Cable Sizing Calculation

This document summarizes the electrical load calculations for a 3-phase power system supplying 1000 kW of total load over 200 meters using a single 1000mm^2 cable. It determines that the derated current capacity of the cable is 1411A, which is within the current rating of 1550A set by the inverter, and concludes that a 1000mm^2 3-core XLPE/PVC cable is suitable to supply the 1000kW load over the given distance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
183 views3 pages

Cable Sizing Calculation

This document summarizes the electrical load calculations for a 3-phase power system supplying 1000 kW of total load over 200 meters using a single 1000mm^2 cable. It determines that the derated current capacity of the cable is 1411A, which is within the current rating of 1550A set by the inverter, and concludes that a 1000mm^2 3-core XLPE/PVC cable is suitable to supply the 1000kW load over the given distance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

PHASE : 3ϕ CASE : PHASE : 3

VOLTAGE DROP (%) : 5% TOTAL LOAD (kW) : 1000


VOLTAGE (V) : 415 V CONDITION : OPEN AREA
NO. OF CABLE : 1
POWER CABLE LENGTH (m) : 200
TOTAL LOAD (kW) : 1000 kW CURRENT RATING (A) : 1550
POWER FACTOR (pf) : 0.8
CONSUMED LOAD (KVA) : 1250 KVA
LOAD CURRENT (A) : 1550 A *NOTE THAT THIS CURRENT IS LIMITED AS THE INVERTER OUTPUT HAS BE
CABLE RUN (m) : 200 m

DERATING FACTOR, k : K1 0.91


DERATING CURRENT (A) : 1411 A

CONCLUSION
1) TYPE OF CABLE : XLPE/PVC
2) CABLE SIZE : 1 x 3C 1000mm sq + E
3) FOR 1000mm sq XLPE/PVC, THE CURRENT CARRYING CAPACITY IS 1436 A.
INVERTER OUTPUT HAS BEEN SET.