Property - Mq.edu - Au - Inspection and Test Plans (ITP) - MUM-08 - Valves FORM - 2p
Property - Mq.edu - Au - Inspection and Test Plans (ITP) - MUM-08 - Valves FORM - 2p
Property - Mq.edu - Au - Inspection and Test Plans (ITP) - MUM-08 - Valves FORM - 2p
INSPECTION HISTORY
NO: DESCRIPTION: INSPECTION:
ACCEPTABLE: DATE: COMMENTS:
Quality Control
1 Control valve types and CV value approved for use Yes No Yes No
2 Control valves not being used are correctly stored Yes No Yes No
Installation
3 Drawings on site are the latest issue Yes No Yes No
Control valves are installed in correct location as per
4 Yes No Yes No
approved drawings and valve schedule
Control valves are installed in the correct direction of
5 Yes No Yes No
water flow
Control valves are undamaged and have all binder points
6 upstream and downstream to allow commissioning and Yes No Yes No
all wells required for pressure/temperature measuring
Control valves are clearly labelled including number, CV
7 Yes No Yes No
and size
Confirm installation does not leak when pipe work system
8 Yes No Yes No
is pressure tested
Control valves installed at a reachable height from the
9 Yes No Yes No
floor or platform
Confirm valves can be removed without disruption to
10 Yes No Yes No
adjacent pipe work
1
INSPECTION HISTORY
NO: DESCRIPTION: INSPECTION:
ACCEPTABLE: DATE: COMMENTS:
Mark alterations, sizes + final location on As Built
11
drawings for record purposes
ADDITIONAL COMMENTS: