Spec sheet: SS17-CPGK

Noise data sheet: ND50-OSHHP


Airflow data sheet: AF50-HHP
Derate data sheet: DD50-OSHHP
Transient data sheet: RTF

Standby Prime
kVA (kW) kVA (kW)
Ratings 2063 (1650) 1875 (1500)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 32.3 54.9 79.2 107.1 29.5 50.2 71.3 95.7
L/hr 122 208 300 406 112 190 270 363

Standby Prime
rating rating
Engine manufacturer Cummins
Engine model QSK60-G3
Configuration Cast iron, 60 º V16 cylinder
Aspiration Turbocharged and low temperature aftercooled
Gross engine power output, kWm 1790 1615
BMEP at set rated load, kPa 2379 2144
Bore, mm 159
Stroke, mm 190
Rated speed, rpm 1500
Piston speed, m/s 9.5
Compression ratio 14.5:1
Lube oil capacity, L 378
Overspeed limit, rpm 1725 ±50
Regenerative power, kW 146
Governor type Electronic
Starting voltage 24V Volts DC

Maximum fuel flow, L/hr 1515


Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70

power.cummins,com
©2016 Cummins Power Generation Inc. | DS48e-CPGK (3/16)
Standby Prime
rating rating
Combustion air, m3/min 135 129
Maximum air cleaner restriction, kPa 6.2

Exhaust gas flow at set rated load, m3/min 332 306


Exhaust gas temperature, °C 440 415
Maximum exhaust back pressure, kPa 6.7

Ambient design, °C 40
Fan load, kWm 33
Coolant capacity (with radiator), L 456
Cooling system air flow, m3/sec @ 12.7 mmH2O 26.4
Total heat rejection, Btu/min 48925 44125
Maximum cooling air flow static restriction mm H2O 12.7

Open Enclosed
Unit dry weight kgs 14880
Unit wet weight kgs 15945
* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Length Width Height


Standard open set dimensions 6175 2286 2537
Standard enclosed set dimensions

Open set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

power.cummins.com
©2016 Cummins Power Generation Inc. | DS48e-CPGK (3/16)
Connection1 Temp rise ºC Duty2 Alternator Voltage
Wye, 3-phase 105/80C S/P MVSI804R1 3300V
Wye, 3-phase 125/105C S/P HVSI804R1 6600V
Wye, 3-phase 125/105C S/P HVSI804R1 11000V
Wye, 3-phase 150/125C S/P P7F 380-440V

Emergency standby power Limited-time running power Base load (continuous)


Prime power (PRP):
(ESP): (LTP): power (COP):

Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited Time Prime Power (PRP) is in unlimited hours.
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Continuous Power (COP) is
Emergency Standby Power accordance with ISO 8528. Ten percent overload in accordance with ISO
(ESP) is in accordance with capability is available in 8528, ISO 3046, AS 2789,
ISO 8528. Fuel Stop power in accordance with ISO 3046, DIN 6271 and BS 5514.
accordance with ISO 3046, AS AS 2789, DIN 6271 and BS
2789, DIN 6271 and BS 5514. 5514.

Three phase output Single phase output

kW x 1000 kW x SinglePhas eFactor x 1000


Voltage x 1.73 x 0.8 Voltage

See your distributor for more information.


Cummins Power Generation
Manston Park, Columbus Avenue
Manston, Ramsgate
Kent CT12 5BF, UK
Telephone: +44 (0) 1843 255000
Fax +44 (0) 1843 255902
E-mail: [email protected]
Web: www.cumminspower.com
power.cummins,com

©2016 Cummins Power Generation Inc. All rights reserved.


Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower
and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names
may be trademarks or service marks of others. Specifications are subject to change without notice.
DS48e-CPGK (3/16)
Specification sheet

Diesel
generator set
QSK60 series
engine
1760kVA - 2500kVA 50 Hz
1825kW - 2250kW 60 Hz

Description
Control system – The PowerCommand®
This Cummins® Power Generation commercial
generator set is a fully integrated power electronic control is standard equipment and
generation system, providing optimum provides total genset system integration
performance, reliability, and versatility for including automatic remote starting/stopping,
stationary standby, prime power, and precise frequency and voltage regulation, alarm
continuous duty applications. and status message display, AmpSentry™
protection, output metering, auto-shutdown at
Features fault detection and NFPA 110 Level 1
compliance.
Cummins® heavy-duty engine - Rugged 4-
cycle industrial diesel delivers reliable power, Cooling system - Standard integral set-
low emissions and fast response to load mounted radiator system, designed and tested
changes. for rated ambient temperatures, simplifies facility
Permanent magnet generator (PMG) - Offers design requirements for rejected heat.
enhanced motor starting and fault clearing NFPA - The genset accepts full rated load in a
short circuit capability. single step in accordance with NFPA 110 for
Alternator - Several alternator sizes offer Level 1 systems.
selectable motor starting capability with low Warranty and service - Backed by a
reactance 2/3 pitch windings; low waveform comprehensive warranty and worldwide
distortion with non-linear loads, fault clearing distributor network.
short-circuits capability, and class F or H
insulation.

