Fibers 10 00026 v2
Fibers 10 00026 v2
Fibers 10 00026 v2
Article
Effectiveness of Hybrid Fibers on the Fracture and Shear
Behavior of Prestressed Concrete Beams
Chandrashekhar Lakavath 1 , Aniket B. Bhosale 1 , S. Suriya Prakash 1 and Akanshu Sharma 2, *
1 Department of Civil Engineering, Indian Institute of Technology Hyderabad, Sangareddy 502285, India;
ce19resch11007@iith.ac.in (C.L.); ce16mtech11027@iith.ac.in (A.B.B.); suriyap@ce.iith.ac.in (S.S.P.)
2 Lyles School of Civil Engineering, Purdue University, West Lafayette, IN 47907, USA
* Correspondence: akanshu@purdue.edu
Abstract: This study investigates the effectiveness of hybrid fibers (steel and macro-synthetic) on
the shear behavior of prestressed concrete beams. The hybrid fiber combination was selected to
avoid workability issues at high volume dosages and ensure effective crack arresting over the crack
opening range. Fracture studies included testing notched concrete prisms to identify the role of
hybrid fibers in the crack bridging mechanism. Seven hybrid fiber reinforced prestressed concrete
(HFRPC) beams were tested at a low shear span (a) to depth (d) ratio of 2.4. The effects of hybrid
fibers on load–deflection behavior and strain in the strand are reported. Similarly, the crack opening,
crack slip and crack angle variation regarding applied shear were investigated using the digital image
correlation (DIC) technique. Test results of HFRPC beams showed considerable improvements in
peak load and the post-peak response with a higher hybrid fiber dosage. The crack opening and crack
slip measurement across the major shear crack revealed continuous dilatant behavior. The kinematic
response of critical shear crack reflects the sustained dilation response up to the ultimate load, which
depends on the critical shear crack angle of the tested beams. As the fiber dosage increases, the shear
crack slip and width are reduced, indicating the roles of hybrid fibers in improving ductility and the
change in failure mode from brittle shear tension to relatively ductile shear tension.
Citation: Lakavath, C.; Bhosale, A.B.;
Prakash, S.S.; Sharma, A. Keywords: crack kinematics; fracture energy; hybrid fibers; prestressed concrete beams; shear
Effectiveness of Hybrid Fibers on the
Fracture and Shear Behavior of
Prestressed Concrete Beams. Fibers
2022, 10, 26. https://doi.org/ 1. Introduction
10.3390/fib10030026
Concrete beams can be very brittle if not adequately reinforced. The addition of
Academic Editor: Martin J. D. Clift discrete and randomly oriented fiber reinforcements in concrete helps to improve its
Received: 16 January 2022
ductility under shear loads. This study focuses on the effects of hybrid combinations of steel
Accepted: 1 March 2022
fibers (SF) and polyolefin (PO)-based macro-synthetic fibers (MSF), on the shear behavior
Published: 8 March 2022
of prestressed concrete beams. Ensuring adequate ductility is an essential design aspect of
reinforced concrete (RC) and prestressed concrete (PSC) beams. However, the prestressed
Publisher’s Note: MDPI stays neutral
concrete beam’s ductile behavior and failure modes depend on different parameters, such
with regard to jurisdictional claims in
as the compressive strength of the concrete, the longitudinal reinforcement ratio, the web
published maps and institutional affil-
reinforcement ratio, and the level of prestressing. Based on previous studies, such as Kani’s
iations.
classical theory [1], the shear span to depth ratio (a/d) of 2.5 is considered a pivot point,
below which the reinforced concrete (RC) beams fail in a shear critical mode. Strut action
or arch action is possible in RC beams tested at very low a/d ratios (a/d < 1.5) [2]. Similarly,
Copyright: © 2022 by the authors.
for a/d ratios between 2.5 and 6, possible failures occur via flexure shear mode due to
Licensee MDPI, Basel, Switzerland. diagonal shear tension after flexure cracking. Therefore, in this study, a shear span to depth
This article is an open access article ratio (a/d) of 2.4 was considered to avoid arch action and ensure the diagonal shear tension
distributed under the terms and (DST) mode in prestressed concrete beams [3–6].
conditions of the Creative Commons Hybrid fiber combinations can be made using the same fibers with different geo-
Attribution (CC BY) license (https:// metrical properties or by combining different types of fibers with various physical and
creativecommons.org/licenses/by/ mechanical properties. In general, steel fibers are the most popular type for enhancing the
4.0/). mechanical properties of concrete, whereas non-metallic fibers are used to enhance other
physical properties. This study used a combination of steel fibers (SF) and macro-synthetic
fibers (MSF) for hybrid combinations. In recent years, the beneficial effects of hybrid fiber
reinforced concrete (HFRC) on various properties of concrete, such as mechanical, thermal,
and shielding properties, have been investigated by many researchers [7–10]. Incorporating
two or more fibers may significantly improve the concrete’s fracture behavior by enhancing
the toughness and tensile strength [11–15]. One of the main reasons for using hybrid fiber
combinations incorporating characteristics such as various elasticity moduli, is to control
the crack opening at various levels [16]. By mixing more than two types and sizes of
fibers, the tensile properties of concrete can be altered, even to achieve strain hardening
behavior [17]. Relatively few studies have focused on shear crack propagation analysis
of hybrid fiber reinforced prestressed concrete beams, using the digital image correlation
(DIC) technique [18,19]. The use of the DIC technique helped us better understand the
shear dilatancy behavior, which was the primary focus of this study. In HFRC, the con-
stituent fibers enhance the material’s properties at various concrete fracture stages, such as
pre-macro cracking and post-macro cracking stages. The addition of macro-synthetic fibers
(MSF) can reduce the balling effect and workability issues associated with steel fibers. They
can also improve fracture toughness, ductility, residual strength, impact resistance and the
synergy effect [13,20–22].
Only a few researchers in the past have investigated the effects of hybrid fibers on
the response of structural elements under shear stress [23–25]. The prestressing force
increases the cracking strength, decreases the angle of the compression strut and reduces
the shear strain in the stirrups. The shear resistance in prestressed concrete beam consists
of contributions from (a) un-cracked concrete, (b) aggregate interlock, (c) the resistance of
fibers bridging the crack, (d) dowel action of longitudinal reinforcement, (e) amount of
pre-compression (prestress) and (f) stirrups [26–30]. Understanding shear crack kinematics
is essential for developing a rational, analytical model for predicting the shear capacity of
fiber-reinforced prestressed concrete beams. A significant improvement is possible in the
early fracture response of concrete containing a hybrid fiber blend after macro-synthetic
fiber addition [16,31]. Shear studies of prestressed steel fiber reinforced concrete beams
have been performed in the past [26,32,33]. However, the particulars of the shear behavior
of prestressed hybrid fiber reinforced concrete beams are mainly unknown.
Prestressing
Specimen
Strand
Figure 1.
Figure 1. Hybrid fiber
fiber reinforced
reinforced prestressed
prestressedconcrete
concretebeam
beamand
andtest
testsetup
setupdetails.
details.PP==applied
appliedload,
load, SG = Strain gauge, A-A = cross section
SG = Strain gauge, A-A = cross section view. view.
TableThe
2. Concrete mixwere
specimens design quantities
named basedin kg/m3.
on the volume fractions (Vf ) of fibers added to the
total concrete volume. Hybrid fibers are mixtures of equal volumes of hooked end steel
CA Hybrid Fiber Combination
Mix ID
fibers C polyolefin
(SF) and CSS NRS (PO)SPmacro-synthetic
Water fibers. For example, HB50 indicates the
20 mm 10 mm SF PO
combination of 0.25% Vf of SF and 0.25% Vf of PO fibers. The details of the quantities
of HB00 450 such
ingredients, 415 as cement,
312 2.6coarse 152 755 fine355
aggregate, 0
aggregates, superplasticizers, 0 and
HB50 450 415 312 2.6 152 755 355 19.65
fibers used in the concrete mixes, are listed in Table 2. All the materials were added in 2.27
HB100
the following450 sequence
415 312 2.6 the152
to avoid balling 755
effect in 355 39.25 concrete. 4.55
fiber reinforced In these
HB150the 450
mixes, 415 312of coarse
full quantities 2.6 aggregates,
152 755fine aggregate,
355 58.87
and cement were2.27added,
Note: C = cement,
followed by 50%CSS = crushed
of the stone sand,
total water NRS Then,
quantity. = natural river
steel sand,
and SP = super plasticizer,
macro-synthetic CA =
fibers were
coarse aggregate.
added manually, and the remaining water and superplasticizers were added to the pan
mixture [34]. The variations in compressive strength measured with the standard cubes due
Table
to fiber3. addition
Summaryareof material characteristics
summarized in Tableof3.concrete.
The compressive strength increased by 4.2%,
14.1%, and 23.8%
Residual Flexural Tensile for HB50,
TotalHB100, and HB150, respectively (increasing portions of fiber).
