EB8000 User Manual
EB8000 User Manual
1
EasyBuilder8000 User’s Manual
2
EasyBuilder8000 User’s Manual
3
EasyBuilder8000 User’s Manual
17.1 Updating Recipe Data with Ethernet or USB cable ............................................ 418
17.2 Updating Recipe Data with SD Card or USB Flash Drive................................... 420
17.3 Transferring Recipe Data ................................................................................... 421
17.4 Saving Recipe Data Automatically ..................................................................... 421
4
EasyBuilder8000 User’s Manual
5
EasyBuilder8000 User’s Manual
6
EasyBuilder8000 User’s Manual
7
EasyBuilder8000 User’s Manual
8
EasyBuilder8000 User’s Manual
9
EasyBuilder8000 User’s Manual
Software:
Download EasyBuilder Pro configuration software from EasyBuilder Pro CD or visiting
Weintek Labs, Inc.’s website at http://www.weintek.com to obtain all software versions
available (including Simplified Chinese, Traditional Chinese, English, Italian, Korean,
Spanish, and French version) and latest upgraded files.
Operating System:
Windows 2000 / Windows NT / Windows XP / Windows Vista / Windows 7.
10
EasyBuilder8000 User’s Manual
2. Click [Install], users will see the window below, select the language and click [Next]
following the installation instructions.
11
EasyBuilder8000 User’s Manual
3. Users will be asked if they would like to remove the old versions of EasyBuilder Pro.
Please tick those should be removed and click [Next] to continue.
12
EasyBuilder8000 User’s Manual
4. Designate a new folder for EasyBuilder Pro installation or choose the folder
recommended and then click [Next].
5. Users will be enquired to select a start menu folder to save the program’s shortcuts.
Click [Browse] to designate a folder or use the folder recommended then click [Next].
13
EasyBuilder8000 User’s Manual
6. Users will be enquired if there are any additional tasks to be done. For example: [Create
a desktop icon]. Tick it if needed then click [Next] to continue.
7. At this moment all the settings are done. Please check if they are all correct. If any
changes need to be made, click [Back] or click [Install] to start installing.
14
EasyBuilder8000 User’s Manual
8. Installation processing.
15
EasyBuilder8000 User’s Manual
10. Start EasyBuilder Pro project from menu [Start] / [All Programs] / [EB8000].
Item Description
When using AB Tags, this tool can be applied to edit Tags
structure
EasyBuilder Pro editing software
Conversion tool for Data Sampling and Event Log
Communication monitoring tool via online simulation
Remote printer server
Tool for executing simulation without installing EasyBuilder
Pro
EasyBuilder Pro project management
Tool for setting format of Recipe data. Users can open Recipe
data or data in External Memory here.
Notes for EasyBuilder Pro version and latest information
To uninstall EasyBuilder Pro
16
EasyBuilder8000 User’s Manual
After installing EB8000 software, users will see a [Project Manager] shortcut, double click
it, users will see a window as shown below.
The Project Manager is a software shell for launching several utilities. Some functions are
duplicated in the EasyBuilder8000 screen-editing program. Project Manager can operate
as a stand-alone program.
17
EasyBuilder8000 User’s Manual
Settings
When operating MT8000/MT6000 HMI by Ethernet or USB cable, users need to designate
the correct IP address and password in HMI. Press [Settings], [Reset and Download]
functions share a set of password while [Upload] function uses another set.
The password provides protection against unauthorized access to the HMI. Be sure to
record any password change, otherwise, while resetting password to default, the project
and data in HMI will be completely erased.
Reboot HMI
There are certain situations that the HMI should reboot, for example, when updating the
files in it. Users don’t need to cut power while rebooting. After rebooting, everything returns
to the conditions of startup.
18
EasyBuilder8000 User’s Manual
19
EasyBuilder8000 User’s Manual
2.2 Utility
Item Description
EasyBuilder8000 To launch the EasyBuilder8000 screen editor.
Easy Converter Conversion tool for Data Sampling and Event
Log.
Easy Printer Remote printer server.
EasyAddressViewer Review the register range of device types for
each PLC supported.
EasyDiagnoser Communication monitoring tool via online
simulation.
Recipe / Extend Provide file format conversion and data editing
Memory Editor function for Recipe/Extend Memory.
Build Download Data The project and data can also be downloaded to
for CF Card/USB Disk the HMI by CF card or USB memory stick. This
function is to build this kind of download data as
shown below.
20
EasyBuilder8000 User’s Manual
Setting Description
Insert CF card or USB stick to PC and press
[Browse…] to assign the file path (or
Select the folder to save
directory name) and then press [Build]. The
download data
whole contents of the source files will be
downloaded to USB stick or CF card
Project Press [Browse…] to assign the desired
Recipe (RW) specific files for download data.
Recipe A (RW_A)
Data log
Note: The path of download data should avoid designating root directory of PC. For
example, “c:\”, also, directory name such as “f:\\” is illegal and should be written as “f:\”.
Take downloading data to the folder named “123” (K:\123) in USB stick for example.
When USB stick (project or recipe included) is inserted to the HMI, a pop-up [Download /
Upload] dialog will appear after few seconds. Please select [Download] and input
Download Password. Check [Download project files] and [Download history files] in
[Download Settings] dialog, and then press [OK]. After that, [Pick a Directory] dialog
will appear. Please select directory: usbdisk/device-0/123 and then press [OK]. Project
will be automatically updated.
Note: Even if users only download historical files, it is still necessary to reboot HMI
manually.
21
EasyBuilder8000 User’s Manual
2.3 Transfer
2.3.1 Download
Download source files to HMI through Ethernet or USB cable. Press [Download] and the
dialog displays as below:
Setting Description
Check this to update all of the kernel
programs of HMI. It is necessary when
Firmware
the latest EB8000 version is
downloaded the first time.
Project To assign the desired specific path for
RW file downloading.
RW_A
Data log
22
EasyBuilder8000 User’s Manual
2.3.2 Upload
Upload files from HMI to PC by Ethernet or USB cable and the dialog shows as below:
Users have to assign the desired path for file storage before uploading.
23
EasyBuilder8000 User’s Manual
Setting Description
Project To assign the desired specific path for
RW file uploading.
RW A
Data log
Event log
Extend Memory
24
EasyBuilder8000 User’s Manual
2.4 Simulation
There are two types of simulations: On -line simulation & Off-line simulation.
By virtual device, PC simulates the operations of HMI without connecting with PLC and
HMI. This shortens the time needed greatly even without the HMI in your hand.
While using Off-line simulation, users are allowed not to download the written project file to
HMI, but still see how it is shown and operated on PC. Users don’t need to connect PLC
with PC under this mode. On the contrary, On-line simulation is executed by connecting
PC with PLC and accurately set the communication parameters. When simulating on PC,
if the control target is a local PLC (i.e. the PLC directly connected to PC), there is 10
minutes simulation limit.
Before executing On-line/Off-line Simulation features, please select the source of XOB file.
25
EasyBuilder8000 User’s Manual
a. “Run EasyDiagnoser”
Execute EasyDiagnoser to monitor current communication status.
b. “Screenshot”
Capture and save current screen image as picture file in the screenshot folder
under installation directory.
26
EasyBuilder8000 User’s Manual
2.5 Pass-Through
The pass-through function allows the PC application to connect PLC via HMI. In this
function, the HMI acts as a converter.
Pass-through provides two types of modes: Ethernet and COM port. Click [Pass-through]
button on Project Manager to start the settings.
2.5.1 Ethernet
27
EasyBuilder8000 User’s Manual
28
EasyBuilder8000 User’s Manual
29
EasyBuilder8000 User’s Manual
In this Chapter, we will take Mitsubishi PLC as an example to illustrate how to create and
compile a new EB8000 project, to simulate it on PC and to download the project to HMI.
First of all, click [New] icon on the toolbar to create a new project.
Under [Device] Tab, click [New…] button to correctly set up the [Device Properties] for
communicating with the PLC.
30
EasyBuilder8000 User’s Manual
31
EasyBuilder8000 User’s Manual
Now, if users would like to add a new object, such as [Toggle Switch], click the icon on
the tool bar.
A [New Toggle Switch Object] dialog will be shown as below. Correctly set the
parameters of the object, click [OK] and place the object wherever users like in the
window.
32
EasyBuilder8000 User’s Manual
33
EasyBuilder8000 User’s Manual
In the menu, select [File] then select [Save], file will be saved as .mtp file. After file is
saved, select [Tools] then select [Compile] to compile the project and check if the project
can run correctly. A .xob file will be obtained after correctly compiling. A .xob file is needed
while downloading to HMI.
Users are allowed to select the languages needed for the project by clicking
[Language 1 to 8].
34
EasyBuilder8000 User’s Manual
There are two types of simulations: On -line simulation & Off-line simulation.
While using Off-line simulation, users don’t need to connect PLC with PC but still see how
PLC is operated via a virtual device. On the contrary, On-line simulation is executed by
connecting PC with PLC and accurately set the communication parameters.
Note: When doing On-line simulation on PC, if the target is a local PLC (i.e. the PLC
directly connected to PC), there is a 10-minutes simulation limit.
35
EasyBuilder8000 User’s Manual
36
EasyBuilder8000 User’s Manual
In the menu, select [Tool] then select [download] to download the project file to HMI.
Before downloading, be sure to check if all the settings are correct.
Setting Description
HMI IP Assign the IP address of HMI
Password Input the password
Firmware Check [Firmware] to update all of the kernel
programs of HMI.
37
EasyBuilder8000 User’s Manual
1. Firstly, please go to [Option] / [Function Properties] then tick [Automatic save and
compile when download and simulate].
38
EasyBuilder8000 User’s Manual
Another way to download project to HMI is to set a HMI name. Before using this function,
please input the HMI Name in the [System settings] window in HMI as shown below.
After setting the HMI Name, please click [Name] in the [Download] window on PC as
below,
39
EasyBuilder8000 User’s Manual
Setting Description
HMI Name Input the HMI name for downloading project
Search Input the HMI name to search the designated HMI
Search all Click to search the HMI shares the same network
40
EasyBuilder8000 User’s Manual
41
EasyBuilder8000 User’s Manual
Support devices with USB interface, such as mouse, keyboard, USB stick, printer…etc.
Download/ Upload project via CF Card or SD Card, including Recipe transfer, Event Log,
Data Log…etc.
COM ports, RS-232, RS485-2W/4W, can be connected to PLC or other peripheral devices.
Here we view RS-422 the same as RS-485 (4 wire). Please refer to the “PLC connection
42
EasyBuilder8000 User’s Manual
guide” to make sure that PLC and HMI are correctly connected. Meanwhile, please make
sure all DIP switches at the back of HMI are pulled down (means off, the default value).
Each HMI is equipped with a set of reset button and DIP switch. When users use DIP
switch to change modes, corresponding functions will be triggered.
If system password is lost or forgotten, users can set DIP Switch 1 to “ON” and the rest
remain “OFF”, then reboot HMI.
43
EasyBuilder8000 User’s Manual
HMI will switch to touch screen calibration mode. After calibration, the pop-up window
appears as shown below. Users will be inquired if they would like to restore the system
password to the default.
When [YES] is chosen, another pop-up dialog appears as below. The system will ask
users to type [yes] to confirm to restore system password to default. Then click [OK].
(The default password is 111111. However, other passwords, including download and
upload password, have to be reset.)
The illustration above shows the steps to restore factory settings of T and i Series HMI. For
X Series, users will need a connected USB keyboard, and press any key (or space key)
right when the first image displayed as HMI power ON to enter the menu. Select "Factory
Mode", the window mentioned will pop up when system displays project. In case users
may miss the very first image shown, to press space key continuously since HMI power
ON will ensure entering the system setting window.
Note: The project and data in the HMI will all be removed once it is reset.
44
EasyBuilder8000 User’s Manual
After rebooting HMI, users can set the system with System Toolbar at the bottom of the
screen. Normally, this bar is hidden automatically. Only by touching the target at the
right-bottom corner of screen will the System Toolbar pops up.
45
EasyBuilder8000 User’s Manual
46
EasyBuilder8000 User’s Manual
Network: Display Network information, including HMI IP address and related information.
47
EasyBuilder8000 User’s Manual
a. Network
A project can be downloaded to HMI via Ethernet. The IP address of target (HMI) must be
correctly set. If [Auto Get IP Address] is selected, IP address will be automatically
assigned from local DHCP network. If [IP address get from below] is selected, IP
address and other network information have to be inputted by the user.
48
EasyBuilder8000 User’s Manual
b. Time/Date
This page is for setting HMI local time and date.
49
EasyBuilder8000 User’s Manual
c. Security
The default of the password is 111111. EB8000 provides strict security for the HMI.
[Local Password]
Password for entering the system
[Upload Password]
Password for uploading the project
[Download Password]
Password for downloading the project
Password confirmation:
50
EasyBuilder8000 User’s Manual
d. History
For clearing the history data in HMI: [Recipe], [Eventlog] and [Datalog].
e. Miscellaneous
Use the rolling bottom on the screen to adjust the brightness of LCD.
51
EasyBuilder8000 User’s Manual
f. Upgrade firmware
For users to upgrade firmware or to enable portrait mode. (Supported only by I series)
52
EasyBuilder8000 User’s Manual
g. CF card Status
When new external device is detected, this function will be enabled.
h. VNC server
Allows users to monitor and control the remote HMI through Ethernet.
53
EasyBuilder8000 User’s Manual
After installing Java IE, enter HMI IP: (The following takes http://192.168.1.28 as an
example)
54
EasyBuilder8000 User’s Manual
55
EasyBuilder8000 User’s Manual
Note:
(1) One HMI allows only one user to log in VNC server at one time.
(2) If users leave VNC server unused for one hour, HMI system will log out automatically.
i. HMI name
Set the HMI name to download/upload a project.
56
EasyBuilder8000 User’s Manual
In this mode when users power on MT8000 series, the screen will display a “+” sign
upper-left of the screen. Use a stylus or finger to touch the center of the “+” until it moves.
The “+” moves to upper-left, upper-right, lower -left, lower-right and center of screen.
When all five “+” are touched, the “+” will disappear. The Touch Screen parameter will be
stored at Flash Rom.
Note: Only X series HMI are with this shortcut of touch screen calibration mode in system
toolbar. For other series, please use DIP switch 1 to adjust.
57
EasyBuilder8000 User’s Manual
Several functions can be selected at this time and some of them need password
confirmation as illustrated below:
After the password is confirmed, directory names of the SD card…etc will be displayed in
[Pick a Directory] window as below (pccard -> CF card (SD card); usbdisk -> USB
device)
58
EasyBuilder8000 User’s Manual
Select the download path for project and click [OK] for downloading.
Note: Users have to create download data from [Build Download Data for CF/USB Disk]
in Project Manager.
MT8000
Project storage
History
When users download the history data, this directory will be created.
59
EasyBuilder8000 User’s Manual
Users have to select the top layer of the directory of the target file when downloading.
In other words, take the structure above as an example; download must be selected
instead of choosing mt8000 or history.
Take the illustration below as another example: If USB disk only stores mt8000 directory
but don’t include history data. In this case, users must choose disk_a_1 (the top layer of
target file that contains file of mt8000) to correctly download the file.
60
EasyBuilder8000 User’s Manual
Enter EB8000, select menu [Edit] / [System Parameters…] and the [System Parameter
Settings] dialog appears:
System Parameter Settings are divided into eight parts: [Device], [Model], [General],
[System Setting], [Security], [Font], [Extended Memory], and [Printer/Backup
Server].
These will be introduced respectively in this chapter.
61
EasyBuilder8000 User’s Manual
5.1 Device
Parameters in [Device] tab determine all of the attributes of each device controlled by the
HMI they are connected with. The device can be a PLC, a remote HMI, or a PC.
After opening a new *.mtp file in EB8000, a default device: “Local HMI” is shown in the
[Device List]. This “Local HMI” is used to identify current HMI, which means, every *.mtp
file must at least contains one “Local HMI” in [Device List].
Select [Settings] under the device list, A dialogue [Device Properties] will be shown as
below. From this we know that the attribute of “Local HMI” is a “HMI” and the location is
“Local”.
62
EasyBuilder8000 User’s Manual
The so-called “local PLC” means a PLC which is connected to the local HMI directly. To
control a local PLC, users need to add this type of device first. Click [New…] under the
Device list and the [Device Properties] dialog appears. Please correctly fill in all of the
properties required.
Setting Description
Name The name of the device set by user.
HMI or PLC To confirm whether this connected device is a HMI or PLC. It’s [PLC]
in this example.
63
EasyBuilder8000 User’s Manual
[Timeout]
If the communication between PLC and HMI is disconnected over the
set time limit in [Timeout] parameter, a pop out window No. 5 will be
shown in HMI as an alert saying “PLC No Response”.
64
EasyBuilder8000 User’s Manual
In addition, station no. can be set in the read address of PLC directly.
Take address 1#20 as an example.
“1” means PLC station no, and has to be named from 0 to 255.
“20” means PLC address, the “#” sign is used to separate station no.
and address.
Default station When setting PLC properties, station no. variables can be selected
no. use station and used as [PLC default station no.]. LW10000~LW10015 can be
no. variable used to set station no. variables.
When using this function, if the station no. is not specified for PLC
65
EasyBuilder8000 User’s Manual
c. PLC address is set to “111”, since PLC station no. is not specified,
and the default station no. is using var3, the PLC station no. is
decided by var3 (LW-10003).
Use broadcast This is for setting the station no. of broadcast command. Command
command for the users of this set station no. will be seen as broadcast
command. For example, if the broadcast station number is set as
255, HMI with an address such as 255#200, will send this command
to all the PLC connected to it, but will ignore the replies of PLC after
receiving this command. (This only works on Modbus).
For example, the interval value is set as “5” and users would like to
read out 1 word from LW3 and 2 words from LW6 respectively.
(Means to read from LW6 to LW7). Since the interval of addresses
between LW3 and LW6 is less than 5, these two commands can be
combined to one. The contents of combination therefore become 5
consecutive words from LW3 (read from LW3~LW7).
Note: Maximum command combination data size must be less than
[Max. read-command size].
Max. The Max. data size to be read out from device at one time. Unit: word
66
EasyBuilder8000 User’s Manual
read-command
size (words)
Max. The Max. data size to be written to device at one time. Unit: word.
write-command
size (words)
After all settings are completed, a new device named “Local PLC 1” is added to the
[Device list].
67
EasyBuilder8000 User’s Manual
The so -called “remote PLC” means a PLC connected to a remote HMI. To control a
remote PLC, users need to add this type of device. Click [New…] under [Device list] and
the [Device Properties] dialog appears. Users need to set all the required properties
correctly.
Setting Description
68
EasyBuilder8000 User’s Manual
After all settings are completed, a new device named “Remote PLC” is added to the
[Device list].
69
EasyBuilder8000 User’s Manual
The so-called “remote HMI” means through network, this HMI is controlled by a local HMI
or a PC running on-line simulation. To control a remote HMI, users need to add this type of
device. Click [New…] under [Device list] and the [Device Properties] dialog appears.
Users need to set all the required properties correctly.
Setting Description
HMI or PLC This is to confirm whether this device is a HMI or PLC.
It is [HMI] in this case.
Location Users can select [Local] or [Remote]. Select [Remote] in this case
and set the [IP address] and [Port no.] of the remote HMI. Click
[Settings…] of [Location] to set these, the dialogue is shown below.
70
EasyBuilder8000 User’s Manual
After all settings are completed, a new device named “Remote HMI” is added to the
[Device list].
71
EasyBuilder8000 User’s Manual
5.2 Model
Parameters in [Model] tab determine the HMI model, [Timer] and [Printer] settings.
Setting Description
HMI model Select current HMI model as shown below.
When changing HMI model and press [OK], users will be inquired if
72
EasyBuilder8000 User’s Manual
HMI station Set the [HMI station no.] used by current HMI. If no specific request is
no. to be made, just use the default number.
Port no. Set the [Port no.] used by current HMI. It is used as port no. of
MODBUS server. If no specific request is to be made, just use the
default number.
Timer [Clock source]
To set up the signal for timer object. The time information of timer is
used by [Data Sampling], [Event Log] ….etc. which are objects that
need the time records.
a. [HMI RTC] means the time signal comes from internal clock of the
HMI.
b. [External device] means the time signal comes from external
device. To correctly set source address of time signal is necessary.
Take the illustration below as an example: It indicates the source of
time signal is from “TV” of the “Local PLC”. The source address “TV”
starts from address 0 contains 6 consecutive words and each of them
contains the following information:
73
EasyBuilder8000 User’s Manual
Printer [Type]
Display printers supported. For HP PCL Series, it has to be connected
through USB interface while other printers through COM port. For more
information, please refer to “Chapter 23 Printer Types supported by
MT8000”.
Storage 1. Storage space available for the project and history data is 12MB. By
space adjusting the space of these two parts, users can reach their
74
EasyBuilder8000 User’s Manual
75
EasyBuilder8000 User’s Manual
5.3 General
Setting Description
Fast Setting all the attributes for fast selection button that is designated as
selection window number 3.
button
a. [Attribute]
76
EasyBuilder8000 User’s Manual
Select the position on the screen of HMI where this button appears. If
[Left] is chosen, the button will show up on screen bottom-left; if [Right]
is chosen, the button will show up on screen bottom-right.
Screen a. [Back light saver]
saver If the screen is left untouched and reaches the time limit set here, back
light will be off. The setting unit is minute. Back light will be on again once
the screen is touched. If [none] is set, the back light will always be on
while using.
b. [Screen saver]
If the screen is left untouched and reaches the time limit set here. The
current screen will automatically switch to a window assigned in [Saver
window no.].The setting unit is minute. If [none] is set, this function is
disabled.
b. [Common window]
77
EasyBuilder8000 User’s Manual
Set the color of caret that appears when inputting in [Numeric Input] and
[Word Input] objects.
d. [Object layout]
e. [RW_A enabled]
Enable or disable recipe data RW_A. Enable this, the objects can then
control the content of RW_A .The size of RW_A is 64K.
Event [Extra no. of events]
The default number of the event in the system is 1000. If users would like
to add more records, the setting value can be modified up to 10000.
Keyboard Users can select to use different types of keyboards for [Numeric Input]
and [Word Input]. Up to 32 keyboards can be added. If users want to
design their own keyboard, a window should be designated for creating
it. Press [add] after creating, and add the window to the list. For more
information, please see “Chapter 12 Key Pad Design and Usage” where
also shows how to fix this keyboard in screen instead of adding it to the
list.
Project User’s project can be restrained and executed on specific HMI (only for i
protection (i series HMI). Please refer to “Chapter 30 Project protection” for more
series only) information.
78
EasyBuilder8000 User’s Manual
Parameters in [System Setting] tab are for setting up some miscellaneous functions of
EasyBuilder.
Some functions are duplicated from system tag, such as [Disable buzzer (LB-9019)], [Hide
system setting bar (LB-9020)], [Hide mouse cursor (LB-9018)], [Disable upload function
(LB-9033)], and [Prohibit remote HMI connecting this machine (LB-9044)]. It means that
79
EasyBuilder8000 User’s Manual
user can also operate these functions via system tag. To select a system tag, users can
tick [system tag] of the [address] while adding new object. To check all the system tags,
users can visit [Library] in EB8000, select [Tag] then [System].
Set the language to use when start up HMI after redownloading the project.
[Auto logout]
If HMI is left unused for longer than the time set here, HMI will logout automatically.
When using this function and fail to communicate with PLC, this icon will be shown in the
lower right corner of the object as shown:
When using this function and fail to communicate with PLC, this icon will be shown in the
lower right corner of the object as shown:
[VNC Server]
80
EasyBuilder8000 User’s Manual
If users check [Disable LW/RW remote-write] and set the protect range in [LW/RW
range], values of this protected range can’t be adjusted via remote HMI.
Through this technology, users can easily access to any MT8000i/X connected to the
internet and operate them on PC just like holding touch screen in hand.
Unlike most server used in HMI, Easy Access don’t need to transmit updated graphic
image but real time data only. This makes transmission really quick and efficient.
For further information, please refer to “EasyAccess”.
81
EasyBuilder8000 User’s Manual
5.5 Security
Parameters in [Security] tab determine the classes accessible for each user to adjust the
objects, and users’ password. The security classes of objects are classified from [A~F],
and [none] for not ticking any class. Up to twelve passwords can be set. Only numeral
setting is acceptable for password and the range is 0~999999999.
According to the security setting, EB8000 will control the classes accessible for each user
to adjust the objects once they input their passwords.
In EB8000, while constructing a project, the security classes of objects are classified from
[A~F], and [None] and can be set as shown below.
If [None] is set, every user can access to adjust this object.
82
EasyBuilder8000 User’s Manual
For example, when the security class of User1 is set as below, only objects with class A, C,
E and “none” can the user adjust. For more information, please see “Chapter 10 Security
of Objects”.
Users can set password to protect the MTP file in [System parameter] / [Security tab].
Users have to input the password set here when they want to edit the MTP file.
Tick [Enable] then click [Setting], and the window is as shown below.
Before editing project, a pop-up window will ask password for access the project.
83
EasyBuilder8000 User’s Manual
MTP files are protected by additional encryption, please follow the steps below:
a. EB8000 V440 or later can open old version EB8000 projects using the password
originally set in old version EB8000.
b. The old version EB8000 can’t open the projects that are built in EB8000 V440 or later
which are protected by password, if necessary, please disable (don’t tick [Enable]) the
password first.
84
EasyBuilder8000 User’s Manual
5.6 Font
Parameters in [Font] tab determine the font of non-ASCII which is used in EB8000.
Users can also test which non-ASCII strings of Windows can be used in EB8000 and add
them to [Fonts for non-ASCII strings] table.
[Line spacing]
Decide the interval between lines in the text.
85
EasyBuilder8000 User’s Manual
86
EasyBuilder8000 User’s Manual
Parameters in [Extended Memory] tab determine the path of the extended memory.
Extended Memory is numbered from EM0 to EM9. Method to use extended memory is
similar to that of other device type (i.e. LW or RW address). Users can simply select from
[Device type] list while adding a new object. Size of each extended memory is up to 2G
word.
87
EasyBuilder8000 User’s Manual
Data in extended memory is stored in [SD card], [USB1], or [USB2] in a form of a file. The
files in extended memory [EM0] ~ [EM9] are entitled as em0.emi~em9.emi. Users can use
RecipeEditor.exe to open the file and edit the data in the extended memory.
Data in extended memory will not be erased when power is cut, which means next time
when user start HMI again, data in extended memory remains just the same before power
off. This is similar to Recipe data (EW, RW_A). What is different is that users can select
where they want to save the data (SD card, USB1 or USB2)
To read data in extended memory from a removed device, the content of data will be
viewed as “0”; if users would like to write data to a removed device, the "PLC no response"
message will appear in HMI.
EB8000 supports "hot swapping" function for SD card and USB devices. Users can insert
or remove the device for extended memory without cutting the power. With this function,
users can update or take data in extended memory.
88
EasyBuilder8000 User’s Manual
Setting Description
Output settings [Orientation]
Set how will words or pictures be printed out, [horizontal] or
[vertical].
[Printer size]
Set to print out in original size or to fit the set printer margins.
[Margin]
Set the top, bottom, right and left margin width.
Communication [IP address]
settings Assign the IP address of a remote printer via network.
89
EasyBuilder8000 User’s Manual
90
EasyBuilder8000 User’s Manual
The basic component of a HMI screen is a Window, This shows its importance. With a
window, all kinds of information like objects, pictures, and words can be shown in HMI
screen. Generally, there’s more than one window in a project, many windows will be
constructed in one project. Users are able to configure 1997 windows or screens
numbered from 3~1999 in EB8000. For how many windows can be used in one project, it
depends on the storage size for windows of HMI. For example, the storage size of MT8000
i series for windows is 16MB, then the size of windows or screens constructed cannot
exceed 16MB. Under this limit users can make most use of it to create as many windows
as possible.
There are 4 types of windows in EB8000 each with different functions and usages.
a. Base Window
b. Common Window
c. Fast Selection Window
d. System Message Window
91
EasyBuilder8000 User’s Manual
Base window should be in the same size as the HMI screen. That is to say, the resolution
of base window and that of HMI should be identical.
The start up screen is a base window and is shown below:
Window no. 4 is the default common window. Objects in this window will be displayed in
other base windows, but it does not include popup window. Therefore, objects in different
windows, whether shared or same, will be placed in common window, for example, the
logo of the product, or a common button. When system is in operation, Clicking [Function
Key] and selecting [Change common window] allow users to change the source of
common window. For example, users can change the common window from window 4 to
window 20.
92
EasyBuilder8000 User’s Manual
Window no. 3 is defined as the Fast Selection Window. This window can coexist with base
window. Generally speaking, it is used to place the frequently-used operation buttons as
the picture below:
When using Fast Selection Window, window no. 3 should be created first, and then users
need to set each function of Fast Selection button. The [Fast Sel] button in the picture
above is the Fast Selection button, which is used to Enable/Disable Fast Selection window
93
EasyBuilder8000 User’s Manual
control. Every setting of the [Fast Selection button] is in [System Parameter Settings].
Please refer to the dialog below.
Apart from Enable/Disable Fast Selection window by Fast Selection button, system
register also provides the following addresses for users to Enable/Disable certain
functions in order to control fast selection window/button. The related registers are listed
below. Please refer to “Chapter 22 system reserved words and bits” for more details.
Window Description
Window no. 5 is the “PLC When the communication between PLC and HMI is
Response” message disconnected, this message window will pop up
window automatically right on the window opened previously.
Window 6 is the “HMI When failing to connect with remote HMI, this message
connection” message window will pop up automatically.
window
Window 7 is the “Password If user wants to control an object without authorization,
Restriction” message this window may pop up as an alert or not depending on
window how this object is set originally.
94
EasyBuilder8000 User’s Manual
Window 8 is the “Storage When HMI built-in memory, USB disk or SD card run out
Space Insufficient” of storage space, this message window will pop up
message window automatically.
The text shown in window no. 5~8 can be adjusted by users to fit what is needed. For
example, text in window no. 5 is “PLC No Response”, users can change it to “HMI and
PLC disconnected!” This works for other windows as well, which makes it easier to read.
Note:
(1) A screen can display 16 pop-up windows simultaneously in maximum including System
Message Window, Direct window and Indirect window.
(2) A window can only be displayed once simultaneously. That is to say, users cannot use
2 Direct (Indirect) windows to open the same window in one base window at the same
time.
(3) Windows 0~9 are for system use only while windows 10~1999 are for users to define.
95
EasyBuilder8000 User’s Manual
The picture below shows the windows information (window tree) in EB8000. This window
is always shown on left side of the editing zone. There are 2 ways to check all types of
windows in EB 8000. If users change [Object List] to [Window Preview], every window
will be shown in pictures. The following section introduces how to create and set these
windows.
96
EasyBuilder8000 User’s Manual
Setting Description
Name The name shown after window is numbered.
The principle is to make it easy to read and be remembered. For
example: “Operate Manually” etc.
97
EasyBuilder8000 User’s Manual
The [Color] of the frame of the window. Users can select a color they like
from the list, or simply click [Custom…] to adjust a self-defined color. If
the Width of the frame is set “0”, then this setting will be ignored.
Background [Color]
The color of the background of the window.
[Pattern]
The pattern of the background of the window. If needed, users can
choose a pattern they like from [pattern style] that pops up after clicking
button of the pattern.
[Pattern color]
The color of the pattern.
[Filled]
Tick to determine if a window is filled with the color and pattern set for the
background
Underlay [Bottom], [Middle], [Top]
window Up to three base windows can be specified as underlay windows for
each base window, from [Bottom] to [Top]. The objects (but not the
backgrounds) in underlay windows are displayed in this order in base
window.
Popup [X], [Y]
window Base window can also be used as pop-up window. Use [X] and [Y] to set
the coordinates indicate where in the screen will this base window pop
98
EasyBuilder8000 User’s Manual
up. The origin of the coordinates is the left-top corner of the screen.
[Monopoly]
If the option is checked, when a base window used as a pop-up window
appears, users are not allowed to operate other windows before this
base window is closed. If a base window is used as a keyboard window,
“Monopoly" is automatically enabled.
Another way to create a window is to select [Window] from menu in EB8000 and then
select [Open Window] to open the dialogue. Please refer to the illustration below.
Window No., Window Name and Size are listed in the [Open Window] dialogue.
Click [New…] and choose window type from [Select Window Style] dialog. Complete all
the settings and click [OK], a new window is created.
99
EasyBuilder8000 User’s Manual
Once the base window is built, its window number sticks with it and can’t be changed. But
the size, color, and name of the window can still be modified.
b. Right click directly in the window without selecting any object and then select [Attribute].
Or, click in EB8000 menu without selecting any object can also open the [Window
Settings] dialogue.
100
EasyBuilder8000 User’s Manual
c. Select [Window] from menu in EB8000 and select [Open Window], a dialogue appears.
Designate a window to modify then choose [Settings] to open the [Window Settings]
dialogue.
To open an existing window, not only double click the window No. from the window tree,
users can also right click the assigned window from the window tree and choose [Open] to
open it.
Similarly, to close or to delete an existing window is same as the procedure above .Please
note that the window to be deleted has to be closed. That is to say, only a closed window
can be deleted.
101
EasyBuilder8000 User’s Manual
“Event log” is used to define the content of an event and the conditions triggering it. In
EB8000, this triggered event, also called “alarm”, and its processing procedure can be
saved to designated places such as HMI memory storage or external memory device. The
saved file is with a name in a format as EL yyyymmdd.evt. In this name, yyyymmdd
records the time that this file is built, and will be set automatically by the system. Take file
name EL_20100524.evt as an example, this shows that this created file records the event
occurred on 24th of May, 2010.
EB8000 also provides the following system address tags to manage the event log:
Address Description
102
EasyBuilder8000 User’s Manual
103
EasyBuilder8000 User’s Manual
With objects like [Alarm Bar], [Alarm Display] and [Event Display], users are able to clearly
understand the life cycle of the whole event from happening, waiting for processing, until
the alarm stops. Before using these objects, the content of an event has to be defined first.
Click the [Alarm (Event Log)] icon, and the dialog appears as below:
104
EasyBuilder8000 User’s Manual
Setting Description
Category EB8000 classifies events. All events are divided into categories 0~255.
[Alarm Bar], [Alarm Display], and [Event Display] can be used to restrain
which category to display.
The [2] of 0[2] in this illustration demonstrates there are two defined events in
category 0.
History Determine the storage device of an event log. However, when users simulate
files the project in PC, the files will be saved under the same event log
subdirectory as EasyBuilder8000.exe.
[Save to HMI memory]
Save the event log data in MT8000 memory.
[Save to SD card]
Save the event log data in SD card.
[Save to USB 1]
Save the event log data in USB disk 1. Numbering rule of USB disk is: the
disk inserted to the USB interface in the first place is numbered 1, next is
numbered 2 and the last is numbered 3. It is not related to the interface
position.
[Save to USB 2]
Save the event log data in USB disk 2.
[Preservation limit]
After choosing the device to save the Event log, users can see the
105
EasyBuilder8000 User’s Manual
[Preservation limit] selection. This setting determines how many days the
data to be preserved.
For example, the preservation time is set two days, which means HMI
memory will keep the data of yesterday and the day before yesterday. Data
that is not built in this period will be deleted automatically to prevent the
storage space from running out.
Print To enable this setting, users have to finish the settings of printer in [system
parameter settings].
There is an Excel icon in the top-right corner of the [Alarm (Event Log) dialog] for users
to edit an Event log through Excel. An editing procedure includes: Edit in Excel, Import
from Excel to Event Log and Export to Excel.
A. Edit in Excel
EB8000 provides a standardized sample of Excel in C:\EB8000\EventLogExample.xls for
users to edit alarm (event) log. The sample includes some dropdown lists for an easier
usage
106
EasyBuilder8000 User’s Manual
Caution:
1. [System tag] and [User-defined tag] can not be set true simultaneously. If both of
them are set true, the system will view System tag to be true and User-defined tag to
be false. If Device type is set as User-defined tag, please set System tag to be false.
2. The format of Color is R: G: B. the values of R, G, and B should be integer from 0 to
255.
3. Click Excel icon to open EventLogExample.xls
107
EasyBuilder8000 User’s Manual
Caution:
1. When user-defined tag is set true in Excel, the system will compare this device type with
the user-defined tag in system. If no suitable tag can be found, the system will set the
user defined tag in event log to be false.
2. Before importing library (label library and sound library), please make sure library
names exist in the system, otherwise the system will simply use the file name of the
imported excel file.
C. Export to Excel
Click [Export excel button] to export data in Event log to excel.
108
EasyBuilder8000 User’s Manual
109
EasyBuilder8000 User’s Manual
[General] tab:
Setting Description
Category The category of an event.
Priority level The priority of an event: Users can define [Low], [Middle], [High], or
[Emergency] according to the importance of the event. When the
number of event log equals to the max number available in the system,
the less important events (lower priority) will be deleted and new events
will be added in. (the default is 1000, please refer to “General” in
“Chapter 5 System Parameters” to set this number)
110
EasyBuilder8000 User’s Manual
Under the condition, system will read values from [Read address] and
compare them with the trigger conditions to decide if an event is to be
triggered. If the trigger condition is set as [==] or [<>], [In tolerance] and
[Out tolerance] need be set while [In tolerance] is used as trigger
condition and [Out tolerance] is used as system’s normal condition.
Example 1:
111
EasyBuilder8000 User’s Manual
will be triggered.
After the event is triggered, only when the value of [Read address] is
greater than 32(=30+2) or less than 28(=30-2) will the system return to
normal condition.
Example 2:
112
EasyBuilder8000 User’s Manual
Setting Description
Text [Content]
The text content of event log shown in [Alarm Bar], [Alarm Display]
and [Event Display]. Please refer to “Chapter 9 Object General
Properties” for more information.
The data of LW address of the triggered event can be included in
the content.
Format: %#d
113
EasyBuilder8000 User’s Manual
%: initial sign
# : LW’s address
d : end sign
Format: $#d
$: initial sign
# : PLC’s address
d : end sign
[Font], [Color]
Users can set Font and Color for each event. The font and color of
an [alarm display] or [event display] object comes from this setting.
As illustration below, these two events use different colors and font
styles.
Write value for When an event item in an [event display] object is touched, the
Event Display value is written to the assigned address. Please refer to “Chapter 13
object Objects” for information about [event display] object.
Sound The warning alarm used when an event is triggered can be
selected.
Click [Sound Library] to choose warning sound, and click [Play] to
114
EasyBuilder8000 User’s Manual
Continuous beep can be set which will only stop when the event is
acknowledged or recovered. (System register [LB-9042] can be set
to acknowledge all alarm events at one time.) The system default
[Beep] sound is used as this continuous beep.
When using continuous beep for Event Log, a delay period can be
set between triggering the alarm and the start of beeping.
found.
Address of Watch User can use the [Syntax] to embed PLC data in the content of an
event log.
About the syntax usage, please refer to below dialog.
115
EasyBuilder8000 User’s Manual
116
EasyBuilder8000 User’s Manual
“Data Sampling” defines how the data is sampled, including sampling time and sampling
address. EB8000 saves the sampled data to the user assigned location.
The directory of saved data: [Storage location]\[filename]\yyyymmdd.dtl
[Storage location] can be HMI, SD (CF) card, USB1 or USB2 which is designated by
users.
[Filename] is usually a name defined by user. This name can’t be used repeatedly by
other sampled data files.
yyyymmdd shows when the file is built and is set by the system automatically.
EB8000 provides the following system registers for data sampling management:
Address Description
LB-9025 delete the earliest data sampling file on HMI memory (set ON)
LB-9026 delete all data sampling files on HMI memory (set ON)
LB-9027 refresh data sampling information on HMI memory (set ON)
LB-9034 save event/data sampling to HMI, USB disk, SD card (set ON)
LB-11949 delete the earliest data sampling file on SD card (set ON)
LB-11950 delete all data sampling files on SD card (set ON)
LB-11951 refresh data sampling information on SD card (set ON)
LB-11952 delete the earliest data sampling file on USB 1 (set ON)
LB-11953 delete all data sampling files on USB 1 (set ON)
LB-11954 refresh data sampling information on USB 1 (set ON)
LB-11955 delete the earliest data sampling file on USB 2 (set ON)
LB-11956 delete all data sampling files on USB 2 (set ON)
LB-11957 refresh data sampling information on USB 2 (set ON)
LW-9063 (16bit) : no. of data sampling files on HMI memory
LW-9064 (32bit) : size of data sampling files on HMI memory
LW-10489 (16bit) : no. of data sampling files on SD card
LW-10490 (32bit) : size of data sampling files on SD card
LW-10492 (16bit) : no. of data sampling files on USB 1
LW-10493 (32bit) : size of data sampling files on USB 1
LW-10495 (16bit) : no. of data sampling files on USB 2
LW-10496 (32bit) : size of data sampling files on USB 2
117
EasyBuilder8000 User’s Manual
118
EasyBuilder8000 User’s Manual
Before using [Trend display] or [History data display] objects to review the content of data
sampling, the method of how the data is sampled has to be defined. Click [Data Sampling]
on the toolbar and then [Data Sampling Object] dialog appears as below.
Setting Description
New Add a new “data sampling” definition.
Delete Delete a specific “data sampling” definition.
Settings Modify a “data sampling” definition.
119
EasyBuilder8000 User’s Manual
Click [New…] and the [Data Sampling Object] setting dialog appears as below:
[Sampling mode]
EB8000 provides two methods of data sampling: [Time-based] and [Trigger-based].
If [Time-based] mode is selected, EB8000 samples the data in a fixed frequency. Users
have to set the [sampling time interval].
If [Trigger-based] mode is selected, users can use the status of specific address to trigger
the data sampling.
120
EasyBuilder8000 User’s Manual
[Mode]
Conditions to trigger the data sampling:
[OFF → ON] This will trigger data sampling when the status of assigned address changes
from OFF to ON.
[ON → OFF] This will trigger data sampling when the status of assigned address changes
from ON to OFF.
[ON←→ OFF] Trigger data sampling when the status of assigned address is changed.
[Read address]
Select a device type to be the source of data sampling.
[Data Record]
[Max. data records]
Max. number of data records that can be saved by one data sampling definition in one day.
If [sampling time interval] is set as 0.1 second then the max number of data records is
86400.
1. If the data source of [trend display] is in [real-time] mode, the earlier record will be
deleted and new record will be added and displayed in the [trend display] object.
2. If the data source of [trend display] is in [historical] mode, the data will still be
sampled.
[Auto stop]
When the number of data sampling equals to [Max. data records], and the [Auto stop]
option is selected, HMI will stop sampling data automatically.
Example:
Condition Set [Max. data records] as Set [Max. data records] as 10
10 without checking [auto. and check [auto. Stop]
Stop]
Trend display – real The data will keep the latest Stop displaying after reaching
time 10 records in the screen 10 data records.
Data sampling Keep recording and delete Stop recording after reaching
the earlier data 10 data records.
[Data Format]
The formats of different data in one data sampling: A data sampling may include more
than one type of records. Data sampling in EB8000 is able to retrieve different types of
121
EasyBuilder8000 User’s Manual
records at the same time. Users can click [Data Format] to open the dialog to define the
content in one data sampling.
Take the following as an example, user defines three types of data: “Index” (16-bit
Unsigned), “Pressure 1” (16-bit Signed) and “Temperature” (32-bit Float) respectively,
which makes data length to be 4 words in total. In this way, EB8000 retrieves a
4-words-lengthed data each time from the assigned address to be the content in one data
sampling.
Caution:
After executing off-line simulation, if users need to change data format, please delete data
log file in C:\EB8000\***\datalog and then run off-line simulation again. The symbol “***”
means the storage location of data files.
[Clear address]
If the status of the assigned address is set ON, the obtained data will be cleared and the
number of data sampling will go back to zero. This won’t affect sampled data that is
already saved in file.
Caution: this function is used for [trend display] in [real-time] mode only.
[Hold address]
If the status of the assigned address is set ON, sampling will be paused until the status of
assigned address returns to OFF.
[History files]
Assign the storage location for data sampling. However, when users execute simulation on
PC, all data will be saved to the same subdirectory of datalog as EasyBuilder 8000.exe.
122
EasyBuilder8000 User’s Manual
[Folder name]
Set the file name of the data sampling. A folder name must be composed entirely of ASCII
characters!!
[Preservation limit]
This setting determines how many days the data to be preserved.
For example, the preservation time is set two days, which means USB 1 will keep the data
of yesterday and the day before yesterday. Data that is not built in this period will be
deleted automatically to prevent the storage space from running out.
If today were July 1st, the USB 1 will keep the data of June 30th and June 29th in the
memory but the data of June 28th will be deleted.
123
EasyBuilder8000 User’s Manual
It is required to designate which PLC to operate while using some objects as shown below.
[PLC name] represents the controlled PLC. In this example there are 2 PLC: “Local HMI”
and “Allen-Brandley DF1.” These listed available PLC devices are sourced from [Device
List] in [System Parameters Settings].
124
EasyBuilder8000 User’s Manual
[PLC name]
This is for selecting device type. Different PLC are with different selections of [device
type].
[Address]
Set the reading and writing address.
[System tag]
Address tag includes “system tag” and “user-defined tag.” Click [Setting…] beside [PLC
name] and tick [system tag]. This allows users to use the preserved addresses by system
for particular purpose.
These address tags are divided into bit or word (LB or LW).
After selecting [System tag] not only will the [Device type] displays the content of the
chosen tag, [Address] will also display the register chosen as shown below.
125
EasyBuilder8000 User’s Manual
The illustration below shows a part of system tags. For further information, please refer
“Chapter 16 Address Tag Library” and “Chapter 22 System Reserved Words and Bits”.
[Index register]
Deciding to use Index register or not, please refer to “Chapter 11 Index Register” for more
information.
126
EasyBuilder8000 User’s Manual
127
EasyBuilder8000 User’s Manual
[Shape Library] and [Picture Library] are used for enhancing the visual effect of an object.
For setting these, please go to [Shape] tab in the dialog for adding new object to set up
[Shape Library] and [Picture Library].
[Shape Library…]
128
EasyBuilder8000 User’s Manual
Users can tick [Use shape] to enable this setting and select the shape from the library.
[Inner]
Tick [Inner] to enable this setting and select a color for inner part of the shape. Click drop
down button to open the [Color] dialogue to choose a color from the list or [customize]
their own color and click [Add to Custom Colors] for system to remember this color.
[Frame]
Tick [Frame] to enable this setting and select a [color] for the frame of the shape. The way
of setting is same as above.
[Interior Pattern]
Click to select the style of the interior pattern of the shape. The color of this pattern can
also be set.
[Pattern Style]
Click [Pattern Style] button to open the dialogue.
129
EasyBuilder8000 User’s Manual
130
EasyBuilder8000 User’s Manual
The illustration above provides information of one of the Shapes in the Shape Library as
follows:
2: Green The number and the name of the shape in the library.
States: 3 The number of the states of the shape. In this case, it shows the
Shape possesses three states.
Frame Indicates that the Shape is set with “frame” only.
The illustration below shows that the Shape is set with “inner” and “frame.”
Note: About all the settings in [Shape Library], please refer to the illustrations in “Chapter
14 Shape Library and Picture Library” for details.
Click [OK] and preview the design of the shape after the setting is completed.
131
EasyBuilder8000 User’s Manual
[Picture Library]
Users can click [Use picture] to enable selecting a picture from the library.
132
EasyBuilder8000 User’s Manual
The illustration above provides information of one of the Pictures in the Picture Library as
follows:
133
EasyBuilder8000 User’s Manual
Note: About all the settings in [Picture Library], please refer to the illustrations in “Chapter
14 Shape Library and Picture Library” for details.
Click [OK] and preview the design of the picture after the setting is completed.
134
EasyBuilder8000 User’s Manual
Go to [Label] tab while adding new object to set the text content as shown below.
[Use label]
Check [Use label] and click [Label Library] button to add and edit the text. EB8000
supports Windows true-font.
135
EasyBuilder8000 User’s Manual
[Label Library…]
Note: About all the settings in [Label Library], please refer to the illustrations in “Chapter
15 Label Library and use Multi-Language” for details.
[Font]
Select font style from font list. EB8000 supports Windows true-font as shown below.
[Color]
Select the text color.
[Size]
Select the text size. The text sizes supported by EB8000 are listed below.
136
EasyBuilder8000 User’s Manual
[Align]
Select how users would like to align the text in multiple lines
137
EasyBuilder8000 User’s Manual
[Blink]
To decide how will the text blink:
Choose [None] to disable this feature or set blinking interval as [1 second] or [0.5
seconds].
[Italic]
Use Italic font.
[Underline]
Use Underline font.
[Movement] setting
[Direction]
Set the direction of the marquee effect.
[Continuous]
Whether this selection is tick or not influences how the marquee effect is displayed:
If not checking [Continuous], the next text appears only when the previous text disappears
completely. See the picture below.
138
EasyBuilder8000 User’s Manual
[Speed]
Adjust the speed of the text movement.
[Content]
Set the content of the text. If using [Label Library], the content will be sourced from Label
Library.
[Tracking]
When [Tracking] is selected, moving the text of one state will also move the text of other
states.
139
EasyBuilder8000 User’s Manual
When an object is created, double click it and go to the [Profile] tab to adjust the position
and size of the object.
a. Position
Set if the position and size of the object is [Pinned]. When it is checked, the position and
size of the object cannot be changed. X and Y mean the [X] and [Y] coordinate of the
left-top corner of the object.
b. Size
Adjust the [width] and [height] of the object.
140
EasyBuilder8000 User’s Manual
EB8000 version 1.31 or higher allows users to set variables of station number in PLC
address. As shown below, “var2” is one of 16 station number variables.
varN#address
var0 LW-10000
var1 LW-10001
var2 LW-10002
var3 LW-10003
var4 LW-10004
var5 LW-10005
var6 LW-10006
var7 LW-10007
var8 LW-10008
var9 LW-10009
var10 LW-10010
var11 LW-10011
var12 LW-10012
var13 LW-10013
var14 LW-10014
var15 LW-10015
141
EasyBuilder8000 User’s Manual
For example, “var0” reads value from LW-10000, when value in LW-10000 is “32”,
var0#234 = 32#234 (the station number is 32); similarly, “var13” reads value from
LW-10013, when value in LW10013 is” 5”, var13#234 = 5#234.
142
EasyBuilder8000 User’s Manual
MT6000/8000 provides two ways for users to enable using broadcast command. First is to
set it directly in [system parameter settings] [Device] tab:
Second way is to use system tag to enable or disable broadcast station number or to
change it.
Corresponding system tags are listed as below:
143
EasyBuilder8000 User’s Manual
Chapter 10 Security
Once password is entered, the objects that the user can adjust are set here. For example,
when the security class of “User 1” is set as above, only objects with class “A, C, E” and
“none” can the user adjust.
144
EasyBuilder8000 User’s Manual
1. Input the passwords to the system reserved register [LW-9220: password] (2 Words,
32 bits).
2. Use [LW-9219: User no. (1~12)] (1 Word, 16bit) to designate current user.
Note: value in [LW-9219] must be 1~12, which represents “User 1”~”User 12” respectively.
If the input password is wrong, state of [LB-9060: password error] will be set ON;
If the input password is correct, state of [LB-9060] returns to OFF automatically.
The passwords of user 1 to user 12 can be obtained from system reserved registers
[LW-9500: user 1’s password] to [LW-9522: user 12’s password], 24 words in total.
When the state of [LB-9050: user logout] switches from OFF to ON, current user will be
forced to logout the system. At this time, only the object defined as “None” can be
operated.
[LW-9222: classes can be operated for current user] records the operable classes
for current user:
bit0 = 1 means the operable object for current user is class “A”;
bit1=1 means the operable object for current user is class “B “and so on.
145
EasyBuilder8000 User’s Manual
Setting Description
Safety control [Safety control] is mainly used to prevent operator from
miss-operating an object accidentally. There are two methods for
protection:
[Min. press time (sec)]
Only when pressing the object continuously longer than the time set
here can an object to be activated successfully.
[Display confirmation request]
After pressing the object, a confirm dialog appears. Users need to click
146
EasyBuilder8000 User’s Manual
Message text (The one above is “Please confirm the operation”) in the
dialogue is defined in [System Message] object and can be changed
by user. Click [System Message] icon in tool bar and the dialog
appears. Content in [Message0] is for operation confirmation.
147
EasyBuilder8000 User’s Manual
grayed normal
User This function is used to set the security class of an object. Only when
restriction user’s permitted security class meets the object’s can it be operated.
When [Object class] is selected as [None], any user with any security
class can operate this object. The following settings are also provided
in the function:
148
EasyBuilder8000 User’s Manual
149
EasyBuilder8000 User’s Manual
Step1: First of all, create a new project. Go to [System parameter]/ [Security], add three
users and set different passwords and classes.
“User 1” can operate objects with class A, “user 2” can operate objects with class A and B,
and “user 3” can operate objects with class A, B, and C.
150
EasyBuilder8000 User’s Manual
[NE_0] and [NE_1] are [numeric input] objects with addresses [LW-9219] and [LW-9220]
that are for inputting user ID and password. [LW-9219] is for entering user ID (1~12), with
the length of 1 word, in a data format of 16-bit Unsigned as below.
[LW-9220] is for entering user password with a length of 2 words, in a data format of 32-bit
Unsigned as below.
[ND_0] is [numeric display] object with address [LW-9222] to indicate user’s state. The
data is in the format of 16-bit Binary.
[SB_0]~ [SB_2] are [Set Bit] objects which are set with different classes but all selected
[Make invisible while protected]. i.e. [SB_0] is class A, [SB_1] is class B, and [SB_2] is
class C. The settings of [SB_0] object:
151
EasyBuilder8000 User’s Manual
The [Set Bit] object (SB_3, LB-9050) is for user logout and is set as below:
Step 3: After completing the design and settings of the objects, please save, compile
project and do the off-line simulation. The illustration below is initial screen of
off-line simulation.
Since no password is entered this time, object [ND_0] [LW9222] shows
“0000000000000000” which means current user can only use objects with “none”
class.
Moreover, [SB_0]~[SB_2] are objects with security levels of class A~ class C and at
the same time [Make invisible while protected] is selected, therefore,
[SB_0]~[SB_2] objects are hidden by the system.
152
EasyBuilder8000 User’s Manual
Step 4: When user enters the password of user 1, “111”, the display will become:
Since “user 1” is permitted to use objects with class “A”, object [SB_0] appears and allows
user to operate. Now, bit 0 in [LW-9222] becomes “1”.
Step 5: Next, when user enters “user 3’s” password (333), the display will become:
Since “user 3” is permitted to use objects with class “A, B, and C”. Now, bit 0 ~ bit 3 in
[LW-9222] becomes “111” and allows current user to use objects with class A, B, and C.
153
EasyBuilder8000 User’s Manual
Step 6: At this time, if [SB_3] [LB-9050] is pressed to force current user to logout, the
system will return to initial state. In other words, current user can only use objects
with “none” class.
154
EasyBuilder8000 User’s Manual
11.1 Introduction
EB8000 provides 32 index registers for users to use addresses flexibly. Via index register,
users can update object’s read / write address without changing its content while HMI is
running the project.
155
EasyBuilder8000 User’s Manual
Press Setting…
But in another case as below, [Index register] is checked and the chosen index register is
[INDEX3]. In this way the read address will change to [LW (100+INDEX3)]. INDEX 3
represents value in address [LW9203]. In other words, if value in [LW9023] is “5”, the read
address in this case will be LW (100+5) = [LW105].
156
EasyBuilder8000 User’s Manual
For example as below, set Index 3 as “0”, which means the value in address [LW9203] is
“0”. Under this situation, the contents of [LW100 + Index 3] and [LW101 + Index 3] are the
same as those of the [LW100] and [LW101].
157
EasyBuilder8000 User’s Manual
Now, if users change value of Index 3 to “20”, the contents of [LW100 + Index 3] and
[LW101 + Index 3] will become those of [LW120] and [LW121], i.e. the values in
[LW100+20=LW120] and [LW101+20=LW121].
158
EasyBuilder8000 User’s Manual
Similarly, the index register can also work with bit address.
1 word = 16 bits, in other words, 1 value change of index register means the change of 16
bits.
See the example below. When INDEX 5 is set as “0”, the state of [Bit Lamp] [LB0] and
[LB6] are the same as those of [Toggle Switch] ~ [LB0+Index 5] and [LB6+Index 5] and are
displayed ON.
159
EasyBuilder8000 User’s Manual
If users change value of index 5 to “1”, the state of [Bit Lamp] [LB16] and [LB22] are the
same as those of [Toggle Switch] ~ [LB0+Index 5] and [LB6+Index 5] and are displayed
ON.
In conclusion: From illustration above, we realize that Index register is used to change
addresses. Through changing the data in index register, we can make an object to read
and write different data from different addresses without changing its own address of the
device. Therefore, we can transmit or exchange data among different addresses.
160
EasyBuilder8000 User’s Manual
Both [Numeric Input] and [ASCII Input] objects need to use keyboard as input tool.
Except for calling up a popup keyboard, users can design a keyboard without title bar or a
fixed keyboard in the window. Even UNICODE keyboard can be created. Both numeric
keyboard and ASCII keyboard are created with [Function Key] object. The process and
usage are illustrated below.
Step 1
Create and open a window for a keyboard to be added. For example, set [WINDOW 200]
as the window for a keyboard.
Step 2
Adjust the height and width of WINDOW 200 and create a variety of [Function Key]
objects in it. Input signals will be triggered by pressing [Function Keys].
161
EasyBuilder8000 User’s Manual
Here FK_11 is used as the [Escape (Esc)] key and its settings:
[Function Key] s other than FK_11 and FK_14 are mostly used to input number or text. For
example, FK_0 is used for inputting number [1] and its settings:
Select a suitable Picture for each [Function Key] object. GP_0 is a [picture] object which
is placed in the bottom layer as the background.
Step 3
Go to [General] tab in [System Parameter Settings] and click [Add…] in [Keyboard].
[Add a keyboard] dialog appears. Select [WINDOW 200] and press [OK].
162
EasyBuilder8000 User’s Manual
After a Keyboard object is created, when open the [Numeric Input] or [ASCII Input]
object, “200.Keyboard” can be found in [Keyboard] Data Entry tab, as shown below.
[Popup Position] is used to decide the display position of the Keyboard in screen.
163
EasyBuilder8000 User’s Manual
Select [200.Keyboard]. When users press [Numeric Input] or [ASCII Input] object,
WINDOW 200 will pop up in HMI screen. Users can press keys in keyboard to input data.
164
EasyBuilder8000 User’s Manual
If users don’t need the title bar of the keyboard, a direct window can be used as follows.
Step 1
Create a [Direct window] and set a read address to activate it.
In [General] / [Attribute] tab of adding new object dialogue, select [No title bar] and
[Window no].
Step 2
Set the [Profile] of [direct window] object to same size as [WINDOW 200].
165
EasyBuilder8000 User’s Manual
Step 3
Create a [Numeric Input] object, and don’t select [Use a popup keypad].
Step 4
Add a [Set Bit] object, set [LB 0] as ON and overlay it on the [Numeric Input] object.
Add [Set Bit] objects on the [Enter] and [ESC] function keys respectively. Set [LB0] as
OFF. In this way when user presses either [Enter] or [ESC] will close the keyboard.
166
EasyBuilder8000 User’s Manual
167
EasyBuilder8000 User’s Manual
Users can also place a fixed keyboard in the window instead of popup keyboard or direct
window. The keyboard can’t be moved or canceled this way.
Step 1
Create a [Numeric Input] object, and don’t select [Use a popup keypad].
Step 2
Design a keyboard with [function keys] and place them in screen.
Step 3
When pressing [numeric input] object, users can input value with function keys directly.
168
EasyBuilder8000 User’s Manual
After the settings are completed, function keys [α] [β] [γ] [δ] are created.
Create an [Enter] key. A simple UNICODE keyboard is built. Place a [ASCII Input] object
in window, set [No. of Words] as [8] (1 word =2 bytes) and tick [Use UNICODE] as below.
169
EasyBuilder8000 User’s Manual
In conclusion: Numeric keyboard and ASCII keyboard are all made by combining function
keys. Users can group up the self made keyboard and add to library for future use. If not
using the default keyboard, self defined keyboard can also be used. Add newly made
keyboard to [System parameter settings]/ [General]/ [Keyboard].
170
EasyBuilder8000 User’s Manual
Chapter 13 Objects
This chapter is to illustrate the ways of using and setting all kinds of objects. For those
settings general for all the objects, such as index register, label, shape, and so on, please
refer to “Chapter 9 Object’s General Properties”.
Overview
Bit Lamp object displays the ON and OFF state of a bit address. If the bit state is OFF, the
State 0 shape will be displayed. If the bit state is ON, the State 1 shape will be displayed.
Configuration
Click the [Bit Lamp] icon in the toolbar and the [Bit Lamp Object’s Properties] dialogue
box will appear, fill in the content of and press [OK], a new bit lamp object will be created.
See the pictures below.
171
EasyBuilder8000 User’s Manual
Setting Description
Description A reference name that’s assigned by user for the object. The system does
not make use of this reference name since it is for user’s document only.
172
EasyBuilder8000 User’s Manual
Read address Click [Setting…] to select the [PLC name], [Address], [Device type],
[System tag], [Index register] of the bit device that controls the bit lamp
object. Users can also set address in [General] tab while adding a new
object.
[Invert signal]
Display shape with inverse state; for example, the present state is “OFF”,
but it displays the shape of “ON” state.
Blinking Set blinking attribute of bit lamp.
[Blinking mode]
a. None
No blinking.
b. Alternating image on state 0
Alternatively display the shape of state 0 and state 1 when the bit value is
OFF (state 0).
c. Alternating image on state 1
Alternatively display the shape of state 0 and state 1 when the bit value is
ON (state 1).
d. Blinking on state 0
Display the shape of state 0 in blinking when the bit value is OFF (state 0).
e. Blinking on state 1
Display the shape of state 1 in blinking when the bit value is ON (state 1).
173
EasyBuilder8000 User’s Manual
Overview
A Word Lamp object displays the corresponding shape according to the value in the
designated word address. (up to maximum of 256 states)
Configuration
Click the [Word Lamp] icon in the toolbar and the[Word Lamp Object’s
Properties]dialogue box will appear, fill in each items and press [OK] button, a new word
lamp object will be created. See the pictures below.
174
EasyBuilder8000 User’s Manual
Setting Description
[Mode] / Word lamp object offers the following three modes for selection:
[Offset]
a. Value
Calculate result of word value to subtract [Offset] and display its
corresponding shape.
175
EasyBuilder8000 User’s Manual
In the above setting, if the value of [LW200] is “5”, the shape of state “2” is
displayed. See the picture below.
b. LSB
Transfer the read address value to binary, the lowest 8 bits other than value 0
decides the state. Please refer to the following table.
176
EasyBuilder8000 User’s Manual
Read address Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of the word device that controls the word lamp
object. Users can also set address in [General] tab while adding a new object.
177
EasyBuilder8000 User’s Manual
state.. Suppose the number of the states is 8, the valid states will be 0, 1~7. In
this case if the word value is 8 or higher, the system will display the shape of
last state.
Restrictions
In label dialog, Language 1 is able to change attribute settings, and for Language 2~8,
only font size can be changed and other settings follows language 1.
178
EasyBuilder8000 User’s Manual
Overview
The [Set Bit] object provides two operation modes: the “manual operation” mode defines
a touch area, users can activate the touch area to set the state of the bit device to be ON
or OFF. When users select the “automatic operation” mode, the operation will be
automatically activated in pre-configured conditions, the touch area has no action in any
circumstance.
Configuration
Click the [Set Bit] icon in the toolbar and the [New Set Bit Object] dialogue box will
appear, fill in each items and press [OK] button, a new Set Bit object will be created. See
the pictures below.
179
EasyBuilder8000 User’s Manual
Setting Description
Write address Click [Setting…] to select the [PLC name], [Device type], [Address],
[System tag], [Index register] of the bit device that system set value to.
Users can also set address in [General] tab while adding a new object.
180
EasyBuilder8000 User’s Manual
Set ON when window When the window containing the Set Bit object
opens is opened, the bit device will be automatically
set to ON.
181
EasyBuilder8000 User’s Manual
Set OFF when window When the window containing the Set Bit object
opens is opened, the bit device will be automatically
set to OFF.
Set ON when window When the window containing the Set Bit object
closes is closed, the bit device will be automatically
set to ON.
Set OFF when window When the window containing the Set Bit object
closes is closed, the bit device will be automatically
set to OFF.
Set ON when When the backlight is turned on, the bit device
backlight on is automatically set ON.
Set OFF when When the backlight is turned on, the bit device
backlight on is automatically set OFF.
Set ON when When the backlight is turned off, the bit device
backlight off is automatically set ON.
Set OFF when When the backlight is turned off, the bit device
backlight off is automatically set OFF.
Macro Users can use [set bit] object to activate macro commands. Macro
commands have to be built before configure this function. Please refer to
related chapter on how to edit Macros.
Set style
When [Set style] is selected as [Toggle], there are three different modes
to trigger macro command, i.e. OFF->ON, ON->OFF, or ON<->OFF.
182
EasyBuilder8000 User’s Manual
Overview
The [Set Word] object provides two operation modes: the “manual operation” mode and
the “automatic operation” mode. The “manual operation” mode defines a touch area, and
users can activate the area to set the value of the word device. When users select the
“automatic operation” mode, the operation will be automatically activated in pre-configured
conditions, the touch area has no action in any circumstance.
Configuration
Click the [Set Word] icon in the toolbar and the [New Set Word Object] dialogue box will
appear, fill in each items and press [OK] button, a new Set Word object will be created.
See the pictures below.
183
EasyBuilder8000 User’s Manual
Setting Description
Write Click [Setting…] to Select the [PLC name], [Device type], [Address],
address [System tag], [Index register] of the word device that system set value to.
Users can also set address in [General] tab while adding a new object.
184
EasyBuilder8000 User’s Manual
Set the state of the designated bit device before or after writing to word
device.
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of the Notification bit that system set value to.
Users can also set the address in the Notification area.
185
EasyBuilder8000 User’s Manual
Attribute [Set style] Set the operation mode. The available modes for selection are
listed as follows:
Set constant function. When the operation is activated, the [Set value] will be
written into the word device. The constant’s format (16-bit BCD, 32-bit
BCD, …) depends on the format of [Write address].
Increase value function. When the operation is activated, the [Inc. value] will
be added to the value of the word device, and the result won’t exceed the
value [Upper limit].
Decrease value function. When the operation is activated, the [Dec. value]
will be subtracted from the value of the word device, and the result won’t go
less than the value [Bottom limit].
Press and hold increment function. When the touch and hold gets longer than
the time set in [JOG delay], the value of the word device will be added by the
value set in [Inc. value] at the speed set in [JOG speed], and the result won’t
exceed the value in [Upper limit].
186
EasyBuilder8000 User’s Manual
Press and hold decrement function. When the touch and hold gets longer
than the time set in [JOG delay], the value of the word device will be
subtracted by the value set in [Dec. value] at the speed set in [JOG speed],
and the result won’t go less than the value in [Bottom limit].
f. Periodical JOG++
Periodically increment function. A set word object can use the interval set in
[Time interval] and the value set in [Inc. value] to automatically increase the
value of the word device, and the result won’t exceed the value in [Upper
limit].
g. Automatic JOG++
Periodically decrement function. A set word object can use the interval set in
[Time interval] and the value set in [Inc. value] to automatically increase the
value of the word device, and the result won’t exceed the value in [Upper
limit].
187
EasyBuilder8000 User’s Manual
h. Automatic JOG--
Periodically decrement function. A set word object can use the interval set in
[Time interval] and the value set in [Dec. value] to automatically decrease
the value of the word device, and the result won’t go less than the value in
[Bottom limit].
i. Periodical bounce
Periodically bouncing function. A Set word object will add the value set in
[Inc. value] to the value of the word device with the regulated interval set in
[Time interval] until the result value reaches the value in [Upper limit], and
then subtract the value set in [Inc. value] from the value of the word device
with the regulated interval set until the result value reaches the value in the
[Bottom limit]. For example, the value in the word device will change
periodically from 0~10 then from 10~0.
j. Periodical step up
Stepping up function. A Set word object will add the value set in [Inc. value]
to the value of the word device with the regulated interval set in [Time
interval] until the result value reaches the value in the [High limit], and the
188
EasyBuilder8000 User’s Manual
value of the word device will return to the value of the [Low limit] and then
repeat the action to keep the value in an active state. In the example shown
below, the value of the word device will change periodically in order of 0, 1,
2,…, 9, 10, 0, 1, 2, ……
Stepping down function. A Set word object will subtract the value set in [Dec.
value] from the value of the word device with the regulated interval set in
[Time interval] until the result value reaches the value of the [Low limit],
and the value of the word device will return to the value of the [High limit]
and then repeat the action to keep the value in an active state. In the
example shown below, the value of the word device will change periodically
in order of 10, 9, 8,…, 1, 0, 10, 9, 8, ……
When the window containing the object is opened, the value of [Set value]
will be automatically written into the word device.
When the window containing the object is closed, the value of [Set value] will
be automatically written into the word device.
189
EasyBuilder8000 User’s Manual
When the backlight is turned from off to on, the value of [Set value] will be
automatically written into the word device.
190
EasyBuilder8000 User’s Manual
Overview
Function key object is used to change base window, pop-up window and close window. It
can also be used to design the keypad buttons.
Configuration
Click the [Function Key] icon in the toolbar and the [Function Key Object’s Properties]
dialogue box will appear, fill in each items and press the [OK] button, a new function key
object will be created. See the pictures below.
191
EasyBuilder8000 User’s Manual
192
EasyBuilder8000 User’s Manual
[Change Change common window; refer to the “windows” chapter for related
common information.
window]
[Display popup Pop up window. The pop up window must be on the top of the base window.
window] There is a [Close this popup window when parent window is closed]
option with this function, see the picture below; when the function is selected,
the pop up window will be closed when executing change base window.
Otherwise, users have to set a “Close” button on the pop-up window to close
the window.
[Window no.] This is used to select the window no. when performing [change base window],
[change common window], and [pop up the window]
[Return to This is used to return to the previous base window. Fox example, when
previous changing window 10 to window 20, users can use this function to return to
window] window 10. This function is only available for base window change.
[Close window] Close the pop-up windows on the top of the base window.
Items in [ASCII/UNICODE mode] is used as elements to configure a keypad, the
ASCII/UNICODE keypad is used where numbers or texts are needed to be input to the
mode [numeric input] object or [ ASCII input] object. Refer to the “Designing and
Using Keypad” chapter for detailed information.
[Enter]
Same as the keyboard’s “enter” function.
[Backspace]
Same as the keyboard’s “backspace” function.
[Clear]
To clear the temperate input alphanumeric strings stored in the buffer.
[Esc]
Same as the [Close window] function, it is used to close the keyboard
window.
[ASCII/UNICODE]
To set the characters that are input in the numeric input object and the ASCII
input object. Digital characters such as 0, 1, 2… or ASCII characters like a, b,
193
EasyBuilder8000 User’s Manual
[Window title A [function Key] which is defined as Window Title Bar can move the popup
bar] window position on the screen. Firstly users can select the popup window that
has the title bar, and then click another position to move the window.
Note: this function is only available on indirect/direct window when [no
title bar] is selected.
[Screen hard Hardcopy current display screen to the printer connected with MT8000. Before
copy] using this function, please choose printer model in [System Parameter] /
[Model] / [printer]. If printer does not support color print, user can select
grayscale to have a better printout effect. Black and white is for improving text
printing quality.
Notification When the function is selected, MT8000 will set the state of the designated bit
device to [ON] or [OFF] after the action is completed.
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of the Notification bit that system set value to.
194
EasyBuilder8000 User’s Manual
Below we illustrate the method to input non-ascii character such as Traditional Chinese,
Simplified Chinese, Japanese, Greece and so on.
Those objects on the window are function keys with input code in accord with the label. For
example, to input ” 简 ” function key, create a function key
object/General/[ASCII]/[UNICODE] mode, type in ”简” in the column as below illustration.
195
EasyBuilder8000 User’s Manual
Go to Function key/Label and then select “Use label”, type ”简” in the content and in the
Attribute/Font select ” AR MingtiM GB”, it must be the same as setp1’s setting, as
illustrated below.
The label of non-ascii function key must use the same Font. For example, in Simplified
Chinese keypad, the fonts all use ” AR MingtiM GB”.
196
EasyBuilder8000 User’s Manual
After complete the keypad configuration, add window11 into System Parameters / General
/ keyboard as illustration below.
197
EasyBuilder8000 User’s Manual
Overview
Toggle Switch object is a combination of bit lamp object and set bit object. The object can
be used not only to display the state of a bit device but also to define a touch area, when
activated, the state of the bit device will be set to “ON” or “OFF”.
Configuration
Click the “Toggle Switch” icon on the toolbar and the “New Toggle Switch Object” dialogue
box will appear, fill in each item and press OK button, a new toggle switch object will be
created. See the pictures below.
198
EasyBuilder8000 User’s Manual
Setting Description
Read Click [Setting…] to Select the [PLC name], [Device type], [Address],
address [System tag], [Index register] of the bit device that control the display
of toggle switch state. Users can also set address in General tab while
adding a new object.
[Invert signal]
Display shape with inverse state; for example, the present state is “OFF”,
but it displays the shape of “ON” state.
Write Click [Setting…] to Select the [PLC name], [Device type], [Address],
199
EasyBuilder8000 User’s Manual
address [System tag], [Index register] of the bit device that system set value to.
The write address can be the same as or different from the read address.
Users can also set address in General tab while adding a new object.
[Write when button is released]
If this function is selected, the operation is activated at touch up. If the
function is not selected, the operation is activated at touch down.
Attribute This is used to select the operation mode. The available operation
modes for selection include “Set ON”, “Set OFF”, ”Toggle”,
and ”Momentary”. Refer to the illustrations in the “Set Bit Object” section
of this chapter for related information.
Macro Users can execute macro command by trigging toggle switch This
function is the same as that of set bit object. Please refer to “the chapter
of set bit object”.
200
EasyBuilder8000 User’s Manual
Overview
Multi-State Switch object is a combination of word lamp object and set word object. The
object can be used not only to display the state of a word device but also to define a touch
area, when activated, the value of the word device can be set.
Configuration
Click the “Multi-State Switch” icon on the toolbar and the “New Multi-State Switch Object”
dialogue box will appear, fill in each items, and click OK button, a new Multi-State Switch
object will be created. See the pictures below.
201
EasyBuilder8000 User’s Manual
Setting Description
[Mode]/ There are “Value” and “LSB” display mode. Refer to the “Word Lamp
[Offset] Object” section of this chapter for related information.
