EE6508 - Power Quality - AG - Lecture - 4 - v2
EE6508 - Power Quality - AG - Lecture - 4 - v2
Voltage Disturbances
presented by
2
References
• Voltage variations
– MHJ Bollen, Understanding Power Quality Problems – Voltage sags and
interruptions, IEEE Press 2000.
– European Standard EN-50160, Voltage characteristics of electricity supplied by
public distribution systems, CENELEC, Brussels, Belgium, 1994
– IEEE Std 493-1997, IEEE recommended practice for the design of reliable
industrial and commercial power systems (Gold book), New York, 1997
– IEEE Std 1159-1995, IEEE recommended practice for monitoring power quality,
New York, 1995
– IEC 61000-4-30, Testing and measurement techniques - Power Quality
measurement methods, 2003
– IEC 61000-4-11 / 61000-4-34, Voltage dip immunity for equipment that requires
less than / more than 16 amps per phase.
– IEEE Std 1346-1998, IEEE Recommended Practice for Evaluating Electric
Power System Compatibility With Electronic Process Equipment, 1998.
– SEMI F47: Specification for semiconductor processing equipment voltage sag
immunity, Semiconductor Equipment and Materials International.
3
References
• Voltage fluctuations
– IEC 61000-4-15, Flickermeter—Functional and design specifications.
– IEEE 1453-2004, IEEE Recommended Practice for Measurement and Limits of
Voltage Fluctuations and Associated Light Flicker on AC Power Systems.
– IEC 61000-3-3, Limitation of voltage changes, voltage fluctuations and flicker in
public low-voltage supply systems, for equipment with rated current ≤ 16 A per
phase and not subject to conditional connection.
– IEC 61000-3-5, Limitation of voltage fluctuations and flicker in low-voltage power
supply systems for equipment with rated current greater than 16 A.
– IEC 61000-3-7, Assessment of emission limits for fluctuating loads in MV and
HV power systems
4
Voltage Variations
Deviation of RMS voltage magnitude characterized by
Change in the voltage magnitude
Voltage dip/sag: decrease in magnitude
Voltage swell: increase in magnitude
Voltage interruption: drop to very low (close to zero)
magnitude
Duration of the disturbance
Jump in voltage phase angle at beginning and end of disturbance
6
Sag Caused by Starting of Induction Motor
Bollen – ss. 4.9 pp. 248-251; Ch. 9 of IEEE Std 399-1997
During start-up of induction motor,
It takes a larger current than normal, typically 5-6 times larger
Current remains high until motors reaches its nominal speed,
typically between several seconds to one minute
Speed
Current
AC line voltage
RMS voltage
7
Useful Induction Motor Link
https://www.youtube.com/playlist?list=PLat6n
FKIgrM702J6fhBX546-d0VA_6awb
[*] http://electricalacademia.com/induction-motor/torque-speed-characteristics-induction-motor/ 8
Sag Caused by Starting of Induction Motor
𝑍𝑍𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
𝑉𝑉𝑠𝑠𝑠𝑠𝑠𝑠 = Zsys
𝑍𝑍𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 + 𝑍𝑍𝑠𝑠𝑠𝑠𝑠𝑠
PCC
Assuming source voltage of 1.0 p.u.,
At starting, Zmotor is locked-rotor Other loads M Zmotor
impedance
9
Sag Caused by Starting of Induction Motor
10
Sag Caused by Starting of Induction Motor
𝑍𝑍𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
𝑉𝑉𝑠𝑠𝑠𝑠𝑠𝑠 =
𝑍𝑍𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 + 𝑍𝑍𝑠𝑠𝑠𝑠𝑠𝑠
𝑉𝑉2
𝑛𝑛
𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
𝑉𝑉𝑠𝑠𝑠𝑠𝑠𝑠 = 𝑉𝑉2 𝑉𝑉2
𝑛𝑛 + 𝑛𝑛
𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠
1 Zsys
𝛽𝛽𝛽𝛽
𝑉𝑉𝑠𝑠𝑠𝑠𝑠𝑠 = 𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
+𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
PCC
𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠
𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠
𝑉𝑉𝑠𝑠𝑠𝑠𝑠𝑠 = Other loads M Zmotor
𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 +𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
The corresponding per-unit change in voltage or voltage sag,
𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
∆𝑉𝑉 = 1 − 𝑉𝑉𝑠𝑠𝑠𝑠𝑠𝑠 = 1 − =
𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 + 𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 + 𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
≈ 𝑓𝑓𝑓𝑓𝑓𝑓 𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 ≫ 𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 11
Other Characteristics of Motor-Startup
Duration of voltage sag depends on motor inertia
Motor torque is proportional to square of voltage
Reduced accelerating torque if voltage sag occurs
Prolong the motor run-up time
Lengthen the duration of voltage sag
Autotransformer starter
Transformer tap of 80, 65 or 50% at starting to reduce
starting current
13
Motor-Starting Methods
14
Motor-Starting Methods
Delta-Wye starter
Stator windings are connected in
wye at starting, reducing starting
voltage to 57% of original level,
and current (and torque) to 33%
of original level
15
Motor-Starting Methods
Without this starter, the motor will be turned on with winding
connected in delta
3𝑉𝑉𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙−𝑡𝑡𝑡𝑡−𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙
𝐼𝐼𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠−𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 = 𝐼𝐼𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙−𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 = 3𝐼𝐼𝑝𝑝ℎ𝑎𝑎𝑎𝑎𝑎𝑎−𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 =
𝑍𝑍𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
Part-Winding starter
Attractive for use with dual-rated
motors (220/440 V or 230/460 V)
(equivalent to two small motors with
each half of motor ratings)
Stator has two windings that can be
connected in parallel or series
Only one winding is connected at
starting to limit starting current
Second winding is only connected
after the motor has sped up and
therefore, the inrush current would
be small
17
Motor-Starting Methods
Part-Winding starter
𝑉𝑉𝑝𝑝ℎ𝑎𝑎𝑎𝑎𝑎𝑎
𝐼𝐼𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠−𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓 = ;
𝑍𝑍𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚
𝑉𝑉𝑝𝑝ℎ𝑎𝑎𝑎𝑎𝑎𝑎 𝐼𝐼𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠−𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓
𝐼𝐼𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠−ℎ𝑎𝑎𝑎𝑎𝑎𝑎 = =
2 × 𝑍𝑍𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 2
𝐼𝐼𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠−ℎ𝑎𝑎𝑎𝑎𝑎𝑎 1 𝛽𝛽𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠−𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓
∴ = ⇒ 𝛽𝛽𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠−ℎ𝑎𝑎𝑎𝑎𝑎𝑎 =
𝐼𝐼𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠−𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓 2 2
18
Motor-Starting Methods
To reduce the voltage sag at PCC, the motor can be fed
through a dedicated transformer, the voltage at PCC at motor
starting is
𝑍𝑍𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 + 𝑍𝑍𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡
𝑉𝑉𝑠𝑠𝑠𝑠𝑠𝑠 =
𝑍𝑍𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 + 𝑍𝑍𝑠𝑠𝑠𝑠𝑠𝑠 + 𝑍𝑍𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡
Zsys
Where,
𝑉𝑉𝑛𝑛2 𝑉𝑉𝑛𝑛2 PCC
𝑍𝑍𝑠𝑠𝑠𝑠𝑠𝑠 = , 𝑍𝑍𝑠𝑠𝑠𝑠𝑠𝑠 =
𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠
Ztrans
𝑉𝑉𝑛𝑛2 𝑉𝑉𝑛𝑛2
𝑍𝑍𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 = , and 𝑍𝑍𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡 = 𝜀𝜀
𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 𝑆𝑆𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡
Zmotor
Assuming transformer is of same power Other loads M
𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠
(1+𝛽𝛽𝛽𝛽)𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠
𝑉𝑉𝑠𝑠𝑠𝑠𝑠𝑠 = M Zmotor
(1+𝛽𝛽𝛽𝛽)𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 +𝛽𝛽𝛽𝛽𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 Other loads
20
Other Motor-Starting Methods
21
Exercise
Example – An 50-kW, 0.8 p.f., 90% efficiency induction motor is
started from a 11kV supply with 1 MVA short circuit capacity.
The motor starting current is six times the nominal or full-load
current. Calculate the amount of voltage sag at starting.
22
Exercise
Example – An 50-kW, 0.8 p.f., 90% efficiency induction motor is
started from a 11kV supply with 1 MVA short circuit capacity.
The motor starting current is six times the nominal or full-load
current. Calculate the amount of voltage sag at starting.
Smotor = 50 kW
= 69.44 kVA
0.8× 0.9
1000
V sag = = 0.706 = 70.6 % ⇒ ∆V = 1−Vsag = 29.4%
1000 + 6× 69.44
If the motor is fed through a dedicated 33/11kV transformer of
the same power rating as the motor and with a leakage
impedance of 10%. Assuming that the short circuit capacity at
PCC remains unchanged,
23
Exercise
Example – An 50-kW, 0.8 p.f., 90% efficiency induction motor is
started from a 11kV supply with 1 MVA short circuit capacity.
The motor starting current is six times the nominal or full-load
current. Calculate the amount of voltage sag at starting.
Smotor = 50 kW
= 69.44 kVA
0.8× 0.9
1000
V sag = = 0.706 = 70.6 % ⇒ ∆V = 1−Vsag = 29.4%
1000 + 6× 69.44
If the motor is fed through a dedicated 33/11kV transformer of
the same power rating as the motor and with a leakage
impedance of 10%. Assuming that the short circuit capacity at
PCC remains unchanged,
25
Exercise
∆V = 1−Vsag = 12.2%
26
Minimum SCC to Maintain Voltage
Employing specific motor-starting method alone may not be
sufficient to solve the problem as the voltage may still
remain low.
What is needed is a stronger supply, also termed higher
short circuit ratio (see page 31)
To limit the voltage drop at the motor terminal to Vmin, the
source strength needs to be (assuming the desirable
voltage is 1 pu, set Vsag = Vmin shown on page 9):
𝑉𝑉𝑚𝑚𝑚𝑚𝑚𝑚
𝑆𝑆𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 = 𝛽𝛽𝑆𝑆𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 ×
1 − 𝑉𝑉𝑚𝑚𝑚𝑚𝑚𝑚
27
Minimum SCC to Maintain Voltage
28
System Voltage Response
31
Short Circuit Capacity (SCC)
Describes voltage support strength of a power network
Product of three-phase fault current and rated voltage
𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆 = 3 × 𝑉𝑉 × 𝐼𝐼 MVA
I – three-phase short circuit fault current in kA
V – phase to phase system nominal voltage in kV
Or expressed in terms of system impedance or reactance
𝑉𝑉 𝑉𝑉 2
𝐼𝐼 = ⇒ 𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆 = MVA
3 × 𝑍𝑍𝑠𝑠𝑠𝑠𝑠𝑠 𝑍𝑍𝑠𝑠𝑠𝑠𝑠𝑠
In per unit system,
V is taken as 1.0 p.u.
I is the fault current at the fault location
1 1
𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆 = or p.u
𝑍𝑍𝑠𝑠𝑠𝑠𝑠𝑠 𝑋𝑋𝑠𝑠𝑠𝑠𝑠𝑠
Note: Last expression assumes negligible system resistance. 32
SCC and Concept of Electrical Distance
33
SCC and Concept of Electrical Distance
34
Switching of reactive compensation
35
Switching of reactive compensation
Reactor switching
Voltage swell occurs at de - energization of reactor
Voltage dip at energization of reactor
𝑄𝑄𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐
∆𝑉𝑉% ≅
𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆
Qcompensation is the amount of reactive power switched in/out
36
Exercise
A single-phase 200kW induction motor, rated with full load
efficiency of 90% and power factor of 0.85 lagging, has a
starting current, which is 6 times its full load value. The voltage
dip at the motor terminals during motor starting is 30%.
In order to enhance the security of supply to the motor, a
second incoming source with a source impedance 4 times the
source impedance of the original supply is connected.
37
Exercise
Solution (a)
Before Reinforcement
Induction motor capacity, P=200kW (1ph)
Rated full-load efficiency,𝜂𝜂 =90%
Rated power factor = 0.85
Since S = VphxIph
Therefore Iph = S/(Vph)
Since motor starting current is 6 times of its full load value, therefore
Iph(starting) = 6 x Iph = (6x200x1000)/(0.85 x 0.90 x Vph)
Where S=P/(eff x pf)
Since ∆V=Q/SCC
Assuming starting current is purely reactive
(i.e. Sstarting = 0+jQstarting)
∆V=Vph x Iph(starting)/SCC 38
Exercise
Given ∆V = 30%
SCC= Vph x 6 x 200 x 1000/(0.85 x 0.90 x Vph x 0.3) = 5228.758kVA
(1 Ph)
After Reinforcement
Xold = 1/ SCCold = 1/5228.75=0.1913µΩ
Xnew= [4 x (Xold)2]/(5x Xold)=4 x Xold/5
SCCnew=1/ Xnew=7 /(6 x Xold)= 5 /(4 x 0.1913 x 10-6)=6534.24kVA (1
Ph)
39
Exercise
b) When the motor is switched on,
∆V=Q/SCC=[Vph x 6 x 200 x 1000/(0.85 x 0.9 x Vph x 6534.24 x
1000)]x100
∆V=24% (DIP)
40
Voltage sags caused by system faults
System connection
VS VL • Fault occurs on the transmission or
Z3
distribution system such as a cable
fault
Z1 Z2
Fault ZL
Customer
Z2
Z1 Z2
VL = VS ×
ZL VL Z3 + Z 2
41
Voltage sags caused by customer faults
Z2
Z4 Z3 Z4 VL1
Z3 Customer 1
• Fault occurs within the premise
VL2 of another customer
Fault
• In general, Zeqv and Z3 << Z4
Z3
Z5 VL1 = VS ×
Z eqv + Z 3
Customer 2
42
Characteristics of fault-induced voltage sags
• Characteristics of voltage sags / interruptions depend very much on the
location of fault and sensitive point
– Fault positions 1 to 5 and sensitive points A to D
• Fault position 1
– Serious sag for both substations
– Deep sag transferred down to all
• Fault position 2
– Minor dip at A, severe dips at others
• Fault position 3
– Very deep sag at D, deep sag at C
– Recloser may cause multiple sags to
occur at C for permanent fault
• Fault position 4
– Deep sag for C, shallow sag for D
• Fault position 5
– Deep sag for D, shallow sag for C
– A and B minimally affected by fault at 4 or 5
43
Voltage sags caused by system faults
• Dugan ss. 3.2.3-3.2.4; Bollen ss. 4.2.2-4.2.5
• Interruptions, dips and swells
– Dip occurs at the faulted phase
– Swell may occur at healthy phases, depending on neutral grounding conditions
– Momentary interruptions when line/busbar/… is isolated to clear fault
• For a radial system, simple voltage divider rule can be used to determine the sag
magnitude at PCC (point of common coupling)
ZF z⋅L
Vsag = = Vsag
ZS + ZF ZS + z ⋅ L E ZF
Fault
ZS
– System voltage E is taken as 1 p.u.
– z is the impedance of feeder per unit length
– L is the distance between the fault and PCC Load
PCC
• Expressed Vsag in terms of fault levels,
Vn2 Vn2 S FLT
S FLT = ; S PCC = ⇒ Vsag = 1−
ZS + ZF ZS S PCC
– SFLT and SPCC are fault levels at the fault point and PCC respectively
– Vn is the nominal voltage level at fault point and PCC
• Extensive impacts if system is highly meshed or interconnected
– Short electrical distance between fault point and sensitive point (small ZF) 44
Local generators
• Local generator to distribution network mitigates voltage sags
– Increase fault level at distribution bus (works well for weak system)
– Keep up voltage at local bus by feeding into system faults
• Without local generator, voltage sag at load terminals is same as that at PCC
• With local generator in, the load terminal becomes local generator bus with the
following relationship,
)= 1−V pcc )
Z4
(1−V Z3 + Z 4 (
sag Local
generator
• Last expression assumes pre-sag voltages of
generators are identical at 1 p.u. Vsag and VPCC
Z1 Z3 Z4
are the voltages at the load and PCC buses
respectively.
PCC
– Lower generator voltage drop (1-Vsag)
Load bus
• Generator impedance Z4 is small and/or
• Link to PCC is weak (large Z3) Z2
Important
• When Z3 = Z4, Vsag = 70% when Vpcc=40% or sensitive
- Short-circuit fault at PCC, load bus voltage load
Fault
Vsag ,min = Z3
Z3 + Z 4
45
Local generator - example
• A system with impedance Z1 has a short circuit capacity of 1 MVA, and Z2 is a 200 kVA (10%
X) transformer. (Refer to the power system of previous page, without local generation).
– Compute the amount of voltage sag Using 200 kVA power base,
experienced by a sensitive load
1
connected to the PCC when a short Z1 = = 0.2 p.u.
circuit fault occurs at the load end of Z2 1 MVA 200 kVA
Z2 0.1
V pcc = 1× = = 0.33
Z1 + Z 2 0.2 + 0.1
• To reduce voltage sag impact, a local generator
is used to supply to the sensitive load. ∆Vload = ∆V pcc = 1− 0.33 = 67%
– Generator is rated at 50 kVA, 5% X and
interconnecting transformer between generator and PCC is rated at 50 kVA, 10% X.
– Compute the voltage sag at the sensitive load when the same fault occurs
200 200
Z 3 = 0.1× = 0.4 p.u. ; Z = 0.05× = 0.2 p.u.
4
50 50
Z eq, pcc = Z1 // (Z 3 + Z 4 ) = 0.15 p.u.
Z2 0.1
V pcc = 1× = = 0.4 p.u.
Z eq, pcc + Z 2 0.15 + 0.1
47
Power quality and other grid-connected
devices
• Dynamic Voltage Restorer (DVR)
48
Power quality and other grid-connected
devices
• Series Active Filter
49
Power quality and other grid-connected
devices
• Static Compensator (STATCOM)
50
Power quality and other grid-connected
devices
• Shunt Active Filter
51