P642 - Test Report
P642 - Test Report
GENERAL CHECK
CT DETAILS:
Page 1 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 2 of 8
DIFFERENTIAL RELAY TEST REPORT
Metering Check:
LV-CT
From Measurement-1
1 1 1 - 1.606K 1.605K 1.608K --
DIFFERENTIAL PROTECTION:
SETTINGS
Page 2 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 3 of 8
DIFFERENTIAL RELAY TEST REPORT
Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0.169 0 0.200 0.09
Y Ph 0 0 0.09 0.10 0.07
B Ph 0 0 0.09 0.09
Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0 0.09 0.1
Y Ph 0.170 0 0.199 0.1 0.06
B Ph 0 0 0.09 0.1
Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0 0.100 0.050
Y Ph 0 0 0.09 0.048 0.04
B Ph 0.171 0 0.199 0.099
Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0.252 0.197 0.099
Y Ph 0 0 0.101 0.050 0.035
B Ph 0 0 0.098 0.049
Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0 0.098 0.050
Y Ph 0 0.255 0.197 0.099 0.032
B Ph 0 0 0.097 0.050
Page 3 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 4 of 8
DIFFERENTIAL RELAY TEST REPORT
Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0 0.099 0.049
Y Ph 0 0 0.101 0.051 0.034
B Ph 0 0.252 0.194 0.099
Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0.113 0 0.196 0.099
0.113 0.040
Y Ph 0 0.200 0.099
B Ph 0.113 0 0.196 0.098
Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph 0 0.168 0.195 0.09
Y Ph 0 0.168 0.197 0.09 0.035
B Ph 0 0.168 0.199 0.09
SLOPE CHARACTERISTICS
Page 4 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 5 of 8
DIFFERENTIAL RELAY TEST REPORT
STABILITY:
STABILITY CHECKS:
Note - Where testing carried out initially made stability current, after that HV current increase
and decrease until relay operates wrt LV side current is constant method.
HIGH SET STAGE-1 – 10.00P.U- - Operation Checked & Found ok
HIGH SET STAGE-2 – 32.00P.U- Operation Checked & Found ok
HARMONICS BLOCK:
Operated
STAGE OPERATE VALUE STATUS
Time(Sec)
2nd FAULT AT 50 Hz 0.040 TRIPPED
2nd If I2diff/Idiff<0.199 AT 100 Hz 0.032 TRIPPED
2nd If I2diff/Idiff>0.200 AT 100 Hz No trip BLOCKED
5th If I5diff/Idiff<0.350 AT 250 Hz 0.036 TRIPPED
5th If I5diff/Idiff>0.340AT 250 Hz No trip BLOCKED
METERING CHECK:
REF:
HV STATUS: ENABLE
Set Mode :--
Is1 :0.06A
K1 :0%
Is2 :0.6A
K2 :150%
Page 6 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 7 of 8
DIFFERENTIAL RELAY TEST REPORT
Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph-NCT 0 0.065 0.1 0.066
Y Ph-NCT 0 0.065 0.1 0.065 TRIP AT 0.034
B Ph-NCT 0 0.065 0.1 0.067
STABILITY CHECKS:
R 0.568 ∟0° 0.568 ∟180° 0.00 227.4 0.003 227.2 Stable No -Trip
Y 0.568 ∟0° 0.568 ∟180° 0.00 227.4 0.003 227.9 Stable No -Trip
B 0.568 ∟0° 0.568 ∟180° 0.00 227.4 0.003 227.1 Stable No -Trip
UNSTABILITY CHECKS:
R 0.568 ∟0° 0.568 ∟0° 454.8 227.4 455.1 227.4 UnStable Trip
456.8 227.4
B 0.568 ∟0° 0.568 ∟0° 454.8 227.4 UnStable Trip
Page 7 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 8 of 8
DIFFERENTIAL RELAY TEST REPORT
Un stable in k2
K2
R 1.340∟0° 0.60∟180° 296.7 389.2 slope región- 150%
slope
Tripped
Un stable in k2
K2
Y 1.340 ∟0° 0.60∟180° 296.4 389.8 slope región- 150%
slope
Tripped
Un stable in k2
K2
b 1.340∟0° 0.60∟180° 296.2 389.4 slope región- 150%
slope
Tripped
METERING CHECK:
LV STATUS: ENABLE
Set Mode : --
Is1 :0.09A
K1 :0%
Is2 :0.9A
K2 :150%
Phase Side-1 (A) Side -2 (A) Id (PU) Ir(PU) Trip Time (S)
R Ph-NCT 0 0.093 0.1 0.091
Y Ph-NCT 0 0.093 0.1 0.092 TTrip At 0.031ms
B Ph-NCT 0 0.093 0.1 0.095
Page 8 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 9 of 8
DIFFERENTIAL RELAY TEST REPORT
STABILITY CHECKS:
Expected values
Injected current (A) Measured Values (A) Time
REF (A) STATUS
(Sec)
PH SIDE NCT SIDE Id IR Id IR
R 0.852 ∟0° 0.852 ∟180° 0.00 1.36 K 0.002 1.36 K Stable No -Trip
Y 0.852 ∟0° 0.852 ∟180° 0.00 1.36 K 0.002 1.36 K Stable No -Trip
B 0.852 ∟0° 0.852 ∟180° 0.00 1.36 K 0.002 1.36 K Stable No -Trip
UNSTABILITY CHECKS:
R 0.852 ∟0° 0.852 ∟180° 2.73 K 1.36 K 2.72 K 1.36 K UnStable Trip
Y 0.852 ∟0° 0.852 ∟180° 2.73 K 1.36 K 2.73 K 1.36 K UnStable Trip
B 0.852 ∟0° 0.852 ∟180° 2.73 K 1.36 K 2.73 K 1.36 K UnStable Trip
Page 9 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 10 of 8
DIFFERENTIAL RELAY TEST REPORT
Measured Values
S.N Injected current (A)
SLOPE (A) STATUS SLOPE
O
PH SIDE NCT SIDE Id IR
Un stable in k2
K2
R 2.7 ∟0° 0.852 ∟180° 2.73K 2.97K slope región- 150%
slope
Tripped
Un stable in k2
K2
Y 2.7 ∟0° 0.852 ∟180° 2.73K 2.97K slope región- 150%
slope
Tripped
Un stable in k2
K2
b 2.7 ∟0° 0.852 ∟180° 2.73K 2.97K slope región- 150%
slope
Tripped
ALARM TIME :
TRIPING TIME:
Page 10 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 11 of 8
DIFFERENTIAL RELAY TEST REPORT
MODEL NO P642811D2M0060P
SL NO 34386320/03/18
66/11KV TRANSFORMER CUMM FEEDER RELAY PANAL-
PANEL (6KLA)
RESULT PASS - RELAY FOUND HEALTHY ON ALL ASPECTS.
REMARKS
Date: 24.07.2023
Page 11 of 11
Transformer Protection Relay – P642
Site: Hanur solar power plant