Read Click [Setting…] to Select the [PLC name], [Device type], [Address],
address [System tag], [Index register] of the word device that controls the
display of multi-state switch.
Users can also set address in General tab while adding a new object.
Write Click [Setting…] to Select the [PLC name], [Device type], [Address],
address [System tag], [Index register] of the word device that system set value
202
EasyBuilder8000 User’s Manual
to. The write address can be the same as or different from the read
address.
Users can also set address in General tab while adding a new object.
[Write when button is released]
If this function is selected, the operation is activated at touch up. If the
function is not selected, the operation is activated at touch down.
Attribute Select the object’s operation mode.
[Switch style]
There are “JOG+” and “JOG-” for selection. When the read address is
the same as the write address, the minimum value of the word value is
[Offset] (state 0), and the maximum value is “[no. of state] -1 + [Offset]”.
See the picture below.
a. “JOG+”
When the Multi-State Switch object is activated, the value of the write
address will be added by 1. In the “Value” display mode, if the resulting
value is equal to or larger than the value of [No. of States] + [Offset] and
“Enable” in [Cyclic] is selected, the value of the write address will return
to [Offset] and show the state 0; otherwise the value of the write address
will maintain as ([No. of states] – 1) + [Offset] and shows the state ([No.
of states no.] – 1).
NOTE: Like the word lamp object, the state shown by Multi-State Switch
object is the value of the word device subtracts [Offset].
203
EasyBuilder8000 User’s Manual
b. “JOG-”
When the Multi-State Switch object is activated, the value of the write
address will be subtracted by 1. In the “Value” display mode, if the
resulting value is smaller than the value of [Offset] and “Enable” in
[Cyclic] is selected, the value of the register will change to ([No. of
states] – 1) + [Offset] and shows the state ([No. of states] – 1); otherwise
the value of the word device will remain in [Offset] and shows the state 0.
[User-defined mapping]
Users can modify the value of state, illegal input and error notification.
Jump to error state: if input an illegal value, multi-state switch will jump to
error state.
204
EasyBuilder8000 User’s Manual
13.8 Slider
Overview
The slide object can be used to create a slot area that changes the word's value by
dragging the pointer.
Configuration
Click the “Slide object” icon on the toolbar and the dialogue box will appear, fill in each
items and click OK button, a new slide object will be created. See the pictures below.
Setting Description
Write Click [Setting…] to Select the [PLC name], [Device type], [Address],
address [System tag], [Index register] of the word device that system set value to.
205
EasyBuilder8000 User’s Manual
Users can also set address in General tab while adding a new object.
Notification Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of the Notification bit that system set value to.
Users can also set the address in the Notification area.
When this function is selected, the state of the designated bit device can be
set before/after the operation is completed. There are [ON] and
[OFF] selection to set the state.
[Before writing] / [After writing]
Set the state of the designated register before or after write to the word
device.
Watch When sliding, the current value can be displayed in real-time fashion.
address
206
EasyBuilder8000 User’s Manual
Setting Description
Attribute [Direction]
The bar on the slide direction, i.e. left, right, up and down.
[Resolution]
To specify the scale value of the slider, if N is the specified minimum
scale value, when
N=10, the numerical display shows only multiples of 10.
N=5, the numerical display shows only multiples of 5.
N=1, the numerical display shows only multiples of 1.
b. Address
The low / high limit of the word device is controlled by a designated
address.
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of designated address or users can
also set address in Attribute.
[Coarse increment:]
If this option is selected, the word value will increase/decrease one
[increment] value for every touch activation. If not, the word value will be
207
EasyBuilder8000 User’s Manual
208
EasyBuilder8000 User’s Manual
Overview
Both of the Numeric Input object and the Numeric Display object can be used to display
the value of the word devices. The difference is the numeric input object can be used to
input data from the keypad, the input value is written to the designated word devices.
Configuration
Click the “Numeric Input” or “Numeric Display” icon on the toolbar and the “New Numeric
Input Object” or “New Numeric Display Object” dialogue box will appear, fill in each item,
click OK button and a new “Numeric Input Object” or “Numeric Display Object” will be
created. See the pictures below.
The difference between the “New Numeric Display Object” and “New Numeric Input
Object” dialogue boxes is that the latter has the settings for ”Notification” and keypad input
while the former doesn’t have. The picture below shows the [General] tab in “New Numeric
Input Object”.
209
EasyBuilder8000 User’s Manual
Setting Description
Read/Write Numeric Input object is provided with [Read/Write use different addresses]
use selection, users can set different addresses for Read and for Write data.
different
address
Read Select the [PLC name], [Device type], [Address] of the word device that
address system display its value and write new data to it.
Write Select the [PLC name], [Device type], [Address] of the word device that
210
EasyBuilder8000 User’s Manual
Notification When this function is selected, the state of the designated bit device will be
set to [ON] or [OFF] after/before the value of the register is changed
successfully.
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of the Notification bit that system set value to.
Users can also set the address in the Notification area.
[Before writing] / [After writing]
Set the state of the designated bit device before or after update the word
device.
Notification When inputting invalid values, it can now automatically set the status of
on valid designated address.
input
211
EasyBuilder8000 User’s Manual
Setting Description
[Mode] z [Touch]
The object enters input state when a user touches it.
z [Bit control]
The object enters input state when turning ON the
designated bit register, and ends input state when turning
OFF. Notice that if there is another input object already in
input state, turning ON the designated bit register won’t
make this input object enters input state until the previous
one ends inputting data.
Allow input bit Click [Setting…] to Select the [PLC name], [Device type],
address [Address], [System tag], [Index register] of the bit register
that controls the object enters and ends input state.
Users can also set address in Data Entry tab.
212
EasyBuilder8000 User’s Manual
Input order By setting Input Order and Input Order Group, users can
continuously input data between multiple input objects. The
system will automatically transfer input state to the next input
object after users complete inputting data, i.e. press ENT.
z Enable
Select [Enable] and set Input Order to enable this feature.
Furthermore, users can also select [Group] to set Input
Order Group.
a. The range of Input Order: 1 ~ 511.
b. The range of Input Order Group: 1 ~ 15.
c. The Input Order Group of an input object with [Group]
unselected is 0.
213
EasyBuilder8000 User’s Manual
214
EasyBuilder8000 User’s Manual
215
EasyBuilder8000 User’s Manual
z When selecting [Bit control] as Mode, the system will automatically unselect
[Use a popup keypad] in [Keyboard].
The picture below shows the [Numeric Format] tab, included in both of the numeric input
object and the numeric display object, which is to set the data display format.
Setting Description
Display [Data format]
To select the data format of the word device designated by the “Read
216
EasyBuilder8000 User’s Manual
See the example in the picture below, the raw data is 15, after being
converted by the above formula as 10 + (15 – 0) × (50 – 10) / (20 - 0) = 40,
and the result “40” will be displayed on the numeric input object.
217
EasyBuilder8000 User’s Manual
Limits To set the source of the range for the input data and to set the warning color
effect.
[Direct]
The low limit and high limit of the input data can be set in [Input low] and [Input
high] respectively. If the input data is out of the defined range, the input value
will be ignored.
[Dynamic limits]
Set the low limit and high limit of the input data to be derived from the
designated register. The data length of the designated register is the same as
the input object itself. In the above example, the low limit and high limit are
derived from [LW100] and the following explains the usage of the low limit and
high limit from designated address.
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] for designated register.
Users can also set address in Numeric Format tab.
Designated address Input Low Limit Input High Limit
16-bit format LW100 LW101 (Address+1)
32-bit format LW100 LW102 (Address+2)
[Low limit]
When the value of the PLC’s register is smaller than [Low limit], the value is
218
EasyBuilder8000 User’s Manual
Setting Description
Attribute [Color]
When the data is within high and low limit, it will be displayed with this color.
[Align]
There are three aligning modes: “Left”, “Leading zero”, and “Right”. The
picture below shows the style of each mode.
219
EasyBuilder8000 User’s Manual
[Size]
Set font size.
220
EasyBuilder8000 User’s Manual
Overview
Both of the ASCII Input object and the ASCII Display object can display the value of the
designated word devices in ASCII format. The ASCII input object can also accept the data
input from the keypad and change the value of the word devices.
Configuration
Click the “ASCII Input” or “ASCII Display” icon on the toolbar and the “New ASCII Input
Object” or “New ASCII Display Object” dialogue box will appear, fill in each item, press OK
button, a new “ASCII Input Object” or “ASCII Display Object” will be created. See the
pictures below.
The difference between the “New ASCII Display Object” and “New ASCII Input Object”
dialogue boxes is that the latter has the settings for “Notification” and keypad input while
the former doesn’t have. The picture below shows the [General] tab of the “New ASCII
Input Object”.
221
EasyBuilder8000 User’s Manual
Setting Description
[Mask] When the data is displayed, “*” will be used to replace all texts.
[Use Click “Use UNICODE” to display data in UNICODE format. Otherwise the
UNICODE] system displays the character in ASCII format. This feature can be used with
function key [UNICODE]. Not every Unicode has corresponding font stored
in the system. The font of UNICODE is only available for those Unicode
character that registered function key.
[Reverse In normal condition, the ASCII code is displayed in “low byte”, “high byte”
high/low byte] order. The reverse selection makes the system display ASCII characters in
“high byte”, “low byte” order.
222
EasyBuilder8000 User’s Manual
Read address Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of the word device that system display its
value and write new data to it.
Users can also set address in General tab while adding a new object.
[No. of words]
To set the length of ASCII data in the unit of words. Each ASCII character
take one byte, each word contains two ASCII characters.
Notification When this function is selected, the state of the designated bit device will be
set to [ON] or [OFF] after/before the value of the register is changed
successfully.
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of the Notification bit that system set value
to.
Users can also set the address in the Notification area.
[Before writing] / [After writing]
Set the state of the designated bit device before or after update the word
device.
About the Data Entry tab, please refer to “Numeric Input and Numeric Display” section.
223
EasyBuilder8000 User’s Manual
Setting Description
Attribute The picture shows the [Font] tab of the ASCII Input object and the
ASCII display object. Users can set the font, font size, font color, and
aligning mode.
224
EasyBuilder8000 User’s Manual
[Align]
There are two aligning modes: “Left” and “Right”. The picture below
shows how each mode performs.
[Size]
Set font size.
225
EasyBuilder8000 User’s Manual
Overview
“Indirect Window” object is to define a popup window location (position / size) and a word
device. When the content of the word device is written a valid window number, the window
will be popup in the predefined location. The popup window will be closed when the value
of the word device is reset (0). The system will only take action when the content of word
device is changed. (0 → valid window number, nonzero → 0, A → B valid window
number).
Configuration
Click the “Indirect Window” icon on the toolbar and the “New Indirect Window Object”
dialogue box will appear, fill in each items, click OK button, a new “Indirect Window Object”
will be created. See the pictures below.
226
EasyBuilder8000 User’s Manual
Setting Description
Read Click [Setting…] to Select the [PLC name], [Device type], [Address],
address [System tag], [Index register] of the word device that control the
window popup.
Users can also set address in General tab while adding a new object.
Attribute [Style]
To set the display style of the popup window. There are two styles, “No
title bar” and “With title bar”.
a. “No title bar”
The popup window does not have title bar, and its position is fix as
predefined in configuration.
227
EasyBuilder8000 User’s Manual
228
EasyBuilder8000 User’s Manual
Use the set word object SW_0 to set the value of [LW100] as 35, and the location of
indirect window will display window 35.
Use the set word object SW_1 to set the value of [LW100] as 36, and the location of
indirect window will display window 36.
.
No matter window 35 or 36 is displayed on the indirect window location, press SW_2 to set
the value of [LW100] to 0 will close the popup window. The other way to close the popup
window from indirect window object is to configure a function key with [close window].
Once you press the function key, the popup window will be closed.
229
EasyBuilder8000 User’s Manual
NOTE: Only 16 windows maximum can be displayed simultaneously at run time, and do
not use this function to open the window when the same window has been
opened by function key or direct window.
230
EasyBuilder8000 User’s Manual
Overview
“Direct window” object is to define a popup window location (position / size), a bit device
and a predefined valid window number. When the content of the bit device is set ON/OFF,
the window will be popup in the predefined location. The popup window will be closed
when the content of the bit device is reset. The system will only take action when the
content of bit device is changed (OFF → ON, ON → OFF).
The difference between the “Direct window” and the “Indirect window” is that the direct
window object sets the popup window in configuration. When system is in operation, users
can use the state of the designated register to control popup or close the window.
Configuration
Click the “Direct Window” icon on the toolbar and the “New Direct Window Object”
dialogue box will appear, fill in each items, press OK button, and a new “Direct Window
Object” will be created. See the pictures below.
231
EasyBuilder8000 User’s Manual
Setting Description
Read Click [Setting…] to Select the [PLC name], [Device type], [Address],
address [System tag], [Index register] of the bit device that control the window
popup.
Users can also set address in General tab while adding a new object.
Attribute [Style]
Refer to the “Indirect Window Object” for related information.
[Window no.]
Set the popup window number.
232
EasyBuilder8000 User’s Manual
Here is an example to explain how to use the direct window object. The picture below
shows the settings of the direct window object. In the example, use [LB10] to call up the
window 35.
When the state of LB10 is set to ON, the window 35 will be popup; when the state of LB10
is OFF, the window 35 will be closed. See the picture below.
233
EasyBuilder8000 User’s Manual
NOTE: Only 16 windows maximum can be displayed simultaneously at run time, and do
not use this function to open the window when the same window has been opened
by function key or direct window.
234
EasyBuilder8000 User’s Manual
Overview
Moving Shape object is used to define the object’s state and moving distance. The Moving
Shape object is used to place an object in a window at a location specified by the PLC.
The state and the absolute location of the shape in the window depend on the current
values of three continuous PLC registers. Typically, the first register controls the state of
the object, the second register controls the horizontal position (X), and the third register
controls the vertical position (Y).
Configuration
Click the “Moving Shape” icon on the toolbar and “New Moving Shape Object” dialogue
box will appear, fill in each items, press OK button, and a new “Moving Shape Object” will
be created. See the pictures below.
235
EasyBuilder8000 User’s Manual
Setting Description
Read Click [Setting…] to Select the [PLC name], [Device type], [Address],
address [System tag], [Index register] of the word devices that control the display
of object’s state and moving distance.
Users can also set address in General tab while adding a new object.
The table below shows the address to control object’s state and moving
distance in each different data format.
236
EasyBuilder8000 User’s Manual
For example, if the object’s read address is [LW100] and the data format is “16-bit
Unsigned”, [LW100] is to control the object’s state, [LW101] is to control the object’s
moving distance on the X-axis, and [LW102] is to control the object’s moving distance on
the Y-axis.
The picture below shows that the object’s read address is [LW100] and initial position is
(100, 50). Supposed you want the object moved to the position (160, 180) and be
displayed in the shape of State 2, the value of [LW100] must be set to 2, [LW101] =
160–100 = 60, [LW102] = 180–50 = 130.
237
EasyBuilder8000 User’s Manual
238
EasyBuilder8000 User’s Manual
For example, the object is only allowed to move within 0~600, but the range
of the register’s value is 300~1000, set [Input low] to 300 and [Input high] to
1000, and set [Scaling low] to 0 and [Scaling high] to 600, and the object will
move within the range.
Data format Address to Address to
control object control Moving
state Distance on the
X-axis
16-bit format Address Address + 1
32-bit format Address Address + 2
e. Y axis w/ scaling
The object is for Y axis movement with scale, and the formula to calculate
the moving distance on the Y-axis is the same as the one in “X axis w/
scaling.”
Data format Address to Address to
control object control Moving
239
EasyBuilder8000 User’s Manual
Limit The object’s moving range can be set not only by [Min. X], [Max. X] and
address [Min. Y] [Max. Y], but also by the designated registers. Supposed that the
object’s moving range is set by the value of the designated register
“Address”, then the address of [Min. X], [Max. X] and [Min. Y] [Max. Y] are
listed in the following table.
240
EasyBuilder8000 User’s Manual
13.14 Animation
Overview
The Animation object is used to place an object on the screen at a specified location
determined by a predefined path and data in the PLC. The state and the absolute location
of the shape on the screen depend on current reading value of two continuous PLC
registers. Typically, the first register controls the state of the object and the second register
controls the position along the predefined path. As the PLC position register changes
value, the shape or picture jumps to the next position along the path.
Configuration
Click the “Animation” icon on the toolbar, move the mouse to each moving position and
click the left button to define all moving positions one by one. When settings of all moving
positions are completed, click the right button of the mouse, a new animation object will be
created. See the pictures below.
To change the object’s attributes, you can double click the left button of the mouse on the
object, and the “Animation Object’s Properties” dialogue box, as shown in the picture
below, will appear.
241
EasyBuilder8000 User’s Manual
Setting Description
Attribute [Total no. of states]
To set the number of the states for this object.
a. Controlled When select “Controlled by register”, the designated register controls the
by register object’s state and position.
Read address
If select “Controlled by register” option, it is necessary to set the read
address.
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] for the read address.
242
EasyBuilder8000 User’s Manual
Users can also set address in General tab while adding a new object.
In the table below, it describes the address that control shape’s state
and position in different data format.
For example, if the designated register is [LW100] and the data format
is ”16-bit Unsigned”, then [LW100] represents object’s state, [LW101]
represents position. In the picture below, [LW100] = 2, [LW101] = 3, so
the object’s state is 2 and position is 3.
b. Based If “Based upon time interval” is chosen, the object automatically changes
upon time status and display location. “Time interval attributes” is to set the time
interval interval for states and positions.
[Position speed]
Position changes speed, the unit is 0.1 second. Supposed that [Speed]
is set to 10, the object will change its position every 1 second.
[Backward cycle]
If the object has four positions: position 0, position 1, position 2, and
position 3, and [Backward cycle] is not selected. In this case when the
243
EasyBuilder8000 User’s Manual
object moves to the last position (position 3), next position will be back to
the initial position 0, and repeat the action over again. The moving path
is shown as follows:
The following dialog shows size setup of animation object. Call up the animation object
dialogue box by double clicking.
244
EasyBuilder8000 User’s Manual
Setting Description
Shape To set the size of the shape.
rectangle size
Trajectory To set the position of each point on the moving path.
245
EasyBuilder8000 User’s Manual
Overview
Bar graph object displays PLC register data as a bar graph in proportion to its value.
Configuration
Click the “Bar Graph” icon on the toolbar, the “Bar Graph” dialogue box will be shown up,
fill in each items of settings, click OK button, a new “Bar Graph Object” will be created. See
the picture below.
The following picture shows the “General” tab of the bar graph object.
246
EasyBuilder8000 User’s Manual
Read address
Click [Setting…] to Select the [PLC name], [Device type], [Address], [System tag],
[Index register] of the word devices that controls the bar graph display.
Users can also set address in General tab while adding a new object.
The following picture shows the “Outline” tab of the bar graph object.
247
EasyBuilder8000 User’s Manual
Setting Description
248
EasyBuilder8000 User’s Manual
Attribute [Type]
There are “Normal” and “Offset” for selection. When select “Offset”,
there must be a original value for reference. Please refer the illustration
below.
[Direction]
To select the bar graph direction, and there are ”Up”, “Down”, “Right”,
and “Left” for selection.
[Zero]、[Span]
The filled bar percentage can be calculated with the following formula:
When select “Offset”, if (Register value – Zero) > 0, the bar will fill up
from origin setting; if (Register value – Zero) < 0, the bar will fill up but
down side from origin setting.
For example,
Origin =5, Span=10, Zero=0 and use different value in read address, it
will display as illustration below.
When read address value is 4,
249
EasyBuilder8000 User’s Manual
Bar To set the bar’s Frame, Background color, Bar style, and Bar color. See
color/style the picture below.
Target When the register value meets the following condition, the color of filled
Indicator area will change to the “Target color”
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of dynamic address.
Users can also set address in Outline tab while adding a dynamic
address.
250
EasyBuilder8000 User’s Manual
Alarm When register’s value is larger than [High limit], the color of filled area
Indicator will change to [High color], when register’s value is smaller than [Low
limit], the color of filled area will change to [Low color].
Target/Alarm When select [Enable], the [Low limit] and [High limit] of “Alarm indicator”
Dynamic and the [Target Value] of “Target indicator” all come from designated
Address register. See the picture below.
251
EasyBuilder8000 User’s Manual
The following table shows the read address of low limit, high limit, and
target. The “Address” means the device address, for example, if the
device address is [LW20] and data format is 16-bit,
The Target indicator is LW22 / The Zero is LW23 / The Span is LW24
252
EasyBuilder8000 User’s Manual
253
EasyBuilder8000 User’s Manual
Overview
The meter display object can display the value of word device with meter.
Configuration
Click the “Meter Display” icon on the toolbar and the “Meter Display Object’s Properties”
dialogue box will appear, fill in each items, press OK button, and a new “Meter Display
Object” will be created. See the picture below.
The picture below shows the “General” tab in the “Meter Display Object’s Properties”
dialogue box.
254
EasyBuilder8000 User’s Manual
Read address
Click [Setting…] to Select the [PLC name], [Device type], [Address], [System tag],
[Index register of the word devices that controls the display of meter.
Users can also set address in General tab while adding a new object.
255
EasyBuilder8000 User’s Manual
In the above dialogue box, users can set the meter display object’s outline. Refer to the
picture below for the names of each part of the meter.
256
EasyBuilder8000 User’s Manual
Setting Description
Degree Set the object’s “start degree” and “end degree”, the angle range is
0-360 degrees. The following pictures show several results of different
settings.
257
EasyBuilder8000 User’s Manual
otherwise the object will display the defined degree range. See the
picture below.
[Transparent]
When the “Transparent” is selected, the object will not display the
background and profile color. See the picture below.
Tick marks To set the tick mark’s number and color.
Pointer To set Pointer’s style, length, width, and color.
Pin point To set pin point’s style, radius, and color
The following pictures show the “Limit” tab and the sign of low and high limit set in the
“Limit” tab.
258
EasyBuilder8000 User’s Manual
Setting Description
Value To set object’s display range. Meter display object will use the value of
[Zero] and [Span] and the value of register to calculate the pointer’s
indication position. For example, supposed that [Zero] = 0, [Span] = 100,
when the value of register is 30 and [Start degree] = 0, [End degree] =
360, then the degree indicated by pointer is:
Pointer will indicate the position of 108 degrees. See the picture below.
259
EasyBuilder8000 User’s Manual
Range limit To set the value of low and high limit, the display color, width of the sign of
low, high limit.
[user-defined radius]
[Dynamic When “Dynamic limits” is not selected, the low limit and high limit are fixed
Limits] / value, which directly comes from the settings. See the example below, the
uncheck low limit is 30 and high limit is 60.
260
EasyBuilder8000 User’s Manual
[Dynamic When Dynamic limits is selected, the low limit and high limit are decided
Limits] / by the register.
check Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] for Dynamic limits.
Users can also set address in Limits tab while adding a new object.
There following table shows the read address of low limit and high limit.
The “Address” means the register’s address. If the register is [LW100],
the “Address” is 100.
261
EasyBuilder8000 User’s Manual
Overview
Trend display object can use the curve to represent the data recorded by data sampling
object. The sampling operation is conducted by data sampling objects. The trend display
object display the result of sampling. The following picture shows an example of trend
display object.
Configuration
Click the “Trend Display” icon on the toolbar and the “Trend Display Object’s Properties”
dialogue box will appear, fill in each items, press the OK button and a new “Trend Display
Object” will be created. See the picture below.
The following picture shows the “General” tab in the “Trend Display Object’s Properties”
dialogue box.
262
EasyBuilder8000 User’s Manual
Setting Description
[Data To select data sampling object as the source of data. Refer to the “data
Sampling sampling” section for related information.
Object index]
[Trend mode] To select the mode of data source. There are “Real-time” and “History”
for selection.
a. Real-time
In this mode, it can display the sampling data from the beginning of the
MT8000 operation to the present time. If previous data are required, you
must select the “History” mode to read the data from historical record.
You can use the “Hold control” object to pause the update of trend
263
EasyBuilder8000 User’s Manual
display, but it is only pause the update of the trend display, and it will not
stop the operation of data sampling object. The picture below shows the
“Hold control” setting page. Set the state of the designated register to
ON, it will pause the updating of the trend display.
b. History
In this mode, the data come from the historical record of the designated
data sampling object in [Data sampling object index]. Data sampling
object will use the sampling data which was sorted in according to dates.
The system use “History control” to select the historical records that are
created by the same data sampling object. The picture below shows the
“History control” setting page.
The system sorts the historical records of sampling data by date; the
latest file is record 0 (In normal condition it is sampling data today), the
second latest file is record 1, and so on.
264
EasyBuilder8000 User’s Manual
Select [Pixel], the [Distance] can be used to set the distance between
two sampling points. See the picture below.
Select [Time], the [Distance] is used to set the X-axis in unit of time
elapsed. See the picture below.
265
EasyBuilder8000 User’s Manual
Otherwise, select Time for X axis time range and go to Trend/Grid for
enable “Time scale” function. Please refer “Time scale” on the following.
Watch line
Using the “Watch line” function, when user touches the trend display
object, it will display a “watch line”, and export the sampling data at the
position of watch line to the designated word device. You may register a
numeric display object to display the result. Please refer to the following
picture
266
EasyBuilder8000 User’s Manual
“Watch line” function also can export sampling data of multiple channels,
The address registered in “watch line” is the start address and those
sampling data will be exported to the word devices starting from “start
address” The data format of each channel may be different, the
corresponding address of each channel is arranged from the first to the
last in sequence.
For example:
267
EasyBuilder8000 User’s Manual
Setting Description
[Frame] The color of frame.
[Background] The color of background.
[Show scroll To enable / disable scroll control on the bottom of trend display object.
controls]
When select [pixel] to set the display interval (see note on the above
268
EasyBuilder8000 User’s Manual
graph and “General” tab), the [Verti. interval] is used to select how many
sampling point will be included between two vertical grid line. See the
picture below.
b. Time
When select [Time] to set the time range of display data, the [Verti.
interval] is used to select the time range between two vertical grid lines.
See the picture below.
Time Scale
To enable the time scale on the bottom of trend display
[Format]
To select time scale as HH:MM or HH:MM:SS
[Font]
To select font style
[Size]
To select font size. Recommend use font size: 8.
269
EasyBuilder8000 User’s Manual
Time / Date The time of latest sampling data will be marked on the top left corner of
the object. It is used to set the time display format and color.
Setting Description
[Channel] Set each sampling line’s format and color, and the display data’s low
limit and high limit.
270
EasyBuilder8000 User’s Manual
sampling line, then [Zero] and [Span] must be set as [50] and [100],
so all the sampling data can be displayed in the trend display object.
Limit / check When Dynamic Limits is selected, the low limit and high limit are
“Dynamic derived from the designated word device. The data length of the
limits” word device for limits is related to the data format of object. In the
example below,
For example, the LW0 and LW1 are to control low limit and high limit, you may change the
value of LW1 to zoom in / out.
This following picture is in original size. The range of trend is between 0~30. The arrow on
the right side are set word (LW1, increment (JOG+) and LW1, decrement (JOG-)) for
control the zoom in and zoom out function.
271
EasyBuilder8000 User’s Manual
272
EasyBuilder8000 User’s Manual
Overview
“History Data Display” object displays data stored by data sampling object. It displays
history data in numeric format. Please note that the history data display will not refresh
automatically, it only retrieve the data from the designated record and display at the time
window popup. If the content of the designated record is updated, the history data display
will not change accordingly.
Configuration
Click the “History Data Display” icon on the toolbar, the “History Data Display” dialogue
box show up on the screen. Fill in each items and click OK button, a new object will be
created. See the pictures below.
273
EasyBuilder8000 User’s Manual
Setting Description
[Data Select the corresponding “Data sampling object” where the history data comes
Sampling from.
object
index]
Grid Set grid enable or disable.
274
EasyBuilder8000 User’s Manual
[Color]
Set color of grid.
[Column interval]
Set space of column.
Profile Set color of frame and background. If it is set as transparent, the frame and
color background will be ignored.
Time and Enable or disable the time and date of data sampling and format.
Date [Time ascending]
“Time ascending” means to put the earlier data in the top and the latest data in
the bottom.
275
EasyBuilder8000 User’s Manual
[Time descending]
“Time descending” means to put the latest data in the top and the earlier data
in the bottom.
History The history files are named with date code. The history control is used to
Control select the designated history data files for display. In case the value of history
control is 0, the latest file is selected. If it is 1, the second latest file is selected,
and so on.
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of History control.
Users can also set address in General tab while adding a new object.
276
EasyBuilder8000 User’s Manual
Each history data display object can display up to 20 channels. You can select the
channels which you want to watch on the screen.
In the example below, there are four channels in the data sampling object, Ch.0 and Ch.3
are selected for display only. The data format of each channel is decided by the related
data sampling objects.
277
EasyBuilder8000 User’s Manual
When display [String] format in history data display object, users may choose:
278
EasyBuilder8000 User’s Manual
Setting Description
[Use title] To enable or disable title.
Title [Transparent]
background To enable or disable transparent.
[Background color]
279
EasyBuilder8000 User’s Manual
You can use label tag library for title with multi-language. Go to [setting]
and select one from label library.
Note:
If you have run the off-line simulation and the sampling data is saved in the record, then
you want to change the format of sampling data, be sure to delete previous data record in
C:\EB8000\HMI_memory\datalog to avoid the system misinterpret the old data record.
280
EasyBuilder8000 User’s Manual
Overview
Data Block is a combination of several word devices with continuous address, for example
LW12, LW13, LW14, LW15 and so on. Use Data Block Display object to display multiple
data blocks in trend curve, for example, it can display two data blocks LW12~LW15 and
RW12~RW15 in trend curve simultaneously. It is very useful to observe and compare the
difference of trend curves.
281
EasyBuilder8000 User’s Manual
Configuration
[New object]
Click the “Data Block Display” icon , “Data Block Display’s properties” dialogue box
appears as follows:
Setting Description
[No. of Set the no of channel for this object. Each channel represents one data
channel] block. The max. no. of channel is 12.
Cursor Line Using the “Cursor line” function, when user touches the Data Block
display object, it will display a cursor line on the data block display object,
and transfer the position of cursor and the data at the cursor position to
282
EasyBuilder8000 User’s Manual
[Device type]
Select the device type where the target data block located.
0 = No action (default)
After executing the operation above, the system will reset the control word
to zero.
“No. of data” is to store the number of word device in each data block, i.e.
the number of data to plot in trend curve. The maximum value is 1024.
283
EasyBuilder8000 User’s Manual
[Format]
If you select 16-bit data format, the address of each data will be start
address, start address + 1, start address + 2 and so on.
If you select 32-bit data format, the address of each data will be start
address, start address + 2, start address + 4 and so on.
Limit Set the minimum and maximum limit of trend curve, the trend curve is
limited by the minimum and maximum limit.
284
EasyBuilder8000 User’s Manual
Setting Description
[Data Set the data samples, samples to scroll, frame and color of background.
samples]
285
EasyBuilder8000 User’s Manual
286
EasyBuilder8000 User’s Manual
Grid
287
EasyBuilder8000 User’s Manual
On line operation
a. Write the number of data to [No. of data address], i.e. “control word address+1”
b. Have the content of data block ready for display.
NOTE: data block start from “control word address + 2”.
c. Write “1” to [Control word address], the previous trend curve remains and the new
content in data block will be plot on the screen.
d. The system will write “0” to [Control word address] after the trend curve displayed.
____________________________________________________________________
____
NOTE : During the period between c and d, do not change the content of [Control], [No.
of Data] and [Data], it might cause error for trend curve plot.
a. Write “2” to [Control word address], all the trend curves will be cleared.
b. The system will write “0” to [Control word address] after the trend curve is cleared.
288
EasyBuilder8000 User’s Manual
How to clear the previous trend curve and display new one
a. Write the number of data to [No. of data address], i.e. “control word address+1”
b. Have the content of data block ready for display.
Note: data block start from “control word address + 2”.
c. Write “3” to [Control word address], the previous trend curves will be cleared and
the new content in data block will be plot on the screen.
d. The system will write “0” to [Control word address] after the trend curve displayed.
289
EasyBuilder8000 User’s Manual
If “offset to start address” is selected, the “Data storage start address” will be calculated
from “control word address + [Offset value storage address]”. “Offset value storage
address” is “control word address +2”.
In the following example, the content of “Offset value storage address” is “m”, therefore
the data block is started from the address “control word address + m”.
____________________________________________________________________
____
NOTE If the control register is 32 bits device, only bit 0-15 will be used as control
purpose, bit 16-31 will be ignored. (as illustration below)
If you do not use “offset to start address”, the system will continuously
read [Control] and [No. of Data]. At the time [Control] is changed to
non-zero, the system will then read the data block. If you use “offset to
start address”, the system will continuously read [Control], [No. of Data]
and [Offset].
290
EasyBuilder8000 User’s Manual
with multiple channels and the same device type. You can register
[Control], [No. of Data] and [Offset] in continuous address for each
channel. The system will read the control words of all the channels in
one read command and it shall speed up the response time.
You may use the “Watch” function to check the value of any point in trend curve. When
operator touches the data block object, it will display a “Cursor line”, the system will
write the index and value of that data in cursor line to the designated address. The user
291
EasyBuilder8000 User’s Manual
shall register NI objects with the designated address. The operator shall be able to
observe the numeric value in across with the cursor line.
In the following example, the data block display contains two data blocks. The data
format of channel 1 is 16 bit BCD and that of channel 2 is 32 bit unsigned. The cursor is
positioned in data index 3 which is corresponding to the fourth data in data block. The
system writes “data index” and the content of watched data to the watch address as
shown in the following picture.
____________________________________________________________________
____
NOTE 1. [Data Index] is a 16 bit unsigned integer; when the designated register of
cursor line is 32 bit device, it will be stored in the bit 0-15.
2. The watch function can only inspect current value in the data block. If there
are multiple trend curves of the same channel on the screen, the data of
previous trend curves is not exist, only the latest value is available for watch.
3. If the trend curve is cleared, when position the cursor line, the “0” will be
displayed as shown below.
292
EasyBuilder8000 User’s Manual
4. If there are only three data in Channel 1, when position the cursor in Data 4,
the “0” will be displayed as shown below.
Limitation:
1. The maximum number of channels is 12.
2. The system can draw up to 32 trend curves.
3. The system can draw up to 1024 points for each channel.
293
EasyBuilder8000 User’s Manual
13.20 XY Plot
Overview
XY Plot object displays two dimension data. Each data contains X and Y values and each
curve is composed of a stream of XY data. The maximum number of trend curves in a XY
plot is 16 channels.
Configuration
[New object]
Click the “XY plot” icon , and “XY Plot Object” dialog box appears.
294
EasyBuilder8000 User’s Manual
Setting Description
General a. Direction: There are four selections, right, left, up or down.
Right: Left:
295
EasyBuilder8000 User’s Manual
Up: Down:
b. No. of channel.
Set the no. of channels of the XY plot. Each channel may conduct the
draw operation alone.
Control [PLC name]
address Select the PLC where the control address coming from
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of Control address.
Users can also set address in General tab while adding a new object.
[Device type]
Select the device type where the control address coming from.
[Control address]
“Control address” is used to control the display of XY curve for each
channel.
1= Plot XY curve
Write ”1” to control address, the system will plot the XY curve, the
previous XY curve if exists would not be clear. The system will reset the
control address after operation complete.
296
EasyBuilder8000 User’s Manual
[PLC address]
297
EasyBuilder8000 User’s Manual
If you check “Separated address for X and Y data”, it allows you to set
different address for X and Y axis respectively.
298
EasyBuilder8000 User’s Manual
Limits The above settings are based on dynamic limits, you can also have
dynamic limits disable and set the fix high and low limits.
The high and low limits is used as scale to calculate the percentage of X
and Y axis. i.e. X or Y % = ( X or Y reading value – low limit ) /
( high limit – low limit )
Based on your settings, the memory allocation for limit and XY data will
be as follows.
The following setting is for 16-bit signed data format and dynamic limits.
The following setting is for 32-bit float data format and dynamic limits.
299
EasyBuilder8000 User’s Manual
NOTE
There are four different type of selection to designate memory location for
high/low limits and XY data. Please refer to the following settings.
300
EasyBuilder8000 User’s Manual
If dynamic limit is checked, you may change the high and low limits to
realize zoom in and zoom out function. (Please refer trend display
object’s dynamic limit.)
In the following example, the dynamic limit is selected, where XL=X low
limit, XH=X high limit, YL=Y low limit, YH=Y high limit, and XY, XY1, XY2
are three XY data. Now we change the high limit of X and Y respectively
and you may observe the effect of zoom in and zoom out.
301
EasyBuilder8000 User’s Manual
302
EasyBuilder8000 User’s Manual
Setting Description
Profile Enable Transparent: It will not display the background color.
color Disable Transparent: It will display the background color
Curve Set the attribute of XY curve (color and width) for each channel.
303
EasyBuilder8000 User’s Manual
Maker There are four different type of XY plot, i.e. Line, Point, X-axis projection and
Y-axis projection, check one of them.
For Line and Point selection, set appropriate point width (unit in pixels).
Remarks:
Please refer to the figure below, there is a curve containing 7 points from P0
304
EasyBuilder8000 User’s Manual
to P6. The system carries out X-axis projection with following steps:
a. Automatically calculate two projected points in X-axis – (X0, 0) and (X6, 0).
b. Link all these points in the order of (X0, 0), P0, P1… P6, (X6, 0) and returns
to (X0, 0) at last.
c. Fill out all enclosed areas formed.