Emissions
Standby rating Prime rating compliance Data sheets
50 Hz 60 Hz 50 Hz 60 Hz TA Luft – EU
Model kVA (kW) kW (kVA) kVA (kW) kW (kVA) Stage 50 Hz 60 Hz
C1760 D5e 1760 (1408) 1600 (1280) 2g TA Luft DS49-CPGK

C2000 D5 2063 (1650) 1875 (1500) DS48-CPGK

C2000 D5e 2000 (1600) 1825 (1460) 2g TA Luft DS50-CPGK

C2250 D5 2250 (1800) 2000 (1600) DS52-CPGK

C2500 D5A 2500 (2000) 2250 (1800) 4g TA Luft DS53-CPGK

C2000 D6 2000 (2500) 1825 (2281) DS86-CPGK

C2250 D6A 2250 (2813) DS87-CPGK

power.cummins.com
©2016 Cummins Power Generation Inc. | SS17e-CPGK (3/16)
Generator set specifications
Transient Performance ISO 8528-5 compliant
Voltage regulation, no load to full load ± 0.5%
Random voltage variation ± 0.5%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
EMC compatibility BS EN 61000-6-4 / BS EN 61000-6-2

Engine specifications
Design 4 cycle, V-black, turbo charged and low temperature after-cooled
Bore 158.8 mm (6.25 in)
Stroke 190.0 mm (7.48 in)
Displacement 60.2 L (3673 in3)
Cylinder block Cast iron, 60ºV 16 cylinder
Battery capacity 2200 amps at ambient temperature 0ºF to 32ºF (-18 °C to 0°C)
Battery charging alternator 40 amps
Starting voltage 24- volt, negative ground
Fuel system Direct injection
Fuel filter Triple element, spin on fuel filters with water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Four spin-on, combination full flow and bypass filters
Standard cooling system 104ºF (40ºC) ambient radiator

Alternator specifications
Design Brushless, 4 pole, drip proof revolving field
Stator 2/3 pitch
Rotor Direct coupled by flexible disc
Insulation system Class H
Standard temperature rise 150 °C standby
Exciter type PMG (Permanent magnet generator)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion No load <1.5%. Non distorting balanced linear load <5%
Telephone influence factor (TIF) < 50% per NEMA MG1-22.43
Telephone harmonic factor (THF) < 3%

Available voltages
50 Hz line – neutral / line - line 60 Hz line – neutral / line - line
 220/380  1905/3300  219/380  2400/4160
 230/400  3640/6300  254/440  7200/12470
 240/415  3810/6600  277/480  7620/13200
 254/440  6350/11000  347/600  7970/13800
Note: Consult factory for other voltages.

Generator set options


Engine Control panel Alternator Generator set
 208/240/480 V thermo-  Multiple language support  120, 240 or 110/240 V control  5A or 10A Batteries
statically controlled coolant  Right or left facing mounting anti-condensation heater  Standalone or wall mountable
heater for ambient above and  Floor mounted  Stator winding temp sensor 2 battery charger
below 4.5 C (40 F)  3 phase differential CTs RTDs/phase  Manual available in multiple
 Oil drain pump - manual (3x or 6x CTs)  Bearing temp sensor RTDs languages
 Engine toolkit  Masterless Load Demand  1 or 2 hole lug output terminal  Standard spring mounts
 Heavy duty air filter  Warning high bearing  Cable entrance box set  Oil sampling valve
Exhaust system temperature mounted top or bottom entry  Fuel transfer pump hand or
 None supplied  Alternator temperature  Cable entrance box left or right electric
 Residential grade exhaust monitoring mounting  Free standing, single wall fuel tank
silencer – shipped loose  Exhaust gas temperature 1350 L /356 US Gal
 Side entry silencer monitoring Cooling system
 6x user-configurable relays  Remote radiator
 120/240 V Heater control cabinet  50C (122 F) radiator
 Mechanical hour meter  Slip fit connection
 2x digital input/output  Flanged (ASA) connection

*Note: Some options may not be available on all models - consult factory for availability.

power.cummins.com
©2016 Cummins Power Generation Inc. | SS17e-CPGK (3/16)
PowerCommand® 3.3 control system
Engine data
 DC voltage
 Engine speed
 Lube oil pressure and temperature
 Coolant temperature
 Comprehensive FAE data (where applicable)
Other data
 Genset model data
 Start attempts, starts, running hours, kW hours
Control system  Load profile (operating hours at % load in 5%
increments)
The PowerCommand® control system is an  Fault history
integrated microprocessor based generator set  Data logging and fault simulation (requires
control system providing voltage regulation, engine InPower)
protection, alternator protection, operator interface
and isochronous governing.
AmpSentry – Includes integral AmpSentry protection,
Standard control functions
which provides a full range of alternator protection
Digital governing (optional)
functions that are matched to the alternator
provided.  Integrated digital electronic isochronous governor
Power management – Control function provides  Temperature dynamic governing
battery monitoring and testing features and smart Digital voltage regulation
starting control system.  Integrated digital electronic voltage regulator
Advanced control methodology – Three phase  3-phase, 4-wire line-to-line sensing
sensing, full wave rectified voltage regulation, with a  Configurable torque matching
PWM output for stable operation with all load types.
Communications interface – Control comes standard AmpSentry AC protection
with PCCNet and Modbus interface.  AmpSentry protective relay
Regulation compliant – Prototype tested: UL, CSA  Over current and short circuit shutdown
and CE compliant.  Over current warning
Service - InPower™ PC-based service tool available  Single and three phase fault regulation
for detailed diagnostics, setup, data logging and fault  Over and under voltage shutdown
simulation.  Over and under frequency shutdown
Reliable design – The control system is designed for  Overload warning with alarm contact
reliable operation in harsh environment.  Reverse power and reverse var shutdown
Multi-language support  Field overload
Engine protection
Operator panel features  Battery voltage monitoring, protection and testing
 Over speed shutdown
Operator panel features – The operator panel, in  Low oil pressure warning and shutdown
addition to the alternator, displays the Utility/AC Bus  High coolant temperature warning and shutdown
data.  Low coolant level warning or shutdown
Operator/display functions  Low coolant temperature warning
 Fail to start (over crank) shutdown
 320 x 240 pixels graphic LED backlight LCD  Fail to crank shutdown
 Auto, manual, start, stop, fault reset and lamp  Cranking lockout
test/panel lamp switches  Sensor failure indication
 Alpha-numeric display with pushbuttons  Low fuel level warning or shutdown
 LED lamps indicating genset running, remote start,  Fuel-in-rupture-basin warning or shutdown
not in auto, common shutdown, common warning,  Full authority electronic engine protection
manual run mode, auto mode and stop
Control functions
Paralleling control functions
 Time delay start and cool down
 Digital frequency synchronization and voltage  Real time clock for fault and event time stamping
matching  Exerciser clock and time of day start/stop
 Isochronous kW and kvar load sharing controls  Data logging
 Droop kW and kvar control  Cycle cranking
 Sync check  Load shed
 Extended paralleling (Peak Shave/Base Load)  Configurable inputs and outputs (4)
 Digital power transfer control (AMF) provides load  Remote emergency stop
transfer operation in open or closed transition or
soft (ramping) transfer mode Options
Alternator data  Auxiliary output relays (2)
 Line-to-neutral and line-to-line AC volts
 3-phase AC current
 Frequency
 kW, kvar, power factor kVA (three phase and total)

power.cummins.com
©2016 Cummins Power Generation Inc. | SS17e-CPGK (3/16)
Emergency standby power (ESP):
Applicable for supplying power to varying electrical load
for the duration of power interruption of a reliable utility
source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and BS
5514.
Limited-time running power (LTP):
This outline drawing is to provide representative configuration
Applicable for supplying power to a constant electrical details for Model series only.
load for limited hours. Limited Time Running Power
(LTP) is in accordance with ISO 8528. See respective model data sheet for specific model outline
drawing number.
Prime power (PRP):
Applicable for supplying power to varying electrical load Do not use for installation design
for unlimited hours. Prime Power (PRP) is in
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046, AS
2789, DIN 6271 and BS 5514.
Base load (continuous) power (COP):
Applicable for supplying power continuously to a
constant electrical load for unlimited hours. Continuous
Power (COP) in accordance with ISO 8528, ISO 3046,
AS 2789, DIN 6271 and BS 5514.

Dim “A” Dim “B” Dim “C” Set Weight* Set Weight*
Model mm mm mm dry kg wet kg
C1760 D5e 6175 2494 3422 14825 16040

C2000 D5 6175 2286 2537 14880 15945

C2000 D5e 6175 2494 3422 15345 16560

C2250 D5 6175 2286 2537 15095 16160

C2500 D5A 6175 2494 3201 16840 17990

C2000 D6 6175 2286 2537 14880 15945

C2250D6A 6175 2494 3201 15380 16530


: Weights represent a set with standard features. See outline drawings for weights of other configurations.

Codes and standards


This generator set is designed in facilities All enclosed products are designed to
certified to ISO 9001 and manufactured in 2000/14/EC meet or exceed EU noise legislation
facilities certified to ISO 9001 or ISO 9002. 2000/14/EC step 2006.

This generator set is available with CE This generator set has been designed to
ISO 8528
certification. comply with ISO 8528 regulation.

Cummins Power Generation

Europe, CIS, Middle East and Africa Americas Asia Pacific

Manston Park Columbus Ave. 1400 73rd Avenue N.E. 10 Toh Guan Road #07-01

Manston, Ramsgate Minneapolis, MN 55432 USA TT International Tradepark

Kent CT12 5BF United Kingdom Phone 763 574 5000 Singapore 608838

Phone 44 1843 255000 Fax 763 574 5298 Phone 65 6417 2388

Fax 44 1843 255902 Fax 65 6417 2399


power.cummins.com

©2016 Cummins Power Generation Inc. All rights reserved.


Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower
and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names
may be trademarks or service marks of others. Specifications are subject to change without notice.
SS17e-CPGK (3/16)
PowerCommand®
3.3 control system

Control system description Features


• 320 x 240 pixels graphic LED backlight LCD.
®
The PowerCommand control system is a microprocessor-
based genset monitoring, metering and control system • Multiple language support.
designed to meet the demands of today’s engine driven
• AmpSentry™ protection - for true alternator overcurrent
gensets. The integration of all control functions into a
protection.
single control system provides enhanced reliability and
performance, compared to conventional genset control • Digital Power Transfer Control (AMF) provides load
systems. These control systems have been designed and transfer operation in open transition, closed transition, or
tested to meet the harsh environment in which gensets are soft (ramping) transfer modes.
typically applied. • Extended Paralleling (Peak Shave/Base Load) regulates
the genset real and reactive power output while
paralleled to the utility. Power can be regulated at either
the genset or utility bus monitoring point.
• Digital frequency synchronization and voltage matching.
• Isochronous Load Share
• Droop KW and KVAR Control
• Real time clock for fault and event time stamping.
• Exerciser clock and time of day start/stop initiate a test
with or without load, or a Base Load or Peak Shave
session.
• Digital voltage regulation. Three phase full wave FET
type regulator compatible with either shunt or PMG
systems.
• Digital engine speed governing (where applicable)
• Generator set monitoring and protection.
• Utility/AC Bus metering and protection
• 12 and 24 V DC battery operation.

®
Modbus interface for interconnecting to customer
equipment.
• Warranty and service. Backed by a comprehensive
warranty and worldwide distributor service network.
• Certifications - Suitable for use on gensets that are
designed, manufactured, tested and certified to relevant
UL, NFPA, ISO, IEC, Mil Std. and CE standards.

©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 1 of 12
PowerCommand digital
• Exerciser clock and time of day start/stop initiate a test
with or without load, or a Base Load or Peak Shave

genset control
session.
• Digital Power Transfer Control (AMF) provides load
PCC 3300 transfer operation in open transition, closed transition, or
soft (ramping) transfer modes.
• Extended Paralleling (Peak Shave/Base Load) regulates
the genset real and reactive power output while
paralleled to the utility. Power can be regulated at either
the genset or utility bus monitoring point.
• Digital frequency synchronization and voltage matching.
• Isochronous Load Share
• Droop KW and KVAR Control
• Sync Check – The sync check function has adjustments
for phase angle window, voltage window, frequency
Description window and time delay.
The PowerCommand genset control is suitable for use on • Utility/AC Bus metering and protection
a wide range of diesel and lean burn natural gas gensets in
• Advanced serviceability – using InPower™, a PC-based
paralleling applications. The PowerCommand control is
software service tool.
compatible with shunt or PMG excitation style. It is
suitable for use with reconnectable or non-reconnectable • Environmental protection – The control system is
generators, and it can be configured for any frequency, designed for reliable operation in harsh environments.
voltage and power connection from 120-600 VAC line-to- The main control board is a fully encapsulated module
line, 601-45,000 VAC with external PT. that is protected from the elements.
• ModBus interface for interconnecting to customer
Power for this control system is derived from the genset
starting batteries. The control functions over a voltage equipment.
range from 8 VDC to 30 VDC. • Configurable inputs and outputs – Four discrete inputs
and four dry contact relay outputs.
Features • Warranty and service – Backed by a comprehensive
warranty and worldwide distributor service network.
• 12 and 24 VDC battery operation.
• Certifications – Suitable for use on gensets that are
• Digital voltage regulation - Three phase full wave FET designed, manufactured, tested and certified to relevant
type regulator compatible with either shunt or PMG UL, NFPA, ISO, IEC, Mil Std. and CE standards.
systems. Sensing is three phase.
• Digital engine speed governing (where applicable) – Base control functions
Provides isochronous frequency regulation.
HMI capability
• Full authority engine communications (where applicable)
Options – Local and remote HMI options
- Provides communication and control with the Engine
Control Module (ECM). Operator adjustments – The HMI includes provisions for
• AmpSentry™ protection - for true alternator overcurrent many set up and adjustment functions.
protection. Genset hardware data – Access to the control and
• Genset monitoring - Monitors status of all critical engine software part number, genset rating in KVA and genset
and alternator functions. model number is provided from the HMI or InPower.
• Digital genset metering (AC and DC). Data logs – Includes engine run time, controller on time,
number of start attempts, total kilowatt hours, and load
• Genset battery monitoring system to sense and warn
profile. (Control logs data indicating the operating hours at
against a weak battery condition.
percent of rated kW load, in 5% increments. The data is
• Configurable for single or three phase AC metering. presented on the operation panel based on total operating
• Engine starting - Includes relay drivers for starter, fuel hours on the generator.)
shut off (FSO), glow plug/spark ignition power and Fault history – Provides a record of the most recent fault
switch B+ applications. conditions with control date and time stamp. Up to 32
• Genset protection – Protects engine and alternator. events are stored in the control non-volatile memory.
• Real time clock for fault and event time stamping. Alternator data

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 2 of 12
- Voltage (single or three phase line-to-line and line-to- - Engine heater status
neutral) - Coolant circulating pump status
- Current (single or three phase) - Lube oil priming pump status
- kW, KVAR, power factor, KVA (three phase and total) - Lube oil status
- Frequency - Oil heater status
- Derate authorization status
For Lean Burn Natural Gas Engine applications:
- Start system status
- Alternator heater status - Ventilator fan status
- Alternator winding temperature (per phase) - Ventilation louvre status
- Alternator drive end bearing temperature - Radiator fan status
- Alternator non-drive end bearing temperature - DC PSU status
Utility/AC bus data - Start inhibit/enable status and setup
Service adjustments – The HMI includes provisions for
- Voltage (three phase line-to-line and line-to-neutral)
adjustment and calibration of genset control functions.
- Current (three phase and total)
Adjustments are protected by a password. Functions
- kW, KVAR, power factor, KVA (three phase and total)
include:
- Frequency
- Engine speed governor adjustments
Engine data - Voltage regulation adjustments
- Starting battery voltage - Cycle cranking
- Engine speed - Configurable fault set up
- Engine temperature - Configurable input and output set up
- Engine oil pressure - Meter calibration
- Engine oil temperature - Paralleling setup
- Intake manifold temperature - Display language and units of measurement
- Coolant temperature
- Comprehensive Full Authority Engine (FAE) data (where Engine control
applicable) SAE-J1939 CAN interface to full authority ECMs (where
For Lean Burn Natural Gas Engine applications: applicable). Provides data transfer between genset and
engine controller for control, metering and diagnostics.
- Safety shutoff valve status
- Valve proving status 12 VDC/24 VDC battery operations - PowerCommand will
- Downstream gas pressure operate either on 12 VDC or 24 VDC batteries.
- Gas inlet pressure Temperature dependent governing dynamics (with
- Gas mass flow rate electronic governing) - modifies the engine governing
- Control valve position control parameters as a function of engine temperature.
- Gas outlet pressure This allows the engine to be more responsive when warm
- Manifold pressure and more stable when operating at lower temperature
- Manifold temperature levels.
- Throttle position
- Compressor outlet pressure Isochronous governing - (where applicable) Capable of
- Turbo speed controlling engine speed within +/-0.25% for any steady
- Compressor bypass position state load from no load to full load. Frequency drift will not
- Cylinder configuration (e.g., drive end and non-drive end exceed +/-0.5% for a 33 °C (60 °F) change in ambient
configurations temperature over an 8 hour period.
- Coolant pressure 1 and 2 (e.g., HT and LT) Droop electronic speed governing - Control can be
- Coolant temperature 1 and 2 (e.g., HT and LT) adjusted to droop from 0 to 10% from no load to full load.
- Exhaust port temperature (up to 18 cylinders)
- Pre-filter oil pressure Remote start mode - It accepts a ground signal from
- Exhaust back pressure remote devices to automatically start the genset and
- CM700 internal temperature immediately accelerates to rated speed and voltage or run
- CM700 isolated battery voltage at idle until engine temperature is adequate. The remote
- Speed bias start signal will also wake up the control from sleep mode.
- CM558 internal temperature The control can incorporate a time delay start and stop.
- CM558 isolated battery voltage
- Knock level (up to 18 cylinders)
- Spark advance (up to 18 cylinders)
- Knock count (up to 18 cylinders)
- Auxiliary supply disconnector status

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 3 of 12
Remote and local emergency stop - The control accepts a Torque-matched V/Hz overload control - The voltage roll-
ground signal from a local (genset mounted) or remote off set point and rate of decay (i.e. the slope of the V/Hz
(facility mounted) emergency stop switch to cause the curve) is adjustable in the control.
genset to immediately shut down. The genset is
Fault current regulation - PowerCommand will regulate the
prevented from running or cranking with the switch
output current on any phase to a maximum of three times
engaged. If in sleep mode, activation of either emergency
rated current under fault conditions for both single phase
stop switch will wakeup the control.
and three phase faults. In conjunction with a permanent
Sleep mode - The control includes a configurable low magnet generator, it will provide three times rated current
current draw state to minimize starting battery current on all phases for motor starting and short circuit
draw when the genset is not operating. The control can coordination purpose.
also be configured to go into a low current state while in
auto for prime applications or applications without a Paralleling functions
battery charger. TM
First Start Sensor system – PowerCommand
Engine starting - The control system supports automatic provides a unique control function that positively prevents
engine starting. Primary and backup start disconnects are multiple gensets from simultaneously closing to an isolated
achieved by one of two methods: magnetic pickup or main bus under black start conditions. The First Start Sensor
alternator output frequency. The control also supports system is a communication system between the gensets
configurable glow plug control when applicable. that allows the gensets to work together to determine
Cycle cranking - Is configurable for the number of starting which genset is a system should be the first to close to the
cycles (1 to 7) and duration of crank and rest periods. bus. The system includes an independent backup
Control includes starter protection algorithms to prevent function, so that if the primary system is disabled the
the operator from specifying a starting sequence that required functions are still performed.
might be damaging. Synchronizing – Control incorporates a digital
Time delay start and stop (cooldown) - Configurable for synchronizing function to force the genset to match the
time delay of 0-300 seconds prior to starting after frequency, phase and voltage of another source such as a
receiving a remote start signal and for time delay of 0-600 utility grid. The synchronizer includes provisions to
seconds prior to shut down after signal to stop in normal provide proper operation even with highly distorted bus
operation modes. Default for both time delay periods is 0 voltage waveforms. The synchronizer can match other
seconds. sources over a range of 60-110% of nominal voltage and
-24 to +6 hertz. The synchronizer function is configurable
For Lean Burn Natural Gas Engine applications: for slip frequency synchronizing for applications requiring a
known direction of power flow at instant of breaker closure
Engine start inhibit/enable – The function will allow
or for applications where phase synchronization
application-specific processes to be started prior to the
performance is otherwise inadequate.
genset/engine start (e.g., pumps, boosters, etc.).
Load sharing control – The genset control includes an
Alternator control integrated load sharing control system for both real (kW)
and reactive (kVar) loads when the genset(s) are operating
The control includes an integrated three phase line-to-line
on an isolated bus. The control system determines kW
sensing voltage regulation system that is compatible with
load on the engine and kVar load on the alternator as a
shunt or PMG excitation systems. The voltage regulation
percent of genset capacity, and then regulates fuel and
system is a three phase full wave rectified and has an FET
excitation systems to maintain system and genset at the
output for good motor starting capability. Major system
same percent of load without impacting voltage or
features include:
frequency regulation. The control can also be configured
Digital output voltage regulation - Capable of regulating for operation in droop mode for kW or Kvar load sharing.
output voltage to within +/-1.0% for any loads between no
load and full load. Voltage drift will not exceed +/-1.5% for
a 40 ºC (104 ºF) change in temperature in an eight hour
period. On engine starting or sudden load acceptance,
voltage is controlled to a maximum of 5% overshoot over
nominal level.
The automatic voltage regulator feature can be disabled to
allow the use of an external voltage regulator.
Droop voltage regulation - Control can be adjusted to
droop from 0-10% from no load to full load.

