S1 S2 S1 S2 S1 S2
Max. current (F3) 12 A

PRESS

PRESS
PRESS

PRESS
71 COM a 71 COM a
45 45 45
23 23 23

67

67

67
01

01

01
72 COM b 72 COM b

89

89

89
EF

EF

EF
AB AB AB
CD CD CD

Max. row length 3m


73 24V~ 73 24V~

74 24V~0 74 24V~0

1 2 3 Honeywell 1 2 3 4 5 6 7 8 Honeywell 1 2 3 4 5 6 Honeywell

A A A
0
AUTO
100
A A A A A A A A
0
AUTO
100
--1
--0
--AUTO
Max. distance between rows 40 m
! ! !

11 21 31 41 51 61 21 22 1 2 3 4 5 6 7 8 11 21 31 41 51 61

Min. cross-section of GND


1.5 mm2
12 22 32 42 52 62 VAUX AI/AO 12 22 32 42 52 62

13 23 33 43 53 63 13 23 33 43 53 63
GND GND

(terminal 9) (protected by F2)


14 24 34 44 54 64 25 9 10 11 12 13 14 15 16 17 18 25 26 14 24 34 44 54 64 25

6 7
Fig. 2. Panel Bus I/O Modules on DIN rails

Legend
1 Controller (e.g., XL800, XL Web II, CPO-PC-6A, etc.)
2 Cable (power and LONWORKS) connection from controller
to Panel Bus I/O Modules
3 Swivel label holder
4 Cable connection between Panel Bus I/O Modules on
separate DIN rails
5 Bridge connectors between Panel Bus I/O Modules on
same DIN rail
6 Stopper (from 3rd-party supplier)
7 Auxiliary terminal packages

LEDs
Each Honeywell Panel Bus I/O Module is equipped with:
 one green power LED
 one yellow service LED

Overvoltage Protection
All Honeywell Panel Bus I/O analog and binary I/O Modules
are protected against short circuit, 24 VAC +20% and
40 VDC. The relay outputs of relay output modules, floating
output modules, and mixed I/O modules should be equipped
with appropriate fusing to protect against short-circuiting of
the load.

Service LED
Each Panel Bus I/O Module is equipped with a yellow service
LED (status: yellow/OFF) for easy diagnosis of failures.

Microprocessor
Each Panel Bus I/O Module is equipped with its own
microprocessor.

System Constraints
Depending upon the given controller, up to 64 I/O modules in
any combination of models may be connected.

Addressing
Addressing is performed using the HEX switch.

5 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

Analog Input Module

1 10 VDC

24.9 kOHM

AI

Vi 199.9 kOHM
(8.9 VDC IF
CONNECTION
INTERRUPTED)
GND

Fig. 6. Analog input impedance setpoint (input circuit for


NTC10kΩ, NTC20kΩ, wall module setpoint)

71 COM
A
COM
A 75
2 3 72 COM
B
COM
B 76
24 24
73 V~ V~ 77
24 24
74 V~0 V~0 78
Fig. 3. XF821 Panel Bus AI Module (shown with terminal
socket)
VAUX VAUX AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8

Legend 21 22 1 2 3 4 5 6 7 8
1 Hex switch S2
2 Service LED
3 Power LED
GND GND GND GND GND GND GND GND GND GND
The pluggable Honeywell Panel Bus Analog Input Module,
with 8 analog inputs, is installed with the XS821-22 or 9 10 11 12 13 14 15 16 17 18 25 26
XSU821-22 Terminal Socket.

Fig. 7. Terminal assignment and internal connections


10 VDC

24.9 kOHM Features


 0…10 VDC, 2…10 VDC without pull-up
AI
 0…10 VDC with pull-up (linear graph, e.g. used for wall
module connection)
RTD
 0/4…20 mA, needs 499 Ω resistor in parallel
GND
 NTC20kΩ (-50…+150 °C, default)
 NTC10kΩ (-30…+100 °C)
 PT1000-1 (-50…+150 °C)
Fig. 4. Analog input low impedance (input circuit for  PT1000-2 (0…+400 °C)
PT1000, Johnson A99 PTC, Balco500, PT3000,  NI1000TK5000 (-30…+130 °C)
NI1000TK5000, slow binary input)  PT3000 (-50…+150 °C)
 BALCO500 (-30…+120 °C)
 Binary input
 16-bit resolution
AI
 Configurable offset per input
Vi 199.9 kOHM
 Auxiliary voltage: 10 VDC, IMAX = 5 mA
 Sensor failure detection
GND

Fig. 5. Analog input high impedance (input circuit for


voltage input for active sensors)

EN0B-0701GE51 R0218 6
PANEL BUS I/O MODULES – PRODUCT DATA

XF821 ANALOG INPUT MODULE


71 COM
A
COM
A 75 71 COM
A

72 COM
B
COM
B 76 72 COM
B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0

VAUX VAUX AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
21 22 1 2 3 4 5 6 7 8
XF...

SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL

GND GND GND GND GND GND GND GND GND GND GND GND

9 10 11 12 13 14 15 16 17 18 25 26 9 10

OPT. AUX. TERMINAL MODULE XS814

A1 A2 A3 A4 A5 A6 A7 B1 B

EXTERNAL (24 VAC)


GROUND
REQUIRED TO
POWER
EXTERNAL
DEVICES
F1

F2
1 2 3 1 2 3
ACTIVE SENSOR AUX. VOLTAGE + POT.
1: 24V~ POWER 1: SIGNAL
2: 0...10 VDC SIGNAL 2: GND
3: GND (24V~0) 3: 10 VDC AUX.

LEGEND:
F1 MAX. 4 A

F2 MAX. 12 A

THIN LINES MIN. 0.75 mm 2

THICK LINES MIN. 1.5 mm 2

DASHED LINES SELECTED INTERNAL CONNECTIONS

Fig. 8. XF821 Panel Bus AI Module, wiring example 1: Active sensor and potentiometer

7 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

COM XF821 ANALOG INPUT MODULE


A 75 71 COM
A
COM
A 75 71 COM
A
COM
B 76 72 COM
B
COM
B 76 72 COM
B
24 24 24 24
V~ 77 73 V~ V~ 77 73 V~
24 24 24 24
V~0 78 74 V~0 V~0 78 74 V~0

VAUX VAUX AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
21 22 1 2 3 4 5 6 7 8
XF... XF...

SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL

GND GND GND GND GND GND GND GND GND GND GND GND

9 10 11 12 13 14 15 16 17 18 25 26 9 10

EXTERNAL
DC POWER EXTERNAL 499 OHM
SUPPLY RESISTOR WITH
TWIN WIRE-END
FERRULES
REQUIRED.

1 2 1 2 1 2
DRY CONTACT
1: SIGNAL 0(4)...20 mA
2: GND
DRY 1: IN
TEMP. SENSOR 2: OUT
CONTACT (NTC20k or Pt1000)

LEGEND:
F1 MAX. 4 A

F2 MAX. 12 A

THIN LINES MIN. 0.75 mm 2

THICK LINES MIN. 1.5 mm 2

DASHED LINES SELECTED INTERNAL CONNECTIONS

Fig. 9. XF821 Panel Bus AI Module, wiring example 2: Passive sensor and 0 (4) … 20 mA signal

EN0B-0701GE51 R0218 8
PANEL BUS I/O MODULES – PRODUCT DATA

Analog Output Modules


They are installed with the XS821-22 or XSU821-22 Terminal
Socket.
1
71 COM
A
COM
A 75
72 COM
B
COM
B 76
24 24
73 V~ V~ 77
24 24
74 V~0 V~0 78

NC NC AO1 AO2 AO3 AO4 AO5 AO6 AO7 AO8

2 21 22 1 2 3 4 5 6 7 8

GND GND GND GND GND GND GND GND GND GND

9 10 11 12 13 14 15 16 17 18 25 26
3 4 5

Fig. 10. XFR822 Panel Bus AO Module (shown with Fig. 11. Terminal assignment and internal connections
terminal socket)
Features
Legend  0…11 VDC, +/-1 mA
1 Hex switch S2  Floating actuator (requires MCD3)
2 Manual overrides  Binary output (0 V / 10 V)
3 Status LEDs  red LED per output (brightness according to signal level)
4 Service LED
 Optional versions with manual override potentiometers
5 Power LED
(Auto, 0…100%; LED flashes in override mode)
 Feedback on manual override signal
The pluggable Honeywell Panel Bus Analog Output Modules,
with 8 analog outputs, are available in the following models:  8-bit resolution
 XF822 Panel Bus Analog Output Module (without manual  Configurable safety position for outputs in case of
overrides) communication problems (remain, 0%, 50%, 100%)
 XFR822 Panel Bus Analog Output Module (with manual
overrides)

9 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

XF822 ANALOG OUTPUT MODULE


71 COM
A
COM
A 75 71 COM
A

72 COM
B
COM
B 76 72 COM
B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0

NC NC AO1AO2AO3AO4AO5AO6AO7AO8
21 22 1 2 3 4 5 6 7 8 XF...

SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL

GND GND GND GND GND GND GND GND GND GND GND GND

9 10 11 12 13 14 15 16 17 18 25 26 9 10

OPT. AUX. TERMINAL MODULE XS814 XS814

A1 A2 A3 A4 A5 A6 A7 B1 B A1 A
EXT. GROUND
REQUIRED
TO POWER (24 VAC)
EXT. DEVICES

F1

F2
1 2 3
24V~ DRIVE WITH
0...10 VDC SIGNAL
1: 24V~ POWER
2: GND (24V~0) M
3: 0...10 VDC SIGNAL

LEGEND:
F1 MAX. 4 A

F2 MAX. 12 A

THIN LINES MIN. 0.75 mm 2

THICK LINES MIN. 1.5 mm 2

DASHED LINES SELECTED INTERNAL CONNECTIONS

Fig. 12. XF822 Panel Bus AO Module, wiring example 1: Actuator

EN0B-0701GE51 R0218 10
PANEL BUS I/O MODULES – PRODUCT DATA

XF822 ANALOG OUTPUT MODULE


71 COM
A
COM
A 75 71 COM
A

72 COM
B
COM
B 76 72 COM
B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0

NC NC AO1AO2AO3AO4AO5AO6AO7AO8
21 22 1 2 3 4 5 6 7 8 XF...

SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL

GND GND GND GND GND GND GND GND GND GND GND GND

9 10 11 12 13 14 15 16 17 18 25 26 9 10

OPT. AUX. TERMINAL MODULE XS814 XS814

A1 A2 A3 A4 A5 A6 A7 B1 B A1 A
EXT. GROUND
REQUIRED
TO POWER (24 VAC)
EXT. DEVICES

F1

F2
1 2 3
24V~ DRIVE WITH
0...10 VDC SIGNAL 11 12 13 14 15 16 17 18
1: 24V~ POWER
2: GND (24V~0) M
3: 0...10 VDC SIGNAL MCD 3
LEGEND:
K1 K2 K3
F1 MAX. 4 A

F2 MAX. 12 A 1 2 3 4 5 6 7 8

THIN LINES MIN. 0.75 mm 2 L N


3 2 1 2 1
THICK LINES MIN. 1.5 mm 2
M M
DASHED LINES SELECTED INTERNAL CONNECTIONS

Fig. 13. XF822 Panel Bus AO Module, wiring example 2: Relay Module MCD 3

 The relay module facilitates the control of peripheral devices with high load via the analog outputs.
 Input terminal 17 of MCD3 controls changeover contact K3.
 Relay terminal 18 of MCD3 controls the N.O. contacts (floating outputs) K1, K2.

11 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

XF822 ANALOG OUTPUT MODULE


71 COM
A
COM
A 75 71 COM
A

72 COM
B
COM
B 76 72 COM
B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0

NC NC AO1AO2AO3AO4AO5AO6AO7AO8
21 22 1 2 3 4 5 6 7 8 XF...

SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL

GND GND GND GND GND GND GND GND GND GND GND GND

9 10 11 12 13 14 15 16 17 18 25 26 9 10

OPT. AUX. TERMINAL MODULE XS814 XS814

A1 A2 A3 A4 A5 A6 A7 B1 B A1
EXT. GROUND
REQUIRED
TO POWER (24 VAC)
EXT. DEVICES

F1

F2
1 2 3
24V~ DRIVE WITH
0...10 VDC SIGNAL 11 12 13 14 15 16 17 18
1: 24V~ POWER
2: GND (24V~0) M
3: 0...10 VDC SIGNAL MCE 3
LEGEND:
K1 K2 K3
F1 MAX. 4 A

F2 MAX. 12 A 1 2 3 4 5 6 7 8

THIN LINES MIN. 0.75 mm 2

THICK LINES MIN. 1.5 mm 2

DASHED LINES SELECTED INTERNAL CONNECTIONS

Fig. 14. XF822 Panel Bus AO Module, wiring example 3: Relay Module MCE 3

The relay module facilitates the control of peripheral devices with high load via the analog outputs.
 Input terminal 16 of MCE3 controls the N.O. contact K3.
 Input terminal 17 of MCE3 controls the changeover contact K2.
 Input terminal 18 of MCE3 controls the changeover contact K1.

EN0B-0701GE51 R0218 12
PANEL BUS I/O MODULES – PRODUCT DATA

Binary Input Module


Features
 Static binary input (dry contact)
1  Totalizer for up to 20 Hz
 LEDs per binary input supporting alarm display mode
(red/green) or status mode (off/yellow).
 Color mode of each LED can be set to OFF/yellow or
green/red in CARE.

Configuration as Fast Totalizer


Using CARE, the binary inputs can be configured as fast
totalizers for operation in conjunction with devices equipped
with an open collector output.
Table 6. Binary inputs used as fast totalizers
Frequency max. 20 Hz

Pulse ON min. 25 ms

2 3 4 Pulse OFF min. 25 ms

Bounce max. 5 ms
Fig. 15. XF823 Panel Bus BI Module (shown with XS823
terminal socket)
+V
Legend
1 Hex switch S2 18 VDC (NOT STABILIZED)
2 Status LEDs
3 Service LED 10 kOHM
4 Power LED

The pluggable Honeywell Panel Bus Binary Input Module, 150 kOHM
with 12 binary inputs, is installed with the XS823 or XSU823
BI
Terminal Socket.
DRY CONTACT
4 ... 40 VDC = OPEN
71 COM
A
COM
A 75 0 ... 2 VDC = CLOSED
72 COM
B
COM
B 76
24 24
73 V~ V~ 77 GND
24
74 V~0 24
78 FAST
V~0
TOTALIZER

BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12
Fig. 17. Configuration of binary input as fast totalizer
1 2 3 4 5 6 7 8 9 10 11 12

GND GND GND GND GND GND GND GND GND GND GND GND

13 14 15 16 17 18 19 20 21 22 23 24 25 26

Fig. 16. Terminal assignment and internal connections

13 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

XF823 BINARY INPUT MODULE


71 COM COM
75 71 COM
F1 A

72 COM
A
COM
76
A

72 COM
B B B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0

BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11BI12
1 2 3 4 5 6 7 8 9 10 11 12
XF...

SHIELD
INTERNALLY
CONNECTED
TO DIN RAIL

GND GND GND GND GND GND GND GND GND GND GND GND

13 14 15 16 17 18 19 20 21 22 23 24 25 26

1 2 1 2
DRY CONTACT TOTALIZER
1: SIGNAL 1: SIGNAL
2: GND 2: GND
DRY MIN. 25 ms
CONTACT TOTALIZER

LEGEND:
F1 MAX. 4 A

THIN LINES MIN. 0.75 mm 2

THICK LINES MIN. 1.5 mm 2

DASHED LINES SELECTED INTERNAL CONNECTIONS

Fig. 18. XF823 Panel Bus BI Module, wiring example: Dry contact and totalizer

EN0B-0701GE51 R0218 14
PANEL BUS I/O MODULES – PRODUCT DATA

Relay Output Modules


71 COM
A
COM
A 75
1 72 COM
B
COM
B 76
24 24
73 V~ V~ 77
24 24
74 V~0 V~0 78

RELAY BLOCK 1 RELAY BLOCK 2


NO 11 NO 21 NO 31 NO 41 NO 51 NO 61
NC 12 NC 22 NC 32 NC 42 NC 52 NC 62
COM 13 COM 23 COM 33 COM 43 COM 53 COM 63

2
REMOVABLE CROSS CONNECTOR (FACTORY-MOUNTED)

25

Fig. 20. Terminal assignment and internal connections


3 4 5
Features
- Cross-Connecter
Fig. 19. XFR824 Panel Bus Relay Output Module (shown - 1 yellow LED per output
with terminal socket) - Optional versions with manual override switches (Auto, 0,
1; LED flashes in override mode)
Legend - Feedback on manual override signal
1 Hex switch S2 - Configurable safety position for outputs in case of
2 Manual overrides communications problems (remain, OFF, ON)
3 Status LEDs - Permissible load per Relay Output Module (total)
4 Service LED  Max. load:
5 Power LED 19…250 VAC: 12 A
1…29 VDC: 12 A resistive, 3 A inductive
The pluggable Honeywell Panel Bus Relay Output Modules, - Permissible load per normally-open contact:
with 6 relay outputs, are available in the following versions:  Max. load:
 XF824 Panel Bus Relay Output Module (without manual 19…250 VAC: 4 A resistive or inductive
overrides) 1…29 VDC: 4 A resistive, 1 A inductive
 XFR824 Panel Bus Relay Output Module (with manual  Min. load: P > 50 mW
overrides) - Permissible load per normally-closed contact:
They are installed with the XS824-25 or XSU824-25 Terminal  Max. load:
Socket. 19…250 VAC: 2 A resistive, 1 A inductive
1…29 VDC: 2 A resistive, 1 A inductive
 Min. load: P > 50 mW

15 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

XF824 RELAY OUTPUT MODULE


71 COM COM
75 71 COM
F1 A

72 COM
A
COM
76
A

72 COM
B B B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0

NO 11 NO 21 NO 31 NO 41 NO 51 NO 61
NC 12 NC 22 NC 32 NC 42 NC 52 NC 62 XF...
COM 13 COM 23 COM 33 COM 43 COM 53 COM 63

SHIELD
INTERNALLY
CROSS CONNECTOR XS815 (FACTORY-MOUNTED) CONNECTED
TO DIN RAIL

25

OPTIONAL AUX. TERMINAL PACKAGE XS814

A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B7

F3

LN FIELD DEVICE
1 2
FIELD DEVICE
1 2
POWER SUPPLY 1: 230 V (N) 1: 230 V (N)
230 VAC
2: 230 V (L) M 2: 230 V (L) M
230 V 230 V

LEGEND:
F1 MAX. 4 A

F3 MAX. 12 A

THIN LINES MIN. 0.75 mm 2

THICK LINES MIN. 1.5 mm 2 - or less, as per F3

DASHED LINES SELECTED INTERNAL CONNECTIONS

Fig. 21. XF824 Panel Bus RO Module, wiring example 1: Both relay blocks with line voltage

EN0B-0701GE51 R0218 16
PANEL BUS I/O MODULES – PRODUCT DATA

XF824 RELAY OUTPUT MODULE


71 COM COM
75 71 COM
F1 A

72 COM
A
COM
76
A

72 COM
B B B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0

NO 11 NO 21 NO 31 NO 41 NO 51 NO 61
NC 12 NC 22 NC 32 NC 42 NC 52 NC 62 XF...
COM 13 COM 23 COM 33 COM 43 COM 53 COM 63

SHIELD
INTERNALLY
CROSS CONNECTOR XS815 (FACTORY-MOUNTED) CONNECTED
TO DIN RAIL

25

OPTIONAL AUX. TERMINAL PACKAGE XS814

A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B7

F3
L N FIELD DEVICE
1 2
FIELD DEVICE
1 2
FIELD DEVICE
1 2
POWER SUPPLY 1: 230 V (N) 1: 230 V (N) 1: 230 V (N)
230 VAC
2: 230 V (L) M 2: 230 V (L) M 2: 230 V (L) M
230 V 230 V 230 V

LEGEND:
F1 MAX. 4 A

F3 MAX. 12 A

THIN LINES MIN. 0.75 mm 2

THICK LINES MIN. 1.5 mm 2 - or less, as per F3

DASHED LINES SELECTED INTERNAL CONNECTIONS

Fig. 22. XF824 Panel Bus RO Module, wiring example 2: Relay blocks with low and line voltage

17 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

Floating Output Module


71 COM
A
COM
A 75
1 72 COM
B
COM
B 76
24 24
73 V~ V~ 77
24 24
74 V~0 V~0 78

ACTUATOR 1 ACTUATOR 2 ACTUATOR 3


NO 11 NO 21 NO 31 NO 41 NO 51 NO 61
NC 12 NC 22 NC 32 NC 42 NC 52 NC 62
COM 13 COM 23 COM 33 COM 43 COM 53 COM 63

2 REMOVABLE CROSS CONNECTOR (FACTORY-MOUNTED)

25

Fig. 24. Terminal assignment and internal connections


3 4 5
Features
- Cross-Connecter
Fig. 23. XFR825 Panel Bus Floating Output Module - 1 red LED (opening) and 1 green LED (closing) per
(shown with socket) floating output
- Manual override potentiometers (Auto, 0%...100%; LED
Legend flashes in override mode)
1 Hex switch S2 - Feedback on manual override signal
2 Manual overrides - Configurable safety position for outputs in case of
3 Status LEDs communication problems (remain, 0%, 50%, 100%)
4 Service LED - Permissible Load per Floating Output Module (total)
5 Power LED  Max. load:
19…250 VAC: 12 A
The pluggable XFR825 Panel Bus Floating Output Module, 1…29 VDC: 12 A resistive, 3 A inductive
with manual overrides and 3 floating outputs, is installed with - Permissible load per normally-open contact:
the XS824-25 or XSU824-25 Terminal Socket.  Max. load:
19…250 VAC: 4 A resistive or inductive
1…29 VDC: 4 A resistive, 1 A inductive
 Min. load: P > 50 mW
- Permissible load per normally-closed contact:
 Max. load:
19…250 VAC: 2 A resistive, 1 A inductive
1…29 VDC: 2 A resistive, 1 A inductive
 Min. load: P > 50 mW

EN0B-0701GE51 R0218 18
PANEL BUS I/O MODULES – PRODUCT DATA

XFR825 FLOATING OUTPUT MODULE


71 COM COM
75 71 COM
F1 A

72 COM
A
COM
76
A

72 COM
B B B
24 24 24
73 V~ V~ 77 73 V~
24 24 24
74 V~0 V~0 78 74 V~0

NO 11 NO 21 NO 31 NO 41 NO 51 NO 61
NC 12 NC 22 NC 32 NC 42 NC 52 NC 62 XF...
COM 13 COM 23 COM 33 COM 43 COM 53 COM 63
CON 14 CON 24 CON 34 CON 44 CON 54 CON 64

SHIELD
INTERNALLY
CROSS CONNECTOR XS815 (FACTORY-MOUNTED) CONNECTED
TO DIN RAIL

25

OPTIONAL AUX. TERMINAL PACKAGE XS814

A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B7

F3
L N 3 2 1 FLOATING ACTUAOR WITH 230VAC
POWER SUPPLY (REQUIRES TWO RELAYS)
230 VAC 1:
M 2:
3: N

LEGEND:
F1 MAX. 4 A

F3 MAX. 12 A

THIN LINES MIN. 0.75 mm 2

THICK LINES MIN. 1.5 mm 2 - or less, as per F3

DASHED LINES SELECTED INTERNAL CONNECTIONS

Fig. 25. XFR825 Panel Bus FO Module, wiring example: Floating actuator

19 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

Mixed I/O Modules A1 A2 A3 A4 A5 A6 A7 A8 A9


1
B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 A2 A3 A4 A5 A6 A7 A8 A9
2
B1 B2 B3 B4 B5 B6 B7 B8 B9

XF830A XFU830A CPO-IO830 A1 A2 A3 A4 A5 A6 A7 A8 A9


3
B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 B1 A2 B2 A3 B3 A4 B4 G1
4
A5 B5 A6 B6 A7 B7 A8 B8 G2

Fig. 26. XF830A, XFU830A, and CPO-IO830 Mixed Panel Honeywell


Binary Inputs Analog Inputs GND Analog Outputs 24V Relays

Bus Modules ComfortPoint Open


TM
B7
7
B8
8
B9
9
B10 B11 B12
10 11 12
AI5
17
AI6
18
AI7
19
AI8
20
AO5 AO6 AO7 AO8
25 26 27 28
IN1
35
IN2
36
IN3
37
IN4
38
IN5
39
IN6
40
1 2 3 4 5 6 13 14 15 16 G1 G2 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 41 42 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
!
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
The mixed Honeywell Panel Bus I/O modules, with 8 analog
Install. Instr.
MU1B-0463GE51 DI DO

inputs, 8 analog outputs, 12 binary inputs, and 6 relay


outputs, are available in the following versions:
 XF830A mixed Honeywell Panel Bus I/O module, with
push-in terminals;
 XFU830A mixed Honeywell Panel Bus I/O module, with Fig. 29. CPO-IO830 mixed Panel Bus I/O module, shown
screw terminals; with 4 optional aux. terminal blocks (top view)
 CPO-IO830 mixed Honeywell Panel Bus I/O module, with
push-in terminals. Features
Each features an integrated terminal socket and electronic - 1 yellow LED per output
module. - Configurable safety position for outputs in case of
The XF830A can be equipped with up to two rows of (XS830 communications problems (remain in last position, OFF,
and/or XS831) auxiliary terminal blocks on the top and/or ON)
bottom. The XFU830A and CPO-IO830 can be equipped with
up to two rows of (XS830 and/or XS831) auxiliary terminal
blocks on the top, only. WARNING
71 COM a COM a 75
Risk of electric shock or equipment damage!
External
40 24V
72 COM b COM b 76
73
74
24V~
24V~0
34 5
24V for relay 1...5
24V~
24V~0
77
78 It is not permitted to wire the relays of the mixed Panel
012

67

S2
8 9A
EF

Bus I/O modules for anything other than low voltage.


BCD
J1 J2 J3 J4 J5

Honeywell
Binary Inputs Analog Inputs GND Analog Outputs 24V Relays
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
1 2 3 4 5 6 13 14 15 16 G1 G2 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4

1 2 3 4 5 6 7 8 9 10 11 12
41 42 AO1 AO2 AO3 AO4 NO1 NO2

1 2 3 4 5 6
NO3 NO4 NO5 NO6

!
Permissible Loads
DO
Table 7. Permissible loads of mixed Panel Bus I/O
Install. Instr.
EN1B-0375GE51 DI

XF830A modules
12 BI / 8 AI / 8 AO / 6 RO 7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
24V, 15VA, T50
0706AX0001-XFU830A max. load min. load
8 Made in Germany
0532
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34
per module 19…29 VAC, 1…29 VDC –
A1 A2 A3 A4 A5 A6 A7 A8 A9
1
B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 A2 A3 A4 A5 A6 A7 A8 A9
2
B1 B2 B3 B4 B5 B6 B7 B8 B9 (total for all 3 A resistive or inductive,
3 4
relay cos φ ≥ 0.6,
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B7 A8 B8 G2
contacts) no capacitive load,
Fig. 27. XF830A mixed Panel Bus I/O module, shown with protected by fuse F4
4 optional aux. terminal blocks (top view)
per nor- 19…29 VAC, 1…29 VDC >50 mW,
71 COM a External COM a 75
mally open 0.5 A resistive or inductive, 0.05 A res./ind.,
cos φ ≥ 0.6, cos φ ≥ 0.6
40
72
73
COM b
24V~
24V
COM b
24V~
76
77
contact
74 24V~0
34 5
24V for relay 1...5 24V~0 78 no capacitive load
012

67

S2
8 9A
EF

BCD
J1 J2 J3 J4 J5

Honeywell
Binary Inputs Analog Inputs GND Analog Outputs 24V Relays
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
1 2 3 4 5 6 13 14 15 16 G1 G2 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 41 42 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6

!
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
Install. Instr.
EN1B-0375GE51 DI DO

XFU830A
12 BI / 8 AI / 8 AO / 6 RO 7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
24V, 15VA, T50
0706AX0001-XFU830A
8 Made in Germany
0532
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34

Fig. 28. XFU830A mixed Panel Bus I/O module, shown


without optional aux. terminal blocks (top view)

EN0B-0701GE51 R0218 20
PANEL BUS I/O MODULES – PRODUCT DATA

+V
18 VDC (NOT STABILIZED)

AI
10 kOHM

150 kOHM
Vi 199.9 kOHM BI
DRY CONTACT
GND 16 ... 22 VDC = OPEN
0 ... 2 VDC = CLOSED

Fig. 30. Analog input high impedance (input circuit for


GND
FAST
voltage input for active sensors) TOTALIZER

Fig. 32. Configuration of a binary input as a fast totalizer


10 VDC

24.9 kOHM

AI

Vi 199.9 kOHM
(8.9 VDC IF
CONNECTION
INTERRUPTED)
GND

Fig. 31. Analog input impedance setpoint (input circuit


for NTC10kΩ, NTC20kΩ, wall module setpoint)

21 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

71 COM
A
XF830 Mixed I/O Module COM
A 75
F1 72 COM
B
24
COM
B 76
73 V~ 24
24 V~ 77
74 V~0 24
V~0 78
BINARY INPUTS ANALOG INPUTS ANALOG OUTPUTS 24V RELAYS

B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40

B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 G1 G2 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34

XS830 OPT. AUX. TERM. MODULE XS830


A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9

(GND) (GND 24 VAC) (24 VAC)

1 2 1 2 1 2 1 2 1 2 3 1 2 3 1 2

0...10 VDC M 0...10 VDC M


ACTIVE 24V~ DRIVE with
DRY DRY NTC20kOHM
TOTALIZER SENSOR 0...10V SIGNAL DCA
CONTACT CONTACT SENSOR
1: GND 1: GND (24V~0) 1: GND (24V~0) 1: 24V~0
1: GND 1: GND
2: SIGNAL
1: GND
2: 24V~ POWER F2 2: 24V~ POWER 2: 24V~
2: SIGNAL 2: SIGNAL 2: SIGNAL
3: 0...10 VDC 3: 0...10 VDC F4

LEGEND: F1 MAX. 4 A F2 MAX. 12 A

F4 MAX. 3 A

THIN LINES MIN. 0.75 mm 2

THICK LINES MIN. 1.5 mm 2 - or less, as per F2, F4

Fig. 33. XF830A mixed Panel Bus I/O Module, wiring example 1: Actuators

EN0B-0701GE51 R0218 22
PANEL BUS I/O MODULES – PRODUCT DATA

ACTIVE
4...20 mA
SENSOR
1: GND (24V~0)
2: 24V~ POWER
OPT. AUX. TERM. MODULE XS831 3: 4...20 mA
A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B7 A8 B8 G2
1 2 3

OPT. AUX. TERM. MODULE XS830 OPT. AUX. TERM. MODULE XS830
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9

F2

71 COM
A
CPO-IO830 Mixed I/O Module COM
A 75
F1 72 COM
B
24
COM
B 76
73 V~ 24
24 V~ 77
74 V~0 24
V~0 78
BINARY INPUTS ANALOG INPUTS ANALOG OUTPUTS 24V RELAYS

B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40

B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 G1 G2 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34

LEGEND: F1 MAX. 4 A F2 MAX. 12 A

THIN LINES MIN. 0.75 mm 2

THICK LINES MIN. 1.5 mm 2 - or less, as per F2

Fig. 34. CPO-IO830 Connection example (for current inputs)

23 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

Approvals, Certifications, and Standards Mounting Methods


DIN-rail mounting (e.g., in control cabinet).
Approvals and Certifications
 CE-approved
 Conforms to EN 60730-1 and EN 60730-2-9 Calculated Lifetime of Weakest Components
 Investigated according to United States Standard MTBF  13.7 years (under typical operating conditions)
UL916 (USL-listed) as well as according to Canadian
National Standard(s) C22.2 (CNL-listed)

Classification according to EN60730-1


Environmental conditions: For use in home (residential,
commercial, and light-industrial)
environments
Pollution degree: Class 2
Protection against shock: Class II
Software class: Class A
Overvoltage category: II

Classification according to EN60529


(Degree of Protection Provided by Enclosures)
Classification: IP20

Ambient Environmental Limits


Operating temperature: 0 … +50 °C at 5…93% r.H.
Storage temperature: -20 … +70 °C at 5…93% r.H.
Humidity: 5 … 93% r.h. non-condensing

Current Requirements and Heat Dissipation


The Panel Bus I/O Modules are equipped with highly-efficient
switching power supplies which provide for relatively uniform
power consumption over a wide range of supply voltages (see
Table 8). The specific heat dissipation inside the modules
amounts to less than 2 W for all models.

Table 8. Current requirements of Panel Bus I/O modules


supply voltage
devices powered
24 VAC 24 VDC
XF821 130 mA 80 mA
XF822, XFR822 150 mA 90 mA
XF823 180 mA 130 mA
XF824, XFR824, XFR825 140 mA 80 mA
XF830A, XFU830A, CPO-IO830 200 mA 95 mA

Mechanical
Housing Dimensions (H x W x D)
The pluggable Panel Bus I/O Modules (mounted on Terminal
Sockets) all have the dimensions: 110 X 90 X 93 mm (see
also Fig. 35 on page 25).
The XF830A and XFU830A mixed Panel Bus I/O Modules
have the dimensions: 216 X 110 X 93 mm (see also Fig. 36
on page 25).
The CPO-IO830 mixed Panel Bus I/O Module has the
dimensions: 216 X 110 X 61 mm (see also Fig. 37 on page
26).

Housing Material
Plastic, flame-retardant

EN0B-0701GE51 R0218 24
PANEL BUS I/O MODULES – PRODUCT DATA

Dimensions
89.5 94.1
TERMINAL
SOCKET

LOCK

REMOVABLE

110

45
ELECTRONIC
MODULE

67.5
SCREW-TYPE
30.6 TERMINALS
83

28
38
14
SWIVEL LABEL HOLDER
XS814 Aux. Terminal Package (optional)
51.5
Fig. 35. Pluggable Honeywell I/O Modules (example with manual overrides), incl. terminal socket, dimensions (in mm)

216 92.5
71 COM a External COM a 75
40 24V
72 COM b COM b 76
73 24V~ 24V~ 77
345
74 24V~0 24V for relay 1...5 24V~0 78
01 2

67

S2
8 9A
EF

BCD
J1 J2 J3 J4 J5

Honeywell
Binary Inputs Analog Inputs GND Analog Outputs 24V Relays
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
110

7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40

45
1 2 3 4 5 6 13 14 15 16 G1 G2 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 41 42 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6

!
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
Install. Instr.
EN1B-0375GE51 DI DO
CLEARANCE

XF830A
69

12 BI / 8 AI / 8 AO / 6 RO 7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
24V, 15VA, T50
0706AX0001-XFU830A
8
28 38
100

Made in Germany
0532
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34

A1 A2 A3 A4 A5 A6 A7 A8 A9
A
B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 A2 A3 A4 A5 A6 A7 A8 A9
B
B1 B2 B3 B4 B5 B6 B7 B8 B9 15 SCREW-TYPE TERMINALS
(XFU830A)
SWIVEL LABEL HOLDER
C D
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B7 A8 B8 G2
51.5
A, B, and C = XS830 Aux. Terminal Packages (optional) D = XS831 Aux. Terminal Package (optional)

Fig. 36. XF830A (shown) and XFU830A mixed Honeywell I/O Module (example with 4 auxiliary terminal packages),
dimensions (in mm)

25 EN0B-0701GE51 R0218
PANEL BUS I/O MODULES – PRODUCT DATA

216 54.4
44

Binary Inputs Analog Inputs GND Analog Outputs 24V Relays


Honeywell

110
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
ComfortPoint Open
TM
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
1 2 3 4 5 6 13 14 15 16 G1 G2 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 41 42 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
!
Install. Instr. 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
MU1B-0463GE51 DI DO

61.1
Fig. 37. CPO-IO830 Mixed Honeywell I/O Modules, dimensions (in mm)

Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

Home and Building Technologies


Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone +49 (0) 7031 637 01
Fax +49 (0) 7031 637 740
http://ecc.emea.honeywell.com

EN0B-0701GE51 R0218 Subject to change without notice

You might also like