X-axis projection :
305
EasyBuilder8000 User’s Manual
Reference In order to make the XY plot more readable, you can configure up to 4
line horizontal reference lines on the graph. Fill in high, low limit and Y axis
coordinate for each reference line.
You may also use PLC address to define high and low limit.
306
EasyBuilder8000 User’s Manual
Note:
XY Plot can be drawn repeatedly up to 32 times:
1 channelÎ32 times
2 channelsÎ16 times
The way to calculate: 32 divided by the number of channels
307
EasyBuilder8000 User’s Manual
Overview
Alarm bar and Alarm display objects are used to display alarm messages. Alarm
messages are those events registered in the “Event log” and meet trigger conditions.
Alarm bar and Alarm display objects display these alarms in order of priority and triggering
time.
Alarm bar object scroll all alarm messages in one line, alarm display object displays alarm
messages in multi-line and each line represents one alarm message. The following
pictures show that the alarm message are displayed in alarm display and alarm bar
objects. Refer to the “Event Log” chapter for related information.
Configuration
Click the “Alarm bar” icon on the toolbar, the “Alarm bar” dialogue box appears; similarly,
click the “Alarm display” icon on the toolbar, the “Alarm display” dialogue box appears, fill
in the setting in the “General tab” and press the OK button, a new object will be created.
See the pictures below.
308
EasyBuilder8000 User’s Manual
Setting Description
Include Select category of events that belongs to the alarm display or alarm
categories bar object. (category of an event is set in event log)
309
EasyBuilder8000 User’s Manual
[Time ascending]
Put the latest trigger alarm message in the bottom.
[Time descending]
Put the latest trigger alarm message in the top.
b. Order & Characters
Users can decide the display item, and how the item display order.
c. Date (Event trigger date)
Display the date tag with alarm message. There are four formats of
date tag.
Display the time tag with alarm message. There are three formats of
time tag.
Set font and color of alarm message in the “Font” tab. See the picture below.
310
EasyBuilder8000 User’s Manual
311
EasyBuilder8000 User’s Manual
Overview
Event display object displays active and finished events. The events are registered in
“Event log” object. The active events are the events which are in trigger condition, or have
been triggered and unacknowledged.
The event display object displays those active events in the order of trigger time. See the
picture below. Event display object can also display the time of the events been triggered,
acknowledged and recovered.
Configuration
Click the “Event Display” icon on the toolbar, the “Event Display” dialogue box appears, set
each items in the “General” tab, press OK button and a new “Event Display Object” will be
created. See the pictures below.
312
EasyBuilder8000 User’s Manual
Setting Description
[Mode] Select the event source format, there are “Real-time” and “History” for
selection.
a. Real-time
Write address
This displays the events in the log triggered from HMI starts up till
present. When the events are acknowledged, the value in [Alarm (Event)
Log]/ [Message]/ [Write value for Event Display object] will be exported
313
EasyBuilder8000 User’s Manual
b. History Control
[Enable reading multiple histories] not selected.
In this mode it displays event log from history record. The system save
the event history in daily basis. The event history of each date is saved
in separated files with date tags attached. The “History control” is used
to select one history record file.
The picture below shows the “History control” setting, which designates
a word device for “History control”.
314
EasyBuilder8000 User’s Manual
3 EL_20061120.evt
a. Number of days
The range of History Data to be displayed will start from number in LW0.
The value in LW1 represents how many days to be included from the
start to days before.
Example: As illustrated below, if value of LW0 is “1”, LW1 is “3”, then the
range of data will start form 20100609, and include data of 2 days before
(while 20100609 itself is counted). We can see that in this example,
since data of 20100607 does not exist, the data displayed will only
include 20100609 and 20100608.
315
EasyBuilder8000 User’s Manual
Range of data to be displayed will take value in LW0 as a start point and
value in LW1 as an end.
Example: if value in LW0 is “1”, and LW1 “3”, the displayed data will start
from No. 1, and include 3 history data (No.1, No.2, No.3).
The maximum size of data that can be displayed by system is 4MB; the
exceeding part will be ignored.
The following shows how data will be stored while the data size is too
big.
Example:
a. 5 history data, each with a size of 0.5MB Æ The size of data to be
displayed will be 5 x 0.5MB
b. 5 history data, each with a size of 1MB Æ The size of data to be
displayed will be 4 x 1MB
c. 5 history data, each with a size of 1.5MB Æ The size of data to be
displayed will be 2 x 1.5MB+1 x 1MB (partial)
Definition:
1. To select confirmed or recovered events to be displayed or
hidden.
2. In [Real- time] mode, select events to be deleted.
316
EasyBuilder8000 User’s Manual
Illustration:
317
EasyBuilder8000 User’s Manual
Setting Description
Include Select category of events that belongs to the event display object.
categories (category of an event is set in event log)
For example, if the category of an event log display is set to 2~4, it will
display all the active event messages with “category” equal to 2, 3, or 4.
318
EasyBuilder8000 User’s Manual
Acknowledge You may select “Click” or “Double click” to acknowledge a new event.
style When a new event comes up, the operator can “Click” or “Double click” to
acknowledge the new event, the system will change the text color of that
event and export the “write value” registered with the event to the
designated register.
Take use of this feature, the user can register a popup window and put
the warning message in the window, then configure an indirect window
object, when the event is acknowledged, the “write value” is written into
the read address of the indirect window and call up the popup window.
Max. event The maximum number of events to be displayed in the event display
no. object. When the number of events is larger than the maximum, the oldest
event will be removed from the event display object.
Color Set the color of events in different states.
a. Acknowledge
b. Return to normal
c. Select box – The system draw a highlight box around the latest
acknowledged event.
319
EasyBuilder8000 User’s Manual
Format
a. Sort
[Time ascending]
[Time descending]
Users can decide the display item, and how the item display order.
c. Date [Event trigger date]
Display the date tag with alarm message. There are four formats of date
tag.
Display the time tag with alarm message. There are three formats of time
tag.
The font tab sets the font size and italic attribute. The font of event message is set with the
event log object.
320
EasyBuilder8000 User’s Manual
Overview
Data Transfer (Trigger-based) object can transfer values from the source registers to the
destination registers. The data transfer operation can be activated by pressing the object
or setting a trigger bit.
Configuration
Click “Data Transfer (Trigger-based) object” icon on the toolbar, “Data Transfer
(Trigger-based) object” dialogue box will show up, set each item in the “General” tab,
press OK button, a new Trigger Data Transfer object will be created. See the picturea
below.
321
EasyBuilder8000 User’s Manual
Setting Description
Source Set source address of data transfer.
address Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of Source address.
Users can also set address in General tab while adding a new object
Destination Set the destination address of data transfer.
address Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of Destination address.
Users can also set address in General tab while adding a new object
322
EasyBuilder8000 User’s Manual
a. Touch trigger
Press the object to activate data transfer operation.
b. External trigger
Register a bit device to trigger the data transfer operation.
[ON → OFF]
Bit device change from ON to OFF to activate data transfer operation.
[OFF → ON]
Bit device change from OFF to ON to activate data transfer operation.
[ON ←→ OFF]
Bit device change state to activate data transfer operation.
323
EasyBuilder8000 User’s Manual
13.24 Backup
Overview
The backup function can store the recipe data (RW, RW_A), event log and sampling data
to USB device or Remote backup server. The [LB-9039] represents the backup status,
when backup operation is in progress, the status of [LB-9039] is ON.
Configuration
Click “Backup Object” icon on the toolbar, the “Backup Object” dialogue box will show up.
See the pictures below.
324
EasyBuilder8000 User’s Manual
Setting Description
Source [RW], [RW_A], [Historical event log], [Historical data sampling]
Select one from the above for the source. There may be several data
sampling objects registered in the project. If you select [Historical
data log], use “Data Sampling object index:” to select the right one
as shown below.
325
EasyBuilder8000 User’s Manual
Backup Select the destination where the source files will be copied to.
Position
a. USB1 or USB2 or SD card
The external device connected to HMI.
Save format User can select the desired format to back up the file.
a. MT8000 Event Log File (*.evt) / MT8000 Data Log File (*.dtl)
When back up event log in csv format, users can find data fields in
EXCEL as below.
326
EasyBuilder8000 User’s Manual
327
EasyBuilder8000 User’s Manual
a. Touch trigger
Touch the object to activate backup operation.
[ON → OFF]
Bit device change from ON to OFF to activate backup operation.
[OFF → ON]
Bit device change from OFF to ON to activate backup operation.
[ON ←→ OFF]
Bit device change state to activate backup operation.
Trigger address
When use “External trigger”, assign an appropriate bit device as
shown below.
328
EasyBuilder8000 User’s Manual
to LW-0):
backup.
LW-1: The data in this address is for specifying the start date of
backup.
LW-2: The data in this address is for specifying the number of days
for backup.
329
EasyBuilder8000 User’s Manual
330
EasyBuilder8000 User’s Manual
For the first time using Media Player object, it’s necessary to download the project to the
HMI via Ethernet. EasyBuilder8000 will install Media Player drivers during the download.
Overview
The Media Player function is not only used to play video files but also to provide uses of
additional controls such as seeking, zooming, volume adjusting and so on. With the Media
Player, users can provide operation and maintenance instructions or standard procedures
on video, which can help to create an environment that enables any on-site operators to
perform tasks efficiently from clear, comprehensible instructions. (Note: The Media Player
function is only available on the MT8000X Series models.)
Configuration
Click “Media Player object” icon on the toolbar, “Media Player object” dialogue box show
up, set each item in the “General” tab, press OK button, a new Media Player object will be
created. See the pictures below. (Note: The instruction of this section is an example to
play a video file located in the “/example” directory.)
331
EasyBuilder8000 User’s Manual
General tab:
Click [Setting…] to Select the [PLC name], [Device type], [Address],
[System tag], [Index register] of Control address.
Users can also set address in General tab while adding a new object.
a. In [Control address], select [Enable] and register a word device to control the
operation of media player object (example:LW0)
332
EasyBuilder8000 User’s Manual
d. In [Attribute], unselect [Auto. repeat] and choose black as the background color.
Preview tab:
Users can examine whether the MT8000 supports the video format via preview
function.
333
EasyBuilder8000 User’s Manual
a. Click [Load…] and select the file to be examined. (Users should put the file in the
/example directory of an USB disk)
b. If the media player starts playing the video, it means the MT8000 supports this
video format. Use [<<] and [>>] to navigate video by 1 minute each time.
c. To play another video, click [Stop] to close the video file and repeat from step a.
a. Set [Parameter 1] to 0.
b. Set [Command] to 1, the system will open the video file and start playing.
c. After the system start operation, it will reset the [Command] to ”0”.
____________________________________________________________________
334
EasyBuilder8000 User’s Manual
Note
During the period between step b and c, don’t change the content of [Command],
[Parameter 1], and [Parameter 2], it may cause unpredictable result.
____________________________________________________________________
a. Set [Command] to 5, the system will stop playing and close the video file.
b. After the system complete step a, it will reset the [Command] to ”0”.
____________________________________________________________________
Note
During the period between step a and b, don’t change the content of [Command],
[Parameter 1], and [Parameter 2], it may cause unpredictable result.
____________________________________________________________________
335
EasyBuilder8000 User’s Manual
General tab:
Setting Description
Enable control z Enable
address a. You can use “Control address” to control the
operation of media player
b. Register a device address for “Control
Control
address”.
address
z Disable
There is no manual control of video play
operation. The system will start to play the first
336
EasyBuilder8000 User’s Manual
Note
337
EasyBuilder8000 User’s Manual
Control command:
Note 1. The files are sorted with file name in ascending order, the “file index=0” is for
to the first file, and son on.
2. If it is unable to scan file, it will set [status] bit 8 to ON.
3. If check [Auto. repeat], it will automatically play the next file after finish.
Note 1. If the [file index] is previously 0, it will re-play the same video from the start.
2. If it is unable to search the right file, it will set [status] bit 8 to ON.
3. If check [Auto. repeat], it will automatically play the next file after finish.
338
EasyBuilder8000 User’s Manual
Note 1. If there is no next video file, it will play the first (index 0) file.
2. If it is unable to search the right file, it will set [status] bit 8 to ON.
3. If check [Auto. repeat], it will automatically play the next file after finish.
Note Parameter 1 (target location) should less than end time. If it is over end time,
the system play video from last second.
g. Forward
[Command] = 7
[Parameter 1] = target location (sec)
[Parameter 2] = ignore (set 0)
h. Backward
[Command] = 8
339
EasyBuilder8000 User’s Manual
i. Adjust volume
[Command] = 9
[Parameter 1] = volume (0 ~ 128)
[Parameter 2] = ignore (set 0)
340
EasyBuilder8000 User’s Manual
15 09 08 02 01 00
bit
Reserved (all 0) 0 0 0 0
Bit 00: open file bit (0: file closed;1: file opened)
Bit 01: play file bit (0: not playing video;1: playing video)
Bit 08: command error bit (0: command accepted;
1: incorrect command or parameters)
Bit 09: file error bit (0: file format accepted;
1: unknown file format or reading file error)
When playing a video, the system will turn ON [open file bit] and [play file bit]. If the
file is unable to be scanned or the command is incorrect, the [command error bit]
will be set ON (0Æ1).
Note 1. If file format is unsupported or disk I/O error happens during playing (e.g.
user unplugs the USB disk), the [file error bit] will be set ON (0Æ1).
2. Refer to the following figure, the value of [status] at each state would be:
“Stop” [status] = 0
“Pause” [status] = 1 ([open file bit])
“Playing” [status] = 3 ([open file bit] + [play file bit])
Playing
play command
(1, 2, 3) stop command switch pause command
(5) (4)
Finish playing
Stop Pause
stop command (5)
Users should only set values to [Command], [Parameter 1] and [Parameter 2], and regard
the other registers as read-only.
Restrictions
341
EasyBuilder8000 User’s Manual
The system can only play one video file each time.
If [Auto. repeat] is unselected, the system will stop playing video and close the file
after complete a video play operation.
If [control address] is unselected, the system will find the first file in the designated
directory and start playing it.
342
EasyBuilder8000 User’s Manual
Overview
Data transfer (Time-based) object is the same as Data transfer (Trigger-based) object, it
also transfers the data from source to destination register. The difference is the way to
activate data transfer operation. The Data transfer (time-based) object conducts data
transfer operation based on time schedule, it can also transfer data in the unit of bits.
Configuration
Click “Data Transfer (Time-based) Object” icon on the toolbar, the summary of data
transfer objects is shown as follows:
Press the “New…” button in the above dialogue box, the Data Transfer (Time-based)
Object dialogue box appear as shown in the picture below, set item and press OK button,
the object will be created.
343
EasyBuilder8000 User’s Manual
Setting Description
Attribute [Address type]
Select the bit or word device.
[No. of words] or [No. of bits]
When select “Word type”, the unit of data transfer is word, set the number
of data to transfer. See the picture below.
When select “Bit type”, the unit of data transfer is bit, set the number of
data to transfer. See the picture below.
344
EasyBuilder8000 User’s Manual
[Interval]
Select the wait interval for each data transfer, for example, select 3
seconds, the system will conduct data transfer operation every 3 seconds.
Note
1. Specifying a small interval or a big number of data to transfer may
cause an overall performance decrease due to the time consuming
in transferring data. Therefore, users should always try to choose a
longer interval and a smaller amount of data to transfer.
After completing all settings and pressing the “OK” button, a new Data Transfer
(Time-based) Object is created. The summary displays all the registered data transfer
objects with brief information as shown below.
345
EasyBuilder8000 User’s Manual
Overview
The PLC control object activates a specific operation when the corresponding control
device is triggered.
Configuration
Click the “PLC Control” icon and the “PLC Control Object” summary appears as shown
below.
Press the “New…” button and the “PLC Control” dialogue box appears. Set all the
attributes of PLC control and press OK button, a new PLC control object will be created.
346
EasyBuilder8000 User’s Manual
Setting Description
Attribute & [Type of control]
Trigger To set the type of control. Click the select button and you can drag down a
address list of all available PLC control functions
a. “Change window”
This is used to change base window. When the value of [Trigger address]
is written in a valid window number, the system will close the current
window and open the window designated by the [Trigger address]. The
347
EasyBuilder8000 User’s Manual
If you use 32-bit device as trigger address, and the device type of the
trigger address is in word basis, then the system will write the window
number into [Trigger address +2].
Below is the list of write address for each different type of data format.
Note: If [LB-9017] = ON, the write back operation will not be executed.
If “Clear data after window changed” is selected, the [Trigger address] will
be reset to 0 after new window is open.
b. “Write data to PLC (current base window)”
When the system changes the base window, the new window number will
348
EasyBuilder8000 User’s Manual
With this function the system uses four continuous word devices, please
refer to the following explanation.
349
EasyBuilder8000 User’s Manual
Set [Trigger address] to “ON”, the system will turn on/off the backlight and
reset the [Trigger address]. Any touch on the screen will turn the backlight
on.
e. “Back light control”
This operation is the same as “Back light control (write back)” except the
system would not reset the [Trigger address].
e. “Sound control”
Activate the [Trigger address], the system will play the sound.
You may configure three different ways to activate the [Trigger address ]:
Activate the [Trigger address], the system will execute the Macro.
You may configure three different ways to activate the [Trigger address ]:
350
EasyBuilder8000 User’s Manual
h. “Screen hardcopy”
Activate the [Trigger address], the system will have designated window
printed out.
You may configure three different ways to activate the [Trigger address ]:
351
EasyBuilder8000 User’s Manual
Note
1. The system performs a background printing process when the
printed window is not the current base window.
2. For a window designed to be printed at background, users should
put neither direct window nor indirect window in it.
352
EasyBuilder8000 User’s Manual
13.28 Schedule
Overview
Schedule object is used to turn on/off a bit or write a value to a word device at designated
time. The time schedule setting is very flexible, it can be on daily basis or weekly basis.
For more advance application you can use a table (a block of word devices) to set start
and terminate time, then update the table at any scheduled time.
Configuration
Click the “Schedule” icon on the toolbar and the “Scheduler list” dialogue box will appear,
press the “New”, the schedule object dialogue box will appear as shown below:
353
EasyBuilder8000 User’s Manual
Example 1:
The motor is scheduled to be power ON at 8:00 and power off at 17:00, Monday to Friday.
Here we use LB100 to control the motor. Follow the steps to set up the schedule object.
354
EasyBuilder8000 User’s Manual
[General tab]
[Power-ON start/end action]
Detail message please refer to below Scheduler settings guide.
355
EasyBuilder8000 User’s Manual
4. Unselect [Setting on individual day]. In [Start], adjust time as 8:00:00 and select
Monday to Friday.
6. Click [OK], a new schedule object is created and display on the schedule list.
356
EasyBuilder8000 User’s Manual
Example 2:
Set temperature at 90F at 8:00 and set it back to 30F (standby mode) at 17:00, Monday to
Friday.
357
EasyBuilder8000 User’s Manual
Click [New…], to add a new schedule object. Follow the steps to set up the schedule
object. The [LW100] is used to store set value of temperature.
[General tab]
1. [Power-ON start/end action]
358
EasyBuilder8000 User’s Manual
4. Check [Constant] and set [Write start value] to 90 in [Word write value settings],
6. Unselect [Setting on individual day]. In [Start], adjust time as 8:00:00 and select
Monday to Friday.
359
EasyBuilder8000 User’s Manual
8. Select [General] tab, set [Write start value] to 90 and [Write end value] to 30.
General tab
360
EasyBuilder8000 User’s Manual
Setting Description
Action Mode Select the type of operation performed at designated time.
[Bit ON] At start time, turn ON the specific bit. At end time, turn OFF the bit.
Example: Start time = 09:00:00
End time = 17:00:00
ON
OFF
[Bit OFF] At start time, turn OFF the specific bit. At end time, turn ON the bit.
Example: Start time = 09:00:00
End time = 17:00:00
Start time End time
ON
OFF
[Word write] At start time, the specific [Write start value] is written to the action
address. At end time, [Write end value] is written to the action
address.
Example: Device address = LW100
Start time = 09:00:00
End time = 12:00:00
Write start value = 10
Write end value = 0
361
EasyBuilder8000 User’s Manual
LW100 10 LW100 0
09:00:00 12:00:00
Action address Specify the address where the scheduler performs actions on.
362
EasyBuilder8000 User’s Manual
Setting Description
Power-ON Select the action to perform when power is turned on.
start/end z Enable
action If the MT8000 power is turned ON within the scheduler range, the
start action is performed. If the MT8000 power is turned ON
outside of the scheduled range, the termination action is
performed.
Inside the scheduled range:
z Disable
If power is turned ON but the time is later than the Start Time, the
action is not automatically performed. However, the termination
action is automatically performed.
Also, if the termination action is not set, the schedule range is
unable to recognize and the action is not performed.
Word write These settings are active only when Action Mode is set to [Word
value Settings Write].
363
EasyBuilder8000 User’s Manual
When performing start action, the system will write this value into
action address.
[Write start value]
z For [Constant]
Designates the value to be written at start time.
z For [Address]
Designates the address used to store the start time value.
[Write end value]
When performing end action, the system will write this value into
action address.
z For [Constant]
Designates the value to be written at end time.
z For [Address]
Designates the address used to store the end time value.
Note
z You can use this option if the [Enable termination action] in [Time
Set] tab is selected.
364
EasyBuilder8000 User’s Manual
Setting Description
Constant/Addres Select the method to set the start time and end time.
s z Constant
Specifies a fixed time and day.
z Address
The start/end time is retrieved from the device address at on
line operation.
Setting on z Enable
individual day Start time and end time can be set in different day of week.
There is only one start time and one end time during the week.
You have to set both start time and end time with this mode.
365
EasyBuilder8000 User’s Manual
Monday
Tuesday
NOTE
1. You must enter settings for the Start Time and End Time.
2. You cannot set the Start Time and End Time to the exact
same day and time.
z Disable
A schedule that is 1 day (Start and End times are within 24
hours) can be entered. Multiple Start and End days can be
selected. You can perform actions at the same time on multiple
days.
Monday
Tuesday
NOTE
z You cannot set the Start Time and End Time to the exact same
day and time.
z The time scheduler is for one day only, so if the End Time is
earlier than the Start Time, the operation of End Time will be
performed on the next day.
366
EasyBuilder8000 User’s Manual
The day settings can only be set when [Setting on individual day] is
enabled.
367
EasyBuilder8000 User’s Manual
User designates the [Time setting address] as the top address used to store time settings
data. The 11 word devices are automatically allotted.
Normally the format of the above word devices is 16-unsigned integer. If a 32-bit word
device is chosen, only 0-15 bits are effective and users should zero the 16-31 bits.
368
EasyBuilder8000 User’s Manual
The layout of the Control word is shown below. Users set the [time acquisition
request bit] ON (0Æ1) to make the system reads the [Action mode], [Start time], and
[End time] and uses them as the new scheduled time.
15 0
Bit
Reserved (0 fixed) 0
Bit 00: time acquisition request bit (0: no action, 1: perform time read)
NOTE The system would not read start and end time data unless the [time
acquisition request bit] is set ON.
Bit 00: time acquisition complete bit (0: null, 1: read operation complete)
Bit 01: error notification bit (0: no error, 1: start or end time format is incorrect)
NOTE After system reads the time data and turns the [time acquisition complete bit]
ON, be sure to turn [Control] [time acquisition request bit] OFF. Once this bit is
turned OFF, the system will set both the [Status] [time acquisition complete bit]
and [error notification bit] to OFF.
369
EasyBuilder8000 User’s Manual
=communication time lag =HMI turn OFF the bit =user turn OFF the bit
15 02 01 00
Bit
Reserved (0 fixed) 0 0
NOTE 1. If [setting on individual day] is OFF, the system still reads all 11 word devices
but ignores the end time data.
2. If [setting on individual day] is ON, be sure to enter all start and end time
information. If 2 or more of the start/end day bits are turned ON simultaneously,
370
EasyBuilder8000 User’s Manual
an error occurs.
d. Start/End Day (Start Day: Time setting address + 3, End Day: Time setting
address + 7)
Designates the day used as a trigger for the start/termination action.
15 07 06 05 04 03 02 01 00 Bit
e. Start/End Time (Start Time: Time setting address + 4 to + 6, End Time: Time
setting address + 8 to + 10)
Set the time values used for the start/termination actions in the following ranges.
Hour: 0 - 23
Minute: 0 - 59
Second: 0 - 59
If you specify a value outside the range, an error will occur.
NOTE The time data format shall be 16-bit unsigned, system doesn’t accept BCD
format.
371
EasyBuilder8000 User’s Manual
Prohibit tab
Setting Description
Prohibit z Enable
MT8000 reads the bit status before performing start action. If
the bit is ON, the schedule action is not performed.
Sound z Enable
When performing start and termination action, the system will
simultaneously play the specified sound.
372
EasyBuilder8000 User’s Manual
Restrictions:
z Once the system execute start action, it will read [Write start address] and [Write end
address] altogether, after then, even you change the value of [Write end address], the
system would not use the new value.
z When the operator changes RTC data, for those schedule object with both start time
and end time setting, the system will check if the time update changes the status
from out of schedule range to within schedule range, if it is, the start action will be
performed.
z If there are several schedule objects registered the same start time or end time, when
time up the system will perform the operation from the first to the last in ascending
order.
z When [Time Set] are specified as [Address] mode, the system will read [control] word
periodically.
z When [Time Set] are specified as [Address] and start time and end time is over valid
range, the system may not execute operation properly.
z When [Time Set] are specified as [Address], the action will not start up until time data
update is success.
373
EasyBuilder8000 User’s Manual
Overview
An Option List displays a list of items that the user can view and select. Once the user
selects an item, the value corresponding to the item will be written to a word register.
There are two forms for this object – Listbox and Drop-down list. The listbox lists all items
and highlights the selected one. However, the drop-down list normally displays only the
selected item. Once the user touches it, the system will display a listbox (which is similar to
the one with Listbox style) beneath the object.
Configuration
Click the “Option List” icon , “Option List object properties” dialogue box appears as
follows:
374
EasyBuilder8000 User’s Manual
Set the number of items for the object. Each item represents a state
displayed in the list and a value to be written to the [Monitor
address].
[Background]
375
EasyBuilder8000 User’s Manual
There are Predefine, Dates of historical data, and Item address for
selection.
Predefine mode Monitor address
[Type]
376
EasyBuilder8000 User’s Manual
[Date]
Users should select the same data sampling object with the one
selected in Historical Trend-Display or Data-Display.
Note:
Item address When selecting [Item address], users have to correctly set the
mode content of [Control address] and [Item address].
Control address
[Address]
Set “1” to the data of the designated register of this address for
[Address] + 1
377
EasyBuilder8000 User’s Manual
Item address
[ASCII]
[UNICODE]
As for item length, it’s now restricted to less than 1024 when
[number of items] times [The length of each item].
Mapping tab
378
EasyBuilder8000 User’s Manual
Setting Description
Mapping table This table displays all available states/items, their item data
and values. To change the number of available items, please
refer to [Option list tab] Î [Attribute] Î [Item no.].
[Item]
[Value]
Here user can assign value for each item, basing on the
following two criteria:
379
EasyBuilder8000 User’s Manual
[Item data]
Users can assign data for each item. The option list object
displays the data of all items in the list for users to review and
select.
[Error state]
380
EasyBuilder8000 User’s Manual
13.30 Timer
Overview
Use timer variables to enable timer instructions. Timer variables consist of the following six
special variables.
Configuration
Click the “Timer” icon , “Timer object properties” dialogue box appears as follows:
381
EasyBuilder8000 User’s Manual
Mode Description
On delay Point 1: When the IN turns ON, the TI be turned ON and
the elapsed time ET increases. The Q remains OFF.
382
EasyBuilder8000 User’s Manual
383
EasyBuilder8000 User’s Manual
384
EasyBuilder8000 User’s Manual
13.31 Video In
MT8000X series provide Video Input function. Users can install surveillance camera, then
monitor the factory any time they want. The video images can also be stored in devices
and play them with Media Player, or analyze them on PC.
This function can be utilized in different aspects. Apart from monitoring factory, it can also
be used in driving device or Building Automation monitoring.
For hardware, MT8000X series provide 2 channels for Video Input. Users can freely switch
channels to monitor, and capture images without being influenced when pause playing.
The captured images will still be real-time external image input. The supported formats are
NTSC and PAL.
Setting Description
Use Definition: For inputting external video image into HMI and play
Control it with HMI.
385
EasyBuilder8000 User’s Manual
Function Illustration:
386
EasyBuilder8000 User’s Manual
387
EasyBuilder8000 User’s Manual
1:1 50%
NTSC 720 x 480 360 x 240
PAL 720 x 576 360 x 288
This function only supports NTSC and PAL format.
388
EasyBuilder8000 User’s Manual
Use this utility to edit messages that displays in popup message boxes.
Setting Description
Confirmation Display whenever security requires the user to confirm operation.
required
The [Message] shown on confirmation dialogue, and the text label of the 2
buttons [OK] and [Cancel], can all be set. Please use the same font for the
labels of [Message], [OK] and [Cancel]. Additionally, only when selecting
[Label Library] for [Message], the use of Label Library for [OK] and [Cancel]
389
EasyBuilder8000 User’s Manual
Deny Display when system tag LB-9196 (local HMI supports monitor function
write-command only) is turned ON.
Allow Display when system tag LB-9196 (local HMI supports monitor function
write-command only) is turned OFF.
390
EasyBuilder8000 User’s Manual
EB8000 provides Shape Library and Picture Library features to add visual effects on
objects. Each Shape and Picture includes up to 256 states. This chapter expatiates on
how to create Shape Library and Picture Library.
For usage of shape and picture library, please refer to “Chapter 9 Object General
Properties”.
A shape is a graph composed of lines, rectangles, and circles. A complete Shape can
possess more than one state, and each state can include two parts: frame and inner. See
the illustration below:
The frame and inner of a shape can be used separately or together by an object. Click
[Call up Shape Library], and the [Shape Library] dialogue appears as below:
391
EasyBuilder8000 User’s Manual
Setting Description
Library Shape Libraries which have been added into the current project.
Select the library source of a Shape from the list.
State Select the state to be displayed by current Shape. If the selected
Shape isn’t displayed, it means that the Shape does not exist or the
state of the Shape isn’t defined.
Select Lib. Click [Select Lib.], and the following dialog appears for users to
select the file path of the Shape Library to be added.
By previewing the content of the library right side of the window, users
can select suitable library.
392
EasyBuilder8000 User’s Manual
Unattach Lib. Click the button to delete the Shape Library in [Library] from current
project.
393
EasyBuilder8000 User’s Manual
The following shows how to create a new Shape Library and add a Shape with two states
to it.
Step 1
Click [New Lib.] and input the name of the new Shape Library.
A new Shape Library “TEST” will be added to the [Shape Library] dialogue. At this
moment, no Shape is in the library.
394
EasyBuilder8000 User’s Manual
Step 2
Add a state to the selected Shape. First, use the drawing tools to draw a graph in the
window and select the graph to be added to the Shape Library.
Chick the [Save to Shape Library] button in toolbar and the following dialogue appears.
Setting Description
Shape library Select the Shape Library for the graph to be added to. In this
example, “TEST” library is selected.
Description The name of the Shape.
Shape no. The number in Shape Library current graph will be added in.
State Select the state of the Shape which this graph represents. In this
case the state is set “0”. EB8000 provides 256 states for each
395
EasyBuilder8000 User’s Manual
Shape.
Frame If [Frame] is selected, the graph will become a frame of the
Shape.
Inner If [Inner] is selected, the graph will become an inner part of the
Shape.
This part shows the current status of the shape, at this moment shape [no. 0] in [state 0] in
library “Test” is with undefined frame and inner.
After clicking [OK], the graph will be added to Shape Library. Illustration below shows that
Shape [No.0] in library “Test” has only one state, [state0], and is defined as a frame.
Step 3
Likewise, create another Shape state by the same process as in Step 2, but this new
graph has to be defined as [state 1]:
396
EasyBuilder8000 User’s Manual
A complete Shape with two states is created. See the following picture.
397
EasyBuilder8000 User’s Manual
Click the [Call up Picture Library] button in toolbar, and the [Picture Library] dialogue
appears.
Setting Description
Library Picture Libraries which have been added into the current project.
Select the library source of a Picture from the list.
State Select the state that current graph represents. If the selected
Picture isn’t displayed, it means that the Picture does not exist or
the state of the Picture isn’t defined.
Select Lib. Click [Select Lib. ...] and the following dialog appears for users to
select the file path of the Picture Library to be added.
By previewing the content of the library right side of the window,
users can select suitable library.
398
EasyBuilder8000 User’s Manual
Unattach Lib. Click the button to delete the Picture Library in [Library] from the
current project.
399
EasyBuilder8000 User’s Manual
Note: The compatible picture format are *.bmp, *.jpg, *.gif, *.dpd, and *.png. When adding
a GIF picture in Picture Library, if this picture file is animated, the number of times to play
this animation can be set by users as below.
400
EasyBuilder8000 User’s Manual
The example below shows how to create a new Picture Library and add a Picture with two
states into it.
Step 1
Click [New Lib.] and input the name of the new Picture Library.
A new Picture Library “TEST” will be added to the [Picture Library] dialogue. At this
moment, there is no Picture in the library.
401
EasyBuilder8000 User’s Manual
Step 2
Prepare the pictures to be added; suppose the two graphs below are used to represent
state 0 and state 1 respectively.
Click [Import Picture] and a dialogue appears as below. Set [Picture no.] and [Picture
name] for it, and then click [Next].
Step 3
When the dialogue below is shown, select the source of picture for state 0, and select the
correct transparent color. In the example below, the blue color RGB (0, 0, 255) is a
transparent color. After the settings of the state 0 are completed, click [Next] button to
continue the settings of the other state.
402
EasyBuilder8000 User’s Manual
Before choosing transparent color, check [Transparent] box first and then left click on
location-to-be of the graph. At this time, EB8000 will automatically display RGB value of
the transparent color. Take above as an example, the actual shape shown as below:
Step 4
Likewise, select the source of a picture for state 1 and select the correct transparent color
for it. After the settings are completed, click the [Finish] button.
403
EasyBuilder8000 User’s Manual
Below shows the complete picture created. A new picture “F Yellow” can be found in the
[Picture Library] dialogue. From the information we know the picture is in the format of
bitmap and with two states.
404
EasyBuilder8000 User’s Manual
Label Library is used in the Multi-Language environment. Users can design the content of
Label Library to meet their demands. Select the suitable label from Label Library when text
is needed.
15.1 Introduction
The system in operation will display the corresponding text to the language in use
according to the settings. EB8000 supports 8 different languages simultaneously. Click
[Label Library Manager] and the dialogue appears as below:
Setting Description
State no. Indicates the current state; each Label has maximum of 256
states (state no. 0~255). The State no. is determined by
[Language no.] selected. If user use 8 languages, 256/8=32
405
EasyBuilder8000 User’s Manual
406
EasyBuilder8000 User’s Manual
In [Label Tag Library] users can see the existing tag and the languages this tag contains.
Different fonts can be selected for different languages.
[Font]
Under the Multi-Language configuration, users can select font type for each language.
[Comment]
Input the comment of each language.
407
EasyBuilder8000 User’s Manual
First of all, open the [Label Tab Library] dialogue and click [New…]. Correctly input the
settings as shown below and then click [OK].
[Label name]
The name of label. In this case it is set “Pump Alarm”.
[No. of states]
The number of states possessed by the Label.
When the process is complete, a new Label “Pump Alarm” with 2 states will be added to
the Label Library. See the picture below.
Select “Pump Alarm”, click [Settings …] and the [Label Tag Content] dialog appears for
users to set up the corresponding language content.
408
EasyBuilder8000 User’s Manual
409
EasyBuilder8000 User’s Manual
When there are already some defined labels in Label Library, users can find those Labels
in [Label tag] by selecting [Use label library] in the object’s [Label] tab.
When [Use label library] is selected, [Content] dialog shows the content of selected label
tag and the settings of Font type are also included in the Label Library.
410
EasyBuilder8000 User’s Manual
When users would like to have the object’s text to show multi-language, except for
using Label Library, it needs to use the system reserved register [LW-9134: language
mode]. The value of [LW-9134] can be set from 0 to 7. Different data of [LW-9134]
corresponds to different Languages. The way of using LW-9134 will differ if the languages
are not all chosen when compiling the downloaded file.
411
EasyBuilder8000 User’s Manual
Next, create a [Numeric Input] Object. Set its Read address as below: The Read address
in use is the system reserved register [LW-9134].
412
EasyBuilder8000 User’s Manual
When the value of [LW-9134] is changed, the content of the Text Object will also be
changed automatically.
413
EasyBuilder8000 User’s Manual
Setting Description
Customized Display the Address Tags defined by users.
System Display the Address Tags reserved by system.
New Add a new Address Tag.
Delete Delete a selected Address Tag.
Delete All Delete all current Address Tags.
Settings Modify the selected Tag.
Save Tag File Save all current Address Tags as .tgl file.
Load Tag file Load existing .tgl file to Address Tag Library.
Export CSV Export current Address Tag Library to the appointed space in CSV
format.
414
EasyBuilder8000 User’s Manual
Import CSV Import the saved CSV file of Address Tag Library to current project.
Export EXCEL Export current address tag library to the appointed space in XLS
format.
Import EXCEL Import the saved XLS file of address tag library to current project.
Before using the Address Tag Library, users need to add the content of the library first.
Click [New…], and the [Address Tag] dialogue appears as below:
Setting Description
Tag name The name of the Address Tag.
415
EasyBuilder8000 User’s Manual
PLC name The name of the PLC which is selected from the [device list].
Address type The type of Address; there are [bit] and [word] types available.
Device type The type of the device; the types available are related to [PLC
name] and [Address type].
Address The content of the address.
Click [OK] when the settings are done, and a new tag will be found in the [Customized]
library as below.
416
EasyBuilder8000 User’s Manual
After creating the Address Tag Library, select the related PLC in [General] tab while
adding a new object and click [Setting...]. Check [User-defined tag], the tags can now be
used as shown below.
When the settings are completed, the window tree will show the name of the Address Tag
used for the object as below.
417
EasyBuilder8000 User’s Manual
Recipe Data are stored in flash memory. When system start-up, both RW and RW_A
memory will be restored from the recipe data in flash memory. The way of reading and
writing Recipe Data is the same as operating the normal Word Register.
The size of Recipe Data in RW is 512K words, and RW_A is 64K words. User can update
Recipe Data with SD Card, USB flash drive, USB cable or Ethernet and use this data to
update data in PLC. It is possible to upload Recipe Data to the designated directory of PC;
furthermore, it can save the PLC’s data in recipe memory. The following explains all of the
ways of operating recipe data.
Click [Download] in Project Manager. Select [RW] and [RW_A] and designate the
directory of the source files. After downloading is completed, start up HMI again, and the
contents of RW and RW_A will be updated.
When [Reset recipe] is selected, before start downloading, EB8000 will set all the data of
[RW] and [RW_A] to “0” first.
418
EasyBuilder8000 User’s Manual
419
EasyBuilder8000 User’s Manual
Insert SD card or USB flash drive to PC and click [Browse…] to assign the file path and
then click [Build] to set all contexts of the download data. EB8000 will then build the
sources into SD card or USB flash drive.
Note: The path of download data should avoid designating root directory of PC. For
example, “c:\”, also, directory name such as “f:\\” is illegal and should be written as “f:\”.
420
EasyBuilder8000 User’s Manual
Use the [Data Transfer (Trigger-based) object] to transfer Recipe Data to the appointed
address, or save the data of the designated address in [RW] and [RW_A] as well. Please
refer to the [Data Transfer (Trigger-based) object] section for more information.
In order to prolong the life of flash memory of HMI, EB8000 will save Recipe Data
automatically every minute to avoid losing data when HMI shuts down. EB8000 provides
user with [LB-9029: save all recipe data to machine (set ON)] system register bit function
to save Recipe Data manually. EB8000 will save Recipe Data when user sets ON to
[LB9029]. But when user sets ON to [LB-9028: reset all recipe data (set ON)], EB8000 will
clear all Recipe Date and return to “0”.
421
EasyBuilder8000 User’s Manual
Macros provide the additional functionality your application may need. Macros are
automated sequences of commands that are executed at run-time. Macros allow you to
perform tasks such as complex scaling operations, string handling, and user interactions
with your projects. This chapter describes syntax, usage, and programming methods of
macro commands.
b. Undo / Redo
d. Select All
The instructions below show you how to use these new functions.
3. Open the macro editor; you’ll see the line numbers displayed on the left‐hand side of the edit
area.
422
EasyBuilder8000 User’s Manual
edit area
4. Right click on the edit area to open the pop‐up menu as shown below:
423
EasyBuilder8000 User’s Manual
The disabled items are colored grey, which indicates that it is not possible to use that function in
the current status of the editor. For example, you should mark a selected area to enable the copy
5. Above the edit area locates the toolbar. It provides “Undo”, “Redo”, “Cut”, “Copy”, “Paste”,
“Toggle Bookmark”, “Next Bookmark”, “Previous Bookmark” and “Clear All Bookmarks”
6. Modifications made to the editor will enable the undo function. Redo function will be enabled
after the undo action is taken. To perform the undo/redo action, right click to select the item
Undo
Undo
424
EasyBuilder8000 User’s Manual
Redo
Redo
7. Select a word in the editor to enable the cut and copy function. After cut or copy is performed,
425
EasyBuilder8000 User’s Manual
8. Use “Select All” to include all the content in the edit area.
426
EasyBuilder8000 User’s Manual
9. If the macro code goes very long, for easier reading, bookmarks are provided. The illustration
a. Move your cursor to the position in the edit area where to insert a bookmark. Right
click, select “Toggle Bookmark”. There will be a blue little square that represents a
b. If there’s already a bookmark where the cursor is placed, select “Toggle Bookmark” to
c. Right click and select “Next Bookmark”, the cursor will move to where the next
bookmark locates. Selecting” Previous Bookmark” will move the cursor to the previous
bookmark.
427
EasyBuilder8000 User’s Manual
Next Bookmark
Next Bookmark
Next Bookmark
10. Macro editor provides macro code outlining function, for easier viewing. This function is to
hide macro codes that belong to same block, and display them with an icon. There
will be a tree diagram on the left side of edit area. Users can click to hide the block or
428
EasyBuilder8000 User’s Manual
11. Right click to select “Toggle All Outlining” to open all macro code blocks.
429
EasyBuilder8000 User’s Manual
12. Sometimes the outlining might be incorrect since that the keywords are misjudged. For
example:
To solve this problem,right click to select “Update All Outlining” to retrieve correct outlining.
13. The statements enclosed in the following keywords are called a “block” of the macro code:
b. Reiterative statements:
i. for – next
c. Logical statements:
i. if – end if
430
EasyBuilder8000 User’s Manual
Macro must have one and only one main function which is the execution start point of
macro. The format is:
macro_command Function_Name()
end macro_command
Local variables are used within the main macro function or in a defined function block. Its
value remains valid only within the specific block.
Global variables are declared before any function blocks and are valid for all functions in
the macro. When local variables and global variables have the same declaration of name,
only the local variables are valid.
The example below is a simple Macro which includes a variable declaration and a function
call.
macro_command main()
short pressure = 10 // local variable declaration
SetData(pressure, "Allen-Bradley DF1", N7, 0, 1) // function calling
end macro_command
431
EasyBuilder8000 User’s Manual
18.3 Syntax
18.3.1.1Constants
Constants are fixed values and can be written directly into statements. The format is as
below:
Constant Type Note Example
Decimal integer 345, -234, 0, 23456
Hexadecimal Must begin with 0x 0x3b, 0xffff, 0x237
ASCII String must be enclosed in single ‘a’, ‘data’, ‘name’
quotes
Boolean true, false
macro_command main()
short A, B // A and B are variables
A = 1234
B = 0x12 // 1234 and 0x12 are constants
end macro_command
18.3.1.2 Variables
Variables are names that represent information. The information can be changed as the
variable is modified by statements.
432
EasyBuilder8000 User’s Manual
There are 8 different Variable types, 5 for signed data types and 3 for unsigned data types:
Declaring Variables
Variables must be declared before being used. To declare a variable, specify the type
before the variable name.
Example:
int a
short b, switch
float pressure
unsigned short c
Declaring Arrays
Macros support one-dimensional arrays (zero-based index). To declare an array of
variables, specify the type and the variable name followed by the number of variables in
the array enclosed in brackets “[]”. Arrays are 1 to 4096 variables in length. (Macros only
support up to 4096 variables per macro).
Example:
int a[10]
short b[20], switch[30]
float pressure[15]
433
EasyBuilder8000 User’s Manual
Minimum of array index is 0 and maximum of array index is (array size – 1).
Example:
char data 100] // array size is 100
where: minimum of array index is 0 and maximum of array index is 99 ( 100 – 1)
434
EasyBuilder8000 User’s Manual
Example:
int a
float b[3]
a = 10
b[0] = 1
2. During declaration
char a = ‘5’, b = 9
The declaration of arrays is a special case. The entire array can be initialized during
declaration by enclosing comma separated values inside curly brackets “{}”.
Example:
float data[4] = {11, 22, 33, 44} // now data[0] is 11, data[1] is 22….
18.3.2 Operators
Operations are used to designate how data is to be manipulated. In each statement, the
operator on the left is set to the conditions on the right.
435
EasyBuilder8000 User’s Manual
Shift and bitwise operators are used to manipulate bits within char, short, and int variable
types with both signed and unsigned. The priority of these operators is from left to right
within the statement.
436
EasyBuilder8000 User’s Manual
Reserved Keywords
The following keywords are reserved for Macro use. They cannot be used for variable,
array, or function names.
+, -, *, /, %, >=, >, <=, <, <>, ==, and, or, xor, not, <<, >>,=, &, |, ^, ~
exit, macro_command, for, to, down, step, next, return, bool, short, int, char, float, void, if,
then, else, break, continue, set, sub, end, while, wend, true, false
SQRT, CUBERT, LOG, LOG10, SIN, COS, TAN, COT, SEC, CSC, ASIN, ACOS, ATAN,
BIN2BCD, BCD2BIN, DEC2ASCII, FLOAT2ASCII, HEX2ASCII, ASCII2DEC,
ASCII2FLOAT, ASCII2HEX, FILL, RAND, DELAY, SWAPB, SWAPW, LOBYTE, HIBYTE,
LOWORD, HIWORD, GETBIT, SETBITON, SETBITOFF, INVBIT, ADDSUM, XORSUM,
CRC, INPORT, OUTPORT, POW, GetError, GetData, GetDataEx, SetData, SetDataEx,
SetRTS, GetCTS, Beep, SYNC_TRIG_MACRO, ASYNC_TRIG_MACRO, TRACE,
FindDataSamplingDate, FindDataSamplingIndex, FindEventLogDate, FindEventLogIndex
StringGet, StringGetEx, StringSet, StringSetEx, StringCopy, StringMid, StringDecAsc2Bin,
StringBin2DecAsc, StringDecAsc2Float, StringFloat2DecAsc, StringHexAsc2Bin,
StringBin2HexAsc, StringLength, StringCat, StringCompare, StringCompareNoCase,
StringFind, StringReverseFind, StringFindOneOf, StringIncluding, StringExcluding,
StringToUpper, StringToLower, StringToReverse, StringTrimLeft, StringTrimRight,
StringInsert
437
EasyBuilder8000 User’s Manual
18.4 Statement
This covers the declaration of variables and arrays. The formal construction is as follows:
type name where define the type of name
Example:
int A //define a variable A as an integer
Example:
int B[10] where define a variable B as a one-dimensional array of
size 10
Assignment statements use the assignment operator to move data from the expression on
the right side of the operator to the variable on the left side. An expression is the
combination of variables, constants and operators to yield a value.
Variable = Expression
Example
A=2 where a variable A is assigned to 2
438
EasyBuilder8000 User’s Manual
Single-Line Format
if <Condition> then
[Statements]
else
[Statements]
end if
Example:
if a == 2 then
b=1
else
b=2
end if
Block Format
If <Condition> then
[Statements]
else if <Condition – n> then
[Statements]
else
[Statements]
end if
Example:
if a == 2 then
b=1
else if a == 3 then
b=2
439
EasyBuilder8000 User’s Manual
else
b=3
end if
Syntax description:
if Must be used to begin the statement
<Condition> Required. This is the controlling statement. It is FALSE when the
<Condition> evaluates to 0 and TRUE when it evaluates to non- zero.
then Must precede the statements to execute if the <Condition> evaluates to
TRUE.
[Statements] It is optional in block format but necessary in single-line format without
else. The statement will be executed when the <Condition> is TRUE.
else if Optional. The else if statement will be executed when the relative
<Condition-n> is TRUE.
<Condition-n> Optional. see <Condition>
else Optional. The else statement will be executed when <Condition> and
<Condition-n> are both FALSE.
end if Must be used to end an if-then statement.
The select-case construction can be used to perform selective group of actions depending
on the value of the given variable. The actions under the matched case are performed until
a break command is read. The syntax is as follows.
Example:
Select Case A
440
EasyBuilder8000 User’s Manual
Case 1
b=1
break
end Select
end Select
Example:
Select Case A
Case 1
b=1
break
Case else
b=0
break
end Select
end Select
Example:
Select Case A
441
EasyBuilder8000 User’s Manual
Case 1
Case 2
b=2
Case 3
b=3
break
end Select
Syntax description:
Select Case Must be used to begin the statement
[variable] Required. The value of this variable will be compared to the value of
each case.
Case else Optional. It represents the default case. If none of the cases above are
matched, the statements under default case will be executed. When a
default case is absent, it will skip directly to the end of the select-case
statements if there is no matched case.
break Optional. The statements under the matched case will be executed until
the break command is reached. If a break command is absent, it simply
keeps on executing next statement until the end command is reached.
end Select Indicates the end of the select-case statements
Reiterative statements control loops and repetitive tasks depending on condition. There
are two types of reiterative statements.
The for-next construction is for stepping through a fixed number of iterations. A variable is
used as a counter to track progress and test for ending conditions. Use this for fixed
execution counts. The syntax is as follows:
442
EasyBuilder8000 User’s Manual
or
Example:
for a = 0 to 10 step 2
b=a
next a
Syntax description:
for Must be used to begin the statement
[Counter] Required. This is the controlling statement. The result of evaluating the
variable is used as a test of comparison.
<StartValue> Required. The initial value of [Counter]
to/down Required. This determines if the <step> increments or decrements the
<Counter>.
“to” increments <Counter> by <StepValue>.
“down” decrements <Counter> by <StepValue>.
<EndValue> Required. The test point. If the <Counter> is greater than this value, the
macro exits the loop.
step Optional. Specifies that a <StepValue> other than one is to be used.
[StepValue] Optional. The increment/decrement step of <Counter>. It can be omitted
when the value is 1 If [step <StepValue>] are omitted the step value
defaults to 1.
[Statements] Optional. Statements to execute when the evaluation is TRUE. “for-next”
loops may be nested.
next Required.
[Counter] Optional. This is used when nesting for-next loops.
443
EasyBuilder8000 User’s Manual
while <Condition>
[Statements]
wend
Example:
while a < 10
a = a + 10
wend
Syntax description:
while Must be used to begin the statement
continue Required. This is the controlling statement. When it is TRUE, the loop
begins execution. When it is FALSE, the loop terminates.
return [value] Statements to execute when the evaluation is TRUE.
wend Indicates the end of the while-end statements
break Used in for-next and while-wend. It skips immediately to the end of the
reiterative statement.
continue Used in for-next and while-wend. It ends the current iteration of a loop
and starts the next one.
return The return command inside the main block can force the macro to stop
anywhere. It skips immediately to the end of the main block.
444
EasyBuilder8000 User’s Manual
445
EasyBuilder8000 User’s Manual
Function blocks are useful for reducing repetitive codes. It must be defined before use and
supports any variable and statement type. A function block is called by putting its name
followed by parameters, in parenthesis, in the Main Macro Function. After the function
block is executed, it returns the value to the Main Function where it is used as an
assignment or condition. A return type is not necessary in definition of function, which
means that a function block is not always necessary to return a value. The parameters can
also be absent in definition of function while the function has no need to take any
parameters from the Main Function. The syntax is as follows:
Example:
sub int Add(int x, int y)
int result
result = x +y
return result
end sub
macro_command main()
int a = 10, b = 20, sum
sum = Add(a, b)
end macro_command
or:
result = x +y
return result
end sub
446
EasyBuilder8000 User’s Manual
macro_command main()
int sum
sum = Add()
end macro_command
Example:
int result
result = x +y
end sub
macro_command main()
int a = 10, b = 20
Add(a, b)
end macro_command
or:
sub Add()
result = x +y
end sub
447
EasyBuilder8000 User’s Manual
macro_command main()
Add()
end macro_command
Syntax description:
sub Must be used to begin the function block
type Optional. This is the data type of value that the function returns. A
function block is not always necessary to return a value.
(parameters) Optional. The parameters hold values that are passed to the function
by the Main Macro. The passed parameters must have their type
declared in the parameter field and assigned a variable name.
For example: sub int MyFunction(int x, int y). x and y would be
integers passed to the function by the Main Macro. This function is
called by a statement that looks similar to this: ret = MyFunction(456,
pressure) where “pressure” must be integer according to the definition
of function.
Notice that the calling statement can pass hard coded values or
variables to the function. After this function is executed, an integer
values is return to ‘ret’.
Local variable Variables that are used in the function block must be declared first.
declaration This is in addition to passed parameters. In the above example x and
y are variables that the function can used. Global variables are also
available for use in function block.
[Statements] Statements to execute
[return [value]] Optional. Used to return a value to the calling statement. The value
can be a constant or a variable. Return also ends function block
execution. A function block is not always necessary to return a value,
but, when the return type is defined in the beginning of the definition of
function, the return command is needed.
end sub Must be used to end a function block.
448
EasyBuilder8000 User’s Manual
EasyBuilder8000 has some build-in functions for retrieving and transferring data to the
PLC, data management and mathematical functions.
Name SQRT
Syntax SQRT(source, result)
Description Calculate the square root of source into result.
Source can be a constant or a variable, but result must be a variable.
Source must be a nonnegative value.
Example macro_command main()
float source, result
SQRT(15, result)
source = 9.0
SQRT(source, result)// result is 3.0
end macro_command
Name CUBERT
Syntax CUBERT (source, result)
Description Calculate the cube root of source into result.
Source can be a constant or a variable, but result must be a variable.
Source must be a nonnegative value.
Example macro_command main()
float source, result
source = 27.0
CUBERT(source, result)// result is 3.0
449
EasyBuilder8000 User’s Manual
end macro_command
Name POW
Syntax POW (source1, source2, result)
Description Calculate source1 raised to the power of source2.
Source1 and source2 can be a constant or a variable, but result must be a
variable.
Source1 and source2 must be a nonnegative value.
Example macro_command main()
float y, result
y = 0.5
Name SIN
Syntax SIN(source, result)
Description Calculate the sine of source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
float source, result
source = 30
SIN(source, result)// result is 0.5
end macro_command
Name COS
Syntax COS(source, result)
Description Calculate the cosine of source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
450
EasyBuilder8000 User’s Manual
source = 60
GetData(source, "Local HMI", LW, 0, 1)
COS(source, result)// result is 0.5
end macro_command
Name TAN
Syntax TAN(source, result)
Description Calculate the tangent of source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
float source, result
source = 60
TAN(source, result)// result is 1.732
end macro_command
Name COT
Syntax COT(source, result)
Description Calculate the cotangent of source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
float source, result
source = 60
COT(source, result)// result is 0.5774
451
EasyBuilder8000 User’s Manual
end macro_command
Name SEC
Syntax SEC(source, result)
Description Calculate the secant of source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
float source, result
source = 60
SEC(source, result)// if source is 60, result is 2
end macro_command
Name CSC
Syntax CSC(source, result)
Description Calculate the cosecant of source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
float source, result
source = 30
CSC(source, result)// result is 2
end macro_command
Name ASIN
Syntax ASIN(source, result)
Description Calculate the hyperbolic sine of source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
452
EasyBuilder8000 User’s Manual
source = 0.5
ASIN(source, result)// result is 30
end macro_command
Name ACOS
Syntax ACOS(source, result)
Description Calculate the hyperbolic cosine of source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
float source, result
source = 0.5
ACOS(source, result)// result is 60
end macro_command
Name ATAN
Syntax ATAN(source, result)
Description Calculate the hyperbolic tangent of source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
float source, result
source = 1.732
ATAN(source, result)// result is 60
end macro_command
453
EasyBuilder8000 User’s Manual
Name LOG
Syntax LOG (source, result)
Description Calculates the natural logarithm of a number.
Source can be either a variable or a constant.
Result must be a variable.
Example macro_command main()
float source = 100, result
end macro_command
Name LOG10
Syntax LOG10 (source, result)
Description Calculates the base-10 logarithm of a number.
Source can be either a variable or a constant.
Result must be a variable.
Example macro_command main()
float source = 100, result
end macro_command
Name RAND
Syntax RAND(result)
Description Calculates a random integer saved into result.
Result must be a variable.
Example macro_command main()
short result
RAND (result)// result is not a fixed value when executes macro every
time
454
EasyBuilder8000 User’s Manual
end macro_command
Name BIN2BCD
Syntax BIN2BCD(source, result)
Description Transforms a binary-type value (source) into a BCD-type value (result).
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
source = 5678
BIN2BCD(source, result)// result is 0x5678
end macro_command
Name BCD2BIN
Syntax BCD2BIN (source, result)
Description Transforms a BCD-type value (source) into a binary-type value (result).
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
source = 0x5678
BCD2BIN(source, result)// result is 5678
end macro_command
455
EasyBuilder8000 User’s Manual
Name DEC2ASCII
Syntax DEC2ASCII(source, result[start], len)
Description Transforms a decimal value (source) into ASCII string saved to an array
(result).
len represents the length of the string and the unit of length depends on
result’s type., i.e. if result’s type is “char” (the size is byte), the length of the
string is (byte * len). If result’s type is “short” (the size is word), the length
of the string is (word * len), and so on.
The first character is put into result[start], the second character is put into
result[start + 1], and the last character is put into result[start + (len -1)].
Source and len can be a constant or a variable, but result must be a
variable. Start must be a constant.
Example macro_command main()
short source
char result1[4]
short result2[4]
source = 5678
DEC2ASCII(source, result1[0], 4)
// result1[0] is '5', result1[1] is '6', result1[2] is '7', result1[3] is '8'
// the length of the string (result1) is 4 bytes( = 1 * 4)
DEC2ASCII(source, result2[0], 4)
// result2[0] is '5', result2[1] is '6', result2[2] is '7', result2[3] is '8'
// the length of the string (result2) is 8 bytes( = 2 * 4)
end macro_command
Name HEX2ASCII
Syntax HEX2ASCII(source, result[start], len)
Description Transforms a hexadecimal value (source) into ASCII string saved to an
array (result).
len represents the length of the string and the unit of length depends on
result’s type., i.e. if result’s type is “char” (the size is byte), the length of the
string is (byte * len). If result’s type is “short” (the size is word), the length
of the string is (word * len), and so on.
source and len can be a constant or a variable, but result must be a
variable. start must be a constant.
456
EasyBuilder8000 User’s Manual
source = 0x5678
HEX2ASCII (source, result[0], 4)
// result[0] is '5', result[1] is '6', result[2] is '7', result[3] is '8'
end macro_command
Name FLOAT2ASCII
Syntax FLOAT2ASCII (source, result[start], len)
Description Transforms a floating value (source) into ASCII string saved to an array
(result).
len represents the length of the string and the unit of length depends on
result’s type., i.e. if result’s type is “char” (the size is byte), the length of the
string is (byte * len). If result’s type is “short” (the size is word), the length
of the string is (word * len), and so on.
Source and len can be a constant or a variable, but result must be a
variable. Start must be a constant.
Example macro_command main()
float source
char result[4]
source = 56.8
FLOAT2ASCII (source, result[0], 4)
// result[0] is '5', result[1] is '6', result[2] is '.', result[3] is '8'
end macro_command
Name ASCII2DEC
Syntax ASCII2DEC(source[start], result, len)
Description Transforms a string (source) into a decimal value saved to a variable
(result).
The length of the string is len. The first character of the string is
source[start].
457
EasyBuilder8000 User’s Manual
source[0] = '5'
source[1] = '6'
source[2] = '7'
source[3] = '8'
end macro_command
Name ASCII2HEX
Syntax ASCII2HEX (source[start], result, len)
Description Transforms a string (source) into a hexadecimal value saved to a variable
(result).
The length of the string is len. The first character of the string is
source[start].
Source and len can be a constant or a variable, but result must be a
variable. Start must be a constant.
Example macro_command main()
char source[4]
short result
source[0] = '5'
source[1] = '6'
source[2] = '7'
source[3] = '8'
end macro_command
458
EasyBuilder8000 User’s Manual
Name ASCII2FLOAT
Syntax ASCII2FLOAT (source[start], result, len)
Description Transforms a string (source) into a float value saved to a variable (result).
The length of the string is len. The first character of the string is
source[start].
Source and len can be a constant or a variable, but result must be a
variable. Start must be a constant.
Example macro_command main()
char source[4]
float result
source[0] = '5'
source[1] = '6'
source[2] = '.'
source[3] = '8'
end macro_command
459
EasyBuilder8000 User’s Manual
Name FILL
Syntax FILL(source[start], preset, count)
Description Sets the first count elements of an array (source) to a specified value
(preset).
source and start must be a variable, and preset can be a constant or
variable.
Example macro_command main()
char result[4]
char preset
FILL(result[0], 0x30, 4)
// result[0] is 0x30, result[1] is 0x30, , result[2] is 0x30, , result[3] is 0x30
preset = 0x31
FILL(result[0], preset, 2) // result[0] is 0x31, result[1] is 0x31
end macro_command
Name SWAPB
Syntax SWAPB(source, result)
Description Exchanges the high-byte and low-byte data of a 16-bit source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
short source, result
source = 0x123
SWAPB(source, result)// result is 0x2301
end macro_command
460
EasyBuilder8000 User’s Manual
Name SWAPW
Syntax SWAPW(source, result)
Description Exchanges the high-word and low-word data of a 32-bit source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
int source, result
source = 0x12345
SWAPW (source, result)// result is 0x23450001
end macro_command
Name LOBYTE
Syntax LOBYTE(source, result)
Description Retrieves the low byte of a 16-bit source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
short source, result
source = 0x123
LOBYTE(source, result)// result is 0x23
end macro_command
Name HIBYTE
Syntax HIBYTE(source, result)
Description Retrieves the high byte of a 16-bit source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
short source, result
461
EasyBuilder8000 User’s Manual
source = 0x123
HIBYTE(source, result)// result is 0x01
end macro_command
Name LOWORD
Syntax LOWORD(source, result)
Description Retrieves the low word of a 32-bit source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
int source, result
source = 0x12345
LOWORD(source, result)// result is 0x2345
end macro_command
Name HIWORD
Syntax HIWORD(source, result)
Description Retrieves the high word of a 32-bit source into result.
Source can be a constant or a variable, but result must be a variable.
Example macro_command main()
int source, result
source = 0x12345
HIWORD(source, result)// result is 0x0001
end macro_command
462
EasyBuilder8000 User’s Manual
Name GETBIT
Syntax GETBIT(source, result, bit_pos)
Description Gets the state of designated bit position of a data (source) into result.
Result’s value will be 0 or 1.
Source and bit_pos can be a constant or a variable, but result must be a
variable.
Example macro_command main()
int source, result
short bit_pos
source = 4
bit_pos = 2
GETBIT(source, result, bit_pos)// result is 1
end macro_command
Name SETBITON
Syntax SETBITON(source, result, bit_pos)
Description Changes the state of designated bit position of a data (source) to 1, and
put changed data into result.
Source and bit_pos can be a constant or a variable, but result must be a
variable.
Example macro_command main()
int source, result
short bit_pos
source = 0
bit_pos = 2
SETBITON (source, result, bit_pos)// result is 4
463
EasyBuilder8000 User’s Manual
end macro_command
Name SETBITOFF
Syntax SETBITOFF(source, result, bit_pos)
Description Changes the state of designated bit position of a data (source) to 0, and
put in changed data into result.
Source and bit_pos can be a constant or a variable, but result must be a
variable.
Example macro_command main()
int source, result
short bit_pos
source = 4
bit_pos = 2
SETBITOFF(source, result, bit_pos)// result is 0
end macro_command
Name INVBIT
Syntax INVBIT(source, result, bit_pos)
Description Inverts the state of designated bit position of a data (source), and put
changed data into result.
Source and bit_pos can be a constant or a variable, but result must be a
variable.
Example macro_command main()
int source, result
short bit_pos
source = 6
bit_pos = 1
INVBIT(source, result, bit_pos)// result = 4
464
EasyBuilder8000 User’s Manual
end macro_command
18.6.5 Communication
Name DELAY
Syntax DELAY(time)
Description Suspends the execution of the current macro for at least the specified
interval (time). The unit of time is millisecond.
Time can be a constant or a variable.
Example macro_command main()
int time == 500
end macro_command
Name ADDSUM
Syntax ADDSUM(source[start], result, data_count)
Description Adds up the elements of an array (source) from source[start] to
source[start + data_count - 1] to generate a checksum.
Puts in the checksum into result. Result must be a variable.
Data_count is the amount of the accumulated elements and can be a
constant or a variable.
Example macro_command main()
char data[5]
short checksum
data[0] = 0x1
data[1] = 0x2
data[2] = 0x3
data[3] = 0x4
data[4] = 0x5
465
EasyBuilder8000 User’s Manual
end macro_command
Name XORSUM
Syntax XORSUM(source[start], result, data_count)
Description Uses an exclusion method to calculate the checksum from source[start] to
source[start + data_count - 1].
Puts the checksum into result. Result must be a variable.
Data_count is the amount of the calculated elements of the array and can
be a constant or a variable.
Example macro_command main()
char data[5] = {0x1, 0x2, 0x3, 0x4, 0x5}
short checksum
end macro_command
Name CRC
Syntax CRC(source[start], result, data_count)
Description Calculates 16-bit CRC of the variables from source[start] to source[start +
count - 1].
Puts in the 16-bit CRC into result. Result must be a variable.
Data_count is the amount of the calculated elements of the array and can
be a constant or a variable.
Example macro_command main()
char data[5] = {0x1, 0x2, 0x3, 0x4, 0x5}
short 16bit_CRC
end macro_command
Name OUTPORT
466
EasyBuilder8000 User’s Manual
The device is named ”MODBUS RTU Device”. The port attribute depends
on the setting of this device. (the current setting is “19200,E, 8, 1”)
macro_command main()
char command[32]
short address, checksum
467
EasyBuilder8000 User’s Manual
address = 0
HIBYTE(address, command[2])
LOBYTE(address, command[3])
CRC(command[0], checksum, 6)
LOBYTE(checksum, command[6])
HIBYTE(checksum, command[7])
end macro_command
Name INPORT
Syntax INPORT(read_data[start], device_name, read_count, return_value)
Description Reads data from a COM port or the ethernet. These data is stored to
read_data[start]~ read_data[start + read_count - 1].
device_name is the name of a device defined in the device table and the
device must be a “Free Protocol”-type device.
read_count is the required amount of reading and can be a constant or a
variable.
If the function is used successfully to get sufficient data, return_value is 1,
otherwise is 0.
Example Below is an example of executing an action of reading holding registers of
a MODBUS device.
468
EasyBuilder8000 User’s Manual
address = 0
HIBYTE(address, command[2])
LOBYTE(address, command[3])
CRC(command[0], checksum, 6)
LOBYTE(checksum, command[6])
HIBYTE(checksum, command[7])
end macro_command
469
EasyBuilder8000 User’s Manual
Name GetData
Syntax GetData(read_data[start], device_name, device_type, address_offset,
data_count)
or
GetData(read_data, device_name, device_type, address_offset, 1)
Description Receives data from the PLC. Data is stored into read_data[start]~
read_data[start + data_count - 1].
Data_count is the amount of received data. In general, read_data is an array,
but if data_count is 1, read_data can be an array or an ordinary variable.
Below are two methods to read one word data from PLC.
macro_command main()
short read_data_1[2], read_data_2
GetData(read_data_1[0], “FATEK KB Series”, RT, 5, 1)
GetData(read_data_2, “FATEK KB Series”, RT, 5, 1)
end macro_command
Device_name is the PLC name enclosed in the double quotation marks (“) and
this name has been defined in the device list of system parameters as follows
(see FATEK KB Series):
Device_type is the device type and encoding method (binary or BCD) of the
PLC data. For example, if device_type is LW_BIN, it means the register is LW
and the encoding method is binary. If use BIN encoding method, “_BIN” can be
ignored.
470
EasyBuilder8000 User’s Manual
method is BCD.
The number of registers actually read from depends on both the type of the
read_data variable and the value of the number of data_count.
471
EasyBuilder8000 User’s Manual
int (32-bit) 2 4
float (32-bit) 1 2
float (32-bit) 2 4
When a GetData() is executed using a 32-bit data type (int or float), the
function will automatically convert the data. For example,
macro_command main()
float f
GetData(f, "MODBUS", 6x, 2, 1) // f will contain a floating point value
end macro_command
Example macro_command main()
bool a
bool b[30]
short c
short d[50]
int e
int f[10]
double g[10]
// get 20 words (10 integer values) from LW0 ~ LW19 to variables f[0] ~ f[9]
472
EasyBuilder8000 User’s Manual
end macro_command
Name GetDataEx
Syntax GetDataEx (read_data[start], device_name, device_type, address_offset,
data_count)
or
GetDataEx (read_data, device_name, device_type, address_offset, 1)
Description Receives data from the PLC and continue executing next command even if
no response from this device.
Descriptions of read_data, device_name, device_type, address_offset and
data_count are the same as GetData.
473
EasyBuilder8000 User’s Manual
// get 20 words (10 integer values) from LW0 ~ LW19 to f[0] ~ f[9]
// since each integer value occupies 2 words
GetDataEx (f[0], “Local HMI”, LW, 0, 10)
end macro_command
Name SetData
Syntax SetData(send_data[start], device_name, device_type, address_offset,
data_count)
or
SetData(send_data, device_name, device_type, address_offset, 1)
Description Send data to the PLC. Data is defined in send_data[start]~ send_data[start
+ data_count - 1].
data_count is the amount of sent data. In general, send_data is an array,
but if data_count is 1, send_data can be an array or an ordinary variable.
Below are two methods to send one word data.
macro_command main()
short send_data_1[2] = { 5, 6}, send_data_2 = 5
SetData(send_data_1[0], “FATEK KB Series”, RT, 5, 1)
SetData(send_data_2, “FATEK KB Series”, RT, 5, 1)
end macro_command
device_name is the PLC name enclosed in the double quotation marks (“)
and this name has been defined in the device list of system parameters.
device_type is the device type and encoding method (binary or BCD) of the
PLC data. For example, if device_type is LW_BIN, it means the register is
474
EasyBuilder8000 User’s Manual
LW and the encoding method is binary. If use BIN encoding method, “_BIN”
can be ignored.
The number of registers actually sends to depends on both the type of the
send_data variable and the value of the number of data_count.
When a SetData() is executed using a 32-bit data type (int or float), the
475
EasyBuilder8000 User’s Manual
macro_command main()
float f = 2.6
SetData(f, "MODBUS", 6x, 2, 1) // will send a floating point value to the
device
end macro_command
Example macro_command main()
int i
bool a = true
bool b[30]
short c = false
short d[50]
int e = 5
int f[10]
for i = 0 to 29
b[i] = true
next i
for i = 0 to 49
d[i] = i * 2
next i
for i = 0 to 9
f [i] = i * 3
next i
476
EasyBuilder8000 User’s Manual
// set the values of LW6 ~ LW7, note that the type of e is int
SetData(e, “Local HMI”, LW, 6, 1)
end macro_command
Name SetDataEx
Syntax SetDataEx (send_data[start], device_name, device_type, address_offset,
data_count)
or
SetDataEx (send_data, device_name, device_type, address_offset, 1)
Description Send data to the PLC and continue executing next command even if no
response from this device.
Descriptions of send_data, device_name, device_type, address_offset and
data_count are the same as SetData.
for i = 0 to 29
b[i] = true
next i
for i = 0 to 49
477
EasyBuilder8000 User’s Manual
d[i] = i * 2
next i
for i = 0 to 9
f [i] = i * 3
next i
// set the values of LW6 ~ LW7, note that the type of e is int
SetDataEx (e, “Local HMI”, LW, 6, 1)
end macro_command
Name GetError
Syntax GetError (err)
Description Get an error code.
478
EasyBuilder8000 User’s Manual
end macro_command
Name PURGE
Syntax PURGE (com_port)
Description com_port refers to the COM port number which ranges from 1 to 3. It can
be either a variable or a constant.
This function is used to clear the input and output buffers associated with
the COM port.
Example macro_command main()
int com_port=3
PURGE (com_port)
PURGE (1)
end macro_command
Name SetRTS
Syntax SetRTS(com_port, source)
Description Set RTS state for RS232.
com_port refers to the COM port number 1 . It can be either a variable or a
constant. Source also can be either a variable or a constant.
This command raise RTS signal while the value of source is greater than 0
and lower RTS signal while the value of source equals to 0.
479
EasyBuilder8000 User’s Manual
end macro_command
Name GetCTS
Syntax GetCTS(com_port, result)
Description Get CTS state for RS232.
com_port refers to the COM port number 1. It can be either a variable or a
constant. Result is used for receiving the CTS signal. It must be a variable.
This command receives CTS signal and stores the received data in the
result variable. When the CTS signal is pulled high, it writes 1 to result,
otherwise, it writes 0.
end macro_command
Name Beep
Syntax Beep ()
Description Plays beep sound.
This command plays a beep sound with frequency of 800 hertz and
duration of 30 milliseconds.
Example macro_command main()
Beep()
end macro_command
480
EasyBuilder8000 User’s Manual
Name StringGet
Syntax StringGet(read_data[start], device_name, device_type, address_offset,
data_count)
Description Receives data from the PLC. The String data is stored into read_data[start]~
read_data[start + data_count - 1]. read_data must be a one-dimensional char
array.
Data_count is the number of received characters, it can be either a constant or
a variable.
Device_name is the PLC name enclosed in the double quotation marks (“) and
this name has been defined in the device list of system parameters as follows
(see FATEK KB Series):
Device_type is the device type and encoding method (binary or BCD) of the
PLC data. For example, if device_type is LW_BIN, it means the register is LW
and the encoding method is binary. If use BIN encoding method, “_BIN” can be
ignored.
481
EasyBuilder8000 User’s Manual
The number of registers actually read from depends on the value of the
number of data_count since that the read_data is restricted to char array.
482
EasyBuilder8000 User’s Manual
end macro_command
Name StringGetEx
Syntax StringGetEx (read_data[start], device_name, device_type, address_offset,
data_count)
Description Receives data from the PLC and continue executing next command even if
no response from this device.
Descriptions of read_data, device_name, device_type, address_offset and
data_count are the same as GetData.
Example macro_command main()
char str1[20]
short test=0
// macro will not continue executing test = 2 until MODBUS device responds
StringGet(str1[0], "MODBUS RTU", 4x, 0, 20)
test = 2
end macro_command
Name StringSet
Syntax StringSet(send_data[start], device_name, device_type, address_offset,
data_count)
Description Send data to the PLC. Data is defined in send_data[start]~ send_data[start
+ data_count - 1]. send_data must be a one-dimensional char array.
data_count is the number of sent characters, it can be either a constant or a
variable.
device_name is the PLC name enclosed in the double quotation marks (“)
and this name has been defined in the device list of system parameters.
483
EasyBuilder8000 User’s Manual
device_type is the device type and encoding method (binary or BCD) of the
PLC data. For example, if device_type is LW_BIN, it means the register is
LW and the encoding method is binary. If use BIN encoding method, “_BIN”
can be ignored.
484
EasyBuilder8000 User’s Manual
end macro_command
The ASCII display object shows:
char str1[10]=”abcde”
end macro_command
Name StringSetEx
Syntax StringSetEx (send_data[start], device_name, device_type, address_offset,
data_count)
Description Send data to the PLC and continue executing next command even if no
response from this device.
Descriptions of send_data, device_name, device_type, address_offset and
data_count are the same as StringSet.
Example macro_command main()
char str1[20]=”abcde”
short test=0
485
EasyBuilder8000 User’s Manual
// macro will not continue executing test = 2 until MODBUS device responds
StringSet(str1[0], "MODBUS RTU", 4x, 0, 20)
test = 2
end macro_command
Name StringCopy
Syntax success = StringCopy (“source”, destination[start])
or
success = StringCopy (source[start], destination[start])
Description Copy one string to another. This function copies a static string (which is
enclosed in quotes) or a string that is stored in an array to the destination
buffer.
The source string parameter accepts both static string (in the form:
“source”) and char array (in the form: source[start]).
destination[start] must be an one-dimensional char array.
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of source string exceeds the max. size of destination
buffer, it returns false and the content of destination remains the same.
The success field is optional.
Example macro_command main()
char src1[5]="abcde"
char dest1[5]
bool success1
success1 = StringCopy(src1[0], dest1[0])
// success1=true, dest1=”abcde”
char dest2[5]
bool success2
success2 = StringCopy("12345", dest2[0])
// success2=true, dest2=”12345”
char src3[10]="abcdefghij"
char dest3[5]
486
EasyBuilder8000 User’s Manual
bool success3
success3 = StringCopy(src3[0], dest3[0])
// success3=false, dest3 remains the same.
char src4[10]="abcdefghij"
char dest4[5]
bool success4
success4 = StringCopy(src4[5], dest4[0])
// success4=true, dest4=”fghij”
end macro_command
Name StringDecAsc2Bin
Syntax success = StringDecAsc2Bin(source[start], destination)
or
success = StringDecAsc2Bin(“source”, destination)
Description This function converts a decimal string to an integer. It converts the decimal
string in source parameter into an integer, and stores it in the destination
variable.
The source string parameter accepts both static string (in the form:
“source”) and char array (in the form: source[start]).
Destination must be a variable, to store the result of conversion.
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the source string contains characters other than ‘0’ to ‘9’, it returns
false.
The success field is optional.
Example macro_command main()
char src1[5]="12345"
int result1
bool success1
success1 = StringDecAsc2Bin(src1[0], result1)
// success1=true, result1 is 12345
char result2
bool success2
success2 = StringDecAsc2Bin("32768", result2)
// success2=true, but the result exceeds the data range of result2
487
EasyBuilder8000 User’s Manual
char src3[2]="4b"
char result3
bool success3
success3 = StringDecAsc2Bin (src3[0], result3)
// success3=false, because src3 contains characters other than ‘0’ to ‘9’
end macro_command
Name StringBin2DecAsc
Syntax success = StringBin2DecAsc (source, destination[start])
Description This function converts an integer to a decimal string. It converts the integer
in source parameter into a decimal string, and stores it in the destination
buffer.
Source can be either a constant or a variable.
Destination must be an one-dimensional char array, to store the result of
conversion.
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of decimal string after conversion exceeds the size of
destination buffer, it returns false.
The success field is optional.
Example macro_command main()
int src1 = 2147483647
char dest1[20]
bool success1
success1 = StringBin2DecAsc(src1, dest1[0])
// success1=true, dest1=”2147483647”
488
EasyBuilder8000 User’s Manual
end macro_command
Name StringDecAsc2Float
Syntax success = StringDecAsc2Float (source[start], destination)
or
success = StringDecAsc2Float (“source”, destination)
Description This function converts a decimal string to floats. It converts the decimal
string in source parameter into float, and stores it in the destination variable.
The source string parameter accepts both static string (in the form:
“source”) and char array (in the form: source[start]).
Destination must be a variable, to store the result of conversion.
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the source string contains characters other than ‘0’ to ‘9’ or ‘.’, it
returns false.
The success field is optional.
Example macro_command main()
char src1[10]="12.345"
float result1
bool success1
success1 = StringDecAsc2Float(src1[0], result1)
// success1=true, result1 is 12.345
float result2
bool success2
success2 = StringDecAsc2Float("1.234567890", result2)
// success2=true, but the result exceeds the data range of result2, which
// might result in loss of precision
char src3[2]="4b"
float result3
bool success3
success3 = StringDecAsc2Float(src3[0], result3)
// success3=false, because src3 contains characters other than ‘0’ to ‘9’ or
// ‘.’
489
EasyBuilder8000 User’s Manual
end macro_command
Name StringFloat2DecAsc
Syntax success = StringFloat2DecAsc(source, destination[start])
Description This function converts a float to a decimal string. It converts the float in
source parameter into a decimal string, and stores it in the destination
buffer.
Source can be either a constant or a variable.
Destination must be an one-dimensional char array, to store the result of
conversion.
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of decimal string after conversion exceeds the size of
destination buffer, it returns false.
The success field is optional.
Example macro_command main()
float src1 = 1.2345
char dest1[20]
bool success1
success1 = StringFloat2DecAsc(src1, dest1[0])
// success1=true, dest1=” 1.2345”
end macro_command
Name StringHexAsc2Bin
490
EasyBuilder8000 User’s Manual
short result2
bool success2
success2 = StringDecAsc2Bin("1a2b3c4d", result2)
// success2=true, result2=3c4d.The result exceeds the data range of
// result2
char src3[2]="4g"
char result3
bool success3
success3 = StringDecAsc2Bin (src3[0], result3)
// success3=false, because src3 contains characters other than ‘0’ to ‘9’
// , ‘a’ to ‘f’ or ‘A’ to ‘F’
end macro_command
Name StringBin2HexAsc
Syntax success = StringBin2HexAsc (source, destination[start])
491
EasyBuilder8000 User’s Manual
Description This function converts binary data to a hexadecimal string. It converts the
binary data in source parameter into a hexadecimal string, and stores it in
the destination buffer.
Source can be either a constant or a variable.
Destination must be an one-dimensional char array, to store the result of
conversion.
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of hexadecimal string after conversion exceeds the size
of destination buffer, it returns false.
The success field is optional.
Example macro_command main()
int src1 = 20
char dest1[20]
bool success1
success1 = StringBin2HexAsc(src1, dest1[0])
// success1=true, dest1=”14”
end macro_command
Name StringMid
Syntax success = StringMid (source[start], count, destination[start])
or
success = StringMid (“string“, start, count, destination[start])
Description Retrieve a character sequence from the specified offset of the source string
and store it in the destination buffer.
492
EasyBuilder8000 User’s Manual
The source string parameter accepts both static string (in the form:
“source”) and char array (in the form: source[start]). For source[start], the
start offset of the substring is specified by the index value. For static source
string(“source”), the second parameter(start) specifies the start offset of the
substring.
The count parameter specifies the length of substring being retrieved.
Destination must be an one-dimensional char array, to store the retrieved
substring.
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of retrieved substring exceeds the size of destination
buffer, it returns false.
The success field is optional.
Example macro_command main()
char src1[20]="abcdefghijklmnopqrst"
char dest1[20]
bool success1
success1 = StringMid(src1[5], 6, dest1[0])
// success1=true, dest1=”fghijk”
char src2[20]="abcdefghijklmnopqrst"
char dest2[5]
bool success2
success2 = StringMid(src2[5], 6, dest2[0])
// success2=false, dest2 remains the same.
char dest3[20]="12345678901234567890"
bool success3
success3 = StringMid("abcdefghijklmnopqrst", 5, 5, dest3[15])
// success3= true, dest3=” 123456789012345fghij”
end macro_command
Name StringLength
Syntax length = StringLength (source[start])
or
length = StringLength (“source“)
Description Obtain the length of a string. It returns the length of source string and stores
493
EasyBuilder8000 User’s Manual
char src3[20]="abcdefghij"
int length3
length3= StringLength(src3 [2])
// length3=8
end macro_command
Name StringCat
Syntax success = StringCat (source[start], destination[start])
or
success = StringCat (“source”, destination[start])
Description This function appends source string to destination string. It adds the
contents of source string to the last of the contents of destination string.
The source string parameter accepts both static string (in the form:
“source”) and char array (in the form: source[start]).
Destination must be an one-dimensional char array.
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of result string after concatenation exceeds the max. size
of destination buffer, it returns false.
The success field is optional.
Example macro_command main()
char src1[20]="abcdefghij"
494
EasyBuilder8000 User’s Manual
char dest1[20]="1234567890"
bool success1
success1= StringCat(src1[0], dest1[0])
// success1=true, dest1=”123456790abcdefghij”
char src3[20]="abcdefghij"
char dest3[20]
bool success3
success3= StringCat(src3[0], dest3[15])
// success3=false, dest3 remains the same.
end macro_command
Name StringCompare
Syntax ret = StringCompare (str1[start], str2[start])
ret = StringCompare (“string1“, str2[start])
ret = StringCompare (str1[start], “string2”)
ret = StringCompare (“string1”, “string2”)
Description Do a case-sensitive comparison of two strings.
The two string parameters accept both static string (in the form: “string1”)
and char array (in the form: str1[start]).
This function returns a Boolean indicating the result of comparison. If two
strings are identical, it returns true. Otherwise it returns false.
The ret field is optional.
Example macro_command main()
char a1[20]="abcde"
char b1[20]="ABCDE"
bool ret1
ret1= StringCompare(a1[0], b1[0])
// ret1=false
char a2[20]="abcde"
char b2[20]="abcde"
495
EasyBuilder8000 User’s Manual
bool ret2
ret2= StringCompare(a2[0], b2[0])
// ret2=true
char a3 [20]="abcde"
char b3[20]="abcdefg"
bool ret3
ret3= StringCompare(a3[0], b3[0])
// ret3=false
end macro_command
Name StringCompareNoCase
Syntax ret = StringCompareNoCase(str1[start], str2[start])
ret = StringCompareNoCase(“string1“, str2[start])
ret = StringCompareNoCase(str1[start], “string2”)
ret = StringCompareNoCase(“string1”, “string2”)
Description Do a case-insensitive comparison of two strings.
The two string parameters accept both static string (in the form: “string1”)
and char array (in the form: str1[start]).
This function returns a Boolean indicating the result of comparison. If two
strings are identical, it returns true. Otherwise it returns false.
The ret field is optional.
Example macro_command main()
char a1[20]="abcde"
char b1[20]="ABCDE"
bool ret1
ret1= StringCompareNoCase(a1[0], b1[0])
// ret1=true
char a2[20]="abcde"
char b2[20]="abcde"
bool ret2
ret2= StringCompareNoCase(a2[0], b2[0])
// ret2=true
char a3 [20]="abcde"
char b3[20]="abcdefg"
496
EasyBuilder8000 User’s Manual
bool ret3
ret3= StringCompareNoCase(a3[0], b3[0])
// ret3=false
end macro_command
Name StringFind
Syntax position = StringFind (source[start], target[start])
position = StringFind (“source“, target[start])
position = StringFind (source[start], “target”)
position = StringFind (“source“, “target“)
Description Return the position of the first occurrence of target string in the source
string.
The two string parameters accept both static string (in the form: “source”)
and char array (in the form: source[start]).
This function returns the zero-based index of the first character of substring
in the source string that matches the target string. Notice that the entire
sequence of characters to find must be matched. If there is no matched
substring, it returns -1.
Example macro_command main()
char src1[20]="abcde"
char target1[20]="cd"
bool pos1
pos1= StringFind(src1[0], target1[0])
// pos1=2
char target2[20]="ce"
bool pos2
pos2= StringFind("abcde", target2[0])
// pos2=-1
char src3[20]="abcde"
bool pos3
pos3= StringFind(src3[3], "cd")
// pos3=-1
end macro_command
497
EasyBuilder8000 User’s Manual
Name StringReverseFind
Syntax position = StringReverseFind (source[start], target[start])
position = StringReverseFind (“source“, target[start])
position = StringReverseFind (source[start], “target”)
position = StringReverseFind (“source“, “target“)
Description Return the position of the last occurrence of target string in the source
string.
The two string parameters accept both static string (in the form: “source”)
and char array (in the form: source[start]).
This function returns the zero-based index of the first character of substring
in the source string that matches the target string. Notice that the entire
sequence of characters to find must be matched. If there exists multiple
substrings that matches the target string, function will return the position of
the last matched substring. If there is no matched substring, it returns -1.
Example macro_command main()
char src1[20]="abcdeabcde"
char target1[20]="cd"
bool pos1
pos1= StringReverseFind(src1[0], target1[0])
// pos1=7
char target2[20]="ce"
bool pos2
pos2= StringReverseFind("abcdeabcde", target2[0])
// pos2=-1
char src3[20]="abcdeabcde"
bool pos3
pos3= StringReverseFind(src3[6], "ab")
// pos3=-1
end macro_command
Name StringFindOneOf
Syntax position = StringFindOneOf (source[start], target[start])
position = StringFindOneOf (“source“, target[start])
498
EasyBuilder8000 User’s Manual
char src2[20]="abcdeabcde"
bool pos2
pos2= StringFindOneOf(src2[1], "agi")
// pos2=4
end macro_command
Name StringIncluding
Syntax success = StringIncluding (source[start], set[start], destination[start])
success = StringIncluding (“source“, set[start], destination[start])
success = StringIncluding (source[start], “set“, destination[start])
success = StringIncluding (“source“, “set“, destination[start])
Description Retrieve a substring of the source string that contains characters in the set
string, beginning with the first character in the source string and ending
when a character is found in the source string that is not in the target string.
The source string and set string parameters accept both static string (in the
form: “source”) and char array (in the form: source[start]).
499
EasyBuilder8000 User’s Manual
char src2[20]="gecabba"
char dest2[20]
bool success2
success2 = StringIncluding(src2[0], "abc", dest2[0])
// success2=true, dest2=""
char set3[20]="abc"
char dest3[4]
bool success3
success3 = StringIncluding("cabbage", set3[0], dest3[0])
// success3=false, dest3 remains the same.
end macro_command
Name StringExcluding
Syntax success = StringExcluding (source[start], set[start], destination[start])
success = StringExcluding (“source“, set[start], destination[start])
success = StringExcluding (source[start], “set“, destination[start])
success = StringExcluding (“source“, “set“, destination[start])
Description Retrieve a substring of the source string that contains characters that are
not in the set string, beginning with the first character in the source string
and ending when a character is found in the source string that is also in the
target string.
The source string and set string parameters accept both static string (in the
form: “source”) and char array (in the form: source[start]).
This function returns a Boolean indicating whether the process is
500
EasyBuilder8000 User’s Manual
char src2[20]="cabbage"
char dest2[20]
bool success2
success2 = StringExcluding(src2[0], "abc", dest2[0])
// success2=true, dest2=""
char set3[20]="ge"
char dest3[4]
bool success3
success3 = StringExcluding("cabbage", set3[0], dest3[0])
// success3=false, dest3 remains the same.
end macro_command
Name StringToUpper
Syntax success = StringToUpper (source[start], destination[start])
success = StringToUpper ("source", destination[start])
Description Convert all the characters in the source string to uppercase characters and
store the result in the destination buffer.
The source string parameter accepts both static string (in the form:
"source") and char array (in the form: source[start]).
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of result string after conversion exceeds the size of
destination buffer, it returns false.
Example macro_command main()
char src1[20]="aBcDe"
501
EasyBuilder8000 User’s Manual
char dest1[20]
bool success1
success1 = StringToUpper(src1[0], dest1[0])
// success1=true, dest1="ABCDE"
char dest2[4]
bool success2
success2 = StringToUpper("aBcDe", dest2[0])
// success2=false, dest2 remains the same.
end macro_command
Name StringToLower
Syntax success = StringToLower (source[start], destination[start])
success = StringToLower ("source", destination[start])
Description Convert all the characters in the source string to lowercase characters and
store the result in the destination buffer.
The source string parameter accepts both static string (in the form:
"source") and char array (in the form: source[start]).
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of result string after conversion exceeds the size of
destination buffer, it returns false.
Example macro_command main()
char src1[20]="aBcDe"
char dest1[20]
bool success1
success1 = StringToUpper(src1[0], dest1[0])
// success1=true, dest1="abcde"
char dest2[4]
bool success2
success2 = StringToUpper("aBcDe", dest2[0])
// success2=false, dest2 remains the same.
end macro_command
502
EasyBuilder8000 User’s Manual
Name StringToReverse
Syntax success = StringToReverse (source[start], destination[start])
success = StringToReverse ("source", destination[start])
Description Reverse the characters in the source string and store it in the destination
buffer.
The source string parameter accepts both static string (in the form:
"source") and char array (in the form: source[start]).
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of reversed string exceeds the size of destination buffer,
it returns false.
Example macro_command main()
char src1[20]="abcde"
char dest1[20]
bool success1
success1 = StringToUpper(src1[0], dest1[0])
// success1=true, dest1="edcba"
char dest2[4]
bool success2
success2 = StringToUpper("abcde", dest2[0])
// success2=false, dest2 remains the same.
end macro_command
Name StringTrimLeft
Syntax success = StringTrimLeft (source[start], set[start], destination[start])
success = StringTrimLeft (“source“, set[start], destination[start])
success = StringTrimLeft (source[start], “set“, destination[start])
success = StringTrimLeft (“source“, “set“, destination[start])
Description Trim the leading specified characters in the set buffer from the source
string.
The source string and set string parameters accept both static string (in the
form: "source") and char array (in the form: source[start]).
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of trimmed string exceeds the size of destination buffer, it
returns false.
503
EasyBuilder8000 User’s Manual
end macro_command
Name StringTrimRight
Syntax success = StringTrimRight (source[start], set[start], destination[start])
success = StringTrimRight (“source“, set[start], destination[start])
success = StringTrimRight (source[start], “set“, destination[start])
success = StringTrimRight (“source“, “set“, destination[start])
Description Trim the trailing specified characters in the set buffer from the source string.
The source string and set string parameters accept both static string (in the
form: "source") and char array (in the form: source[start]).
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of trimmed string exceeds the size of destination buffer, it
returns false.
Example macro_command main()
char src1[20]= "# *a*#bc# * "
char set1[20]="# *"
char dest1[20]
bool success1
504
EasyBuilder8000 User’s Manual
end macro_command
Name StringInsert
Syntax success = StringInsert (pos, insert[start], destination[start])
success = StringInsert (pos, “insert“, destination[start])
success = StringInsert (pos, insert[start], length, destination[start])
success = StringInsert (pos, “insert“, length, destination[start])
Description Insert a string in a specific location within the destination string content. The
insert location is specified by the pos parameter.
The insert string parameter accepts both static string (in the form: "source")
and char array (in the form: source[start]).
The number of characters to insert can be specified by the length
parameter.
This function returns a Boolean indicating whether the process is
successfully done or not. If successful, it returns true, otherwise it returns
false. If the length of string after insertion exceeds the size of destination
buffer, it returns false.
Example macro_command main()
505
EasyBuilder8000 User’s Manual
end macro_command
506
EasyBuilder8000 User’s Manual
507
EasyBuilder8000 User’s Manual
18.6.7 Miscellaneous
Name SYNC_TRIG_MACRO
Syntax SYNC_TRIG_MACRO(macro_id)
Description Trigger the execution of a macro synchronously (use macro_id to
designate this macro) in a running macro.
The current macro will pause until the end of execution of this called
macro.
macro_id can be a constant or a variable.
Example macro_command main()
char ON = 1, OFF = 0
end macro_command
Name ASYNC_TRIG_MACRO
Syntax ASYNC_TRIG_MACRO (macro_id)
Description Trigger the execution of a macro asynchronously (use macro_id to
designate this macro) in a running macro.
The current macro will continue executing the following instructions after
triggering the designated macro; in other words, the two macros will be
active simultaneously.
macro_id can be a constant or a variable.
Example macro_command main()
char ON = 1, OFF = 0
508
EasyBuilder8000 User’s Manual
end macro_command
Name TRACE
Syntax TRACE(format, argument)
Description Use this function to send specified string to the EasyDiagnoser. Users can
print out the current value of variables during run-time of macro for
debugging.
When TRACE encounters the first format specification (if any), it converts
the value of the first argument after format and outputs it accordingly.
format refers to the format control of output string. A format specification,
which consists of optional (in [ ]) and required fields (in bold), has the
following form:
%[flags] [width] [.precision] type
Each field of the format specification is described as below:
flags (optional):
-
+
width (optional):
A nonnegative decimal integer controlling the minimum
number of characters printed.
precision (optional):
A nonnegative decimal integer which specifies the precision and
the number of characters to be printed.
type:
C or c : specifies a single-byte character.
d : signed decimal integer.
i : signed decimal integer.
o : unsigned octal integer.
u : unsigned decimal integer.
X or x : unsigned hexadecimal integer.
E or e : Signed value having the form.
[ – ]d.dddd e [sign]ddd where d is a single decimal
digit, dddd is one or more decimal digits, ddd is
exactly three decimal digits, and sign is + or –.
f : Signed value having the form [ – ]dddd.dddd,
where dddd is one or more decimal digits.
509
EasyBuilder8000 User’s Manual
end macro_command
Name FindDataSamplingDate
Syntax return_value = FindDataSamplingDate (data_log_number, index, year,
month, day)
or
FindDataSamplingDate (data_log_number, index, year, month, day)
Descripti A query function for finding the date of specified data sampling file according
on to the data sampling no. and the file index. The date is stored into “year”,
“month” and “day” respectively in the format of YYYY, MM and DD.
510
EasyBuilder8000 User’s Manual
// if there exists a data sampling file named 20101230.dtl, with data sampling
// number 1 and file index 2.
// the result after execution: success == 1, year == 2010, month == 12 and
//day == 30
success = FindDataSamplingDate(data_log_number, index, year, month,
day)
end macro_command
Name FindDataSamplingIndex
Syntax return_value = FindDataSamplingIndex (data_log_number, year, month,
day, index)
or
FindDataSamplingIndex (data_log_number, year, month, day, index)
Descripti A query function for finding the file index of specified data sampling file
on according to the data sampling no. and the date. The file index is stored into
“index”. “year”, “month” and “day” are in the format of YYYY, MM and DD
respectively.
511
EasyBuilder8000 User’s Manual
// if there exists a data sampling file named 20101210.dtl, with data sampling
// number 1 and file index 2.
// the result after execution: success == 1 and index == 2
success = FindDataSamplingIndex (data_log_number, year, month, day,
index)
end macro_command
Name FindEventLogDate
Syntax return_value = FindEventLogDate (index, year, month, day)
or
FindEventLogDate (index, year, month, day)
Description A query function for finding the date of specified event log file according to
file index. The date is stored into “year”, “month” and “day” respectively in
the format of YYYY, MM and DD.
512
EasyBuilder8000 User’s Manual
The event log files stored in the designated position (such as HMI memory
storage or external memory device) are sorted according to the file name
and are indexed starting from 0. The most recently saved file has the
smallest file index number. For example, if there are four event log files as
follows:
EL_20101210.evt
EL_20101230.evt
EL_20110110.evt
EL_20110111.evt
The file index are:
EL_20101210.evt -> index is 3
EL_20101230.evt -> index is 2
EL_20110110.evt -> index is 1
EL_20110111.evt -> index is 0
“return_value” equals to 1 if referred data sampling file is successfully
found, otherwise it equals to 0.
“index” can be constant or variable. “year”, “month”, “day” and
“return_value” must be variable.
The “return_value” field is optional.
Example macro_command main()
short index = 1, year, month, day
short success
end macro_command
Name FindEventLogIndex
Syntax return_value = FindEventLogIndex (year, month, day, index)
or
FindEventLogIndex (year, month, day, index)
Description A query function for finding the file index of specified event log file
according to date. The file index is stored into “index”. “year”, “month” and
“day” are in the format of YYYY, MM and DD respectively.
The event log files stored in the designated position (such as HMI memory
513
EasyBuilder8000 User’s Manual
storage or external memory device) are sorted according to the file name
and are indexed starting from 0. The most recently saved file has the
smallest file index number. For example, if there are four event log files as
follows:
EL_20101210.evt
EL_20101230.evt
EL_20110110.evt
EL_20110111.evt
The file index are:
EL_20101210.evt -> index is 3
EL_20101230.evt -> index is 2
EL_20110110.evt -> index is 1
EL_20110111.evt -> index is 0
“return_value” equals to 1 if referred data sampling file is successfully
found, otherwise it equals to 0.
“year”, “month” and “day” can be constant or variable. “index” and
“return_value” must be variable.
The “return_value” field is optional.
Example macro_command main()
short year = 2010, month = 12, day = 10, index
short success
end macro_command
514
EasyBuilder8000 User’s Manual
515
EasyBuilder8000 User’s Manual
Step 1:
Click on “Macro Manager” icon on the tool bar of EasyBuilder 8000 to open Macro
Manager dialogue box as follows.
516
EasyBuilder8000 User’s Manual
On Macro Manager, all macros compiled successfully are displayed in “Macro list”, and all
macros in developing are displayed in ‘Macro under development”. The following is a
description of the various buttons.
[New]
Opens a blank “WorkSpace” editor for creating a new macro.
[Delete]
Deletes the selected macro.
[Edit]
Opens the “WorkSpace” editor, and loads the selected macro.
[Copy]
Copies the selected macro into the clipboard.
[Paste]
Pastes the macro in the clipboard into the list, and creates a new name for the macro.
Step 2:
Press the “New” button to open a blank “WorkSpace” editor. Every macro has a unique
number defined in “Macro ID” edit box, and macro name must exist, otherwise an error will
appear while compiling.
517
EasyBuilder8000 User’s Manual
Step 3:
Design your macro. If it is necessary to use build-in functions (like SetData() or Getdata()),
press ‘Get/Set FN…” button to open API dialog and select the function and set essential
parameters.
518
EasyBuilder8000 User’s Manual
Step 4:
After the completion of a new macro, press ‘Compile” button to compile the macro.
519
EasyBuilder8000 User’s Manual
If there is no error, press “Exit” button and find that a new macro “macro_test” exists in
“Macro list”.
520
EasyBuilder8000 User’s Manual
521
EasyBuilder8000 User’s Manual
char a[4096]
bool b[4096]
short c[2048]
int d[1024]
float e[1024]
522
EasyBuilder8000 User’s Manual
When EasyBuilder 8000 does not provide an essential driver for communication with a
device, Users also can make use of OUTPORT and INPORT to control the device. The
data sent with OUTPORT and INPORT must follow the device’s communication protocol.
The following example explains how to use these two functions to control a MODBUS RTU
device.
First, create a new device in the device table. The device type of the new device is set to
“Free Protocol” and named with “MODBUS RTU device” as follows:
The interface of the device (PLC I/F) uses “RS-232” now. If connecting a MODBUS
TCP/IP device, the interface must select ‘Ethernet”. In addition, it is necessary to set
correct IP and port number as follows:
523
EasyBuilder8000 User’s Manual
Suppose that HMI will read the data of 4x_1 and 4x_2 on the device. First, utilize
OUTPORT to send out a read request to the device. The prototype of OUTPORT is:
Since “MODBUS RTU device” is a MODBUS RTU device, the read request must follow
MODBUS RTU protocol. The request uses”Reading Holding Registers (0x03)” command
to read data. The following picture displays the content of the command. (The items of the
station number (byte 0) and the last two bytes (CRC) are ignored).
Depending on the protocol, the content of a read command as follows (The total is 8
bytes):
command[0] : station number (BYTE 0)
command[1] : function code (BYTE 1)
command[2] : high byte of starting address (BYTE 2)
command[3] : low byte of starting address (BYTE 3)
command[4] : high byte of quantity of registers (BYTE 4)
command[5] : low byte of quantity of registers (BYTE 5)
command[6] : low byte of 16-bit CRC (BYTE 6)
command[7] : high byte of 16-bit CRC (BYTE 7)
So a read request is designed as follows :
char command[32]
short address, checksum
524
EasyBuilder8000 User’s Manual
LOBYTE(checksum, command[6])
HIBYTE(checksum, command[7])
After sending out the request, use INPORT to get the response from PLC. Depending on
the protocol, the content of the response is as follows (the total byte is 9):
command[0] : station number (BYTE 0)
command[1] : function code (BYTE 1)
command[2] : byte count (BYTE 2)
command[3] : high byte of 4x_1 (BYTE 3)
command[4] : low byte of 4x_1 (BYTE 4)
command[5] : high byte of 4x_2 (BYTE 5)
command[6] : high byte of 4x_2 (BYTE 6)
command[7] : low byte of 16-bit CRC (BYTE 7)
command[8] : high byte of 16-bit CRC (BYTE 8)
Where the real read count is restored to the variable return_value (unit is byte). If
return_value is 0, it means reading fails in executing INPORT.
525
EasyBuilder8000 User’s Manual
Depending on the protocol, response[1] must be equal to 0x3, if the response is correct.
After getting correct response, calculate the data of 4x_1 and 4x_2 and put in the data into
LW100 and LW101 of HMI.
address = 0
address = 0// starting address (4x_1) is 0
HIBYTE(address, command[2])
LOBYTE(address, command[3])
LOBYTE(checksum, command[6])
526
EasyBuilder8000 User’s Manual
HIBYTE(checksum, command[7])
end macro_command
The following example explains how to design a request to set the status of 0x_1. The
request uses ”Write Single Coil(0x5)” command.
527
EasyBuilder8000 User’s Manual
address = 0
HIBYTE(address, command[2])
LOBYTE(address, command[3])
CRC(command[0], checksum, 6)
LOBYTE(checksum, command[6])
HIBYTE(checksum, command[7])
end macro_command
528
EasyBuilder8000 User’s Manual
When there are compile errors, the error description can be referenced by the compiler
error message number.
2. Error Description
For example:
macro_command main()
char i, 123xyz // this is an unsupported variable name
end macro_command
For example:
macro_command main()
char i
int g[i] // i must be a numeric constant
end macro_command
For example:
macro_command main()
int g[10],g // error
end macro_command
529
EasyBuilder8000 User’s Manual
For example:
sub int if() // error
For example:
macro_command main ) // missing “(“
end if
Any format other than this format will cause a compile error.
530
EasyBuilder8000 User’s Manual
next [variable]
Any format other than this format will cause a compile error.
wend
Any format other than this format will cause a compile error.
531
EasyBuilder8000 User’s Manual
For example :
macro_command main( )
int a, b
for a = 0 to 2
b = 4 + xyz // illegal : xyz is undefined
next a
end macro_command
For example::
sub int pow(int exp)
…….
end sub
Any format other than this format will cause a compile error.
532
EasyBuilder8000 User’s Manual
Any format other than this format will cause a compile error.
(C40) execution syntax should not exist before variable declaration or constant
definition
For example :
macro_command main( )
int a, b
for a = 0 To 2
b=4+a
int h , k // illegal – definitions must occur before any statements or expressions
// for example, b = 4 + a
next a
end macro_command
533
EasyBuilder8000 User’s Manual
macro_command function_name( )
end macro_command
For example :
“PLC 1“ is connected with the remote HMI ,so it can not work.
534
EasyBuilder8000 User’s Manual
1. ”for” statement and other expressions (arithmetic, bitwise shift, logic and
comparison)
macro_command main()
int a[10], b[10], i
for i = 0 to 4 step 1
if (a[0] == 400) then
GetData(a[0],”Device 1”, 4x, 0,9)
GetData(b[0],”Device 1”, 4x, 11,10)
end If
next i
end macro_command
macro_command main()
int b[10], i
i=5
while i == 5 - 20 % 3
GetData(b[1], ”Device 1”, 4x, 11, 1)
535
EasyBuilder8000 User’s Manual
wend
end macro_command
char g
sub int fun(int j, int k)
int y
return y
end Sub
macro_command main()
int a, b, i
a=2
b=3
i = fun(a, b)
SetData(i, “Local HMI”, LB, 16, 1)
end macro_command
4. ”if” statement
macro_command main()
int k[10], j
for j = 0 to 10
k[j] = j
next j
if k[0] == 0 then
SetData(k[1], “Device 1”, 4x, 0, 1)
end if
536
EasyBuilder8000 User’s Manual
if k[0] == 0 then
SetData(k[1], “Device 1”, 4x, 0, 1)
else
SetData(k[2], “Device 1”, 4x, 0, 1)
end if
if k[0] == 0 then
SetData(k[1], “Device 1”, 4x, 1, 1)
else if k[2] == 1 then
SetData(k[3], “Device 1”, 4x, 2, 1)
end If
if k[0] == 0 then
SetData(k[1], “Device 1”, 4x, 3, 1)
else if k[2] == 2 then
SetData(k[3], “Device 1”, 4x, 4, 1)
else
SetData(k[4], “Device 1”, 4x, 5, 1)
end If
end macro_command
macro_command main()
char i = 0
int a[13], b[14], c = 4848
b[0] = 13
while b[0]
a[i] = 20 + i * 10
i=i+1
537
EasyBuilder8000 User’s Manual
wend
macro_command main()
char i = 0
int a[13], b[14], c = 4848
b[0] = 13
while b[0]
a[i] = 20 + i * 10
i=i+1
if c == 200 then
SetData(c, “Device 1”, 4x, 2, 1)
break
end if
wend
end macro_command
7. Array
macro_command main()
int a[25], b[25], i
b[0] = 13
538
EasyBuilder8000 User’s Manual
539
EasyBuilder8000 User’s Manual
1. TRACE function is added to MACRO, and can be used with EasyDiagnoser, for viewing
First of all, add macro_1 in the project, and in macro_1 add TRACE (“LW = %d”, a). “%d”
following:
macro_command main()
short a
a= a + 1
end macro_command
For the detailed usage of TRACE function, please refer to the illustration in the following
paragraph.
540
EasyBuilder8000 User’s Manual
Secondly, add Numeric Display and Function Key objects in window 10 of the project. The
settings of these objects are shown below. Function Key object is used to execute
macro_1.
541
EasyBuilder8000 User’s Manual
Lastly, compile the completed project and execute Off-line or On-line simulation.
When processing simulation on PC, right click and select “Run EasyDiagnoser” in the
pop-up menu.
EasyDiagnoser is able to connect with the HMI to be watched or not. [Output] window
displays the output of the TRACE function. The illustration below shows that
542
EasyBuilder8000 User’s Manual
When EasyDiagnoser is not able to connect with HMI, [Logger] window displays content
as shown below:
543
EasyBuilder8000 User’s Manual
The possible reason of not being able to get connection with HMI can be failure in
executing simulation on PC. Another reason is that the Port No. used in project for
simulation on PC is incorrect (or occupied by system). Please change Port No. as shown,
When opening EasyDiagnoser, the Port No. should be set the same as that in project.
The three successive ports of the project port no. are preserved for HMI communication.
Take the setting above as example, Port No. is set as 8005, therefore port 8005, 8006 and
544
EasyBuilder8000 User’s Manual
8007 will be preserved. In this case when executing simulation on PC, please make sure
545
EasyBuilder8000 User’s Manual
end macro_command
Manager, current HMI on line will be listed; users can simply select the HMI to be
watched.
Please note that Project Port should be the same as Port No. used in project file.
546
EasyBuilder8000 User’s Manual
connection with the HMI to be watched, it is possible that HMI power is not ON, or Port
No. is incorrect. This may cause EasyDiagnoser to connect then disconnect with HMI
continuously. Please check if the Port No. in EasyDiagnoser settings is same as that of
[Output] window will then display the output of the TRACE function.
547
EasyBuilder8000 User’s Manual
548
EasyBuilder8000 User’s Manual
The string “abcdef” is stored in LW0~LW2 as follows (LB represents low byte and HB
represents high byte):
The ASCII input object reads 1 word (2 bytes) at a time as described in the previous
chapter. Suppose an ASCII input object is set to read 3 words as shown in the above
549
EasyBuilder8000 User’s Manual
example, it can actually read at most 6 ASCII characters since that one ASCII character
occupies 1 byte.
The functionality of each string operation function is described in the following table:
Function name Description
StringGet Read string data from a device.
StringGetEx Read string data from a device and continue
executing next command even if no response from
that device.
StringSet Write string data to a device.
StringSetEx Write string data to a device and continue executing
next command even if no response from that device.
StringCopy Copy one string to another.
StringMid Retrieve a substring.
StringDecAsc2Bin Convert a decimal string to an integer.
StringBin2DecAsc Convert an integer to a decimal string.
StringDecAsc2Float Convert a decimal string to floats.
