The document provides a test report for a transformer protection panel with differential relay. It summarizes the general checks, power system details, differential protection settings, pickup tests for various phases at high and low voltage sides, and stability checks at full load current. The pickup tests confirm the relay operates within expected parameters. Stability checks show the relay remains stable under normal load conditions and unstable inside the protection characteristics.

Uploaded by

sravankotlas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
271 views11 pages

P642 - Test Report

The document provides a test report for a transformer protection panel with differential relay. It summarizes the general checks, power system details, differential protection settings, pickup tests for various phases at high and low voltage sides, and stability checks at full load current. The pickup tests confirm the relay operates within expected parameters. Stability checks show the relay remains stable under normal load conditions and unstable inside the protection characteristics.

Uploaded by

sravankotlas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

HANUR SOLAR POWERPLANT

66/11KV SUBSTATION Page 1 of 8


DIFFERENTIAL RELAY TEST REPORT

TEST REPORT FOR 26 MVA TRANSFORMER PROTECTION PANEL–TRANSFORMER


DIFFERENTIAL RELAY

Customer : M/S ECOREN ENERGY Date : 24.07.2023

Model No : P642811D2M0060P Aux. Voltage : 110 VDC

Serial No : 34386320/03/18 Frequency : 50 Hz

Software Version :-- Settings Recommended by:-

Panel Ref: 66/11KV TRANSFORMER CUMM


FEEDER RELAY PANAL-(6KLA)

All setting values are reference to secondary.

GENERAL CHECK

Item Description Result


1 Physical inspection of the Relay  Yes  N/A PASS
2 AC/DC Voltage Checks  Yes  N/A PASS
3 Earthling Checks  Yes  N/A PASS
4 Inspect for physical damage / defects.  Yes  N/A PASS

CT DETAILS:

Winding PHASE NEUTRAL


CT RATIO_CT-1 (HV) (Amps) 400/1 400/1
CT RATIO_CT-2 (LV)(Amps) 1600/1 1600/1
VT RATIO 66kV/110

Page 1 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 2 of 8
DIFFERENTIAL RELAY TEST REPORT

Metering Check:

Injected Current (A) Measured Current (A)


@Secondary side value in terms of primary value
Winding
R Y B N R Y B N
HV-CT
From Measurement-1
1 1 1 - 401.8 401.1 402.3 --

LV-CT
From Measurement-1
1 1 1 - 1.606K 1.605K 1.608K --

POWER SYSTEM DETAILS:

Winding Type Conventional


HV CT Terminals 01
LV CT Terminals 10
Ref Power S 26.00MVA
HV Connection Y-Wye
HV Nominal 66.0kV
HV Rating 26.00MVA
LV Vector Group YNyn0
LV Connection y-wye
LV Nominal 11.00kV
LV Rating 26.00MVA
Phase Sequence Standard ABC
CT1 Reversal No Swap
CT2 Reversal No Swap

DIFFERENTIAL PROTECTION:
SETTINGS

Trans Diff Enabled Is-HS2 32.00PU


Set Mode -- Zero seq filt HV Enabled
Is1 0.2 Zero seq filt LV Disabled
K1 30.00% 2nd harm blocked Enabled
Is2 1.00PU Ih(2)%> 15.00%
K2 80.00% Cross blocking Enabled
tDIFF LS 0s CTSat and NoGap Enabled
Is-CTS 1.500PU 5th harm blocked Enabled
Is-HS1 10.000PU Ih(5)%> 35.00%
HS2 Status Enabled Circuitry Fail Disabled

Page 2 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 3 of 8
DIFFERENTIAL RELAY TEST REPORT

1 PHPICK UP TEST: HV-R Phase

Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0.169 0 0.200 0.09
Y Ph 0 0 0.09 0.10 0.07
B Ph 0 0 0.09 0.09

1 PHPICK UP TEST: HV-Y Phase

Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0 0.09 0.1
Y Ph 0.170 0 0.199 0.1 0.06
B Ph 0 0 0.09 0.1

1 PHPICK UP TEST: HV-B Phase

Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0 0.100 0.050
Y Ph 0 0 0.09 0.048 0.04
B Ph 0.171 0 0.199 0.099

1 PHPICK UP TEST: LV-R Phase

Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0.252 0.197 0.099
Y Ph 0 0 0.101 0.050 0.035
B Ph 0 0 0.098 0.049

1 PHPICK UP TEST: LV-Y Phase

Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0 0.098 0.050
Y Ph 0 0.255 0.197 0.099 0.032
B Ph 0 0 0.097 0.050

Page 3 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 4 of 8
DIFFERENTIAL RELAY TEST REPORT

1 PHPICK UP TEST: LV-B Phase

Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0 0.099 0.049
Y Ph 0 0 0.101 0.051 0.034
B Ph 0 0.252 0.194 0.099

3 PHPICK UP TEST: HV Phase

Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0.113 0 0.196 0.099
0.113 0.040
Y Ph 0 0.200 0.099
B Ph 0.113 0 0.196 0.098

3 PHPICK UP TEST: LV Phase

Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0.168 0.195 0.09
Y Ph 0 0.168 0.197 0.09 0.035
B Ph 0 0.168 0.199 0.09

SLOPE CHARACTERISTICS

Page 4 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 5 of 8
DIFFERENTIAL RELAY TEST REPORT

STABILITY:

CHECKING STABLE CONDITION AT FULL LOAD CURRENT:


Full Load Current At HV side: 227.4A Primary 0.568A Secondary
Full Load Current At LV side: 1364.2 A Primary 0.852A Secondary

STABILITY CHECKS:

Injected current ( A ) Expected values Measured Values Time


S.NO STATUS
HV SIDE LV SIDE Id.PU IR,PU Id.PU IR,PU (Sec)

0.568 ∟0° 0.852 ∟180° 0.00 1.00 0.003 1.002 Stable


in k2
1. 0.568 ∟-120° 0.852 ∟60° 0.00 1.00 0.003 1.003 No -Trip
slope
0.568 ∟120° 0.852 ∟300° 0.00 1.00 0.002 1.005 region
0.568 ∟0° 0.852 ∟0° 2.0 1.0 2.005 1.002 Unstable
in k2 Trip
2. 0.568 ∟-120° 0.852 ∟-120° 2.0 1.0 2.002 1.001
slope 0.028
0.568 ∟120° 0.852 ∟120° 2.0 1.0 2.009 1.004 region

VERIFYING SLOPE CHARECTERSTICS:


SLOPE k1 slope and k2 slope VERIFICATION:
S.N Injected current ( A ) Measured Values
SLOPE STATUS SLOPE
O HV SIDE LV SIDE Id.PU IR,PU
0.393 ∟0° 0.426∟150° 0.193 0.869 Un stable in k1
k1
1. 0.393∟-120° 0.426 ∟30° 0.193 0.870 slope región- 32.4%
slope
0.393∟+120° 0.426∟270° 0.193 0.595 Tripped
1.216 ∟0° 1.640∟150° 1.164 2.086
1.216∟-120° 1.640∟30° 1.164 2.086
1.216∟+120° 1.640∟270° 1.164 2.086 Un stable in k2
k2 80.1%
2. slope región-
slope 2.173∟0° 1.704∟150° 1.164 2.929 Tripped
2.173∟-120° 1.704∟30° 1.164 2.929
2.173∟+120° 1.704∟270° 1.164 2.929
Page 5 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 6 of 8
DIFFERENTIAL RELAY TEST REPORT

Note - Where testing carried out initially made stability current, after that HV current increase
and decrease until relay operates wrt LV side current is constant method.
HIGH SET STAGE-1 – 10.00P.U- - Operation Checked & Found ok
HIGH SET STAGE-2 – 32.00P.U- Operation Checked & Found ok

HARMONICS BLOCK:
Operated
STAGE OPERATE VALUE STATUS
Time(Sec)
2nd FAULT AT 50 Hz 0.040 TRIPPED
2nd If I2diff/Idiff<0.199 AT 100 Hz 0.032 TRIPPED
2nd If I2diff/Idiff>0.200 AT 100 Hz No trip BLOCKED
5th If I5diff/Idiff<0.350 AT 250 Hz 0.036 TRIPPED
5th If I5diff/Idiff>0.340AT 250 Hz No trip BLOCKED

Where 2nd Harmonics frequency (100Hz)&fundamental normal frequency (50Hz) are


suppressed at HV winding side for testing purpose.

METERING CHECK:

Injected Current (A) Measured Current (A)


WINDING @Secondary side value in terms of primary value
HV NCT-CT
From Measurement-1
1 400.2

REF:

HV STATUS: ENABLE
Set Mode :--
Is1 :0.06A
K1 :0%
Is2 :0.6A
K2 :150%

Page 6 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 7 of 8
DIFFERENTIAL RELAY TEST REPORT

PICK UP TEST: Phase-NCT

Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph-NCT 0 0.065 0.1 0.066
Y Ph-NCT 0 0.065 0.1 0.065 TRIP AT 0.034
B Ph-NCT 0 0.065 0.1 0.067

STABILITY CHECKS:

Injected current ( A ) Expected values Measured Values Time


REF STATUS
PH SIDE NCT SIDE Id IR Id IR (Sec)

R 0.568 ∟0° 0.568 ∟180° 0.00 227.4 0.003 227.2 Stable No -Trip

Y 0.568 ∟0° 0.568 ∟180° 0.00 227.4 0.003 227.9 Stable No -Trip

B 0.568 ∟0° 0.568 ∟180° 0.00 227.4 0.003 227.1 Stable No -Trip

UNSTABILITY CHECKS:

Injected current ( A ) Expected values Measured Values Time


REF STATUS
PH SIDE NCT SIDE Id.PU IR,PU Id.PU IR,PU (Sec)

R 0.568 ∟0° 0.568 ∟0° 454.8 227.4 455.1 227.4 UnStable Trip

Y 0.568 ∟0° 0.568 ∟0° 454.8 227.4 UnStable Trip


454.2 227.4

456.8 227.4
B 0.568 ∟0° 0.568 ∟0° 454.8 227.4 UnStable Trip

Page 7 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 8 of 8
DIFFERENTIAL RELAY TEST REPORT

VERIFYING SLOPE CHARECTERSTICS:

S.N Injected current ( A ) Measured Values


SLOPE STATUS SLOPE
O PH SIDE NCT SIDE Id.PU IR,PU

Un stable in k2
K2
R 1.340∟0° 0.60∟180° 296.7 389.2 slope región- 150%
slope
Tripped

Un stable in k2
K2
Y 1.340 ∟0° 0.60∟180° 296.4 389.8 slope región- 150%
slope
Tripped

Un stable in k2
K2
b 1.340∟0° 0.60∟180° 296.2 389.4 slope región- 150%
slope
Tripped

METERING CHECK:

Injected Current (A) Measured Current (A)


WINDING @Secondary side value in terms of primary value
LV NCT-CT
From Measurement-1
1 1600.3

LV STATUS: ENABLE
Set Mode : --
Is1 :0.09A
K1 :0%
Is2 :0.9A
K2 :150%

PICK UP TEST: LV Phase-NCT

Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph-NCT 0 0.093 0.1 0.091
Y Ph-NCT 0 0.093 0.1 0.092 TTrip At 0.031ms
B Ph-NCT 0 0.093 0.1 0.095

Page 8 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 9 of 8
DIFFERENTIAL RELAY TEST REPORT

STABILITY CHECKS:

Expected values
Injected current (A) Measured Values (A) Time
REF (A) STATUS
(Sec)
PH SIDE NCT SIDE Id IR Id IR

R 0.852 ∟0° 0.852 ∟180° 0.00 1.36 K 0.002 1.36 K Stable No -Trip

Y 0.852 ∟0° 0.852 ∟180° 0.00 1.36 K 0.002 1.36 K Stable No -Trip

B 0.852 ∟0° 0.852 ∟180° 0.00 1.36 K 0.002 1.36 K Stable No -Trip

UNSTABILITY CHECKS:

Injected current (A) Expected values Measured Values (A) Time


REF STATUS
PH SIDE NCT SIDE Id IR Id IR (Sec)

R 0.852 ∟0° 0.852 ∟180° 2.73 K 1.36 K 2.72 K 1.36 K UnStable Trip

Y 0.852 ∟0° 0.852 ∟180° 2.73 K 1.36 K 2.73 K 1.36 K UnStable Trip

B 0.852 ∟0° 0.852 ∟180° 2.73 K 1.36 K 2.73 K 1.36 K UnStable Trip

Page 9 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 10 of 8
DIFFERENTIAL RELAY TEST REPORT

VERIFYING SLOPE CHARECTERSTICS:

Measured Values
S.N Injected current (A)
SLOPE (A) STATUS SLOPE
O
PH SIDE NCT SIDE Id IR

Un stable in k2
K2
R 2.7 ∟0° 0.852 ∟180° 2.73K 2.97K slope región- 150%
slope
Tripped

Un stable in k2
K2
Y 2.7 ∟0° 0.852 ∟180° 2.73K 2.97K slope región- 150%
slope
Tripped

Un stable in k2
K2
b 2.7 ∟0° 0.852 ∟180° 2.73K 2.97K slope región- 150%
slope
Tripped

V/f Test (99):


V/Hz Alm Status Disabled V/Hz>3 Status Disabled
V/Hz Alarm Set 1.1PU V/Hz>3 Trip Set 1.300PU
V/Hz Alarm Delay 2.00s V/Hz>3 Delay 2.000s
V/Hz>1 Status Enabled V/Hz>4 Status Disabled
V/Hz>1 Trip Func DT V/Hz>4 Trip Set 1.400PU
V/Hz>1 Trip Set 2.66 PU V/Hz>4 Delay 1.000s
V/Hz>1 Trip TMS ---
V/Hz>1 Delay 5.000s
V/Hz>1 tReset 0s
V/Hz>2 Status Disabled
V/Hz>2 Trip Set 1.200PU
V/Hz>2 Delay 3.000s

ALARM TIME :

Stage Injected (v)- Operating Remarks


Time(Sec)
Stage-1 69.85 2.021 Ok

TRIPING TIME:

Stage Injected (v)- Operating Remarks


Time (Sec)
Stage-1 168.91 5.036 Ok

Page 10 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 11 of 8
DIFFERENTIAL RELAY TEST REPORT

MODEL NO P642811D2M0060P
SL NO 34386320/03/18
66/11KV TRANSFORMER CUMM FEEDER RELAY PANAL-
PANEL (6KLA)
RESULT PASS - RELAY FOUND HEALTHY ON ALL ASPECTS.
REMARKS

Tested By Witnessed By Witnessed By


For M/s. ISSPL For M/s. For M/s.

Name: KAMAL P Name: Name

Date: 24.07.2023

Page 11 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant