Evac
Evac
Evac
EVACUATING
Quick Disconnect 1. CONNECT QUICK DISCONNECT ADAPTER TO
Adapter CHARGING HOSES
Charging
Hose 2. REMOVE CAPS FROM SERVICE VALVES ON RE-
FRIGERANT LINES
3. SET ON MANIFOLD GAUGE SET
Service Valve (a) Close both hand valves of manifold gauge set.
(b) Connect the quick disconnect adapters to the service
N13795
valves.
(b) Connect the center hose of the manifold gauge set to the
vacuum pump adapter.
Manifold (c) Open both the high and low hand valves and run the vacu-
Gauge
um pump.
Set
(d) After 10 minutes or more, check that the low pressure
gauge indicates 750 mmHg (30 in. Hg) or more.
HINT:
If the reading 750 mmHg (30 in. Hg) or more, close both hand
Low Pressure valves of manifold gauge set and stop the vacuum pump.
Service Valve
Check the system for leaks and repair necessary.
(e) Close both the high and low hand valves and stop the vac-
uum pump.
(f) Leave the system in this condition for 5 minutes or more
and check that there is no gauge indicator.
High Pressure
Service Valve