StringFloat2DecAsc Convert a float to a decimal string.
StringHexAsc2Bin Convert a hexadecimal string to binary data.
StringBin2HexAsc Convert binary data into a hexadecimal string.
StringLength Obtain the length of a string.
StringCat Append source string to destination string.
StringCompare Do a case-sensitive comparison of two strings.
StringCompareNoCase Do a case-insensitive comparison of two strings.
StringFind Find a substring inside a larger string.
StringReverseFind Find a substring inside a larger string; starts from the
end.
StringFindOneOf Find the first matching character from a set.
StringIncluding Extracts a substring that contains only the characters
in a set.
StringExcluding Extracts a substring that contains only the characters
not in a set.
StringToUpper Convert the characters of a string to uppercase.
StringToLower Convert the characters of a string to lowercase.
StringToReverse Reverse the characters of a string.
StringTrimLeft Trim the leading specified characters in a set from
the source string.
StringTrimRight Trim the trailing specified characters in a set from the
550
EasyBuilder8000 User’s Manual
source string.
StringInsert Insert a string in a specific location within another
string.
For more detailed information of the above string operation functions, please check out the
“Build-In Function Block” section. In order to demonstrate the powerful usage of string
operation functions, the following examples will show you step by step how to create
executable project files using the new functions; starts from creating a macro, ends in
executing simulation.
1. How to read (or write) a string from a device.
Create a new macro:
The first function “StringGet” is used to read a string from LW0~LW19, and store it into the
str array. The second function “StringSet” is used to output the content of str array.
Add ASCII Input and Function Key objects in window 10 of the project. The
settings of these objects are shown as below. Function Key object is used to execute
macro_1.
551
EasyBuilder8000 User’s Manual
552
EasyBuilder8000 User’s Manual
2. Initialization of a string.
Create a new macro and edit the content:
553
EasyBuilder8000 User’s Manual
The data enclosed in double quotation mark (“”) is viewed as a string. str1 is initialized as a
string while str2 is initialized as a char array. The following snapshot of simulation shows
the difference between str1 and str2 using two ASCII input objects.
str1
str2
Macro compiler will add a terminating null character (‘\0’) at the end of a string. The
function “StringSet” will send each character of str1 to registers until a null character is
reached. The extra characters following the null character will be ignored even if the data
count is set to a larger value than the length of string.
On the contrary, macro compiler will not add a terminating null character (‘\0’) at the end of
a char array. The actual number of characters of str2 being sent to registers depends on
the value of data count that is passed to the “StringSet” function.
554
EasyBuilder8000 User’s Manual
The first two “StringGet” functions will read the strings input by users and store them into
arrays named name_input and password_input separately. Use the function
“StringCompare” to check if the input account name and password are matched. If the
account name is matched, name_match is set true; if the password is matched,
password_match is set true. If both name_match and password_match are true, output the
string “Success! Access Accepted.”. Otherwise, output the string “Fail! Access Denied.”.
Add ASCII Input and Function Key objects in window 10 of the project. The
settings of these objects are shown as below. Function Key object is used to execute
macro_1.
Object 2
Object 3
Object 1
Object 4
Object settings:
555
EasyBuilder8000 User’s Manual
556
EasyBuilder8000 User’s Manual
Step 1: input
account name
557
EasyBuilder8000 User’s Manual
Step 2: input
password
Step 3: press
“Login” button
558
EasyBuilder8000 User’s Manual
Login
success
Login
fail
559
EasyBuilder8000 User’s Manual
On MACRO editing window there’s the [Password protect] selection, tick it and click [Set
After setting MACRO password, users will have to input correct password when opening
EasyBuilder8000 should be rebooted for typing the password again after 3 incorrect
attempts.
560
EasyBuilder8000 User’s Manual
[Caution] When MACRO is password protected, decompilation of XOB file will not be able
561
EasyBuilder8000 User’s Manual
Once HMI is set as MODBUS Server, the data of HMI can be read or written via MODBUS
protocol.
Refer to the illustration above, it shows HMI is set as MODBUS Server. The HMI, PC or
other devices can use MODBUS protocol to read or write the data from HMI via Ethernet
or RS232/485 interface. Please follow the steps as below.
First of all, add a new device “MODBUS Server” in the [Device] tab of [System
Parameter Settings]. The [PLC I/F] can be set to RS232, RS485 2W, RS485 4W,
Ethernet.
562
EasyBuilder8000 User’s Manual
If [PLC I/F] is set as [RS232] or [RS485], please fill in [COM Port Settings] also.
If [PLC I/F] is set as [Ethernet], the [IP address] is the same as HMI.
For communication, MODBUS Server [Port no.] should be set the same as HMI Port no.
563
EasyBuilder8000 User’s Manual
Please refer to HMI Port no. to set MODBUS Server Port no. Go to [Model] tab of
[System Parameter Settings], the HMI [Port no]. is shown there.
After finishing the setting, MODBUS Server will be listed in [Device] tab.
You can send MODBUS command to read or write the data from MODBUS Server after
downloading the XOB file to HMI.
564
EasyBuilder8000 User’s Manual
HMI (the client) can read from / write to another HMI (the server) via MODBUS protocol.
Add a new device in the project of client. If client’s [PLC I/F] is set as [Ethernet], please
select”MODBUS TCP/IP” as [PLC type] and fill in the correct [IP] (the IP of server HMI)
and [Port no.].
If the client use [RS232/485] interface, the [PLC type] must be set as”MODBUS RTU”.
Please make sure the communication parameter setting is correct.
565
EasyBuilder8000 User’s Manual
Set and click [OK], a new device”MODBUS RTU” will be listed in the [Device] tab.
In the setting page of each object, there is a “MODBUS RTU” in the [PLC name] selection
list; you can then select appropriate device type and address.
566
EasyBuilder8000 User’s Manual
Since the server is HMI, the corresponding read and write address are as follows:
567
EasyBuilder8000 User’s Manual
Change the related reserved registers to modify the station number of a MODBUS/ASCII
server (HMI).
568
EasyBuilder8000 User’s Manual
Address types under MODBUS protocol in EB8000 are 0x, 1x, 3x, 4x, 5x, 6x,
3x_bit and 4x_bit.
Modbus RTU function code:
Note:
1 Address type “5x” is mapping to Hold Reg. The communication protocol of 5x is
almost same as “4x” except “5x”makes double word swap.
If 4x contains following information
Address 1 2 3 4 5 6 ...
Data in word 0x1 0x2 0x3 0x4 0x5 0x6
Data 0x20001 0x40003 0x60005
3The communication protocol of 3x_bit and 4x_bit are the same as 3x and 4x. The
difference is that 3x_bit and 4x_bit read single bit of the whole data.
569
EasyBuilder8000 User’s Manual
Barcode interfaces:
Weintek HMI support connecting barcode (USB/COM) device. Please add a new barcode
device in [Edit]/ [System Parameter Settings]/ [Device list] first as shown below.
570
EasyBuilder8000 User’s Manual
For example:
When [Read byte limit] is set to “10”, if the data the barcode device should read: “0x34
0x39 0x31 0x32 0x30 0x30 0x34 0x37 0x30 0x38 0x33 0x38”. (12 bytes)
For example: if the start code is 255(0xff), and original data read:
“0xff 0x34 0x39 0x31 0x32 0x30 0x30 0x34 0x37”,
571
EasyBuilder8000 User’s Manual
[Terminator]
Terminator means the end of data, when terminator is detected; it stands for the end of
data stream.
After completing all settings described above, a new “Barcode” device will be listed in the
[Device list].
Now the barcode device can be selected in [PLC type] on the object parameters setting
dialogue box. There are 2 types of address:
Address Address
Description
type name
FLAG 0 indicates the status of data reading. When reading
data is complete, the status of FLAG 0 will be changed
Bit FLAG
from OFF to ON. It will not return to OFF automatically,
users are free to set base on actual usage.
BARCODE 0 Number of bytes currently read.
Word BARCODE
BARCODE 1 ~ n Store the data read by barcode device.
The following is a barcode device setting example, the barcode read is 9421007480830.
BARCODE 0 is the address of “Numeric Display” object (bytes) and BARCODE 1~n is the
address of “ASCII Display” object (barcode).
572
EasyBuilder8000 User’s Manual
Barcode
Data
corresponding address
13 bytes (decimal)
The data saved in this address is 14 bytes = 7 words. If
BARCODE 0
the number of byte is odd, system will add a byte (0x00)
to make it even.
BARCODE 1 3439HEX
BARCODE 2 3132HEX
BARCODE 3 3030HEX
BARCODE 4 3437HEX
BARCODE 5 3038HEX
BARCODE 6 3338HEX
BARCODE 7 0030HEX
BARCODE 8 empty
Please confirm your Internet connection before downloading the demo project.
573
EasyBuilder8000 User’s Manual
Through Ethernet network, EB8000 provides following methods for data transmission:
There are two ways of Ethernet communication: one is to use RJ45 straight through cable
with hubs. Another is to use RJ45 crossover cable with no hubs, but this is limited to the
condition of point to point connection (HMI to HMI, or PC to HMI). The following illustrates
ways of how to set up and perform the Ethernet connection.
574
EasyBuilder8000 User’s Manual
Different HMI can monitor and control each other’s data through Ethernet network. With
system reserved register (LB and LW); one HMI can master performance of other HMI(s).
One HMI can handle requests from a maximum of other 32 HMI simultaneously.
Here is an example of communicating two HMI (HMI A and HMI B). When HMI A wants to
use a [set bit] object to control the address [LB123] of HMI B, the procedure for setting the
Project files (MTP) of HMI A is as follows:
Step 1
Set the IP address of the two HMI (Refer to the related chapter for details). Suppose the IP
address of HMI A and HMI B are set as “192.168.1.1” and “192.168.1.2” respectively.
Step 2
Run the project of HMI A in EB8000, under [Device] tab in [System Parameter Settings]
menu, add the [IP address] and [Port number] of HMI B as below.
575
EasyBuilder8000 User’s Manual
Step 3
Select “HMI B” for [PLC name] of [New Set Bit Object] dialogue, and now HMI A can
operate the content of the LB of HMI B.
576
EasyBuilder8000 User’s Manual
With Simulation Function of EB8000, PC can catch data of HMI through Ethernet network
and save the data files in computer.
PC can master HMI by operating the system reserved register (LB and LW) of HMI. On the
contrary, HMI can also directly control operation of PC, for example, asking PC to save
data from HMI or PLC.
Suppose PC is going to communicate with two HMI (HMI A and HMI B), the procedure for
setting PC’s MTP projects is as follows:
Step 1
Set the IP address of the two HMI (Refer to the related chapter for details). Suppose that
the [IP address] of HMI A and HMI B are set as “192.168.1.1” and “192.168.1.2”
respectively.
Step 2
Run the project of PC in EB8000, under [Device] tab in [System Parameter Settings]
menu, add the [IP address] and [Port number] of HMI A and HMI B as below.
577
EasyBuilder8000 User’s Manual
Step 3
Select correct PLC for [PLC name] In [General] tab of [Set Bit Object’s Attributes]. If LB
of HMI A is to be controlled, “HMI A” must be selected as below.
Step 4
Use HMI MTP projects on PC and perform simulation (either online mode or offline mode),
all data of HMIA and B can be controlled by PC.
It is also available for HMI to control data of PC, simply considering PC another HMI. Add
PC as a new Remote HMI device to the MTP projects of HMI A or HMI B and set the IP
address pointing to the PC.
578
EasyBuilder8000 User’s Manual
Through Ethernet network, PC or HMI can also operate PLC that is connected to other
HMI; for example, suppose there is a Mitsubishi PLC connected to COM 1of HMI B. When
PC or HMI A wants to read data from this PLC, the procedure for setting PC or HMI A MTP
projects is as follows:
Step 1
Set the [IP address] of HMI B; suppose the IP address of HMI B is set as”192.168.1.2”.
Step 2
Run project of PC or HMI A and add a Remote PLC device (defined as Mitsubishi
FX0n_FX2 in the example below) in [Device] tab in [System Parameter Settings] menu,
then set the correct communication parameters.
579
EasyBuilder8000 User’s Manual
Since this device is a remote PLC connected with Remote HMI B, the [IP address] should
be the same as HMI B (192.168.1.2)
Step 3
In using the [set bit] object to operate the Mitsubishi PLC connected to HMI B, just need to
select “PLC on HMI B” for [PLC name], then it is able to operate the PLC connected to the
remote HMI B on PC through the simulation function.
580
EasyBuilder8000 User’s Manual
581
EasyBuilder8000 User’s Manual
22.1.1 Bits
Example:
567a
RW_Bit address = 567 +
[LW-9000]
bit offset = a
Retentive RW_Bit 0 ~ 524287f DDDDDh
Memory Word DDDDD: address
Bits h: bit no. (0 ~ f)
Retentive RW_A_Bit 0 ~ 65535f DDDDh
Memory A Word DDDDD: address
Bits h: bit no. (0 ~ f)
582
EasyBuilder8000 User’s Manual
22.1.2 Words
583
EasyBuilder8000 User’s Manual
584
EasyBuilder8000 User’s Manual
Please confirm your Internet connection before downloading the demo project.
585
EasyBuilder8000 User’s Manual
586
EasyBuilder8000 User’s Manual
587
EasyBuilder8000 User’s Manual
588
EasyBuilder8000 User’s Manual
589
EasyBuilder8000 User’s Manual
590
EasyBuilder8000 User’s Manual
591
EasyBuilder8000 User’s Manual
592
EasyBuilder8000 User’s Manual
Please confirm your Internet connection before downloading the demo project.
593
EasyBuilder8000 User’s Manual
Want to know how to trigger relevant registers to change window with finger slide?
Please confirm your Internet connection before downloading the demo project.
594
EasyBuilder8000 User’s Manual
595
EasyBuilder8000 User’s Manual
Please confirm your Internet connection before downloading the demo project.
596
EasyBuilder8000 User’s Manual
597
EasyBuilder8000 User’s Manual
598
EasyBuilder8000 User’s Manual
599
EasyBuilder8000 User’s Manual
(COM 1)
LW-9542 (16bit) : MODBUS/ASCII server station no.
R/W R/W R/W
(COM 2)
LW-9543 (16bit) : MODBUS/ASCII server station no.
R/W R/W R/W
(COM 3)
LW-9544 (16bit) : MODBUS/ASCII server station no.
R/W R/W R/W
(ethernet)
LW-9570 (32bit) : received data count (bytes) (COM 1
R R R
MODBUS server)
LW-9572 (32bit) : received data count (bytes) (COM 2
R R R
MODBUS server)
LW-9574 (32bit) : received data count (bytes) (COM 3
R R R
MODBUS server)
LW-9576 (32bit) : received data count (bytes) (Ethernet
R R R
MODBUS server)
600
EasyBuilder8000 User’s Manual
LB-9030 update COM 1 communication parameters (set ON) R/W R/W R/W
LB-9031 update COM 2 communication parameters (set ON) R/W R/W R/W
LB-9032 update COM 3 communication parameters (set ON) R/W R/W R/W
LB-9065 disable/enable COM1 broadcast station no. R/W R/W R/W
LB-9066 disable/enable COM2 broadcast station no. R/W R/W R/W
LB-9067 disable/enable COM3 broadcast station no. R/W R/W R/W
LW-9550 (16bit) : COM 1 mode(0:RS232,1:RS485
R/W R/W R/W
2W,2:RS485 4W)
LW-9551 (16bit) : COM 1 baud
rate(7:1200,8:2400,0:4800,1:9600,2:19200,3:3840 R/W R/W R/W
0,4:57600,..)
LW-9552 (16bit) : COM 1 databits (7 : 7 bits, 8 : 8 bits) R/W R/W R/W
LW-9553 (16bit) : COM 1 parity (0 : none, 1: even, 2 : odd) R/W R/W R/W
LW-9554 (16bit) : COM 1 stop bits (1 : 1 bit, 2 : 2 bits) R/W R/W R/W
LW-9555 (16bit) : COM 2 mode(0:RS232,1:RS485
R/W R/W R/W
2W,2:RS485 4W)
LW-9556 (16bit) : COM 2 baud
rate(7:1200,8:2400,0:4800,1:9600,2:19200,3:3840 R/W R/W R/W
0,4:57600,..)
LW-9557 (16bit) : COM 2 databits (7 : 7 bits, 8 : 8 bits) R/W R/W R/W
LW-9558 (16bit) : COM 2 parity (0 : none, 1: even, 2 : odd) R/W R/W R/W
LW-9559 (16bit) : COM 2 stop bits (1 : 1 bit, 2 : 2 bits) R/W R/W R/W
LW-9560 (16bit) : COM 3 mode(0:RS232,1:RS485 2W) R/W R/W R/W
LW-9561 (16bit) : COM 3 baud
rate(7:1200,8:2400,0:4800,1:9600,2:19200,3:3840 R/W R/W R/W
0,4:57600,..)
LW-9562 (16bit) : COM 3 databits (7 : 7 bits, 8 : 8 bits) R/W R/W R/W
LW-9563 (16bit) : COM 3 parity (0 : none, 1: even, 2 : odd) R/W R/W R/W
LW-9564 (16bit) : COM 3 stop bits (1 : 1 bit, 2 : 2 bits) R/W R/W R/W
LW-9565 (16bit) : COM 1 broadcast station no. R/W R/W R/W
LW-9566 (16bit) : COM 2 broadcast station no. R/W R/W R/W
LW-9567 (16bit) : COM 3 broadcast station no. R/W R/W R/W
LW-10500 (16bit) : PLC 1 timeout (unit : 100ms) R/W R/W R/W
601
EasyBuilder8000 User’s Manual
LW-10501 (16bit) : PLC 1 turn around delay (unit : ms) R/W R/W R/W
LW-10502 (16bit) : PLC 1 send ACK delay (unit : ms) R/W R/W R/W
LW-10503 (16bit) : PLC 1 parameter 1 R/W R/W R/W
LW-10504 (16bit) : PLC 1 parameter 2 R/W R/W R/W
LW-10505 (16bit) : PLC 2 timeout (unit : 100ms) R/W R/W R/W
LW-10506 (16bit) : PLC 2 turn around delay (unit : ms) R/W R/W R/W
LW-10507 (16bit) : PLC 2 send ACK delay (unit : ms) R/W R/W R/W
LW-10508 (16bit) : PLC 2 parameter 1 R/W R/W R/W
LW-10509 (16bit) : PLC 2 parameter 2 R/W R/W R/W
LW-10510 (16bit) : PLC 3 timeout (unit : 100ms) R/W R/W R/W
LW-10511 (16bit) : PLC 3 turn around delay (unit : ms) R/W R/W R/W
LW-10512 (16bit) : PLC 3 send ACK delay (unit : ms) R/W R/W R/W
LW-10513 (16bit) : PLC 3 parameter 1 R/W R/W R/W
LW-10514 (16bit) : PLC 3 parameter 2 R/W R/W R/W
LW-10515 (16bit) : PLC 4 timeout (unit : 100ms) R/W R/W R/W
LW-10516 (16bit) : PLC 4 turn around delay (unit : ms) R/W R/W R/W
LW-10517 (16bit) : PLC 4 send ACK delay (unit : ms)
R/W R/W R/W
(SIEMENS S7/400 Link type)
LW-10518 (16bit) : PLC 4 parameter 1 (SIEMENS S7/400
R/W R/W R/W
rack)
LW-10519 (16bit) : PLC 4 parameter 2 (SIEMENS S7/400
R/W R/W R/W
CPU slot)
LW-10520 (16bit) : PLC 5 timeout (unit : 100ms) R/W R/W R/W
LW-10521 (16bit) : PLC 5 turn around delay (unit : ms) R/W R/W R/W
LW-10522 (16bit) : PLC 5 send ACK delay (unit : ms)
R/W R/W R/W
(SIEMENS S7/400 Link type)
LW-10523 (16bit) : PLC 5 parameter 1 (SIEMENS S7/400
R/W R/W R/W
rack)
LW-10524 (16bit) : PLC 5 parameter 2 (SIEMENS S7/400
R/W R/W R/W
CPU slot)
LW-10525 (16bit) : PLC 6 timeout (unit : 100ms) R/W R/W R/W
LW-10526 (16bit) : PLC 6 turn around delay (unit : ms) R/W R/W R/W
LW-10527 (16bit) : PLC 6 send ACK delay (unit : ms)
R/W R/W R/W
(SIEMENS S7/400 Link type)
LW-10528 (16bit) : PLC 6 parameter 1 (SIEMENS S7/400
R/W R/W R/W
rack)
LW-10529 (16bit) : PLC 6 parameter 2 (SIEMENS S7/400 R/W R/W R/W
602
EasyBuilder8000 User’s Manual
CPU slot)
603
EasyBuilder8000 User’s Manual
604
EasyBuilder8000 User’s Manual
605
EasyBuilder8000 User’s Manual
LB-9153 auto. connection for PLC 4 (ethernet) (when ON) R/W R/W R/W
LB-9154 auto. connection for PLC 5 (ethernet) (when ON) R/W R/W R/W
LB-9155 auto. connection for PLC 6 (ethernet) (when ON) R/W R/W R/W
LB-9156 auto. connection for PLC 7 (ethernet) (when ON) R/W R/W R/W
LB-9157 auto. connection for PLC 8 (ethernet) (when ON) R/W R/W R/W
LB-9158 auto. connection for PLC 9 (ethernet) (when ON) R/W R/W R/W
LB-10070 forced to reconnect PLC 4 (ethernet) when IP or
R/W R/W R/W
system parameters changed on-line (set ON)
LB-10071 forced to reconnect PLC 5 (ethernet) when IP or
R/W R/W R/W
system parameters changed on-line (set ON)
LB-10072 forced to reconnect PLC 6 (ethernet) when IP or
R/W R/W R/W
system parameters changed on-line (set ON)
LB-10073 forced to reconnect PLC 7 (ethernet) when IP or
R/W R/W R/W
system parameters changed on-line (set ON)
LB-10074 forced to reconnect PLC 8 (ethernet) when IP or
R/W R/W R/W
system parameters changed on-line (set ON)
LB-10075 forced to reconnect PLC 9 (ethernet) when IP or
R/W R/W R/W
system parameters changed on-line (set ON)
LB-10100 PLC 4 status (ethernet), set on to retry connection R/W R/W R/W
LB-10400 PLC 5 status (ethernet), set on to retry connection R/W R/W R/W
LB-10700 PLC 6 status (ethernet), set on to retry connection R/W R/W R/W
LB-11000 PLC 7 status (ethernet), set on to retry connection R/W R/W R/W
LB-11300 PLC 8 status (ethernet), set on to retry connection R/W R/W R/W
LB-11600 PLC 9 status (ethernet), set on to retry connection R/W R/W R/W
LB-11900 PLC 10 status (ethernet), set on to retry
R/W R/W R/W
connection
LB-11901 PLC 11 status (ethernet), set on to retry
R/W R/W R/W
connection
LB-11902 PLC 12 status (ethernet), set on to retry
R/W R/W R/W
connection
LB-11903 PLC 13 status (ethernet), set on to retry
R/W R/W R/W
connection
LB-11904 PLC 14 status (ethernet), set on to retry R/W R/W R/W
606
EasyBuilder8000 User’s Manual
connection
LB-11905 PLC 15 status (ethernet), set on to retry
R/W R/W R/W
connection
LB-11906 PLC 16 status (ethernet), set on to retry
R/W R/W R/W
connection
LW-9600 (16bit) : PLC 4's IP0 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9601 (16bit) : PLC 4's IP1 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9602 (16bit) : PLC 4's IP2 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9603 (16bit) : PLC 4's IP3 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9604 (16bit) : PLC 4's port no. R/W R/W R/W
LW-9605 (16bit) : PLC 5's IP0 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9606 (16bit) : PLC 5's IP1 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9607 (16bit) : PLC 5's IP2 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9608 (16bit) : PLC 5's IP3 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9609 (16bit) : PLC 5's port no. R/W R/W R/W
LW-9610 (16bit) : PLC 6's IP0 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9611 (16bit) : PLC 6's IP1 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9612 (16bit) : PLC 6's IP2 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9613 (16bit) : PLC 6's IP3 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9614 (16bit) : PLC 6's port no. R/W R/W R/W
LW-9615 (16bit) : PLC 7's IP0 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9616 (16bit) : PLC 7's IP1 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9617 (16bit) : PLC 7's IP2 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
607
EasyBuilder8000 User’s Manual
608
EasyBuilder8000 User’s Manual
609
EasyBuilder8000 User’s Manual
LB-9068 auto. connection for remote HMI 1 (when ON) R/W R/W R/W
LB-9069 auto. connection for remote HMI 2 (when ON) R/W R/W R/W
LB-9070 auto. connection for remote HMI 3 (when ON) R/W R/W R/W
LB-9071 auto. connection for remote HMI 4 (when ON) R/W R/W R/W
LB-9072 auto. connection for remote HMI 5 (when ON) R/W R/W R/W
LB-9073 auto. connection for remote HMI 6 (when ON) R/W R/W R/W
LB-9074 auto. connection for remote HMI 7 (when ON) R/W R/W R/W
LB-9075 auto. connection for remote HMI 8 (when ON) R/W R/W R/W
LB-9100 remote HMI 1 status (set on to retry connection) R/W R/W R/W
LB-9101 remote HMI 2 status (set on to retry connection) R/W R/W R/W
LB-9102 remote HMI 3 status (set on to retry connection) R/W R/W R/W
LB-9103 remote HMI 4 status (set on to retry connection) R/W R/W R/W
LB-9104 remote HMI 5 status (set on to retry connection) R/W R/W R/W
LB-9105 remote HMI 6 status (set on to retry connection) R/W R/W R/W
LB-9106 remote HMI 7 status (set on to retry connection) R/W R/W R/W
LB-9107 remote HMI 8 status (set on to retry connection) R/W R/W R/W
LB-9149 forced to reconnect remote HMI when IP changed
R/W R/W R/W
on-line (set ON)
LW-9800 (16bit) : remote HMI 1's IP0 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9801 (16bit) : remote HMI 1's IP1 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9802 (16bit) : remote HMI 1's IP2 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9803 (16bit) : remote HMI 1's IP3 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9804 (16bit) : remote HMI 1's port no. R/W R/W R/W
LW-9805 (16bit) : remote HMI 2's IP0 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9806 (16bit) : remote HMI 2's IP1 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9807 (16bit) : remote HMI 2's IP2 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
610
EasyBuilder8000 User’s Manual
611
EasyBuilder8000 User’s Manual
LW-9829 (16bit) : remote HMI 6's port no. R/W R/W R/W
LW-9830 (16bit) : remote HMI 7's IP0 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9831 (16bit) : remote HMI 7's IP1 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9832 (16bit) : remote HMI 7's IP2 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9833 (16bit) : remote HMI 7's IP3 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9834 (16bit) : remote HMI 7's port no. R/W R/W R/W
LW-9835 (16bit) : remote HMI 8's IP0 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9836 (16bit) : remote HMI 8's IP1 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9837 (16bit) : remote HMI 8's IP2 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9838 (16bit) : remote HMI 8's IP3 (IP address =
R/W R/W R/W
IP0:IP1:IP2:IP3)
LW-9839 (16bit) : remote HMI 8's port no. R/W R/W R/W
612
EasyBuilder8000 User’s Manual
613
EasyBuilder8000 User’s Manual
614
EasyBuilder8000 User’s Manual
615
EasyBuilder8000 User’s Manual
616
EasyBuilder8000 User’s Manual
LB-9000 ~ initialized as ON
R/W R/W R/W
LB-9009
LB-9010 data download indicator R R R
LB-9011 data upload indicator R R R
LB-9012 data download/upload indicator R R R
LB-9016 status is on when a client connects to this HMI R R R
LB-9017 disable write-back in PLC control's [change
R/W R/W R/W
window]
LB-9039 status of file backup activity (backup in process if
R R R
ON)
LB-9045 memory-map communication fails (when ON) R R R
LB-9049 enable (set ON)/disable (set OFF) watch dog (i
R/W R/W R/W
series support only) *1
LB-9059 disable MACRO TRACE function (when ON) *2 R/W R/W R/W
LB-9064 enable USB barcode device (disable keyboard)
R/W R/W R
(when ON) *3
LW-9006 (16bit) : connected client no. R R R
LW-9024 (16bit) : memory link system register R/W R/W R/W
LW-9032 (8 words) : folder name of backup history files to
R/W R/W R/W
SD, USB memory
LW-9050 (16bit) : current base window ID R R R
LW-9134 (16bit) : language mode *4 R/W R/W R/W
LW-9300 (16bit) : driver ID of local PLC 1 R R R
LW-9301 (16bit) : driver ID of local PLC 2 R R R
LW-9302 (16bit) : driver ID of local PLC 3 R R R
LW-9303 (16bit) : driver ID of local PLC 4 R R R
LW-9530 (8 words) : VNC server password R/W R/W R/W
617
EasyBuilder8000 User’s Manual
4. When users would like to have the object’s text to show multi-language, except for using
Label Library, it needs to use the system reserved register [LW-9134: language mode].
The value of LW-9134 can be set from 0 to 7. Different data of LW-9134 corresponds to
different Languages. The way of using LW-9134 will differ if the languages are not all
chosen when compiling the downloaded file.
Want to know how to swith languages using Option List object toghther with LW-9134?
Please confirm your Internet connection before downloading the demo project.
618
EasyBuilder8000 User’s Manual
619
EasyBuilder8000 User’s Manual
22.24 EasyAccess
Read/Write Control
620
EasyBuilder8000 User’s Manual
621
EasyBuilder8000 User’s Manual
622
EasyBuilder8000 User’s Manual
Please confirm your Internet connection before downloading the demo project.
623
EasyBuilder8000 User’s Manual
624
EasyBuilder8000 User’s Manual
625
EasyBuilder8000 User’s Manual
626
EasyBuilder8000 User’s Manual
1. EPSON ESC/P2
Impact Printer:
LQ-300, LQ-300+, LQ-300K+ (RS232)
LQ-300+II (RS232)
Inkjet Printer:
Stylus Photo 750
Laser Printer:
EPL-5800
2. HP PCL Series
Laser Printer:
HP LaserJet P1505n: HP PCL 5e
• PCL 5 was released on HP LaserJet III in March 1990, added Intellifont font scaling
(developed by Compugraphic, now part of Agfa), outline fonts and HP-GL/2 (vector)
graphics.
627
EasyBuilder8000 User’s Manual
Please ensure that the HP printer supports PCL5 before connecting with MT8000
series. Otherwise MT8000 will stop responding with a black screen.
Inkjet Printer:
HP DeskJet 920C, 930C, D2360, D2560, D2568
3. SP-M, D, E, F
RS232 port
SIUPO
http://www.siupo.com
SP-M, D, E, F series
SP-E1610SK (paper width: 45mm)
SP-E400-4S (paper width: 57.5mm)
SP-MDEF
Recommended SP printer type for customers outside China
628
EasyBuilder8000 User’s Manual
4. Axiohm A630
Micro printer Axiohm A630 from France connected via serial port.
6. EPSON TM-L90
629
EasyBuilder8000 User’s Manual
Recipe Editor is a Win32 application and can only run on MS Windows 2000 / XP / Vista /
7. It allows users to create, view and modify Recipe (*.rcp) and EMI (*.emi) files.
Additionally, it can convert Recipe and EMI files to CSV format and vice versa.
24.1 Introduction
Under Recipe Editor [file] -> [new], the following dialogue appears:
Setting Description
Address range Fill in the address range users want to examine. The unit is “word”.
Add Add a column to the current data format template.
Delete Delete the selected column.
Clear All Delete all columns.
Modify Modify the description and data info for the selected column.
630
EasyBuilder8000 User’s Manual
Save Format Save the settings of the current data format template so that users
can load it every time when needed without recreating it repeatedly.
The template data will be stored as “data.fmt” file in the
EasyBuilder8000 installation directory.
Delete Format Delete an existed data format template.
Select your Select an existing data format template for examining the Recipe or
data format EMI data.
First, users can assign a name as [Description] for the column and then select the correct
data type. If [String] is selected, users must specify the length of the string.
631
EasyBuilder8000 User’s Manual
(2) Click [Add…] and select [16-bit Unsigned] as data format type.
632
EasyBuilder8000 User’s Manual
(3) After all the settings finished, a new document appears as follow
(5) In [Save As], select the correct format and file name to create a recipe or emi file.
633
EasyBuilder8000 User’s Manual
Chapter 25 EasyConverter
This application program is utilized when converting the history record of data sampling
(dtl) or event log (evt) stored in HMI to Excel (csv) that is readable on PC installed with
Microsoft Excel. The completed conversion can be exported to Excel.
25.1 Introduction
634
EasyBuilder8000 User’s Manual
Click [OK],
635
EasyBuilder8000 User’s Manual
When converting event log in csv format, users can find data fields in EXCEL as below.
636
EasyBuilder8000 User’s Manual
637
EasyBuilder8000 User’s Manual
For example, here is a data of voltage and data format is 16-bit unsigned (range: 0~4096).
If users want to map those data to volt range form -5 to +5, the calculation:
638
EasyBuilder8000 User’s Manual
Settings of data above can be saved as a sample and loaded next time.
639
EasyBuilder8000 User’s Manual
640
EasyBuilder8000 User’s Manual
Step3: After adding files, check [Combine to a file], files will be separated into sheets of
one EXCEL file labeled with the dated it is added.
641
EasyBuilder8000 User’s Manual
Note: If users don't check this box, the files will be exported to Excel individually.
642
EasyBuilder8000 User’s Manual
User can load an existing Setting file to apply to a data log file(s).
Step1: Save the setting to test.lgs after filling out [scaling & offset].
643
EasyBuilder8000 User’s Manual
644
EasyBuilder8000 User’s Manual
645
EasyBuilder8000 User’s Manual
Step3: Select the files that you would like to combine and check both [Enable Setting file]
and [Combine to a file] boxes. With [Combine to a file] edit, please indicate a file name
for the new outcome.
Step5: Open the newly combined file to examine the data in Microsoft Excel.
646
EasyBuilder8000 User’s Manual
Setting Description
setting Indicate the setting file.(*.lgs)
source Indicate the source file.(*.dtl or *.evt)
destination Indicate the destination file.(*.csv or *.xls)
Type of file output. If this is set, a CSV file will be output,
/c
otherwise an EXCEL file.
Whether involving a setting file or not. If this is set, it indicates
/s
that users utilize a setting file.
647
EasyBuilder8000 User’s Manual
Chapter 26 EasyPrinter
EasyPrinter is a Win32 application and can only run on MS Windows 2000 / XP / Vista / 7. It
enables MT8000 Series to output screen hardcopies to a remote PC via Ethernet. Please see the
following illustration:
Additionally, EasyPrinter can also be a backup server. Users can use backup objects in MT8000
HMI to copy history files such as Data‐Sampling and Event‐Log histories onto a remote PC via
Ethernet. Please see the following illustration:
648
EasyBuilder8000 User’s Manual
Users can make screen hardcopies with a [Function Key] object. The hardcopies will be
transferred to the MT Remote Printer Server via Ethernet and then printed out.
649
EasyBuilder8000 User’s Manual
1. In [Server], assign [Port number of the server socket] to “8005”, [User name] to
“admin” and [Password] to “111111”. (Note: These are default values.)
2. In [Naming Convention for HMI Folder], select [Use IP address] and assign “IP_”
as the [Prefix].
3. In [Properties], select [Minimize to system tray].
Click [Hardcopy] tab on the left side in the dialogue box as follows:
4. In [Output], select [Print out to] and choose a printer as the output device for
screen hardcopies. (Note: Users can only choose from the printers available in
their system, so it is possible that “hp LaserJet 3380 PCL 5” can’t be found in the
list as the example.)
5. Click [OK] to apply the settings.
6. In [Menu] Î [File], select [Enable Output] to allow EasyPrinter to output any
650
EasyBuilder8000 User’s Manual
In [Menu] Î [Edit] Î [System Parameters], click [Printer Server] tab and select [Use MT
Remote Printer Server], the following dialogue appears:
651
EasyBuilder8000 User’s Manual
In [Menu] Î [Objects] Î [Buttons], select [Function Key] and assign [Screen hardcopy] to [MT
Remote Printer Server].
9. Place the [Function Key] object in the common window (window no. 4), and users
will be able to make screen hardcopies anytime when needed.
10. [Compile] and [download] project to MT8000 HMI. Press the [Function Key]
object set in step 9 to make a screen hardcopy.
z Users can also use a [PLC Control] object to make screen hardcopies.
z Users cannot print alarm information via EasyPrinter.
z EasyPrinter can only communicate with HMI via Ethernet, so this feature is
unavailable in MT6000 Series.
652
EasyBuilder8000 User’s Manual
Users can upload historical data such as Data‐Sampling and Event‐Log history files onto MT
remote backup server with [Backup] objects.
1. In [Server], assign [Port number of the server socket] to “8005”, [User name] to
“admin” and [Password] to “111111”. (Note: These are default values.)
653
EasyBuilder8000 User’s Manual
2. In [Naming Convention for HMI Folder], select [Use IP address] and assign “IP_”
as the [Prefix].
3. In [Properties], select [Minimize to system tray].
Click [Backup] tab on the left side in the dialogue box as follows:
4. In [Output], click the button to browse and select a path for storage of the
incoming history files.
5. Click [OK] to apply the settings.
6. In [Menu] Î [File], select [Enable Output] to allow EasyPrinter to store any
incoming backup request in the location specified in step 4.
In [Menu] Î [Edit] Î [System Parameters], click [Printer Server] tab and select [Use MT
Remote Printer Server], the following dialogue appears:
654
EasyBuilder8000 User’s Manual
7. In [Communication settings], fill in the [IP address] of printer server same as step
1, assign [port number] to “8005”, [User name] to “admin” and [Password] to
“111111”.
655
EasyBuilder8000 User’s Manual
656
EasyBuilder8000 User’s Manual
26.3.1 Appearance
657
EasyBuilder8000 User’s Manual
The following tables describe the meaning and explain how to use all EasyPrinter menu items.
658
EasyBuilder8000 User’s Manual
MenuÆOptions Description
Toolbars To show or hide toolbars.
Status Bar To show or hide the status bar.
Settings Configuration for EasyPrinter. Please refer to the following
illustrations:
[General]
659
EasyBuilder8000 User’s Manual
660
EasyBuilder8000 User’s Manual
z [Output]
EasyPrinter provides two modes to output hardcopy
results: Print-Out and Save-to-File.
a. Print-Out
Select this option to inform EasyPrinter to print out the
hardcopy result with specified printers.
b. Save-to-File
661
EasyBuilder8000 User’s Manual
[Specified Path] Æ
[HMI Folder] Æ
yymmdd_hhmm.bmp
[Backup]
z [Output]
EasyPrinter stores the backup files to the specified path.
662
EasyBuilder8000 User’s Manual
[datalog] Æ
[Folder name of the Data-Sampling
object]Æ
yyyymmdd.dtl
For Recipe:
[Specified Path] Æ
[HMI Folder] Æ
[recipe] Æ
recipe.rcp or recipe_a.rcp
663
EasyBuilder8000 User’s Manual
EasyPrinter provides a mechanism for converting the uploaded Data‐Sampling and Event‐Log
history files stored in binary mode to CSV files automatically. Users requesting this function have
to prepare a Convert Batch File to provide EasyPrinter with the information of how to convert the
history files.
As shown in the illustration above, the conversion is actually carried out by EasyConverter.
EasyPrinter simply follows the criteria in Convert Batch File and activates EasyConverter with
proper arguments to achieve the conversion.
The following is the default Convert Batch File included in the EasyBuilder 8000 software
package:
664
EasyBuilder8000 User’s Manual
There are two lines of text in the file. Each line has two arguments separated by a comma and
forms a criterion of how to deal with a specific type of files, e.g. Data‐Sampling and Event‐Log
history files. The first argument specifies the extension name for the type of the files to be
processed and the second one specifies the exact command to execute in console mode. Please
note “$(PathName)” is a key word to tell EasyPrinter to replace it with the real name of the
backup file in conversion. For example, if a Data‐Sampling history file named 20090112.dtl is
uploaded and stored, EasyPrinter will send out the following command to a console window:
EasyConverter /c 20090112.dtl
z Actually, the “$(PathName)” in the second argument stands for the full path
name of the file. In the previous case, EasyPrinter replaces it with:
[Specified Path] \ [HMI Folder] \ [datalog] \
[Folder name of the Data-Sampling object] \ 20090112.dtl
z EasyPrinter interprets the Convert Batch File on a line basis, i.e. each line
forms a criterion.
z Any two arguments should be separated by a comma.
z Every argument should be put in double quotes.
z Do not put any comma inside an argument.
z For further information about how to use EasyConverter, please refer to the
“chapter25 Easy Converter”.
Sometimes users may need a special handling for the files uploaded from a specific HMI. Here is
an example:
Or in the case of needing special handling for different Data‐Sampling history files.
Specialized Criterion for the Data-Sampling object’s folder name = Voltage
5: "dtl", "EasyConverter /s Voltage.lgs $(PathName)", "*", "Voltage"
The 5th criterion can only be performed on the history files uploaded from the [Data Sampling]
objects with the folder name “Voltage”. The 3rd argument (“*”) indicates this criterion accepts the
qualified Data‐Sampling files from any HMI. Users can also change the 3rd argument to
“192.168.1.26”, “192.168.1.*”, HMI name, etc. for narrowing the target HMI.
666
EasyBuilder8000 User’s Manual
EasyPrinter examines criteria in ascending order every time a file is uploaded. Once the file is
qualified for a criterion, it stops the examination and starts over for next file. Therefore, users
should place the criteria with more specification upward in the Convert Batch File and place the
less‐specific criteria downward. Take the 5 criteria mentioned in the previous sections for
example, the correct order is:
667
EasyBuilder8000 User’s Manual
Chapter 27 EasySimulator
1. [driver] Æ [win32]
2. 320x234.bmp
3. 480x234.bmp
4. 480x272.bmp
5. 640x480.bmp
6. 800x480.bmp
7. 800x600.bmp
8. 1024x768.bmp
9. com.exe
10. EasySimulator.exe
11. gui.exe
12. xob_pos.def
Users can find all the above files in EasyBuilder installation directory, which means users
have to install EasyBuilder software package on a PC and copy the files to the target PC.
668
EasyBuilder8000 User’s Manual
Step 1. Open xob_pos.def using a text editing tool (e.g. Notepad) and set the contents
correctly.
669
EasyBuilder8000 User’s Manual
670
EasyBuilder8000 User’s Manual
Multi-HMI intercommunication means that HMI uses COM port to connect with a remote
HMI, and read/write data from/to PLC connected to remote HMI as below:
Above shows the PLC is connected with HMI 1, and HMI 1 is connected with HMI 2 via
COM port, so that HMI 2 can control the PLC through HMI 1.
An example describes how to use EB8000 to create projects used on HMI 1 and HMI 2.
671
EasyBuilder8000 User’s Manual
The following is the project content of HMI 1 in [System Parameter Settings] / [Device].
1. Due to COM 1 of HMI 1 connects PLC, the device list must include [Local PLC 1] in this
case is “FATEK FB Series”. The communication parameter must be set correctly.
2. Due to COM 2 of HMI 1 is used to receive commands from HMI 2; users must add a
new device – [Master-Slave Server] for setting communication properties of COM 2.
Picture above shows the parameters of COM 2 are “115200, E, 8, 1”, and uses RS232.
These parameters are not required to be the same as PLC, but the “data bits” must set
to 8. In general, a higher baud rate for COM 2 is recommended for communication more
efficient.
672
EasyBuilder8000 User’s Manual
The following is the project content of HMI 2 in [System Parameter Settings] / [Device].
Due to the PLC that HMI 2 reads from is connected with HMI 1, thus HMI 2 views PLC as a
remote device. Therefore, it is necessary to add a [*Remote PLC 1] into the device list and
in this case is “FATEK FB Series”. The way to create [*Remote PLC 1] is described below:
Step 1
Create a new device”FATEK FB Series” for [PLC type]. [PLC default station no.] must
be the same as the connected PLC.
Step 2
Correctly set the parameters. COM 1 of HMI 2 connects with COM 2 of HMI 1, so they both
must have the same communication parameters and interfaces, ignoring the PLC
parameters. As below, COM 2 of HMI 1 and COM 1 of HMI 2 use RS232 and the
parameters are [115200, E, 8, 1].
673
EasyBuilder8000 User’s Manual
Step 3
Since HMI 2 views PLC a remote device, here we change [Location] to [Remote], and
select [COM port] to connect remote HMI (HMI 1).
After completing all settings described above, users can find a new device named
[*Remote PLC 1] in the [device table]. This device has the “*” symbol means that HMI
uses a COM port (not Ethernet) to control a remote PLC via other HMI.
Users can check local registers of HMI to view the communication status.
([*Remote PLC1] uses same registers as [Local PLC1])
674
EasyBuilder8000 User’s Manual
Tag Description
When ON, auto. connection with PLC (COM 1) when disconnected.
LB-9150
When OFF, ignore disconnection with PLC.
When ON, auto. connection with PLC (COM 2) when disconnected.
LB-9151
When OFF, ignore disconnection with PLC.
When ON, auto. connection with PLC (COM 3) when disconnected.
LB-9152
When OFF, ignore disconnection with PLC.
Tag Description
These local registers indicate the connection states with PLC
(through COM1).
LB9200 indicates the connection state with PLC (station no. 0), and
LB-9200~ LB9201 indicates the connection state with PLC (station no. 1) and
LB-9455 so on.
When ON, indicates connection state is normal.
When OFF, indicates disconnection with PLC.
Set ON again, the system will then try to connect with PLC.
These local registers indicate the connection states with PLC
(through COM2).
LB9500 indicates the connection state with PLC (station no. 0), and
LB-9500~ LB9501 indicates the connection state with PLC (station no. 1) and
LB-9755 so on.
When ON, indicates connection state is normal.
When OFF, indicates disconnection with PLC.
Set ON again, the system will then try to connect with PLC.
These local registers indicate the connection states with PLC
(through COM3).
LB9800 indicates the connection state with PLC (station no. 0), and
LB-9800~ LB9801 indicates the connection state with PLC (station no. 1) and
LB-10055 so on.
When ON, indicates connection state is normal.
When OFF, indicates disconnection with PLC.
Set ON again, the system will then try to connect with PLC.
675
EasyBuilder8000 User’s Manual
Allowing MT500 using Master-Slave protocol to read MT6000/8000 Local data and data of
PLC connected with MT6000/8000.
¾ MT8000 Settings
Step 1
Select “Master-Slave Server” driver and click [Settings...]. If a PLC is connected, follow the
original settings.
Step 2
Select RS232 and click [Settings...].
676
EasyBuilder8000 User’s Manual
Step 3
Fill in MT500 PLC ID No. in Parameter 1 (Refer to MT500 settings).
677
EasyBuilder8000 User’s Manual
¾ MT500 Settings
Step 1
In EB500/System Parameter Setting, set Multiple HMI: Slave, HMI-HMI link speed:
115200
Step 2
Double click on PLC Address View.exe to check PLC ID No. and fill in Parameter 1 of
MT8000.
678
EasyBuilder8000 User’s Manual
Note: There will always be a PLC selected in EB500 system parameters setting, in this
case, even to read/write MT8000 Local Data only, the ID of selected PLC in EB500 system
parameters must also be filled in EB8000 parameter 1.
Also, when using S7-200, S7-300 drivers, since in EB500 the high and low bytes are sent
in reverse order, this will cause MT500 to misread MT8000 Local data.
Step 3
COM Port used: RS232, connect it with RS232 of MT8000, the communication is then
enabled.
Device address:
Bit/Word MT500 MT8000 Range Memo
dddd:0~4095
B Ms_RB RW_Bit (h): 0~f
B Ms_LB LB dddd:0~9999
W Ms_RW RW ddddd:0~65535
W Ms_LW LW dddd:0~9999
679
EasyBuilder8000 User’s Manual
The pass-through function allows the PC application to control PLC via HMI. In this case
the HMI acts as a converter.
The pass-through function provides two modes: [Ethernet] and [COM port]. Click
[Pass-through] in [Project Manager] will open a setting dialogue.
680
EasyBuilder8000 User’s Manual
If [Virtual COM port (PC<->PLC)] displays [Please install weintek virtual serial port
driver], please click [Install].
If the dialogue below pops up during installation, please click [Continue Anyway].
681
EasyBuilder8000 User’s Manual
Open [System Properties] -> [Device Manager] to check if the virtual serial port is
installed successfully.
If users want to change the number of virtual serial port, please click [Weintek Virtual
Serial Port] to open [Port Settings] / [Advanced…], as follows:
682
EasyBuilder8000 User’s Manual
For example, user changes virtual serial port from COM 3 to COM 9.
683
EasyBuilder8000 User’s Manual
Select COM 9 and click [OK], the virtual serial port will be changed to COM 9.
It can be found that the virtual COM port be changed to COM 9 in [Project Manager].
684
EasyBuilder8000 User’s Manual
After installing virtual serial port driver, users should follow four steps to use Ethernet
mode of pass-through.
Step 1
Set IP of the HMI connected with PLC. For example, HMI IP is 192.168.1.206
Step 2
Assign serial port properties of the port connects HMI with PLC. For example, COM2 (use
RS232) is used to connect PLC.
Step 3
Click [Apply], and these settings will be updated.
Step 4
685
EasyBuilder8000 User’s Manual
In the PC application, the number of the serial port must be the same as the virtual one.
For example, using a Mitsubishi application, if the virtual serial port is COM 7, please open
[PC side I/F Serial setting] / [COM port] to select COM 7, as follows:
After completing all settings, when users execute PLC application on PC, the HMI will be
switched automatically to pass-through mode (the communication between HMI and PLC
will be suspended this moment and it will be resumed if the application closes), as follows:
At this moment the application is controlling PLC directly via virtual serial port.
686
EasyBuilder8000 User’s Manual
When using [COM port] mode of pass-through, users should correctly set the properties
of source COM port and Destination COM port.
There are two ways to enable [COM port] mode of pass-through function.
(1) Use Project Manager
(2) Use system registers LW-9901 and LW-9902
LW-9901: pass-through source COM port (1~3: COM1~COM3)
LW-9902: pass-through destination COM port (1~3: COM1~COM3)
Note: When finish using Pass Through function, users should click [Stop Pass-through] to
disable it so that HMI can start to communicate with PLC
687
EasyBuilder8000 User’s Manual
[HMI IP]
Assign HMI IP address.
688
EasyBuilder8000 User’s Manual
Click [Get HMI Communication Parameters] to update HMI current states and
communication parameters.
Mode Description
Unknown Before getting the settings of HMI, the work mode is displayed
“Unknown”.
Normal After getting the settings of HMI, if work mode displays “Normal”
PC can’t control PLC via HMI.
Pass-through HMI is working on pass-through state; at this time, the PC
application can control PLC via source com port.
689
EasyBuilder8000 User’s Manual
The communication parameters of source and destination COM port are displayed in
these two areas. The settings will be used when [Start pass-through] is clicked.
The “Baud rate”, “Data bits”, “Parity”, and “Stop bits” of [Source COM Port] and
[Destination COM Port] have to be the same.
[Source COM Port] connects PC, so select RS232 mode; [Destination COM Port]
connects PLC, so settings depend on the PLC requirements.
The illustration below shows the setting when HMI connects SIEMENS S7/200.
The HMI COM 1 (RS232) connects PC, COM 3 (RS485 2W) connects PLC. The
communication parameter of PLC is”9600, E, 8, 1”. Before starting pass-through, users
must set the parameters in MTP project and download the project to HMI.
After the project is downloaded to HMI, open the same project and change the PLC I/F and
COM port to COM 1 RS232 (PC uses COM 1 to connect HMI) as follows:
690
EasyBuilder8000 User’s Manual
After that, press [Pass-through] to assign HMI IP address; for example, 192.168.1.37.
Finally, press [Get HMI Communication Parameters], as follows:
691
EasyBuilder8000 User’s Manual
Press [Start Pass-through] and HMI work mode is switched into “Pass-through”. Users
can execute on-line simulation. Now PC application can control PLC via HMI, and HMI is
acting as a converter at this moment.
Note: The communication between HMI and PLC will be paused when pass-through is
active. If users want to resume communication between HMI and PLC, please press [Stop
Pass-through] to disable this function.
692
EasyBuilder8000 User’s Manual
Other way to enable pass-through is to use LW-9901/LW-9902 to set source COM port
and destination COM port directly. When the values of LW-9901 and LW-9902 match
conditions as below, HMI will start pass-through automatically:
Note: If users want to stop pass-through, just change the values of LW-9901 and LW-9902
to 0.
If users need to change the communication parameters, just change the value in related
reserved addresses and set ON to LB-9030, LB-9031 and LB-9032. HMI will be forced to
accept new settings.
Tag Description
LB-9030 Update COM1 communication parameters (set ON)
LB-9031 Update COM2 communication parameters (set ON)
LB-9032 Update COM3 communication parameters (set ON)
693
EasyBuilder8000 User’s Manual
The copyright of program design must be protected. EB8000 supports protection function
of project file to ensure users' design achievement.
After project (MTP) is completed, users can compile the file to XOB format that can be
downloaded to HMI. Users can set password to protect the XOB file in Compiling window.
A password must be input if users want to decompile the XOB file to MTP. (XOB password
range: 0~4294901760)
694
EasyBuilder8000 User’s Manual
If this box is ticked, the system will automatically deny [XOB password]. Furthermore, the
XOB file can’t be decompiled to MTP file.
695
EasyBuilder8000 User’s Manual
EB8000 provides system reserved address LB9033. When this address is set ON, the HMI
will disable upload function of XOB file and vice versa. HMI needs to be rebooted to active
LB9033.
696
EasyBuilder8000 User’s Manual
User’s project can be restrained to be executed only on specific HMI (for i series HMI
only).
Please go to [System Parameters Settings]/ [General]/ [Project protection].
Users can use LW9046~LW9047 (32-bit) to set the [HMI key]. The value can’t be read or
written into these two registers even by remote HMI. While using this function, user can set
the password ([project key] password range: 0~4294901750), and the XOB file can only
be executed on specific HMI whose [HMI Key] is the same as [Project key]. If [Project Key]
is different from [HMI key], the system will turn LB9046 ON. HMI needs to be rebooted
while setting [HMI key] every time.
697
EasyBuilder8000 User’s Manual
Users can set password to protect the MTP file in [System parameter] / [Security] tab.
Enabling this, password must be input if user wants to edit MTP file. (MTP password range:
1~4294967295)
After setting, each time when try to open the project, a window pops up for password input.
Note: When using “Window Copy” function, if the source file is protected by MTP
password, users have to input correct password for EasyBuilder8000 to execute window
copy.
698
EasyBuilder8000 User’s Manual
699
EasyBuilder8000 User’s Manual
The corresponding memory has the same property as MT8000’s register MW(MB) from
Master and Slave (The 1000 words MW(MB) are reserved for MemoryMap in MT8000 for
communication.) The feature of memory: MB is correspondence with MW, according to the
following list, MB0~MBf and MW0, MB10~MB1f and MW1…, they all indicate the same
register.
When using MemoryMap communication protocol, the master and slave have to use the
same communication setting. The wiring diagram as follow:
RS232
Master Slave
TX(#) RX(#)
RX(#) TX(#)
GND(#) GND(#)
RS485 (4W)
Master Slaver
TX+(#) RX+(#)
TX-(#) RX-(#)
RX+(#) TX+(#)
RX-(#) TX-(#)
700
EasyBuilder8000 User’s Manual
GND(#) GND(#)
Start
Yes
Send data
No
Receiving
STX(02H)
No
Yes
Sending ACK(06H),
waiting time is
3sec.(default)
No
Yes
No
Received Out of 3
Data sec.
Yes
Sending ACK(06H)
Sending STX(02H,
waiting time is 3 sec.
Yes
No
No Yes
Receiving Out of 3
sec.
(b)
Flowchart 2
(a)
Yes Checking
Delay 100ms NAK(15H)
No No
Checking No Yes
ACK(06H) Out of 3
sec.
Yes
Sending data
No
Receiving No Yes
ACK(06H) Out of 3
sec.
701
Stop sending
EasyBuilder8000 User’s Manual
Flowchart 2
Checking No
STX(02H) Going to flowchart (a)
Yes
Sending ACK(06H
The waiting time is 3
sec. (default)
No
No Yes
Receiving Out of 3
data sec.
Yes
Sending ACK(06H)
Go to flowchart (b)
Caution:
Flowchart 2 is available for slave but not master, STX is asking signal for communication,
ACK is feedback signal, and NAK is busy signal.
There are two data formats, one is for MB and another is for MW:
For MB command
Offset (byte) Format Description
0 0x02 The operating sign to MB
1 0x## Address (Low byte)
2 0x## Bit Address (High byte)
For example:MB12=>1*16+2=18, is 0x12 and 0x00
3 0x00( or 0x01) The data of MB address.
(This is Bit, so has to be 0 or 1)
4,5 0x10,0x03 Stop sign
6 0x## checksum, xor from 0 byte to fifth byte.
For MW command
Offset(byte) Format Description
0 0x01 The operating sign to MW
1 0x## Address (Low byte)
2 0x## Bit Address (High byte)
If there is a 0x10 included in address, and insert a
702
EasyBuilder8000 User’s Manual
0x10 after it, the byte will move to next position. For
example: 0x10, 0x04 will become 0x10,0x10,0x04
3 0x## Sending byte (The byte has to be even, due to
operating for word). If byte is 0x10 then insert a
0x10 after it, the byte will move to next position
4~4+n-1 0x##(L) The data of initial address for corresponding
0x##(H) address for 1,2 byte, n is byte of data, if data
0x##(L)… includes 0x10 and then insert a 0x10, the sending
byte number remains same, then n=n+1, and so
on…
4+n,4+n+1 0x10,0x03 End sign
4+n+2 0x## checksum,Xor check-up and bytes in the front
703
EasyBuilder8000 User’s Manual
When finishing communication, master sending revised data of MW to slave, and slave
changes the MW which corresponds to that of master. At this time, master and slave keep
the same data in the same address.
Another example below, the address and data include 0x10; please notice the change in
data format. Now, if we have 0x10 in MW16 in slave, according to this protocol, slave will
communicate with master immediately, and master will put 0x10 in data of corresponding
MW16, the procedure is as following:
When finishing communication, slave sending the address and content of MW to master,
at this time, master changes data of MW corresponding to that of Slave, then master and
slave keep the same data in the same address.
704
EasyBuilder8000 User’s Manual
705
EasyBuilder8000 User’s Manual
Note:
1. Between two HMI, Time out has to set to 0.5 sec. and another has to set to 0.8 sec.
2. [Data bit] has to be 8 bits.
3. The rest of the settings should be identical between two HMI.
706
EasyBuilder8000 User’s Manual
707
EasyBuilder8000 User’s Manual
[Save],[Compile],[Download]
Change parameter in [System Parameter Setting]/[PLC] and download to another HMI.
708
EasyBuilder8000 User’s Manual
Users may try to touch the screen; the other HMI will act the same as current HMI.
The communicating way is the same as above-mentioned. The point is to keep the
same data in the same register.
709
EasyBuilder8000 User’s Manual
710
EasyBuilder8000 User’s Manual
1 2
3 4
Protocol
1 Robust
The protocol uses the non-printable characters STX (02H) and ETX (03H), ACK
(06H), and NAK (15H); and includes a 2-byte checksum.
2 Simple
Some Host devices (such as Motion Controllers) are not capable of generating
the non-printable characters, or calculating the checksum. In this mode, the
data packets are formed as defined below, but do not include the STX, ACK,
ETX, NAK, or checksum. The 0x0D is at the end of the packet, the packet sent
by MT8000 also has a 0x0D at the end.
Note: If set to 1, the Turn Around Delay setting (Parameter 2) has no affect.
711
EasyBuilder8000 User’s Manual
32.3.1 Wiring
The MT8000 ASCII protocol shall support network wiring using RS485 2-wire, 4-wire, or
RS232.
32.3.2 Addressing
The protocol shall support each MT8000 having a unique Station ID. Valid Station ID
shall be from 1 to 255.
712
EasyBuilder8000 User’s Manual
32.4.1.1 Request
This command reads up to 99 consecutive 16-bit items from the ‘LW’ memory area of HMI.
The command is always 14 bytes long.
Byte 1 Bytes Bytes 4, Bytes 6-9 Bytes 10, 11 Byte 12 Bytes 13, 14
2,3 5
1 Byte 2 Bytes 2 Bytes 4 Bytes 2 Bytes 1 Byte 2 Bytes
STX Station RD Addr. No. of Items ETX Checksum
Example: Read 3 words starting from address LW100, from the HMI at station 10 (0AH).
This will read addresses LW100 – LW102.
Byte 1 Bytes 2, Bytes 4, Bytes 6-9 Bytes 10, 11 Byte 12 Bytes 13, 14
3 5
STX 0A RD 0100 03 ETX 2E
02 30,41 52,44 30,31,30,30 30,33 03 32,45
The checksum (bytes 13 and 14) is calculated as the lowest 8 bits of the sum of the Hex
codes for bytes 2 – 12.
30 + 41+ 52 + 44 + 30 + 31 + 30 + 30 + 30 + 33 + 03 = 22E.
713
EasyBuilder8000 User’s Manual
32.4.1.2 Reply
L = (N * 4) + 8
Byte Byte
L-2 L-1, L
ETX Checksum
The example above returns the following, assuming the HMI contains the following data:
Address Data
100 75 (4BH)
101 8047 (1F6FH)
102 16,321 (3FC1H)
STX ‘0’ ‘A’ ‘R’ ‘D’ ‘0’ ‘0’ ‘4’ ‘B’ ‘1’ ‘F’ ‘6’ ‘F’ ‘3’ ‘F’ ‘C’ ‘1’
02H 30H 41H 52H 44H 30H 30H 34H 42H 31H 46H 36H 46H 33H 46H 43H 31H
714
EasyBuilder8000 User’s Manual
The values in each requested device are returned in Hex. The checksum is calculated on
bytes 2 – (L-2).
32.4.2.1 Request
This command writes up to 99 consecutive 16-bit items to the LW memory area of HMI.
The length of the command is
L = (N * 4) + 14
The command will be at least 18 bytes long, but can be up to 410 bytes long.
Byte Bytes Byte Byte Bytes Bytes Bytes Bytes Bytes Byt Byte
1 2, 3 s s 10, 12-15 16-19 20 - (L-7) (L-6) - e L-1, L
4, 5 6-9 11 (L-3) L-2
STX Statio WD Addr. No. of Data Data Data 3 – Data ETX Chec
n Items 1 2 Data (N-1) N k-su
m
715
EasyBuilder8000 User’s Manual
Example: Write 3 words starting from address LW201, to the HMI at station 17 (11H).
This will write to addresses LW201, LW202, and LW203.
Byte Bytes Bytes Bytes 6-9 Bytes Bytes Bytes Bytes Byte Bytes
1 2, 3 4, 5 10,11 12-15 16-19 20-23 24 25,26
STX 11 WD 0201 03 0065 023F 0419 ETX 9A
02 31,31 57,44 30,32,30,31 30,33 30,30,36,35 30,32,33,46 30,34,31,39 03 39,41
The checksum (bytes 25 and 26) is calculated as the lowest 8 bits of the sum of the Hex
codes for bytes 2 – 24.
31+ 31 + 57 + 44 + 30 + 32 + 30 + 31 + 30 + 33 + 30 + 30 + 36 + 35 + 30 + 32 + 33+ 46 +
30 + 34+ 31+ 39 + 03 = 49A.
The lowest 8 bits of the result returns 9A.
32.4.2.2 Reply
716
EasyBuilder8000 User’s Manual
32.4.3.1 Request
L = (N * 4) + 8
717
EasyBuilder8000 User’s Manual
32.4.3.2 Reply
L = (N * 4) + 8
If successful, the reply length will be at least 12 bytes, but can be up to 406 bytes. It
consists of the STX, followed by four bytes for each requested device, then the ETX and
Checksum.
Byte Byte
L-2 L-1, L
ETX Checksu
m
The values in each requested device are returned in Hex. The checksum is calculated as
the lowest 8 bits of the sum of bytes 2 – (L-2)...
718
EasyBuilder8000 User’s Manual
32.4.4.1 Request
L = (N * 8) + 8
719
EasyBuilder8000 User’s Manual
32.4.4.2 Reply
32.4.5.1 Request
This command reads up to 99 consecutive coils from the ‘LB’ memory area of HMI. The
command is always 14 bytes long.
Byte 1 Bytes 2, Bytes 4, Bytes 6-9 Bytes 10, 11 Byte 12 Bytes 13, 14
3 5
1 Byte 2 Bytes 2 Bytes 4 Bytes 2 Bytes 1 Byte 2 Bytes
STX Station RC Addr. No. of Items ETX Checksum
720
EasyBuilder8000 User’s Manual
Bytes 6-9: This is the starting address to read from. Must be 4 bytes long,
Bytes 10, 11: This is the number of coils to read, up to 99. Must be 2 bytes long.
Byte 12: Always ETX (0x03)
Bytes 13, 14: The checksum is the lowest 8 bits of the sum of bytes 2 through 12.
Example: Read 12 coils starting from address LB100, from the HMI at Station 7. This will
read coils LB100 – LB111.
Byte 1 Bytes Bytes 4, Bytes 6-9 Bytes 10, 11 Byte 12 Bytes 13, 14
2,3 5
STX 07 RC 0100 02 ETX 22
02 30,37 52,43 30,31,30,30 30,32 03 32,32
The checksum (bytes 13 and 14) is calculated as the lowest 8 bits of the sum of the Hex
codes for bytes 2 – 12.
30 + 37 + 52 + 43 + 30 + 31 + 30 + 30 + 30 + 32 + 03 = 222.
32.4.5.2 Reply
L=N+8
If the command is successful, the reply length will be at least 9 bytes, but could be as long
as 107 bytes. It consists of the STX, followed by one byte for each requested device,
then the ETX and Checksum.
721
EasyBuilder8000 User’s Manual
The values in each requested device are returned in Hex. The checksum is calculated on
bytes 2 – (L-2).
32.4.6.1 Request
This command writes up to 99 consecutive coils to the ‘LB’ memory area of HMI. The
length of the command is
L = N + 14
722
EasyBuilder8000 User’s Manual
The command will be at least 15 bytes long, but can be up to 113 bytes long.
Example: Write 5 bits starting from address LB214 to the HMI at station 12. This will write
to addresses LB214 – LB218.
Byt Bytes Bytes Bytes Bytes Byte Byte Byte Byte Byte Byte Bytes
e1 2,3 4, 5 6-9 10,11 12 13 14 15 16 17 18, 19
STX 0C WC 0214 05 1 1 0 0 1 ETX 2F
02 30,43 57,43 30,32,31,3 30,35 31 31 30 30 31 03 32,46
4
723
EasyBuilder8000 User’s Manual
The checksum (bytes 18 and 19) is calculated as the lowest 8 bits of the sum of the Hex
codes for bytes 2 – 17.
30 + 43+ 57 + 43 + 30 + 32 + 31 + 34 + 30 + 35 + 31 + 31 + 30 + 30 + 31 + 03 = 32F.
32.4.6.2 Reply
724
EasyBuilder8000 User’s Manual
The following table lists the error conditions, and the Error Codes returned for those errors.
Code Description
06H Invalid Checksum
10H Unknown Command
11H Data Length Error – data overflowed receive
buffer
12H Communication Data Error – ETX not found
7AH Illegal Address
7BH More than 99 data items were requested
725
EasyBuilder8000 User’s Manual
Chapter 33 EasyDiagnoser
33.1 Overview and Configuration
Overview
EasyDiagnoser is a tool for detecting the error occurs while HMI is communicating with
PLC.
Configuration
Step 1.
Open Project Manager and click EasyDiagnoser.
EasyDiagnoser
Step 2.
726
EasyBuilder8000 User’s Manual
Input HMI IP
address
Search HMI
It is also available to right click and select “Run EasyDiagnoser” for entering the setting
window when executing On-Line Simulation in EB8000.
727
EasyBuilder8000 User’s Manual
After setting completed, click OK, EasyDiagnoser operation window appears as below:
728
EasyBuilder8000 User’s Manual
Exit
Exit current file.
View
Click [Device Bar] to display Device window.
Click [Package Bar] to display Package window.
Click [Logger Bar] to display Logger window.
Click [Output Bar] to display Output window.
Options Toolbars
Display toolbar icons of [Device Bar] [Package Bar] [Logger
Bar] [Output Bar].
729
EasyBuilder8000 User’s Manual
z Activity area
In the activity area, users can observe the communication between HMI and PLC.
730
EasyBuilder8000 User’s Manual
Item Description
Command a. Read + Write
Display Read and Write commands in activity area.
b. Read
Display only Read commands in activity area.
c. Write
Display only Write commands in activity area.
Device a. All
Display information of Local HMI and PLC. It depends on the setting of
command as following.
731
EasyBuilder8000 User’s Manual
If command is set Read + Write, the Read and Write information of PLC
will be displayed in activity area.
If command is set Read, the Read information of PLC will be displayed
in activity area.
If command is set Write, the Write information of PLC will be displayed
in activity area.
Station Select specific Station for display on the screen. (This function will be
disabled when selecting [All] in Device).
Address Users can select all or a part of address types to be displayed on the
Type screen. (This function will be disabled when selecting [All] in Device).
Range Set the range of address types to be displayed. (This function will be
disabled when selecting [All] in Address Type).
Capture Click to start/stop capturing communication message.
Error Please refer to the section coming later.
z Polling Packages
Item Description
Package ID Use the information of package ID to check the PID in activity area for
finding the problem.
Device Displays HMI and PLC type.
Station Displays PLC station number.
Index Display objects-used index register numbers.
732
EasyBuilder8000 User’s Manual
After opening Package, the information such as Object, Screen, ID, Address inside
it will be displayed.
Object Package ID where this object is placed.
Screen Window in the project where this object is placed.
ID ID of the object.
Address Address of the object.
Note:
a. Click [Package ID], the device station number will be displayed in 3rd column.
b. Double click [Package ID] then select [object], the 1st column directs the object’s
position.
For example, select [Numeric Input] and the screen no. displays 10.
This shows that this object is in window no. 10 in the project and will be marked with pink
frame in HMI as shown below.
733
EasyBuilder8000 User’s Manual
z Devices
Devices window displays information of HMI and PLC.
734
EasyBuilder8000 User’s Manual
735
EasyBuilder8000 User’s Manual
0: Normal
1: Time out
2: Fail Error
12: Ignore
When error occurs, error message will be shaded red as shown below.
The error code is 1 since PLC is disconnected with HMI.
The error code is 12 since “PLC No Response” message window is shown.
736
EasyBuilder8000 User’s Manual
33.4 Save As
The captured information of Easy Diagnoser can be saved as *.xls which can be read in
Excel.
737
EasyBuilder8000 User’s Manual
Smart Docking
Smart Docking
Note:
EasyDiagnoser doesn’t support Siemens S7/1200 (Ethernet) and Allen-Bradley
Ethernet/IP (CompactLogix/ControlLogix) – Free Tag Names since both of the PLC use
tag.
738
EasyBuilder8000 User’s Manual
Therefore, AB Data Type Editor in EB8000 is for users to import and edit User-Defined,
Predefined and Module-Defined Structure.
739
EasyBuilder8000 User’s Manual
740
EasyBuilder8000 User’s Manual
Step 4. In object dialog, select PLC, click Tag and select a controller tag.
741
EasyBuilder8000 User’s Manual
Step 2. Input the [Name] of the data type. [Description] can be skipped.
For adding data member, click [Add].
742
EasyBuilder8000 User’s Manual
Step 3. Input in [Name] and [Data Type] then click [OK] to leave.
743
EasyBuilder8000 User’s Manual
Step 4. After adding all data members, click [OK]. The built data type will be listed on the
left side.
Note: After changing [Name] or [Description] of a data type, [OK] must be clicked to
activate revision.
744
EasyBuilder8000 User’s Manual
34.3 Paste
Step 1. When adding new data members, this function allows users to add multiple data at
one time. The way is to click [Paste] in the [AB Data Type Editor] window.
Step 2. The way to edit is to input data name in each line first, then use space or tab key to
leave a space in each line. And then input data type or click [Sample] to see some
reference. It is recommended to directly copy and paste from RSLogix5000 to avoid
errors.
745
EasyBuilder8000 User’s Manual
Step 3. The table above shows the defined data types in RSLogix. Select [Name] and
[Data Type] with mouse. This can be done by pressing and holding on the first option, then
slide down to the bottom until the scroll rolls to the end then stop holding. All the items will
then be selected. Press ctrl+v to copy then paste to the editing window.
Step 4. At this moment press [OK] to finish operating then return to the main window to
view the successfully added multiple data.
746
EasyBuilder8000 User’s Manual
747
EasyBuilder8000 User’s Manual
34.4 Miscellaneous
Revising member data:
Directly double click on the data member to be revised in the main window, or click on the
data member then press [Edit].
To Re-edit:
For giving up all revision done and to re-edit, click [Reload] button in main window.
748
EasyBuilder8000 User’s Manual
34.5 Module-Defined
Here is an example showing how to define a default structure for a module.
In I/O Configuration of RSLogix contains setting of I/O module.
The Tags of these modules won’t list the structure when exported to CSV file. Therefore,
users should build it first.
①
In [Controller Organizer/Data Types/Module-Defined] of RSLogix5000, double click Data
Type of the module. Data members of that type of the module will be listed in a window
pops up. Copy the [Name] and [Data Type] of the Members.
749
EasyBuilder8000 User’s Manual
②
In [AB Data Type Editor.exe] in EB8000, right click on [Module-Defined], and then click
[New Data Type…].
750
EasyBuilder8000 User’s Manual
③
Click [Paste], in dialogue box press Ctrl+V to paste Name and Data Type.
751
EasyBuilder8000 User’s Manual
Select data then click [Edit], since the data of the modules can be operated by bit, here
[Binary Access] should be selected, then click [OK] to return to [Data Type Editor].
752
EasyBuilder8000 User’s Manual
Step 2. Enter HMI IP: ftp://192.168.1.103, login user name: uploadhis, and the HMI history
upload password (if not changed, the default is 111111). Or, to directly enter
ftp://uploadhis:[email protected]/
Step 3. After entering IP, ftp://192.168.1.103/ is shown, and the “datalog”, “eventlog”, and
“recipe” folders can be seen.
753
EasyBuilder8000 User’s Manual
Select “datalog” folder, the file names set by EB8000 can be seen, click them to check the
“datalog” files.
754
EasyBuilder8000 User’s Manual
Note: After updating “recipe.rcp”, HMI must be restarted in one minute or use [LB-9048]
and [LB-9047] to restart HMI. Set [LB-9048] to ON and then set [LB-9047] to ON to
successfully restart HMI.
755