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 4 of 12
Load govern control – When PowerCommand receives Under voltage sensor: 3-phase L-N or L-L under voltage
a signal indicating that the genset is paralleled with an sensing adjustable for pickup from 85-100% of nominal.
infinite source such as a utility (mains) service, the genset Dropout adjustable from 75-98% of pickup. Dropout delay
will operate in load govern mode. In this mode the genset adjustable from 0.1-30 sec.
will synchronize and close to the bus, ramp to a pre-
Over voltage sensor: 3-phase L-N or L-L over voltage
programmed kW and kVar load level, and then operate at sensing adjustable for pickup from 95-99% of dropout.
that point. Control is adjustable for kW values from 0-
Dropout adjustable from 105-135% of nominal. Dropout
100% of standby rating, and 0.7-1.0 power factor
delay adjustable from 0.5-120 sec. Standard configuration
(lagging). Default setting is 80% of standby and 1.0 power
is disabled, and is configurable to enabled in the field using
factor. The control includes inputs to allow independent
the HMI or InPower service tools.
control of kW and kVar load level by a remote device while
in the load govern mode. The rate of load increase and Over/Under frequency sensor: Center frequency
decrease is also adjustable in the control. In addition, the adjustable from 45-65 Hz. Dropout bandwidth adjustable
control can be configured for operation in kW or kVAR from 0.3-5% of center frequency beyond pickup
load govern droop. bandwidth. Pickup bandwidth adjustable from 0.3-20% of
center frequency. Field configurable to enable.
Load demand control – The control system includes the
ability to respond to an external signal to initiate load Loss of phase sensor: Detects out of range voltage phase
demand operation. On command, the genset will ramp to angle relationship. Field configurable to enable.
no load, open its paralleling breaker, cool down, and shut Phase rotation sensor: Checks for valid phase rotation of
down. On removal of the command, the genset will source. Field configurable to enable.
immediately start, synchronize, connect, and ramp to its
share of the total load on the system. Breaker tripped: If the breaker tripped input is active, the
associated source will be considered as unavailable.
Sync check – The sync check function decides when
permissive conditions have been met to allow breaker Timers: Control provides adjustable start delay from 0-
closure. Adjustable criteria are: phase difference from 300sec, stop delay from 0-800sec, transfer delay from 0-
0.1-20 deg, frequency difference from 0.001-1.0 Hz, 120sec, retransfer delay from 0-1800sec, programmed
voltage difference from 0.5-10%, and a dwell time from transition delay from 0-60sec, and maximum parallel time
0.5-5.0 sec. Internally the sync check is used to perform from 0-1800sec.
closed transition operations. An external sync check Breaker control – Utility and Genset breaker interfaces
output is also available. include separate relays for opening and closing breaker, as
Genset and utility/AC bus source AC metering – well as inputs for both 'a' and 'b' breaker position contacts
The control provides comprehensive three phase AC and tripped status. Breaker diagnostics include Contact
metering functions for both monitored sources, including: Failure, Fail to Close, Fail to Open, Fail to Disconnect, and
3-phase voltage (L-L and L-N) and current, frequency, Tripped. Upon breaker failure, appropriate control action
phase rotation, individual phase and totalized values of is taken to maintain system integrity.
kW, kVAR, kVA and Power Factor; totalized positive and Extended paralleling – In extended paralleling mode
negative kW-hours, kVAR-hours, and kVA-hours. Three (when enabled) the controller will start the genset and
wire or four wire voltage connection with direct sensing of parallel to a utility source and then govern the real and
voltages to 600V, and up to 45kV with external reactive power output of the genset based on the desired
transformers. Current sensing is accomplished with either control point. The control point for the real power (kW) can
5 amp or 1 CT secondaries and with up to 10,000 amp be configured for either the genset metering point ("Base
primary. Maximum power readings are Load") or the utility metering point ("Peak Shave"). The
32,000kW/kVAR/kVA. control point for the reactive power (kVAR or Power Factor)
Power transfer control – provides integrated automatic can also be independently configured for either the genset
power transfer functions including source availability metering point or the utility metering point. This flexibility
sensing, genset start/stop and transfer pair monitoring and would allow base kW load from the genset while
control. The transfer/retransfer is configurable for open maintaining the utility power factor at a reasonable value to
transition, fast closed transition (less than 100msec avoid penalties due to low power factor. The System
interconnect time), or soft closed transition (load ramping) always operates within genset ratings. The control point
sequences of operation. Utility source failure will can be changed while the system is in operation. Set
automatically start genset and transfer load, retransferring points can be adjusted via hardwired analog input or
when utility source returns. Test will start gensets and adjusted through an operator panel display or service tool.
transfer load if test with load is enabled. Sensors and
timers include:

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 5 of 12
Exerciser clock –The exerciser clock (when enabled)
allows the system to be operated at preset times in either
test without load, test with load, or extended parallel
mode. A Real Time Clock is built in. Up to 12 different
programs can be set for day of week, time of day,
duration, repeat interval, and mode. For example, a test
with load for 1 hour every Tuesday at 2AM can be
programmed. Up to 6 different exceptions can also be set
up to block a program from running during a specific date
and time period.
Application types – Controller is configured to operating
in one of six possible application types. These topologies
are often used in combinations in larger systems, with
coordination of the controllers in the system either by
external device or by interlocks provided in the control.
Topologies that may be selected in the control include:

Standalone: Control provides monitoring, protection and


control in a non-paralleling application.

Utility Single: Control monitors one genset and utility. The


control will automatically start and provide power to a load
if the utility fails. The control will also resynchronize the
genset back to the utility and provides extended paralleling
capabilities.

PCC
3300

Synchronizer only: control will synchronize the genset to G


other source when commanded to either via a hardwired
or Modbus driven input.
Position Only

Utility Multiple: Supports all functionality of Isolated Bus


and provides extended paralleling to the utility. Extended
paralleling load set points follow a constant setting;
dynamically follow an analog input, Modbus register or
HMI.

