RBX1 Technical Data ENU
RBX1 Technical Data ENU
Technical Data
RBX1 Technical Data
2 OMICRON
Device overview
1 Device overview
RBX1 front view
Front view
CONNECTION
1 USB connectors Future use – currently deactivated
2 CTRL Network connector
Ethernet connector for control and management interface
LINK (X20)
3 LEDs Status LEDs for Ethernet connectors
Off: no link
On: link established but no activity
Flashing: link and activity
STATUS
4 Device status
READY LED is on when RBX1 is connected to power supply
ERROR
Information is available in the software; severity corresponding to
WARNING
the LED
INFO
5 Mounting holes (×4) For mounting the RBX1 to the rack panel
► For technical data refer to section RBX1 front connectors on page 12.
OMICRON 3
RBX1 Technical Data
Back view
1 FC – X30 Fault contact for RBX1 status indication
Fault contact Form C contact with Normally Closed (NC) and
Normally Open (NO) contact
• X30:1: contact is open when the device is powered on and
functional; otherwise closed
• X30:2: contact closed when the device is powered on and
functional; otherwise open
2 BINARY OUT – X31|X32 Binary output contacts to signal different states of the software
running on the RBX1
Binary outputs
Default setting for StationGuard:
• X31:1 contact is closed when there is at least one
unacknowledged alert (high priority)
• X31:2 contact is closed when there is at least one
unacknowledged warning (low priority)
3 BINARY IN – X33|X34 Binary input contacts to signal different states to the software
running on the RBX1
Binary inputs
4 Grounding screw For connection to protective earth
4 OMICRON
Device overview
Back view
5 POWER 1 – X41 Connection to power supply
POWER 2 – X42 Optional second power supply
6 X50 HDMI Future use
7 STATION – X20 Ethernet connectors for connection to substation
Network connectors Link state on RBX1 front (→ LEDs on page 3)
STATION – X20:1 ... 4 are combo ports, so either RJ45 or SFP
can be used. If both are connected, SFP is preferred (→ SFP
modules on page 6).
► For technical data refer to sections Power supply on page 10 and RBX1 back connectors on
page 13.
OMICRON 5
RBX1 Technical Data
2 Accessories
The STATION – X20 connectors on the back side of the RBX1 (→ page 5) support modules with the
following characteristics:
It is possible that modules compliant to the specifications above are incompatible with the
RBX1. This can be the case if additional configuration data in a module's EEPROM do not
match the RBX1 SFP ports. To guarantee for compatibility, we recommend using SFP
modules supplied by OMICRON (→ page 7).
6 OMICRON
Accessories
OMICRON 7
RBX1 Technical Data
2.2 Adapters
Mains adapter (C14)
A C14 mains adapter (cable length 180 mm) is included in the delivery of the RBX1-40 and RBX1-44
(→ 3.3 Power supply on page 10)
It is designed to supply the RBX1-40 and RBX1-44 in a laboratory environment.
WARNING
Death or severe injury caused by arc fault or electric shock possible
► Only connect the C14 mains adapter to AC supplies.
It is not designed for DC supplies.
► First connect the adapter to the RBX1 and tighten the screws, then connect to
mains AC.
WARNING
Death or severe injury caused by arc fault or electric shock possible
► First connect the adapter to the RBX1 and tighten the screws, then connect to the
measurement/test signal.
► Outputs FC – X30 and BINARY OUT – X31|X32, and inputs BINARY IN – X33|
X34 must be protected by a fuse with sufficient breaking capacity (→ Technical
data – Connectors on page 12). This can also be an electronic fuse inside a
laboratory supply.
8 OMICRON
RBX1 technical data
OMICRON 9
RBX1 Technical Data
10 OMICRON
RBX1 technical data
OMICRON 11
RBX1 Technical Data
3.5 Connectors
RBX1 front
CONNECTION
USB
Type 4 × USB 3.0 (SuperSpeed, 5 GBit/s)
Connector USB type A
CTRL
Type 10/100/1000Base-TX, according to IEEE 802.3
Connector RJ45
Cable type LAN cable of category 5 (CAT5) or better
Green LED: physical link present
Status indication
Yellow LED: network traffic on interface
12 OMICRON
RBX1 technical data
RBX1 back
FC – X30 1
Type Potential-free contacts; software-controlled
Connection PHOENIX CONTACT MSTB 2.5/3-GF-5.08 (socket)
PHOENIX CONTACT MSTB 2.5/3-STF-5.08 (plug)
Maximum conductor cross-section 2.5 mm²
Number of binary outputs 1 form C contact with Normally Closed (NC) and
Normally Open (NO) contact
Number of potential groups 1 (FC – X30)
-X30: 1 2 3
FC
AC loading capacity
Vmax = 250 V, Imax = 8 A, Pmax = 2000 VA
AC breaking capacity
DC loading capacity → Load limit breaking capacity curve for binary output relays with
DC breaking capacity DC voltages on page 15
Inrush current 15 A (max. 4 s at 10 % duty cycle)
Carry capacity 5 A continuous at 60 °C (140 °F)
Electrical lifetime 100,000 switching cycles at 230 VAC/8 A and ohmic load
Operate time2 Max. 10 ms (no bouncing)
Release time 2 Max. 5 ms (no bouncing)
Overvoltage category II, according to IEC 61010-1
III, according to IEC 60255-27
1
Outputs FC – X30 and BINARY OUT – X31|X32 must be protected by a fuse with sufficient breaking capacity: slow-breaking
fuse type, 8 A/250 V. Breaking capacity 50 kA (CAT III) can be decreased by the impedance value of the connection line.
2
Relay timing without software delays
OMICRON 13
RBX1 Technical Data
-X31: 1 2 3 4 5 -X32: 1 2 3 4 5
OUT – 1 2 3 4 OUT – 5 6 7 8
AC loading capacity
Vmax = 250 V, Imax = 8 A, Pmax = 2000 VA
AC breaking capacity
DC loading capacity → Load limit breaking capacity curve for binary output relays with
DC breaking capacity DC voltages on page 15
Inrush current 15 A (max. 4 s at 10 % duty cycle)
Carry capacity 5 A continuous at 60 °C (140 °F)
Electrical lifetime 100,000 switching cycles at 230 VAC/8 A and ohmic load
Operate time 2 Max. 10 ms (no bouncing)
Release time 2 Max. 5 ms (no bouncing)
Overvoltage category II, according to IEC 61010-1
III, according to IEC 60255-27
1
Outputs FC – X30 and BINARY OUT – X31|X32 must be protected by a fuse with sufficient breaking capacity: slow-breaking
fuse type, 8 A/250 V. Breaking capacity 50 kA (CAT III) can be decreased by the impedance value of the connection line.
2
Relay timing without software delays
14 OMICRON
RBX1 technical data
Load limit breaking capacity curve for binary output relays with DC voltages
OMICRON 15
RBX1 Technical Data
BINARY IN – X33|X34 1
Connection PHOENIX CONTACT MSTB 2.5/3-GF-5.08 (socket)
PHOENIX CONTACT MSTB 2.5/3-STF-5.08 (plug)
One terminal block for each potential group; maximum conductor
cross-section 2.5 mm²
Number of binary inputs 4
Number of potential groups 2 (X33 and X34)
-X33: 1 2 3 -X34: 1 2 3
+ + + +
IN – 1 2 IN – 3 4
– – – –
1
Inputs BINARY IN – X33|X34 must be protected by a fuse with sufficient breaking capacity: slow-breaking fuse type, 8 A/
250 V. Breaking capacity 50 kA (CAT III) can be decreased by the impedance value of the connection line.
16 OMICRON
RBX1 technical data
STATION – X20
STATION – X20:1 ... 4 1
Type 10/100/1000Base-TX, according to IEEE 802.3
Connector RJ45
Cable type LAN cable of category 5 (CAT5) or better
Green LED: physical link present
Status indication
Yellow LED: traffic on interface
STATION – X20:1 ... 8
Type 1000BASE-X, according to IEEE 802.3
Connector SFP
Status indication LINK (X20), RBX1 front
1
STATION – X20:1 ... 4 are combo ports, so either RJ45 or SFP can be used. If both are connected, SFP is preferred.
X50 HDMI
Type HDMI 1.4, up to 4096 × 2160 at 24 Hz
Connector HDMI type A
OMICRON 17
RBX1 Technical Data
Environmental conditions
Operating –20 °C ... +55 °C
–4 °F ... +131 °F
Temperature
Storage –25 °C ... +70 °C
–13 °F ... +158 °F
Operating 2,000 m
6,561 ft
Maximum altitude
Storage 15,000 m
49,212 ft
Humidity 5 % ... 95 % relative humidity; non-condensing
Mechanical tests 1
Vibration Non-operational 1 g; 5 Hz ... 500 Hz; 40 sweeps per direction
IEC 60068-2-6 During operation 0.5 g; 10 Hz ... 150 Hz; 2 sweeps per direction
10 g/16 ms; 1000 impacts per direction
Shock Non-operational
15 g/11 ms; 3 impacts per direction
IEC 60068-2-27
During operation 5 g/11 ms; 3 impacts per direction
Drop
Non-operational 5 cm, 2 drops per direction
IEC 60068-2-31
1
According to IEC 60255-21-1/2, Class 1
18 OMICRON
RBX1 technical data
OMICRON 19
RBX1 Technical Data
Damped oscillatory wave • Common mode: 2.5 kV, 100 kHz, 1 MHz, 10 MHz
20 OMICRON
RBX1 technical data
Safety
Safety standards
Europe EN 61010-2-030; EN 60255-26; EN 61010-1
International IEC 61010-2-030; IEC 60255-26; IEC 61010-1
USA UL; 61010-2-030; UL 61010-1
Canada CAN/CSA-C22.2 No 61010-2-030; CAN/CSA-C22.2 No 61010-1
Certificates
OMICRON 21