Toughness Tf × 10−3 (kN-mm)
Strength (MPa) Fracture 𝑮𝒇
Mix ID fcm (S.D) ΔGf =
Energy 𝑮𝒇𝒄
fR1 fR3 fR4 I II III IV Total (Tf)
Gf (N/mm)
45.30
HB00 0.60 - - 0.156 1.00 0.53 3.14 - - 3.67
(1.73)
47.21
HB50 1.93 1.93 1.15 0.976 6.25 0.35 6.29 13.36 3.59 23.60
(1.52)
Fibers 2022, 10, 26 4 of 26
Similarly, the average flexural tensile strength increased by 68.9% and 114.5% for
HB50 and HB100 beams. The types of fibers and their mechanical properties used in the
experimental program are detailed in Table 1. The effect of steel fibers on the shear behavior
of prestressed beams was previously studied by other authors [32]. Due to variations in the
compressive strength of concrete, the behavior of specimens with only steel fibers could
not be directly compared with the behavior of specimens with hybrid fiber dosages. In
addition, a large volume of macro-synthetic fibers may be required for improving the shear
performance of prestressed concrete under shear stress. The main reason for selecting
the hybrid combination of fibers is that hybrid fibers provide excellent residual strength
over a range of crack mouth opening displacements (CMOD) without compromising the
workability during casting. Various researchers [16,32] discussed the advantages of a
hybrid combination of fibers and their fracture behavior. Based on their investigation,
it was concluded that hybrid fibers will improve the residual tensile strength without
compromising workability.
24
HB150
20
16
Load (kN)
HB100
12
8 HB50
4
HB00
0
0 1 2 3 4 5
CMOD (mm)
(a) (b)
Fibers 2022, 10, x FOR PEER REVIEW 6 of 28
Figure 2. Fracture
Figure test. test.
2. Fracture (a) Fracture test setup.
(a) Fracture 1. Actuator.
test setup. 2. Loading
1. Actuator. jig. 3. FRC
2. Loading specimen.
jig. 3. 4. Roller4. Roller
FRC specimen.
supports. 5. CTOD gauge. 6. CMOD gauge. 7. Light source. 8. DIC camera. (b) Load versus CMOD.
supports. 5. CTOD gauge. 6. CMOD gauge. 7. Light source. 8. DIC camera. (b) Load versus CMOD.
4.1.1. Residual
Gustafsson
Gustafsson Flexural
and and Strength
Hillerborg
Hillerborg Calculations
[37][37]
introduced
introduced aUsing
parameterRILEM
a parameter Recommendations
to to
associate
associate thethe
fracture
fracture ener-
energies with the
The residual
gies with shear
the shearflexural capacities
capacities tensileof
of the the
strengthbeams, called characteristic
R,i) is characteristic
beams, (fcalled typically usedlength. length.TheyThey
to estimate the fibers’
concluded
concluded
that that the
contribution to the
the characteristic characteristic
tensile length of
lengthresistance
parameter parameter
FRC. It can
is proportional is proportional
be to the
conservatively
to the material’s material’s
calculated
fracture as (G
energy per
f ).
fracture energy (Gf). Therefore, it is essential to understand the fracture energy variations
Therefore,
RILEM [40] it recommendations
is essential to understand the fracture
using Equation (1),energy
whichvariations
is derived of assuming
composite the materials,
linear
of composite materials, such as HFRC. Foster et al. [38] estimated the shear capacities of
such
elasticasresponse
HFRC. Foster of FRC et al.
in [38]
bothestimated
compression the shear capacitiesFrom
and tension. of SFRC beams bycurves
load–CMOD using
SFRC beams by using the residual tensile strengths obtained from the inverse analysis.
the residual tensile strengths obtained from the inverse analysis.
obtained from the tests on HFRC prisms, we observed that peak load did not increase The tensile stress–strain
The tensile stress–strain response from the fracture test can be obtained from the multi-
response from
significantly the the
with fracture test in
increase can be obtained
fiber volume. The fromfiberthe multi-linear
contributes to tensile stress–strain
the load-carrying
linear tensile stress–strain response proposed by Bhosale et al. [7,39]. The inter-
response
mechanism proposed
soon bycracking
after Bhosale the et al. [7,39]. Thus,
concrete. The inter-relationship
the crack is between
initiated only the reaching
after concrete
relationship between the concrete matrix and fiber reinforcement components to shear
matrix and fiber reinforcement components to shear capacity is shownisinalleviated
Figure 3. In this
capacity is shown in Figure 3. In this study, the residual tensile strengths obtained from in the
the peak load in all the prisms. However, the strength degradation
study,
post-peakthe residual
region tensile
due to strengths
the fibers’ obtained
resistancefrom the
towards International
crack
the International Union of Laboratories and Experts in Construction Materials, Systems
Union
propagation. of Laboratories
The detailed
andand Experts(RILEM)
investigation
Structures inof
Construction
crack Materials,
propagation
recommendations wasSystems
werecarried
used and to Structures
out using the
estimate the (RILEM)
digital recommendations
image
shear capacities correlation
of
were
HFRPC used
(DIC)beams. to
technique estimate the
at various
The impacts shear capacities
points
of fiber of
of load–CMOD
volume HFRPC
fraction on curves,beams. The
as shown
crack arresting impacts of fiber
in Figure
mechanism 4a.volume
and In this
fraction
fracture on crack
experimental
energy are arresting
program,
discussed inmechanism
the highest the and
detail in flexural fracture
tensile
following energy are
strengths
sections. werediscussed
observed in detail
in the in the
range
following
of 0 to 0.05sections.
mm of CMOD.
Figure 3. 3. The
The interrelationship
interrelationshipbetween
betweenconcrete
concretematrix,
matrix, fibers,
fibers, andand reinforcement
reinforcement components
components in
in the
the determination of shear capacity [37]. V = fibers contribution, V = Concrete matrix contribution,
determination of shear capacity [37]. Vuf = fibers contribution, Vuc = Concrete matrix contribution,
uf uc
V us = Stirrups Contribution.
Vus = Stirrups Contribution.
kN-mm/mm)
HB00
60 HB50
HB100
HB150
(DIC) technique at various points of load–CMOD curves, as shown in Figure 4a. In this
experimental program, the highest flexural tensile strengths were observed in the range
of 0 to 0.05 mm of CMOD.
20
0
0 1 2 3 4 5
CMOD (mm)
(a) (b)
Figure
Figure4. Fracture testtest
4. Fracture results. (a) (a)
results. Schematic representation
Schematic of considered
representation points
of considered pointsin load–CMOD
in load–CMOD
curve. I = phases I, II = phases II, III = phases II, IV = phase IV, i = peak load, ii = fist load
curve. I = phases I, II = phases II, III = phases II, IV = phase IV, i = peak load, ii = fist load drop point,
drop point,
iii = second peak load due to fibers, iv = ultimate load point (CMOD = 3.5 mm). (b) Absorbed fracture
energy of HB notched beams.
The flexure tensile strengths at different points of load–CMOD curves were calculated
and reported in Table 3. Test results show that the residual loads of prism beams at CMOD
of 3 mm are 53%, 31.7%, and 27.5% of the peak loads of HB50, HB100, and HB150 speci-
mens. Higher residual strength indicates a more substantial contribution of fibers in stress
redistribution and load resistance. The shear capacity calculations of HFRPC beams require
residual tensile strength as an input parameter. The residual tensile strengths fR1 and fR4
were used to estimate the shear load resisting capacity of HFRPC beams using fib-MC2010
code provisions and RILEM recommendations.
0.75Wo + W1
Gf = (2)
Alig
S
W1 = 0.75( m1 + 2m2 ) g × CMODc (3)
L
Fibers 2022, 10, 26 7 of 26
According to JCI [35] code, the fracture energy (Gf ) calculated for the control specimen
(HB00) was 0.156 N/mm. With the addition of fiber, the fracture energy increased signifi-
cantly to 0.976 and 3.06 N/mm for HB50 and HB150, respectively. The increase in Gf due to
the addition of hybrid fibers ranged from 6.25 to 19.63 times that of the control specimen
(HB00), as shown in Table 3.
The fracture energy is the energy required to open a unit area of the crack surface. At
certain stages in the load–CMOD response, the post-cracking parameters, such as crack
length and strain redistribution of HB prisms, were evaluated. According to RILEM [40]
recommendations, the CMOD of 0.5 mm is considered a serviceability limit. A higher
CMOD value of 3.5 mm is the limit for the ultimate state. The variation in absorbed fracture
energy with respect to CMOD is shown in Figure 4b. The energy required to open a CMOD
of 0.01 mm is evaluated by calculating the area under the load–CMOD curve in equal
intervals of 0.01 mm CMOD. It is represented as toughness (Tf ). The variation in absorbed
fracture energy with respect to CMOD is illustrated in Figure 4b. Comparing fracture
energy values also suggests not much variation in the cumulative fracture energy up to
peak load for all the specimens. However, in the post-cracking regime, the cumulative
absorbed fracture energy slopes increased with fiber volume fraction. No change in slope
represents that the contribution of fibers to the energy dissipation capacity of HFRPC beams
is minimal (HB50 compared to the control). In HB50 notched beams, the lesser quantity of
fibers activated across the cracked plane to bridge the crack was not effective. Hence, the
variations in the slope are not significant. In the case of HB100 and HB150 beams, the slope
changes in cumulative absorbed fracture energy are substantial, signifying that fibers can
significantly improve the ductility and change the failure mode (Figure 4b).
