Catalogs C2000D5
Catalogs C2000D5
Standby Prime
kVA (kW) kVA (kW)
Ratings 2063 (1650) 1875 (1500)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 32.3 54.9 79.2 107.1 29.5 50.2 71.3 95.7
L/hr 122 208 300 406 112 190 270 363
Standby Prime
rating rating
Engine manufacturer Cummins
Engine model QSK60-G3
Configuration Cast iron, 60 º V16 cylinder
Aspiration Turbocharged and low temperature aftercooled
Gross engine power output, kWm 1790 1615
BMEP at set rated load, kPa 2379 2144
Bore, mm 159
Stroke, mm 190
Rated speed, rpm 1500
Piston speed, m/s 9.5
Compression ratio 14.5:1
Lube oil capacity, L 378
Overspeed limit, rpm 1725 ±50
Regenerative power, kW 146
Governor type Electronic
Starting voltage 24V Volts DC
power.cummins,com
©2016 Cummins Power Generation Inc. | DS48e-CPGK (3/16)
Standby Prime
rating rating
Combustion air, m3/min 135 129
Maximum air cleaner restriction, kPa 6.2
Ambient design, °C 40
Fan load, kWm 33
Coolant capacity (with radiator), L 456
Cooling system air flow, m3/sec @ 12.7 mmH2O 26.4
Total heat rejection, Btu/min 48925 44125
Maximum cooling air flow static restriction mm H2O 12.7
Open Enclosed
Unit dry weight kgs 14880
Unit wet weight kgs 15945
* Weights represent a set with standard features. See outline drawing for weights of other configurations.
Open set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
power.cummins.com
©2016 Cummins Power Generation Inc. | DS48e-CPGK (3/16)
Connection1 Temp rise ºC Duty2 Alternator Voltage
Wye, 3-phase 105/80C S/P MVSI804R1 3300V
Wye, 3-phase 125/105C S/P HVSI804R1 6600V
Wye, 3-phase 125/105C S/P HVSI804R1 11000V
Wye, 3-phase 150/125C S/P P7F 380-440V
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited Time Prime Power (PRP) is in unlimited hours.
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Continuous Power (COP) is
Emergency Standby Power accordance with ISO 8528. Ten percent overload in accordance with ISO
(ESP) is in accordance with capability is available in 8528, ISO 3046, AS 2789,
ISO 8528. Fuel Stop power in accordance with ISO 3046, DIN 6271 and BS 5514.
accordance with ISO 3046, AS AS 2789, DIN 6271 and BS
2789, DIN 6271 and BS 5514. 5514.
Diesel
generator set
QSK60 series
engine
1760kVA - 2500kVA 50 Hz
1825kW - 2250kW 60 Hz
Description
Control system – The PowerCommand®
This Cummins® Power Generation commercial
generator set is a fully integrated power electronic control is standard equipment and
generation system, providing optimum provides total genset system integration
performance, reliability, and versatility for including automatic remote starting/stopping,
stationary standby, prime power, and precise frequency and voltage regulation, alarm
continuous duty applications. and status message display, AmpSentry™
protection, output metering, auto-shutdown at
Features fault detection and NFPA 110 Level 1
compliance.
Cummins® heavy-duty engine - Rugged 4-
cycle industrial diesel delivers reliable power, Cooling system - Standard integral set-
low emissions and fast response to load mounted radiator system, designed and tested
changes. for rated ambient temperatures, simplifies facility
Permanent magnet generator (PMG) - Offers design requirements for rejected heat.
enhanced motor starting and fault clearing NFPA - The genset accepts full rated load in a
short circuit capability. single step in accordance with NFPA 110 for
Alternator - Several alternator sizes offer Level 1 systems.
selectable motor starting capability with low Warranty and service - Backed by a
reactance 2/3 pitch windings; low waveform comprehensive warranty and worldwide
distortion with non-linear loads, fault clearing distributor network.
short-circuits capability, and class F or H
insulation.
Emissions
Standby rating Prime rating compliance Data sheets
50 Hz 60 Hz 50 Hz 60 Hz TA Luft – EU
Model kVA (kW) kW (kVA) kVA (kW) kW (kVA) Stage 50 Hz 60 Hz
C1760 D5e 1760 (1408) 1600 (1280) 2g TA Luft DS49-CPGK
power.cummins.com
©2016 Cummins Power Generation Inc. | SS17e-CPGK (3/16)
Generator set specifications
Transient Performance ISO 8528-5 compliant
Voltage regulation, no load to full load ± 0.5%
Random voltage variation ± 0.5%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
EMC compatibility BS EN 61000-6-4 / BS EN 61000-6-2
Engine specifications
Design 4 cycle, V-black, turbo charged and low temperature after-cooled
Bore 158.8 mm (6.25 in)
Stroke 190.0 mm (7.48 in)
Displacement 60.2 L (3673 in3)
Cylinder block Cast iron, 60ºV 16 cylinder
Battery capacity 2200 amps at ambient temperature 0ºF to 32ºF (-18 °C to 0°C)
Battery charging alternator 40 amps
Starting voltage 24- volt, negative ground
Fuel system Direct injection
Fuel filter Triple element, spin on fuel filters with water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Four spin-on, combination full flow and bypass filters
Standard cooling system 104ºF (40ºC) ambient radiator
Alternator specifications
Design Brushless, 4 pole, drip proof revolving field
Stator 2/3 pitch
Rotor Direct coupled by flexible disc
Insulation system Class H
Standard temperature rise 150 °C standby
Exciter type PMG (Permanent magnet generator)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion No load <1.5%. Non distorting balanced linear load <5%
Telephone influence factor (TIF) < 50% per NEMA MG1-22.43
Telephone harmonic factor (THF) < 3%
Available voltages
50 Hz line – neutral / line - line 60 Hz line – neutral / line - line
220/380 1905/3300 219/380 2400/4160
230/400 3640/6300 254/440 7200/12470
240/415 3810/6600 277/480 7620/13200
254/440 6350/11000 347/600 7970/13800
Note: Consult factory for other voltages.
*Note: Some options may not be available on all models - consult factory for availability.
power.cummins.com
©2016 Cummins Power Generation Inc. | SS17e-CPGK (3/16)
PowerCommand® 3.3 control system
Engine data
DC voltage
Engine speed
Lube oil pressure and temperature
Coolant temperature
Comprehensive FAE data (where applicable)
Other data
Genset model data
Start attempts, starts, running hours, kW hours
Control system Load profile (operating hours at % load in 5%
increments)
The PowerCommand® control system is an Fault history
integrated microprocessor based generator set Data logging and fault simulation (requires
control system providing voltage regulation, engine InPower)
protection, alternator protection, operator interface
and isochronous governing.
AmpSentry – Includes integral AmpSentry protection,
Standard control functions
which provides a full range of alternator protection
Digital governing (optional)
functions that are matched to the alternator
provided. Integrated digital electronic isochronous governor
Power management – Control function provides Temperature dynamic governing
battery monitoring and testing features and smart Digital voltage regulation
starting control system. Integrated digital electronic voltage regulator
Advanced control methodology – Three phase 3-phase, 4-wire line-to-line sensing
sensing, full wave rectified voltage regulation, with a Configurable torque matching
PWM output for stable operation with all load types.
Communications interface – Control comes standard AmpSentry AC protection
with PCCNet and Modbus interface. AmpSentry protective relay
Regulation compliant – Prototype tested: UL, CSA Over current and short circuit shutdown
and CE compliant. Over current warning
Service - InPower™ PC-based service tool available Single and three phase fault regulation
for detailed diagnostics, setup, data logging and fault Over and under voltage shutdown
simulation. Over and under frequency shutdown
Reliable design – The control system is designed for Overload warning with alarm contact
reliable operation in harsh environment. Reverse power and reverse var shutdown
Multi-language support Field overload
Engine protection
Operator panel features Battery voltage monitoring, protection and testing
Over speed shutdown
Operator panel features – The operator panel, in Low oil pressure warning and shutdown
addition to the alternator, displays the Utility/AC Bus High coolant temperature warning and shutdown
data. Low coolant level warning or shutdown
Operator/display functions Low coolant temperature warning
Fail to start (over crank) shutdown
320 x 240 pixels graphic LED backlight LCD Fail to crank shutdown
Auto, manual, start, stop, fault reset and lamp Cranking lockout
test/panel lamp switches Sensor failure indication
Alpha-numeric display with pushbuttons Low fuel level warning or shutdown
LED lamps indicating genset running, remote start, Fuel-in-rupture-basin warning or shutdown
not in auto, common shutdown, common warning, Full authority electronic engine protection
manual run mode, auto mode and stop
Control functions
Paralleling control functions
Time delay start and cool down
Digital frequency synchronization and voltage Real time clock for fault and event time stamping
matching Exerciser clock and time of day start/stop
Isochronous kW and kvar load sharing controls Data logging
Droop kW and kvar control Cycle cranking
Sync check Load shed
Extended paralleling (Peak Shave/Base Load) Configurable inputs and outputs (4)
Digital power transfer control (AMF) provides load Remote emergency stop
transfer operation in open or closed transition or
soft (ramping) transfer mode Options
Alternator data Auxiliary output relays (2)
Line-to-neutral and line-to-line AC volts
3-phase AC current
Frequency
kW, kvar, power factor kVA (three phase and total)
power.cummins.com
©2016 Cummins Power Generation Inc. | SS17e-CPGK (3/16)
Emergency standby power (ESP):
Applicable for supplying power to varying electrical load
for the duration of power interruption of a reliable utility
source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and BS
5514.
Limited-time running power (LTP):
This outline drawing is to provide representative configuration
Applicable for supplying power to a constant electrical details for Model series only.
load for limited hours. Limited Time Running Power
(LTP) is in accordance with ISO 8528. See respective model data sheet for specific model outline
drawing number.
Prime power (PRP):
Applicable for supplying power to varying electrical load Do not use for installation design
for unlimited hours. Prime Power (PRP) is in
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046, AS
2789, DIN 6271 and BS 5514.
Base load (continuous) power (COP):
Applicable for supplying power continuously to a
constant electrical load for unlimited hours. Continuous
Power (COP) in accordance with ISO 8528, ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Dim “A” Dim “B” Dim “C” Set Weight* Set Weight*
Model mm mm mm dry kg wet kg
C1760 D5e 6175 2494 3422 14825 16040
This generator set is available with CE This generator set has been designed to
ISO 8528
certification. comply with ISO 8528 regulation.
Manston Park Columbus Ave. 1400 73rd Avenue N.E. 10 Toh Guan Road #07-01
Kent CT12 5BF United Kingdom Phone 763 574 5000 Singapore 608838
Phone 44 1843 255000 Fax 763 574 5298 Phone 65 6417 2388
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 1 of 12
PowerCommand digital
• Exerciser clock and time of day start/stop initiate a test
with or without load, or a Base Load or Peak Shave
genset control
session.
• Digital Power Transfer Control (AMF) provides load
PCC 3300 transfer operation in open transition, closed transition, or
soft (ramping) transfer modes.
• Extended Paralleling (Peak Shave/Base Load) regulates
the genset real and reactive power output while
paralleled to the utility. Power can be regulated at either
the genset or utility bus monitoring point.
• Digital frequency synchronization and voltage matching.
• Isochronous Load Share
• Droop KW and KVAR Control
• Sync Check – The sync check function has adjustments
for phase angle window, voltage window, frequency
Description window and time delay.
The PowerCommand genset control is suitable for use on • Utility/AC Bus metering and protection
a wide range of diesel and lean burn natural gas gensets in
• Advanced serviceability – using InPower™, a PC-based
paralleling applications. The PowerCommand control is
software service tool.
compatible with shunt or PMG excitation style. It is
suitable for use with reconnectable or non-reconnectable • Environmental protection – The control system is
generators, and it can be configured for any frequency, designed for reliable operation in harsh environments.
voltage and power connection from 120-600 VAC line-to- The main control board is a fully encapsulated module
line, 601-45,000 VAC with external PT. that is protected from the elements.
• ModBus interface for interconnecting to customer
Power for this control system is derived from the genset
starting batteries. The control functions over a voltage equipment.
range from 8 VDC to 30 VDC. • Configurable inputs and outputs – Four discrete inputs
and four dry contact relay outputs.
Features • Warranty and service – Backed by a comprehensive
warranty and worldwide distributor service network.
• 12 and 24 VDC battery operation.
• Certifications – Suitable for use on gensets that are
• Digital voltage regulation - Three phase full wave FET designed, manufactured, tested and certified to relevant
type regulator compatible with either shunt or PMG UL, NFPA, ISO, IEC, Mil Std. and CE standards.
systems. Sensing is three phase.
• Digital engine speed governing (where applicable) – Base control functions
Provides isochronous frequency regulation.
HMI capability
• Full authority engine communications (where applicable)
Options – Local and remote HMI options
- Provides communication and control with the Engine
Control Module (ECM). Operator adjustments – The HMI includes provisions for
• AmpSentry™ protection - for true alternator overcurrent many set up and adjustment functions.
protection. Genset hardware data – Access to the control and
• Genset monitoring - Monitors status of all critical engine software part number, genset rating in KVA and genset
and alternator functions. model number is provided from the HMI or InPower.
• Digital genset metering (AC and DC). Data logs – Includes engine run time, controller on time,
number of start attempts, total kilowatt hours, and load
• Genset battery monitoring system to sense and warn
profile. (Control logs data indicating the operating hours at
against a weak battery condition.
percent of rated kW load, in 5% increments. The data is
• Configurable for single or three phase AC metering. presented on the operation panel based on total operating
• Engine starting - Includes relay drivers for starter, fuel hours on the generator.)
shut off (FSO), glow plug/spark ignition power and Fault history – Provides a record of the most recent fault
switch B+ applications. conditions with control date and time stamp. Up to 32
• Genset protection – Protects engine and alternator. events are stored in the control non-volatile memory.
• Real time clock for fault and event time stamping. Alternator data
PCC
3300
Emergency stop
Power Transfer Control: control operates a single Annunciated whenever either emergency stop signal is
genset/single utility transfer pair in open transition, fast received from external switch.
closed transition, or soft closed transition. Extended
paralleling functionality also provides base load and peak General engine protection
shave options. Low and high battery voltage warning - Indicates status of
battery charging system (failure) by continuously
monitoring battery voltage.
PCC
3300
Weak battery warning - The control system will test the
G battery each time the genset is signaled to start and
indicate a warning if the battery indicates impending
failure.
Fail to start (overcrank) shutdown - The control system will
indicate a fault if the genset fails to start by the completion
of the engine crack sequence.
Fail to crank shutdown - Control has signaled starter to
crank engine but engine does not rotate.
Cranking lockout - The control will not allow the starter to
Protective functions attempt to engage or to crank the engine when the engine
On operation of a protective function the control will is rotating.
indicate a fault by illuminating the appropriate status LED Fault simulation –The control in conjunction with InPower
on the HMI, as well as display the fault code and fault software, will accept commands to allow a technician to
description on the LCD. The nature of the fault and time of verify the proper operation of the control and its interface
occurrence are logged in the control. The service manual by simulating failure modes or by forcing the control to
and InPower service tool provide service keys and operate outside of its normal operating ranges. InPower
procedures based on the service codes provided. also provides a complete list of faults and settings for the
Protective functions include: protective functions provided by the controller.
Battle short mode For Lean Burn Natural Gas Engine applications:
When enabled and the battle short switch is active, the Off load running (protection) – This feature protects the
control will allow some shutdown faults to be bypassed. If engine in the event the genset is being called to go off load
a bypassed shutdown fault occurs, the fault code and for too long.
description will still be annunciated, but the genset will not
shutdown. This will be followed by a fail to shutdown fault. Hydro mechanical fuel system engine
Emergency stop shutdowns and others that are critical for
protection
proper operation (or are handled by the engine ECM) are
not bypassed. Please refer to the Control Application Overspeed shutdown – Default setting is 115% of nominal
Guide or Manual for list of these faults. Low lube oil pressure warning/shutdown – Level is preset
(configurable with InPower or HMI) to match the
Derate capabilities of the engine used. Control includes time
The Derate function reduces output power of the genset in delays to prevent nuisance alarms.
response to a fault condition. If a Derate command occurs High lube oil temperature warning/shutdown – Level is
while operating on an isolated bus, the control will issue preset (configurable with InPower or HMI) to match the
commands to reduce the load on the genset via contact capabilities of the engine used. Control includes time
closures or Modbus. If a Derate command occurs while in delays to prevent nuisance alarms.
utility parallel mode, the control will actively reduce power
by lowering the base load kW to the derated target kW.
Our energy working for you.™
www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 7 of 12
High engine temperature warning/shutdown – Level is High AC voltage shutdown (59) - Output voltage on any
preset (configurable with InPower or HMI) to match the phase exceeds preset values. Time to trip is inversely
capabilities of the engine used. Control includes time proportional to amount above threshold. Values adjustable
delays to prevent nuisance alarms. from 105-125% of nominal voltage, with time delay
adjustable from 0.1-10 seconds. Default value is 110% for
Low coolant temperature warning – Indicates that engine
10 seconds.
temperature may not be high enough for a 10 second start
or proper load acceptance. Low AC voltage shutdown (27) - Voltage on any phase has
Low coolant temperature warning – Can be set up to be a dropped below a preset value. Adjustable over a range of
warning or shutdown. 50-95% of reference voltage, time delay 2-20 seconds.
Default value is 85% for 10 seconds. Function tracks
High intake manifold temperature shutdown – Level is reference voltage. Control does not nuisance trip when
preset (configurable with InPower or HMI) to match the voltage varies due to the control directing voltage to drop,
capabilities of the engine used. Control includes time such as during a V/Hz roll-off or synchronizing.
delays to prevent nuisance alarms.
Under frequency shutdown (81 u) - Genset output
Full authority electronic engine protection frequency cannot be maintained. Settings are adjustable
from 2-10 Hz below reference governor set point, for a 5-
Engine fault detection is handled inside the engine ECM. 20 second time delay. Default: 6 Hz, 10 seconds. Under
Fault information is communicated via the SAE-J1939 data frequency protection is disabled when excitation is
link for annunciation in the HMI. switched off, such as when engine is operating in idle
speed mode.
Alternator protection
Over frequency shutdown/warning (81o) - Genset is
AmpSentry protective relay - A comprehensive
operating at a potentially damaging frequency level.
monitoring and control system integral to the
Settings are adjustable from 2-10 Hz above nominal
PowerCommand Control System that guards the
governor set point for a 1-20 second time delay. Default: 6
electrical integrity of the alternator and power system by Hz, 20 seconds, disabled.
providing protection against a wide array of fault
conditions in the genset or in the load. It also provides Overcurrent warning/shutdown (51) - Implementation of
single and three phase fault current regulation so that the thermal damage curve with instantaneous trip level
downstream protective devices have the maximum calculated based on current transformer ratio and
current available to quickly clear fault conditions without application power rating.
subjecting the alternator to potentially catastrophic Loss of sensing voltage shutdown - Shutdown of genset
failure conditions. See document R1053 for a full size will occur on loss of voltage sensing inputs to the control.
time over current curve. The control does not included
protection required for interconnection to a utility (mains) Field overload shutdown - Monitors field voltage to
service. shutdown genset when a field overload condition occurs.
Over load (kW) warning - Provides a warning indication
when engine is operating at a load level over a set point.
Adjustment range: 80-140% of application rated kW, 0-
120 second delay. Defaults: 105%, 60 seconds.
Reverse power shutdown (32) - Adjustment range: 5-20%
of standby kW rating, delay 1-15 seconds. Default: 10%, 3
seconds.
Reverse Var shutdown - Shutdown level is adjustable: 15-
50% of rated Var output, delay 10-60 seconds. Default:
20%, 10 seconds.
Short circuit protection - Output current on any phase is
more than 175% of rating and approaching the thermal
damage point of the alternator. Control includes
algorithms to protect alternator from repeated over current
conditions over a short period of time.
Negative sequence overcurrent warning (46) – Control
protects the generator from damage due to excessive
imbalances in the three phase load currents and/or power
factors.
machine interface
configured to activate on any control warning or
shutdown fault as well as ready to load, not in auto,
HMI320
common alarm, common warning and common
shutdown.
- Ready to load (genset running) signal: Operates when
the genset has reached 90% of rated speed and voltage
and latches until genset is switched to off or idle mode.
- Paralleling circuit breaker relays outputs: Control
includes (4) relay output contacts (3.5A, 30 VDC) for
opening and closing of the genset and utility breakers.
For Lean Burn Natural Gas Engine applications:
- Start inhibit/enable event
- Emergency stop event
- Ventilator fan run control
- Louvre control Description
- Radiator fan control
- Alternator heater control This control system includes an intuitive operator interface
- Engine at idle speed event panel that allows for complete genset control as well as
system metering, fault annunciation, configuration and
Communications connections include: diagnostics. The interface includes five genset status LED
- PC tool interface: This RS-485 communication port lamps with both internationally accepted symbols and
allows the control to communicate with a personal English text to comply with customers needs. The
computer running InPower software. interface also includes an LED backlit LCD display with
tactile feel soft-switches for easy operation and screen
- Modbus RS-485 port: Allows the control to navigation. It is configurable for units of measurement and
communicate with external devices such as PLCs using has adjustable screen contrast and brightness.
Modbus protocol.
The run/off/auto switch function is integrated into the
Note - An RS-232 or USB to RS-485 converter is interface panel.
required for communication between PC and control.
All data on the control can be viewed by scrolling through
- Networking: This RS-485 communication port allows screens with the navigation keys. The control displays the
connection from the control to the other Cummins current active fault and a time-ordered history of the five
Power Generation products. previous faults.
2
PI734F
WINDING 312
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
PROTECTION IP23
WINDING LEADS 6
MAIN STATOR RESISTANCE 0.00076 Ohms PER PHASE AT 22°C STAR CONNECTED
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
1 BEARING 2 BEARING
50 Hz 60 Hz
COOLING AIR 2.69 m³/sec 5700 cfm 3.45 m³/sec 7300 cfm
VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
kVA BASE RATING FOR REACTANCE
2020 2080 2080 2040 2345 2500 2550 2600
VALUES
Xd DIR. AXIS SYNCHRONOUS 2.93 2.73 2.53 2.21 3.55 3.38 3.16 2.96
X'd DIR. AXIS TRANSIENT 0.18 0.17 0.15 0.13 0.21 0.20 0.19 0.18
X''d DIR. AXIS SUBTRANSIENT 0.13 0.12 0.11 0.10 0.16 0.15 0.14 0.13
Xq QUAD. AXIS REACTANCE 1.89 1.75 1.63 1.42 2.28 2.18 2.03 1.90
X''q QUAD. AXIS SUBTRANSIENT 0.26 0.25 0.23 0.20 0.32 0.31 0.29 0.27
XL LEAKAGE REACTANCE 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.03
X2 NEGATIVE SEQUENCE 0.19 0.17 0.16 0.14 0.23 0.22 0.20 0.19
X0 ZERO SEQUENCE 0.02 0.02 0.02 0.02 0.03 0.03 0.02 0.02
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.154s
T''d SUB-TRANSTIME CONST. 0.02s
T'do O.C. FIELD TIME CONST. 2.54s
Ta ARMATURE TIME CONST. 0.02s
SHORT CIRCUIT RATIO 1/Xd
3
PI734F
50 Winding 312
Hz THREE PHASE EFFICIENCY CURVES
APPROVED DOCUMENT
4
PI734F
60 Winding 312
Hz THREE PHASE EFFICIENCY CURVES
APPROVED DOCUMENT
5
PI734F
Winding 312
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15 APPROVED DOCUMENT
10
0
0 1000 2000 3000 4000 5000 6000
LOCKED ROTOR kVA
60
30
Hz 380V 416V 440V 460V 480V
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
0
0 1000 2000 3000 4000 5000 6000 7000
LOCKED ROTOR kVA
6
PI734F
Winding 312
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.
50
Hz
100000
SYMMETRICAL
ASYMMETRICAL
CU RR E NT (Am p s)
10000
APPROVED DOCUMENT
1000
0.001 0.01 0.1 1 10
TIME (secs)
Sustained Short Circuit = 6,850 Amps
60 100000
Hz
SYMMETRICAL
ASYMMETRICAL
CU RR E NT (Am p s)
10000
1000
0.001 0.01 0.1 1 10
TIME (secs)
7
PI734F
Winding 312 / 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
kVA 1880 1935 1935 1900 2020 2080 2080 2040 2105 2170 2170 2125 2165 2250 2250 2185
kW 1504 1548 1548 1520 1616 1664 1664 1632 1684 1736 1736 1700 1732 1800 1800 1748
Efficiency (%) 96.1 96.2 96.3 96.4 96.0 96.0 96.1 96.3 95.9 95.9 96.0 96.2 95.8 95.8 96.0 96.2
kW Input 1565 1609 1607 1577 1683 1733 1732 1695 1756 1810 1808 1767 1808 1878 1876 1817
60Hz Star (V) 416 440 460 480 416 440 460
APPROVED DOCUMENT 480 416 440 460 480 416 440 460 480
kVA 2190 2325 2370 2420 2345 2500 2550 2600 2435 2600 2650 2705 2505 2675 2730 2785
kW 1752 1860 1896 1936 1876 2000 2040 2080 1948 2080 2120 2164 2004 2140 2184 2228
Efficiency (%) 96.0 96.1 96.1 96.2 95.9 95.9 96.0 96.1 95.8 95.8 95.9 96.0 95.7 95.8 95.9 95.9
kW Input 1825 1935 1973 2012 1957 2086 2125 2164 2033 2171 2211 2254 2094 2234 2277 2323
DIMENSIONS
8
APPROVED DOCUMENT
www.cumminsgeneratortechnologies.com
PI7F-312-TD-EN-SG-A