The tension stiffening response of fiber-reinforced concrete beams depends on many
factors, such as length, diameter, aspect ratio, types of fiber, the volume fraction of fibers,
concrete matrix strength, and aggregate size. In the past, few researchers [42–44] studied
the influences of fiber orientation factors on mechanical performance indicators, such
as strength, load–CMOD, and fracture energy. Considerable improvements can result
from proper orientation, due to which the post-peak response of the fracture beam will
increase [42,45]. An increment in the post-peak response of the load–CMOD curve leads to
an increase in residual flexural tensile strength (fR ). Then, the fiber-reinforced prestressed
concrete beam ductility may increase in both flexure and shear dominant cases.
18
15
* i HB00 (Vf=0.0%)
a
12
Load (kN)
3
iv
0
0 * 1 2
CMOD (mm)
3 4 5
(a)
24
21
18
i-1 HB50 (Vf=0.5%)
Load (kN)
15
12
9
ii-1 iii-1
iv-1
6
3
0
0 1 2 3 4 5
CMOD (mm)
(b)
24
HB100-Exp (Vf=1.0%)
21
18 i-2
Load (kN)
15
ii-2 iii-2 iv-2
12
9
6
3
0
0 1 2 3 4 5
CMOD (mm)
(c)
24 iii-3
21
18 ii-3
iv-3
Load (kN)
15 i-3
12 HB150-Exp (Vf=1.5%)
9
6
3
0
0 1 2 3 4 5
CMOD (mm)
(d)
Figure 5. Load–CMOD curves with surface strain contour in x-direction of HB prisms: (a) HB00; (b)
Figure 5. Load–CMOD curves with surface strain contour in x-direction of HB prisms: (a) HB00;
HB50; (c) HB100; (d) HB150.
(b) HB50; (c) HB100; (d) HB150.
Fibers 2022, 10, 26 10 of 26
The effective cover of the beam was kept as 50 mm from the bottom of the beam, as
shown in Figure 1. Stirrups of 8 mm diameter with a spacing of 75 mm were provided
outside the test region to avoid failure, as shown in Figure 1. The prestressed beams were
tested with a shear span to an effective depth ratio (a/d) of 2.4 [32,48,49]. A shear span to
depth ratio (a/d) of 2.4 was chosen to avoid arch action and induce diagonal shear tension
mode for understanding the effect of hybrid fibers on the shear behavior. The effect of fibers
on the shear behavior of beams at a low a/d ratio (less than 2) would be interesting, and
this was discussed by Sagi et al. [25]. The load was applied in a displacement control mode
at a rate of 0.025 mm/s [24,34,50]. The actuator load was transferred to beams through a
rectangular plate of 70 mm width. This distribution plate was used to avoid local failure
in compression due to concentrated load application in the compression zone. One linear
variable displacement transducer (LVDT) was placed below the loading point and the
other at the center of the shear span. Similarly, the strain in the prestressing strands was
monitored by mounting strain gauges, and the locations of the attached gauges are shown
in Figure 1.
HB50 Beams
HB50 beams were cast with concrete mix reinforced with 19.65 kg/m3 (Vf = 0.25%) of
steel fibers and 2.27 kg/m3 (Vf = 0.25%) of macro-synthetic fibers. From the load–deflection
responses of beams, insignificant increases in peak load (Figure 7a) and the post-peak
strength were observed when compared to the control beam (HB00). However, the increase
in post-peak stiffness due to the addition of fibers was considerable. To evaluate the post-
peak response, the energy absorption capacities (EAC) of beams were measured as the
ratios of the area under the load–deflection curves of the FRC beams to the area under
the load–deflection curve of the control beams. The area under the load–deflection curve
showed an up to 20% drop in peak load in the post-peak range. The EAC of HB50 beams
varied from 5.3 to 6.2 times that of control beams (HB00), as stated in Table 4. The failure
mode of the HB50 beam was identified as diagonal shear tension mode (DST). Thus, a low
fiber dosage of 0.50% could not alter the brittle shear tension failure mode, although it
significantly increased the energy absorption capacity.
results. The test configuration and DIC setup are shown in Figure 6a,b. The complete
load–deflection response was compared at different key-points: (i) flexure crack denoted
as “a”, (ii) load at the formation of shear crack denoted as “b”, (iii) peak load point denoted
as “c”, and (iv) ultimate loading point denoted as “d” (80% of peak load), as shown in
Fibers 2022, 10, 26 Figure 6c. After the post-processing, the results of both the prisms and hybrid11fiber of 26
reinforced prestressed beams were verified by comparing CMOD and deflections
obtained from DIC analysis (Figure 6c,d).
(a) (b)
18
HB50 Clip Gauge
16 HB50 DIC
14
P
12
Load (kN)
10
CTOD Gauge
8
6
4
2
0
0 1 2 3 4 5
CTOD (mm)
(c) (d)
Figure 6. Experimental test setup for shear study: (a) Test setup. 1. Controller monitor. 2. The light
Figure 6. Experimental test setup for shear study: (a) Test setup. 1. Controller monitor. 2. The light
source. 3. Controller. 4. FTM frame of 300 kN capacity. 5. Test specimen. 6. Data Acquisition system
source. 3. Controller. 4. FTM frame of 300 kN capacity. 5. Test specimen. 6. Data Acquisition system
(DAQ). 7. DAQ storage. 8. Digital image correlation camera. (b) Schematic view of instrumentation
(DAQ).
details of7. shear
DAQ beams.
storage.(c)8. Calibration
Digital image correlation
of DIC camera.
correlated (b) Schematic
deflections with LVDT viewdeflections.
of instrumen-
i =
tation
flexuredetails of shear
crack load beams.
point, (c) crack
ii= shear Calibration of DIC
load point, iii correlated
= peak loaddeflections
point, iv = with LVDT
ultimate loaddeflections.
point, (d)
iCalibration
= flexure crack load
of DIC point, ii =CTOD
correlated shear with
crackexperimentally
load point, iii =obtained
peak load point, iv = ultimate load point,
CTOD.
(d) Calibration of DIC correlated CTOD with experimentally obtained CTOD.
Control Specimen (HB00)
HB100 Beams
HB100 beams were cast with concrete mix reinforced with 39.3 kg/m3 of steel fibers
(Vf = 0.5%) and 4.55 kg/m3 (Vf = 0.5%) of macro-synthetic fibers. Thus, the total volume
fraction of fibers corresponded to 1% in HB100 beams. Considerable improvements in peak
load carrying capacity and EAC were observed due to 1% fiber addition (Figure 7b). No
difference in load–deflection behavior until cracking was observed between the control and
high-fiber-dosage beams (HB100) (Figure 7b). Thus, as expected, the fibers are activated
and effectively contribute to the load-carrying capacity only after the initiation of cracks.
The EAC of the HB100 beam was significantly increased compared to that of control beams
(Table 4). The shear crack angle of the HB100 beams was in the range of 35◦ to 40◦ with
respect to the beam’s longitudinal axis. Though energy absorption increased significantly,
the failure mode did not change even with a 1.0% fiber dosage. This was due to the
strain-softening response of fiber reinforced concrete, which can be witnessed by observing
responses of beams, insignificant increases in peak load (Figure 7a) and the post-peak
strength were observed when compared to the control beam (HB00). However, the
increase in post-peak stiffness due to the addition of fibers was considerable. To evaluate
the post-peak response, the energy absorption capacities (EAC) of beams were measured
as the ratios of the area under the load–deflection curves of the FRC beams to the area
Fibers 2022, 10, 26 12 of 26
under the load–deflection curve of the control beams. The area under the load–deflection
curve showed an up to 20% drop in peak load in the post-peak range. The EAC of HB50
beams varied from 5.3 to 6.2 times that of control beams (HB00), as stated in Table 4. The
Figure 5c.
failure modeEven withHB50
of the a larger
beamcrack
wasopening (CMOD
identified = 3 mm),
as diagonal thetension
shear strain redistribution
mode (DST).
across the crack can be observed. This resulted in a higher energy absorption capacity,
Thus, a low fiber dosage of 0.50% could not alter the brittle shear tension failure and
mode,
the ductility influenced the failure mode.
although it significantly increased the energy absorption capacity.
300
250
200
Load (kN)
150
0
0 10 20 30 0 10 20 30 0 10 20 30 0 10 20 30
Deflection (mm)
(a) (b) (c) (d)
Figure 7. Load–deflection responses of HFRPC: (a) HB00; (b) HB50; (c) HB100; (d) HB150 beams.
Figure 7. Load–deflection responses of HFRPC: (a) HB00; (b) HB50; (c) HB100; (d) HB150 beams.
Table 4. Summary of experimental results on beams.
Table 4. Summary of experimental results on beams.
HB00-1 HB50-1 HB50-2 HB100-1 HB100-2 HB150-1 HB150-2
HB00-1 HB50-1 HB50-2 HB100-1 HB100-2 HB150-1 HB150-2
Flexure Cracking Load (kN) 150.4 145.8 143.5 150.4 150.8 150.9 153.7
DeflectionCracking
Flexure Load
at Flexure (kN)
Cracking 150.4
Load (mm) 145.8
2.30 143.5
1.51 1.65 150.4 2.26 150.82.20 150.9
1.65 153.7
1.73
DeflectionShear
at Flexure
CrackCracking
Load (kN) 178.3 148.5 150.3 204.8 207.1 217.8 153.7
2.30 1.51 1.65 2.26 2.20 1.65 1.73
Load (mm)
Deflection at Shear Crack Load (mm) 2.96 1.70 1.73 3.30 3.11 1.65 1.73
Shear Crack Load
Peak (kN)(kN)
Load 178.3 148.5
215.9 150.3 224.4 204.8260.6 207.1
216.9 276.9 217.8
275.5 153.7
268.1
Deflection at Shear Crack
Deflection Load
at Peak (mm)
Load (mm) 2.96 1.70
4.01 9.611.73 4.77 3.30 9.66 3.116.79 1.65
13.35 1.73
16.65
Peak Load (kN) 215.9 216.9 224.4 260.6 276.9 275.5 268.1
Deflection at Peak Load (mm) 4.01 9.61 4.77 9.66 6.79 13.35 16.65
Ultimate Load (0.8× Peak Load) (kN) 172.7 173.5 179.6 208.5 221.5 220.4 214.57
Deflection at Ultimate Load (mm) 5.19 20.80 17.74 30.71 12.72 31.05 35.52
% increase in peak load compared to
0 0.5 3.9 20.7 28.3 27.6 24.2
HB00, ∆P (%)
Post-peak stiffness in load–deflection
curve from peak load to ultimate load, −36.6 −3.9 −3.5 −2.5 −9.3 −3.1 −2.8
K0 (kN/mm)
% increase in post-peak stiffness,
0 89.4 90.4 93.2 74.6 91.5 92.3
∆K0 (%)
Energy absorption capacity,
643 3931 3371 6828 3667 7862 8509
EAC (Joules)
∆EAC = EAC
EACc
1 6.1 5.3 10.6 6.0 12.2 13.2
Crack failure angle, θ◦ 40.8◦ 42.8◦ 39.2◦ 35.9◦ 40.4◦ 59.3◦ 56.7◦
Failure Mode DST DST DST DST DST DST DST
Fibers 2022, 10, 26 13 of 26
HB150 Beams
HB150 beams were cast with concrete mix reinforced with 58.58 kg/m3 of steel fibers
(Vf = 0.75%) and 6.83 kg/m3 (Vf = 0.75%) of macro-synthetic fibers. The load–deflection
behavior of HB150 beams is shown in Figure 7c. Although there was no significant improve-
ment in the peak load capacity of HB150 beams compared to HB100 beams, a considerable
enhancement in ductility was observed. In HB150 beams, the first shear crack initiated at a
load of 217 kN (i.e., 80% to peak load). With a further increase in displacement, the same
shear crack propagated towards the loading plate and the support along the prestressing
strand. The beam failed due to discrete diagonal shear cracking in a diagonal shear tension
(DST) mode. However, the critical shear crack angle increased from 35◦ to 60◦ .
1.2
Normalized Load (P/(fcmbd))
0.9
0.6
SF00 MSF00 HB00
SF50 MSF50 HB50
0.3 SF100 MSF100 HB100
MSF150 HB150
0.0
0 5 10 15 20 25 30 0 5 10 15 20 25 30 0 5 10 15 20 25 30
Deflection (mm) Deflection (mm) Deflection (mm)
Figure 8. Normalized load–deflection curves of prestressed concrete beams reinforced with steel
Figure 8. Normalized load–deflection curves of prestressed concrete beams reinforced with steel
fibers (SF), macro-synthetic fibers (MSF), and hybrid fibers (HB).
fibers (SF), macro-synthetic fibers (MSF), and hybrid fibers (HB).
4.2.4. Analysis
4.2.4. Analysis of of Average
Average Shear
Shear Strain
Strain andand Angle
Angle ofof Principal
PrincipalStrain
StrainUsing
UsingDIC DIC
Using post-processed
Using post-processed datadata from
from DIC DICanalysis,
analysis,the
theaverage
averageshearshearstrain
strain and
and angle of
angle
principal strains were calculated by installing gauge or virtual gauges,
of principal strains were calculated by installing gauge or virtual gauges, as shown in as shown in Figure
9a. The9a.
Figure measurement of the angle
The measurement of theof principal
angle strain is
of principal important
strain since itsince
is important is related to the
it is related
shear
to transfer
the shear mechanisms.
transfer The The
mechanisms. angle of the
angle principal
of the principalstrain
strainwas
was calculated using
calculated using
Equation (5)
Equation (5) [52–54].
[52–54]. The
The angles
angles θ θ 11 and
and θ are with
θ 33 are with respect
respect to to the
the longitudinal
longitudinal axis,axis, as
as
shown in Figure 9a. Similarly, d is the displacement, and L is the
shown in Figure 9a. Similarly, d1 is the displacement, and L1 is the distance between
1 1 distance between virtual
gauges G1 and G2. The average shear strains (γxy) were measured by installing four
rectangular gauges (G1, G2, G3, and G4) at the corners of the area of interest in test beams,
as shown in Figure 9a. However, the shear strain values depend on the field of
measurement and location of rectangular inspection gauges (G1 to G4). In this
Fibers 2022, 10, 26 14 of 26
virtual gauges G1 and G2 . The average shear strains (γxy ) were measured by installing
four rectangular gauges (G1 , G2 , G3 , and G4 ) at the corners of the area of interest in test
beams, as shown in Figure 9a. However, the shear strain values depend on the field of
measurement and location of rectangular inspection gauges (G1 to G4 ). In this experimental
program, the inspection gauges were installed at the farthest corners of the test region to
capture the entire shear crack. Similarly, the angle of principal strain was experimentally
measured using Equation (5). ex and ey are the longitudinal and vertical strains measured
using virtual gauges, as shown in Figure 9a.
d1 d2
θ + θ3 L1 + L3
γxy = 1 = (4)
2 2
Fibers 2022, 10, x FOR PEER REVIEW
γxy
15 of 28
−1
θ ps = 0.5 tan (5)
e x − ey
300
50 0.01 0.02
Angle of Principal Strain (Degree)
HB00
45 250
HB50
40 HB100
35 HB150 200
30 Load (kN)
25 d4
L1
150
20
G1
G’1 θ1
G2
d1 HB00
G’2 100 HB50
15 L4
θ4 L2
10 L3
θ2 HB100
G4
G’4
G3
d2 50 HB150
5 θ3
d3
G’3
0 0
0.00 0.02 0.04 0.06 0.08 0.10 0.00 0.02 0.04 0.06 0.08 0.10
Average Shear Strain (mm/mm) Average Shear Strain (mm/mm)
(a) (b)
Figure 9. Load versus average shear strains and the angle of the average principal strain of HFRPC
Figure 9. Load versus average shear strains and the angle of the average principal strain of HFRPC
beams: (a) angle of principal strain vs. average shear strain; (b) load vs. average shear strain.
beams: (a) angle of principal strain vs. average shear strain; (b) load vs. average shear strain.
Beam ID Shear crack load point (b) Peak load point (c) Ultimate load (d) (80% Pmax) Final failure point Principal strain (e1)
HB00
HB50
HB150
Figure 10. Strain variation in all test HB beams at various points of load–deflection curves.
Fibers 2022, 10, 26 16 of 26
In the HB50 beams, a flexural crack initiated just below the loading point. After that, a
shear crack formed at a distance of 295 mm away from the nearest support to the loading
point. All these crack initiation points were identified using principal strain contours.
With a further increase in the deflection of the beam, the same shear crack approached the
loading beam. From DIC strain contours, it was observed that the strain was distributed
uniformly across the crack at the peak load of 217 kN. The strain localization revealed the
propagation path, as shown in Figure 10.
HB100 beams initially cracked from flexure. After initiating a major shear crack, the
flexure cracks stopped propagating (Figure 10). The first shear crack in HB100 initiated at
82% of the peak load, i.e., 204.8 kN, which can be identified from principal strain contours.
After the initiation of shear cracks, the nonlinearity in the load–deflection curve increased
(Figure 7b). At a deflection of 3.98 mm, a sudden drop in the load resistance occurred due to
the formation of a major shear crack at an angle of 36◦ (Figure 10). HB100 beams had major
shear cracking at 65 kN. From the peak load point, the rate of load drop was constant up
to a deflection of 30.7 mm. Load resistance dropped continuously in the post-peak region
due to the complete pull-out of fibers in the cracked surface of beams. Similarly, beams
reinforced with regular shear reinforcements were tested by different authors [27,55–59],
and the shear cracking load and crack angle variations were discussed.
Both the HB150 beams exhibited nonlinearity in load–deflection response after a load
of 150 kN, as shown in principal strain plots (Figure 10). Due to the crack bridging action of
fibers, secondary cracks did not propagate towards the compression zone. After reaching
a load of 218 kN, the load–deflection curve exhibited nonlinearity, indicating the major
crack (shear crack). The same shear crack propagated towards the loading point at higher
displacements. Like HB50 and HB100 beams, HB150 beams also developed one full depth
shear crack each at the peak load. In the post-peak region, a second major shear crack
developed at 150 mm in HB150 above the tension side of the beam (Figure 10). At 80%
of peak load in the post-peak regime, a second major crack propagated from the tension
side to the compression side. The increased applied displacement continuously progressed
towards the left support, as shown in Figure 10.
The primary crack propagated towards the support, with a continuous distribution
of strains. The progressive detachment of prestressing strands started at the shear crack
initiation location close to the support. From the principal strain contours of all the test
specimens, it can be observed that the uncracked concrete depth reduced with an increase
in fiber dosage. This reduction indicates the complete strength of concrete was utilized in
load resistance due to the improved tensile behavior of concrete from fiber addition.
Devalpura and Tadros [60] tested low relaxation prestressing strands and proposed
models for stress–strain curves. Their test results showed that the yielding strain of the
prestressing strand was about 10,000 microns. The tested HFRPC beams showed none of
the prestressing strands of HFRPC beams yielded (reached a strain of about 10,000 microns)
up to peak load. Thus, all the tested beams failed in the shear dominant mode (diagonal
shear tension) without yielding the prestressing strand. However, the failure mode changed
from brittle shear mode to a less brittle shear mode with higher energy absorption due to
fiber addition. Likewise, the crack angle increased from 35◦ to 60◦ due to increased fiber
dosage. An increase in crack angle also highlights the change in failure mode from brittle
shear to less brittle shear (diagonal shear tension mode) with significant energy absorption.
is the volume change of the chosen area of interest when the beam is subjected to shear
deformations. It is different from dilatancy, referred to in the context of confinement, where
the volumetric expansion results from axial compression loads. The increases in crack
width and slip are collectively termed here shear dilatancy. The effect of fiber dosage on the
shear dilatancy of prestressed concrete beams is analyzed here. The effect of fiber dosage
on the crack pattern, Uw , and Us , along with the depth of the beam at a few critical points
of load–deflections curves, is presented and discussed in the following section.
(a) (b)
(c) (d)
Figure 11.
11. Failure
Failure mode
mode and
and crack
crack slip
slip (U
(Us)) and crack opening (Uw) with respect to load: (a) HB00; (b) HB50, (c) HB100, (d) HB150, * = post peak loads.
Figure s and crack opening (Uw ) with respect to load: (a) HB00, (b) HB50, (c) HB100, (d) HB150, * = post peak loads.
Fibers2022,
Fibers 2022, 10,
10, 26x FOR PEER REVIEW 20 ofof2628
19
The responsesofofUU
Theresponses andUUs sin
w wand indifferent
differentlayers
layersatatan
aninterval
intervalofof60
60mm
mmacross
acrossthethedepth
depth
(Figure
(Figure 11) were extracted from DIC grid data. The load versus crack openingand
11) were extracted from DIC grid data. The load versus crack opening andslip
slip
behavior
behaviorisisrepresented
representedtotounderstand
understandthe thecontributions
contributionsofofthethehybrid
hybridfibers
fibersatatall
allloading
loading
stages
stagesupuptotothetheultimate
ultimateload.
load.Similarly,
Similarly,thetheschematics
schematicsofofthe thecrack
crackpattern
pattern(Figure
(Figure11) 11)
represent
represent the load values at different crack depth levels for visualizing the crackinitiation
the load values at different crack depth levels for visualizing the crack initiation
and
andits
itspropagation
propagationduring
duringtesting.
testing.For
Forexample,
example,ininthe thecase
caseofofthe
theHB50
HB50beam
beamatat188 188kNkN
load,
load,the
theaverage
average crack opening
crack opening and slipslip
and was 1 mm.
was 1 mm.Likewise, the the
Likewise, complete responses
complete responses of allof
HFRPC beams can be visualized. The crack opening and slip responses of layer 2, layer 3,
all HFRPC beams can be visualized. The crack opening and slip responses of layer 2, layer
and layer 4 were similar in all the specimens (Figure 11). To compare the critical shear crack
3, and layer 4 were similar in all the specimens (Figure 11). To compare the critical shear
behavior in terms of Us and Uw , the average measurements from all four layers for beams
crack behavior in terms of Us and Uw, the average measurements from all four layers for
with different mixes are reported in Figure 12.
beams with different mixes are reported in Figure 12.
-5
-10
HB00
-15 HB50
HB100
-20 HB150
Up to peak load
-25
Figure 12. Average crack opening (Uw) versus crack slip (Us) up to an ultimate load point.
Figure 12. Average crack opening (Uw ) versus crack slip (Us ) up to an ultimate load point.
Allthe
All thetested
testedspecimens
specimensshowed showeda acontinuous
continuousincrease
increaseininthe
thecrack
crackopening
opening(U(U w) with
w ) with
progressivecrack
progressive crackslip
slip(U(U s) across the major shear crack. The increases in slip and opening
s ) across the major shear crack. The increases in slip and opening
ofofcritical
criticalcrack
crackindicate
indicatethatthatthethecrack
crackslip
slipreduced
reducedsignificantly
significantlywithwithananincrease
increaseininfiber
fiber
volume fraction except for HB100 (Figure 12). The shear dilation response
volume fraction except for HB100 (Figure 12). The shear dilation response of hybrid fiber of hybrid fiber
reinforced concrete beams was nearly linear up to the ultimate load
reinforced concrete beams was nearly linear up to the ultimate load (Figure 12). No effect (Figure 12). No effect
ofoffiber
fiberwas
wasobserved
observedup uptotothetheinitiation
initiationofofcritical
criticalshear
shearcrack.
crack.However,
However,withwithan anincrease
increase
ininfiber
fibervolume
volumefraction
fraction inin HFRPC
HFRPC beams,
beams, thethe crack
crack slips
slips reduced
reduced from from 155 to
15 to mm5 mm
withwith
an
an increase
increase in fiber
in fiber dosagedosage
up toup to ultimate
ultimate load load (Figure
(Figure 12). 12).
4.3.3.
4.3.3.Variations
VariationsininCrack CrackOpening
Openingand andCrack
CrackSlipSlipacross
acrossthe theDepth
DepthofofBeam
Beam
To
Tounderstand
understandthe theprogressive
progressivegrowth
growthofofcrack
crackopening
openingwith withan anincrease
increaseininapplied
applied
load,
load,ititisisessential
essentialto to observe
observe the variations of of UUssand
andUUwwacross
acrossthethedepth
depth ofofthethe beam.
beam. To
To estimate
estimate thethe shear
shear resistance
resistance duedue to aggregate
to aggregate interlock,
interlock, the variations
the variations in Uin Us U
s and and Uw
w across
across the depth
the depth had tohad be to be studied.
studied. Us and UsUand Uw measured
w were were measured at an at an interval
interval of 5 mm of 5upmm toup
the
toultimate
the ultimate
load point. For this, a MATLAB program was written to extract Uw and Us and
load point. For this, a MATLAB program was written to extract U w from
Uthe
s from
gridthe datagrid data 11).
(Figure (Figure
The 11).
crackThe crack propagation
propagation depth candepth can be identified
be identified from the Ufrom w and
the U
Us, along
w and U , along the depth of the beam (Figure 13). The crack
thes depth of the beam (Figure 13). The crack opening at different deflections opening at differentis
deflections
shown in is shown13).
(Figure in (Figure 13). Forat
For example, example, at 5 mm deflection,
5 mm deflection, thecrack
the critical critical crackreached
depth depth
reached almost 200 mm in the HB00 beam. At the same crack
almost 200 mm in the HB00 beam. At the same crack depth, the crack opening was in the depth, the crack opening
was in the
range of 2range
to 3 mm.of 2 toSimilarly,
3 mm. Similarly,
in HB50inand HB50HB150and beams,
HB150 beams,
the crackthepropagation
crack propagationdepths
depths were identified as 100 and 75 mm, respectively,
were identified as 100 and 75 mm, respectively, at 5 mm deflection. Thus, at 5 mm deflection. Thus, thetheeffect
effectof
offibers
fibersinincontrolling
controllingthe thecrack
crack arresting
arresting mechanism
mechanism at at aa particular depth can be
particular depth can be clearly clearly
understood
understoodfor fora aspecific
specificdeflection.
deflection.TheThetip
tipofofthe
thecrack
crackcancanbebecalled
calledaapivot
pivotpoint,
point,which
which
arrests the crack progression up to some extent, which can open up. Thus, a progressive
arrests the crack progression up to some extent, which can open up. Thus, a progressive
Fibers 2022,10,
Fibers2022, 10,26
x FOR PEER REVIEW 20 of
21 of 26
28
shear
shear stress
stress transfer
transfer occurs
occurs in
in fiber-reinforced
fiber-reinforcedconcrete
concretebeams.
beams.In
InFigure
Figure13a–d,
13a–d,itit is
is shown
shown
that the full depth crack developed at a deflection of 10
that the full depth crack developed at a deflection of 10 mm. mm.
250 250
HB00 HB50
2.5 mm 2.5 mm
200 5.0 mm 200 5.0 mm
Depth (mm)
Depth (mm)
10 mm 10 mm
150 15 mm 150 15 mm
20 mm 20 mm
100 100
50 50
0 0
-15 -10 -5 0 5 10 15 20 -20 -15 -10 -5 0 5 10 15 20
Us (mm) Uw (mm) Us (mm) Uw (mm)
(a) (b)
10 mm 10 mm
150 15 mm 150 15 mm
20 mm 20 mm
100 100
50 50
0 0
-20 -15 -10 -5 0 5 10 15 20 -20 -15 -10 -5 0 5 10 15 20
Us (mm) Uw (mm) Us (mm) Uw (mm)
(c) (d)
Figure 13. Crack opening (Uw) and crack slip (Us) at different deflection points: (a) HB00 beam; (b)
Figure 13. Crack opening (Uw ) and crack slip (Us ) at different deflection points: (a) HB00 beam;
HB50 beam; (c) HB100 beam; (d) HB150 beam.
(b) HB50 beam; (c) HB100 beam; (d) HB150 beam.
In the
In thecase
caseofofHBHB150
150beams,
beams, thethe maximum
maximum crack
crack widthwidth at the
at the deflection
deflection of 20ofmm
20 was
mm
was 11.5 mm, which was much less than that of the control (HB00) beam.
11.5 mm, which was much less than that of the control (HB00) beam. This reduction in crack This reduction
in crack
width width
shows shows
that that the of
the addition addition
a higher of dosage
a higher ofdosage of fibers improves
fibers improves the crack
the crack arresting
arresting mechanisms, which enhances the ductility of the beams. Similarly,
mechanisms, which enhances the ductility of the beams. Similarly, the crack slip response the crack slip
response
across theacross
depth the depthrepresents
of beam of beam represents the of
the influence influence
hybrid of hybrid
fibers fibers in controlling
in controlling the crack
the crack
slip slip response.
response. At the deflection
At the deflection of 10 mm, of the10slips
mm,across
the slips
the across the beam
beam depth weredepth were
similar in
similar
all in all specimens
specimens (HB00, HB50, (HB00, HB50,
HB100, andHB100,
HB150). and HB150).
The The crack propagation
crack propagation length
length can also be
can also be
estimated estimated
from fromUthe
the Us and Us and Uof
w responses w responses
the beam. A of few
the beam. A few
deflection deflection
points points
at an interval
at an interval of 5 mm deflection up to 20 mm were considered
of 5 mm deflection up to 20 mm were considered to track the crack propagation. The crack to track the crack
propagation.
slip responses The werecrack
more orslip responses
less similar inwereall themore
beams oratless similar in all
corresponding the beams
deflection pointsat
corresponding
(Figure 13). This deflection
shows thatpoints
the (Figure
hybrid 13).
fibersThis
areshows
more that the hybrid
effective fibers the
in arresting are crack
more
effectivethan
opening in arresting the crack opening than sliding/slipping.
sliding/slipping.
4.4.
4.4. Shear Capacity
Capacity Predictions
Predictions Using
Using Code
Code Provisions
Provisions
The
The shear
shear capacities
capacities of
of fiber-reinforced
fiber-reinforced prestressed
prestressed concrete
concrete beams
beams were
were predicted
predicted
using
using the
theprovisions
provisionsof of
RILEM
RILEM [40][40]
and and
Fib-MC2010 [61] code.
Fib-MC2010 The effect
[61] code. The ofeffect
fiber of
orienta-
fiber
tion [62,63] on the structural response was not considered, and the distribution
orientation [62,63] on the structural response was not considered, and the distribution ofof fibers
was considered
fibers uniform
was considered and randomly
uniform oriented.
and randomly The FRC
oriented. Thematerial was considered
FRC material homo-
was considered
homogeneous and isotropic. The average tensile strength of FRC can be obtained from
Fibers 2022, 10, 26 21 of 26
geneous and isotropic. The average tensile strength of FRC can be obtained from RILEM
recommendations, or the stress-crack opening relationship can be obtained from the inverse
analysis [7,39,64,65], and the same was used for shear capacity calculations. The shear re-
sistance offered by the fiber-reinforced prestressed concrete beams included the uncracked
concrete contribution, shear reinforcement contribution, fiber contribution, aggregate inter-
lock, the vertical component of prestressing force, and dowel action due to longitudinal
rebars [32]. The flexural tensile strength of concrete can be used to identify the fiber contri-
bution along the shear crack direction. To identify the fibers’ contribution in shear stress, a
few authors assumed constant stress distribution along the crack [38,50,66,67].
wu
f Ftu (wu ) = f Fts − (0.45 f R1 − 0.5 f R3 + 0.2 f R1 ) ≥ 0 (12)
2.5
f ctm = 0.3 f ck 2/3 (13)
The obtained shear capacities of HFRPC beams are listed in Table 5. Due to the
increase in the fiber dosage, both compressive and tensile strengths of concrete increased.
Its influence was included in the RILEM calculation in the Vcd term. Similarly, in the Fib-
MC2010 provision, the influence of compressive strength is included in VRd,F term. From
this limited experimental study on hybrid fiber reinforced prestressed concrete beams, the
experimental shear capacity to theoretically calculate shear capacity varied in the range
of 1.4 to 1.6. It shows that with an increase in fiber volume fraction, the shear capacity of
the beam increased, as listed in Table 5. The predicted shear capacity and experimental
measurement comparisons of fib-MC2010 and RILEM provisions show that the fib-MC2010
predictions were closer to the experimental results than the RILEM, as detailed in Table 5.
6. Conclusions
Structural tests on prestressed concrete beams were conducted to understand the
influences of different volume fractions (Vf = 0%, 0.5%, 1.0%, and 1.5%) of hybrid fibers
on ductility, failure mode, and kinematics of the critical shear crack until failure. From the
limited test results presented in this study, the following conclusions can be made:
• Fracture test results of the HFRC prism specimens showed an extended softening re-
sponse compared to control specimens. Similarly, the residual flexural tensile strengths
of hybrid fiber reinforced concrete compared to control concrete were 3.2, 4.7, and
10.35 times for HB50, HB100, and HB150 beams. The measurement of the residual
strength of HFRC is critical for shear capacity calculations.
• The comparison of the load–deflection responses of steel, macro-synthetic, and hybrid
fiber-reinforced beams shows that the performance of hybrid FRC beams was high.
They had good ductility due to their better workability in the fresh state.
Fibers 2022, 10, 26 23 of 26
• All the tested beams initially cracked from flexure. However, the final failure was
because of a critical shear crack forming at an angle of 36◦ –60◦ to the longitudinal axis
of the member. The failure mode changed from brittle shear to less brittle flexure-shear
with an increase in fiber dosage.
• With an increase in fiber volume fraction in HFRPC beams, the crack opening and
crack propagation depth in prestressed beams reduced at any specific load point,
indicating effective crack bridging action.
• Only a marginal influence of hybrid fibers was observed on the dilatancy behavior up
to the peak load. However, hybrid fibers significantly influenced the shear dilatancy
response in the post-peak regime from peak load until final failure.
• The experimental to shear capacity predictions using RILEM recommendations vary
from 1.6 to 2. However, fib-MC2010 code predictions are 1.5 times those of experimen-
tal results. Comparisons indicate that predictions using RILEM are more conservative
than the fib-MC2010 provisions.
Author Contributions: C.L., A.B.B., S.S.P., and A.S. designed the test matrix. C.L. performed the
experiments and wrote the paper. A.B.B., S.S.P., and A.S. reviewed the paper. All authors have read
and agreed to the published version of the manuscript.
Funding: “Utchattar Avishkar Yojana (UAY) Scheme, Government of India through Grant No:
YSS/2015/000677” by the Ministry of Human Resources Development, Department of Science and
Technology; and the Prime Minister Research Fellowship—India, Project Number CE19RESCH11007.
Institutional Review Board Statement: Not applicable.
Informed Consent Statement: Not applicable.
Data Availability Statement: The data presented in this study are available within the manuscript.
Conflicts of Interest: The authors declare no conflict of interest.
Notations
Alig = Area of the ligament (b × h) (mm2 )
Area of the tension reinforcement extending not less than ‘d + anchorage length’ beyond the
As = (mm2 )
section considered
b’ = Width of the prism specimen (mm)
b = Width of the prestressed concrete beam (mm)
bf = Width of the flange (mm)
bw = Minimum width of the section over the effective depth (mm)
CMODC = Crack mouth opening displacement at the time of rupture (mm)
D = The effective depth of the prestressed concrete beam (mm)
d1 = Vertical displacement of virtual gauge G2 − G20 in DIC (mm)
d2 = Vertical displacement of virtual gauge G3 − G30 in DIC (mm)
Ec = Modulus of elasticity of concrete (MPa)
ex = Strain in x-direction (∆L3 /L3 ) (mm/mm)
ey = Strain in x-direction (∆L4 /L4 ) (mm/mm)
EAC = The energy absorption capacity of prestressed concrete beam (Joule)
EACc = The energy absorption capacity of the prestressed concrete control beam (Joule)
fc ’ = Average cylinder compressive strength (MPa)
fctk = Characteristic tensile strength of concrete (MPa)
fcm = Average compressive strength of concrete (MPa)
fFtu = The ultimate residual tensile strength at 1.5 mm crack width (MPa)
fctm = Mean axial tensile strength of concrete (MPa)
ffctm,fl = Mean flexural tensile strength (MPa)
Fibers 2022, 10, 26 24 of 26
References
1. Kani, G. How Safe are Our Large Reinforced Concrete Beams? ACI J. Proc. 1967, 64, 128–141. [CrossRef]
2. Birrcher, D.B.; Tuchscherer, R.G.; Huizinga, M.; Bayrak, O. Minimum Web Reinforcement in Deep Beams. ACI Struct. J. 2013, 110,
297–306. [CrossRef]
3. Shahnewaz, M.; Alam, M.S. Improved Shear Equations for Steel Fiber-Reinforced Concrete Deep and Slender Beams. ACI Struct.
J. 2014, 111, 851–860. [CrossRef]
4. Mihaylov, B.I.; Liu, J.; Simionopoulos, K.; Bentz, E.C.; Collins, M.P. Effect of Member Size and Tendon Layout on Shear Behavior
of Post-Tensioned Beams. ACI Struct. J. 2019, 116, 265–274. [CrossRef]
5. Isojeh, B.; El-Zeghayar, M.; Vecchio, F.J. Fatigue Resistance of Steel Fiber-Reinforced Concrete Deep Beams. ACI Struct. J. 2017,
114, 1215–1226. [CrossRef]
6. Ahmad, S.; Bhargava, P. Shear Strength Models for Reinforced Concrete Slender Beams: A Comparative Study. Structures 2018,
16, 119–128. [CrossRef]
7. Bhosale, A.B.; Lakavath, C.; Prakash, S.S. Multi-linear tensile stress-crack width relationships for hybrid fibre reinforced concrete
using inverse analysis and digital image correlation. Eng. Struct. 2020, 225, 111275. [CrossRef]
8. Karimipour, A.; Ghalehnovi, M. Comparison of the effect of the steel and polypropylene fibres on the flexural behaviour of
recycled aggregate concrete beams. Structures 2021, 29, 129–146. [CrossRef]
9. Sharma, A.; Reddy, G.R.; Varshney, L.; Bharathkumar, H.; Vaze, K.K.; Ghosh, A.K.; Kushwaha, H.S.; Krishnamoorthy, T.S.
Experimental investigations on mechanical and radiation shielding properties of hybrid lead–steel fiber reinforced concrete. Nucl.
Eng. Des. 2009, 239, 1180–1185. [CrossRef]
10. Bošnjak, J.; Sharma, A.; Grauf, K. Mechanical Properties of Concrete with Steel and Polypropylene Fibres at Elevated Temperatures.
Fibers 2019, 7, 9. [CrossRef]
11. Zhang, J.; Wang, Q.; Wang, Z. Properties of Polyvinyl Alcohol-Steel Hybrid Fiber-Reinforced Composite with High-Strength
Cement Matrix. J. Mater. Civ. Eng. 2017, 29, 04017026. [CrossRef]
12. Padmarajaiah, S.K.; Ramaswamy, A. Flexural strength predictions of steel fiber reinforced high-strength concrete in fully/partially
prestressed beam specimens. Cement Concrete Compos. 2004, 26, 275–290. [CrossRef]
13. Yoo, D.-Y.; Lee, J.-Y.; Shin, H.-O.; Yang, J.-M.; Yoon, Y.-S. Effects of blast furnace slag and steel fiber on the impact resistance of
railway prestressed concrete sleepers. Cement Concrete Compos. 2019, 99, 151–164. [CrossRef]
Fibers 2022, 10, 26 25 of 26
14. Vakili, S.E.; Homami, P.; Esfahani, M.R. Effect of fibers and hybrid fibers on the shear strength of lightweight concrete beams
reinforced with GFRP bars. Structures 2019, 20, 290–297. [CrossRef]
15. Patil, G.M.; Suriya Prakash, S. Effect of Macrosynthetic and Hybrid Fibers on the Behavior of Square Concrete Columns Reinforced
with GFRP Rebars under Axial Compression. J. Compos. Constr. 2021, 25, 04021053. [CrossRef]
16. Bhosale, A.; Rasheed, M.A.; Prakash, S.S.; Raju, G. A study on the efficiency of steel vs. synthetic vs. hybrid fibers on fracture
behavior of concrete in flexure using acoustic emission. Constr. Build. Mater. 2019, 199, 256–268. [CrossRef]
17. Curosu, I.; Liebscher, M.; Mechtcherine, V.; Bellmann, C.; Michel, S. Tensile behavior of high-strength strain-hardening cement-
based composites (HS-SHCC) made with high-performance polyethylene, aramid and PBO fibers. Cement Concrete Res. 2017, 98,
71–81. [CrossRef]
18. Bhowmik, S.; Ray, S. An experimental approach for characterization of fracture process zone in concrete. Eng. Fract. Mech. 2019,
211, 401–419. [CrossRef]
19. Das, S.; Aguayo, M.; Sant, G.; Mobasher, B.; Neithalath, N. Fracture process zone and tensile behavior of blended binders
containing limestone powder. Cement Concrete Res. 2015, 73, 51–62. [CrossRef]
20. Abadel, A.; Abbas, H.; Almusallam, T.; Al-Salloum, Y.; Siddiqui, N. Mechanical properties of hybrid fibre-reinforced concrete—
Analytical modelling and experimental behaviour. Mag. Concr. Res. 2016, 68, 823–843. [CrossRef]
21. Sivakumar, A.; Santhanam, M. Mechanical properties of high strength concrete reinforced with metallic and non-metallic fibres.
Cement Concrete Compos. 2007, 29, 603–608. [CrossRef]
22. Shao, Y.; Billington, S.L. Impact of UHPC Tensile Behavior on Steel Reinforced UHPC Flexural Behavior. J. Struct. Eng. 2022,
148, 04021244. [CrossRef]
23. Witchukreangkrai, E.; Mutsuyoshi, H.; Takag, M.; De Silva, S. Evaluation of Shear Crack Width in Partially Prestressed Concrete
Members. Proc. JCI 2006, 28, 823–828.
24. Joshi, S.S.; Thammishetti, N.; Prakash, S.S. Efficiency of steel and macro-synthetic structural fibers on the flexure-shear behaviour
of prestressed concrete beams. Eng. Struct. 2018, 171, 47–55. [CrossRef]
25. Sagi, M.S.V.; Lakavath, C.; Prakash, S.S.; Sharma, A. Experimental Study on Evaluation of Replacing Minimum Web Reinforcement
with Discrete Fibers in RC Deep Beams. Fibers 2021, 9, 73. [CrossRef]
26. Zarate Garnica, G. Analysis of Shear Transfer Mechanisms in Concrete Members without Shear Reinforcement Based on Kinematic
Measurements; TU Delft: Delft, The Netherlands, 2018.
27. Gali, S.; Subramaniam, K.V.L. Shear Behavior of Slender and Non-Slender Steel Fiber-Reinforced Concrete Beams. ACI Struct. J.
2019, 116, 149–158. [CrossRef]
28. Torres, J.A.; Lantsoght, E.O. Influence of Fiber Content on Shear Capacity of Steel Fiber-Reinforced Concrete Beams. Fibers 2019,
7, 102. [CrossRef]
29. Abambres, M.; Lantsoght, E.O. ANN-Based Shear Capacity of Steel Fiber-Reinforced Concrete Beams without Stirrups. Fibers
2019, 7, 88. [CrossRef]
30. Lantsoght, E.O.L. Database of Shear Experiments on Steel Fiber Reinforced Concrete Beams without Stirrups. Materials 2019,
12, 917. [CrossRef]
31. Guerini, V.; Conforti, A.; Plizzari, G.; Kawashima, S. Influence of Steel and Macro-Synthetic Fibers on Concrete Properties. Fibers
2018, 6, 47. [CrossRef]
32. Lakavath, C.; Joshi, S.S.; Prakash, S.S. Investigation of the effect of steel fibers on the shear crack-opening and crack-slip behavior
of prestressed concrete beams using digital image correlation. Eng. Struct. 2019, 193, 28–42. [CrossRef]
33. Tan, K.H.; Murugappan, K.; Paramasivam, P. Shear Behavior of Steel Fiber Reinforced Concrete Beams. ACI Struct. J. 1993, 90,
176–184. [CrossRef]
34. Lakavath, C.; Prakash, S.S.; Dirar, S. Experimental and numerical studies on shear behaviour of macro-synthetic fibre reinforced
prestressed concrete beams. Constr. Build. Mater. 2021, 291, 123313. [CrossRef]
35. JCI-S-002-2003; Method of Test for Load-Displacement Curve of Fiber Reinforced Concrete by Use of Notched Beam. Japan
Concrete Institute: Tokyo, Japan, 2003; pp. 3–8. Available online: https://www.jci-net.or.jp/j/jci/study/jci_standard/JCI-S-001-
2003-e.pdf (accessed on 13 January 2019).
36. Test Method for Metallic Fiber Concrete—Measuring the Flexural Tensile Strength (Limit of Proportionality (LOP), Residual); EN
14651:2005+A1:2007; British Standards Institution: London, UK, 2008.
37. Gustafsson, P.J.; Hillerborg, A. Sensitivity in Shear Strength of Longitudinally Reinforced Concrete Beams to Fracture Energy of
Concrete. ACI Struct. J. 1988, 85, 286–294.
38. Foster, S.J.; Agarwal, A.; Amin, A. Design of steel fiber reinforced concrete beams for shear using inverse analysis for determination
of residual tensile strength. Struct. Concr. 2018, 19, 129–140. [CrossRef]
39. Sahoo, S.; Lakavath, C.; Prakash, S.S. Experimental and Analytical Studies on Fracture Behavior of Fiber-Reinforced Structural
Lightweight Aggregate Concrete. J. Mater. Civ. Eng. 2021, 33, 04021074. [CrossRef]
40. Rilem Tc 162-Tdf: Test and design methods for steel fibre reinforced concrete. Mater. Struct. 2003, 36, 560–567. [CrossRef]
41. JCI-S-001-2003; Method of Test for Fracture Energy of Concrete by Use of Notched Beam. Japan Concrete Institute: Tokyo, Japan,
2003; Volume 2, pp. 1–14.
42. Enfedaque, A.; Alberti, M.G.; Galvez, J. Influence of Fiber Distribution and Orientation in the Fracture Behavior of Polyolefin
Fiber-Reinforced Concrete. Materials 2019, 12, 220. [CrossRef]
Fibers 2022, 10, 26 26 of 26
43. Kang, S.-T.; Kim, J.-K. The relation between fiber orientation and tensile behavior in an Ultra High Performance Fiber Reinforced
Cementitious Composites (UHPFRCC). Cement Concrete Res. 2011, 41, 1001–1014. [CrossRef]
44. Laranjeira, F.; Aguado, A.; Molins, C.; Grünewald, S.; Walraven, J.; Cavalaro, S. Framework to predict the orientation of fibers in
FRC: A novel philosophy. Cement Concrete Res. 2012, 42, 752–768. [CrossRef]
45. Abrishambaf, A.; Pimentel, M.; Nunes, S. Influence of fibre orientation on the tensile behaviour of ultra-high performance fibre
reinforced cementitious composites. Cement Concrete Res. 2017, 97, 28–40. [CrossRef]
46. Yang, T.; Dashlejeh, A.A.; Arabzadeh, A.; Hizaji, R. New model for prediction of ultimate load of prestressed RC deep beams.
Structures 2020, 23, 509–517. [CrossRef]
47. Ramirez-Garcia, A.T.; Floyd, R.W.; Hale, W.M.; Martí-Vargas, J. Effect of concrete compressive strength on transfer length.
Structures 2016, 5, 131–140. [CrossRef]
48. Kani, G.N.J. Basic Facts Concerning Shear Failure. ACI J. Proc. 1966, 63, 675–692. [CrossRef]
49. Juárez, C.; Valdez-Tamez, P.L.; Durán, A.; Sobolev, K. The diagonal tension behavior of fiber reinforced concrete beams. Cement
Concrete Compos. 2007, 29, 402–408. [CrossRef]
50. Amin, A.; Foster, S. Shear strength of steel fibre reinforced concrete beams with stirrups. Eng. Struct. 2016, 111, 323–332.
[CrossRef]
51. Perceka, W.; Liao, W.-C.; Wu, Y.-F. Shear Strength Prediction Equations and Experimental Study of High Strength Steel Fiber-
Reinforced Concrete Beams with Different Shear Span-to-Depth Ratios. Appl. Sci. 2019, 9, 4790. [CrossRef]
52. Hwang, J.-H.; Lee, D.H.; Ju, H.; Kim, K.S.; Kang, T.H.-K.; Pan, Z. Shear Deformation of Steel Fiber-Reinforced Prestressed Concrete
Beams. Int. J. Concr. Struct. Mater. 2016, 10, 53–63. [CrossRef]
53. Tadepalli, P.R.; Hoffman, N.; Hsu, T.T.; Mo, Y.L. Steel Fiber Replacement of Mild Steel in Prestressed Concrete Beams (No. FHWA/TX-
09/0-5255-2); University of Houston: Houston, TX, USA, 2011.
54. Vecchio, F.J.; Collins, M.P. Modified Compression-Field Theory for Reinforced Concrete Elements Subjected To Shear. J. Am. Concr.
Inst. 1986, 83, 219–231. [CrossRef]
55. Khan, M.A.; Ahmed, F.S. Effect of Web Reinforcement On Ultimate Strength Of Reinforced Concrete Deep Beams. ACI Struct. J.
1997, 94, 572–581.
56. Smith, K.N.; Vantsiotis, A.S. Shear Strength of Deep Beams. J. Am. Concr. Inst. 1982, 79, 201–213. [CrossRef]
57. Adebar, P.; Van Leeuwen, J. Side-Face Reinforcement for Flexural and Diagonal Cracking in Large Concrete Beams. ACI Struct. J.
1999, 96, 693–704. [CrossRef]
58. Susanto, T.; Ma, W.; Fang, W. Shear strength of high-strength concrete deep beams under Fatigue Loading. ACI Struct. J. 2000, 97,
572–580.
59. Sahoo, D.R.; Bhagat, S.; Reddy, T.C.V. Experimental study on shear-span to effective-depth ratio of steel fiber reinforced concrete
T-beams. Mater. Struct. Constr. 2016, 49, 3815–3830. [CrossRef]
60. Devalapura, R.K.; Tadros, M.K. Stress-Strain Modeling of 270 ksi Low-Relaxation Prestressing Strands. PCI J. 1992, 37, 100–106.
[CrossRef]
61. Model Code 2010-First Complete Draft-Volume 2: Model Code; Fédération Internationale du Béton (fib): Lausanne, Switzerland, 2010;
Volume 56, ISBN 964-7445-88-1.
62. Alberti, M.; Enfedaque, A.; Gálvez, J. On the prediction of the orientation factor and fibre distribution of steel and macro-synthetic
fibres for fibre-reinforced concrete. Cement Concrete Compos. 2017, 77, 29–48. [CrossRef]
63. Mudadu, A.; Tiberti, G.; Germano, F.; Plizzari, G.A.; Morbi, A. The effect of fiber orientation on the post-cracking behavior of
steel fiber reinforced concrete under bending and uniaxial tensile tests. Cement Concrete Compos. 2018, 93, 274–288. [CrossRef]
64. Reddy, K.C.; Subramaniam, K. Analysis for multi-linear stress-crack opening cohesive relationship: Application to macro-synthetic
fiber reinforced concrete. Eng. Fract. Mech. 2017, 169, 128–145. [CrossRef]
65. Stephen, S.J.; Raphael, B.; Gettu, R.; Jose, S. Determination of the tensile constitutive relations of fiber reinforced concrete using
inverse analysis. Constr. Build. Mater. 2019, 195, 405–414. [CrossRef]
66. Kaufmann, W.; Amin, A.; Beck, A.; Lee, M. Shear transfer across cracks in steel fibre reinforced concrete. Eng. Struct. 2019, 186,
508–524. [CrossRef]
67. El-Helou, R.G.; Graybeal, B.A. Shear Behavior of Ultrahigh-Performance Concrete Pretensioned Bridge Girders. J. Struct. Eng.
2022, 148, 04022017. [CrossRef]