Isolated Bus: allows the genset to perform a dead bus


closure or synchronize to the bus and isochronously share
kW and kVAR loads with other gensets.

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 6 of 12
Configurable alarm and status inputs

Utility Parallel Enable


The control accepts up to four alarm or status inputs
(configurable contact closed to ground or open) to indicate
a configurable (customer-specified) condition.
The control is programmable for warning, derate,
shutdown, shutdown with cooldown or status indication
and for labeling the input.

Emergency stop
Power Transfer Control: control operates a single Annunciated whenever either emergency stop signal is
genset/single utility transfer pair in open transition, fast received from external switch.
closed transition, or soft closed transition. Extended
paralleling functionality also provides base load and peak General engine protection
shave options. Low and high battery voltage warning - Indicates status of
battery charging system (failure) by continuously
monitoring battery voltage.
PCC
3300
Weak battery warning - The control system will test the
G battery each time the genset is signaled to start and
indicate a warning if the battery indicates impending
failure.
Fail to start (overcrank) shutdown - The control system will
indicate a fault if the genset fails to start by the completion
of the engine crack sequence.
Fail to crank shutdown - Control has signaled starter to
crank engine but engine does not rotate.
Cranking lockout - The control will not allow the starter to
Protective functions attempt to engage or to crank the engine when the engine
On operation of a protective function the control will is rotating.
indicate a fault by illuminating the appropriate status LED Fault simulation –The control in conjunction with InPower
on the HMI, as well as display the fault code and fault software, will accept commands to allow a technician to
description on the LCD. The nature of the fault and time of verify the proper operation of the control and its interface
occurrence are logged in the control. The service manual by simulating failure modes or by forcing the control to
and InPower service tool provide service keys and operate outside of its normal operating ranges. InPower
procedures based on the service codes provided. also provides a complete list of faults and settings for the
Protective functions include: protective functions provided by the controller.
Battle short mode For Lean Burn Natural Gas Engine applications:
When enabled and the battle short switch is active, the Off load running (protection) – This feature protects the
control will allow some shutdown faults to be bypassed. If engine in the event the genset is being called to go off load
a bypassed shutdown fault occurs, the fault code and for too long.
description will still be annunciated, but the genset will not
shutdown. This will be followed by a fail to shutdown fault. Hydro mechanical fuel system engine
Emergency stop shutdowns and others that are critical for
protection
proper operation (or are handled by the engine ECM) are
not bypassed. Please refer to the Control Application Overspeed shutdown – Default setting is 115% of nominal
Guide or Manual for list of these faults. Low lube oil pressure warning/shutdown – Level is preset
(configurable with InPower or HMI) to match the
Derate capabilities of the engine used. Control includes time
The Derate function reduces output power of the genset in delays to prevent nuisance alarms.
response to a fault condition. If a Derate command occurs High lube oil temperature warning/shutdown – Level is
while operating on an isolated bus, the control will issue preset (configurable with InPower or HMI) to match the
commands to reduce the load on the genset via contact capabilities of the engine used. Control includes time
closures or Modbus. If a Derate command occurs while in delays to prevent nuisance alarms.
utility parallel mode, the control will actively reduce power
by lowering the base load kW to the derated target kW.
Our energy working for you.™
www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 7 of 12
High engine temperature warning/shutdown – Level is High AC voltage shutdown (59) - Output voltage on any
preset (configurable with InPower or HMI) to match the phase exceeds preset values. Time to trip is inversely
capabilities of the engine used. Control includes time proportional to amount above threshold. Values adjustable
delays to prevent nuisance alarms. from 105-125% of nominal voltage, with time delay
adjustable from 0.1-10 seconds. Default value is 110% for
Low coolant temperature warning – Indicates that engine
10 seconds.
temperature may not be high enough for a 10 second start
or proper load acceptance. Low AC voltage shutdown (27) - Voltage on any phase has
Low coolant temperature warning – Can be set up to be a dropped below a preset value. Adjustable over a range of
warning or shutdown. 50-95% of reference voltage, time delay 2-20 seconds.
Default value is 85% for 10 seconds. Function tracks
High intake manifold temperature shutdown – Level is reference voltage. Control does not nuisance trip when
preset (configurable with InPower or HMI) to match the voltage varies due to the control directing voltage to drop,
capabilities of the engine used. Control includes time such as during a V/Hz roll-off or synchronizing.
delays to prevent nuisance alarms.
Under frequency shutdown (81 u) - Genset output
Full authority electronic engine protection frequency cannot be maintained. Settings are adjustable
from 2-10 Hz below reference governor set point, for a 5-
Engine fault detection is handled inside the engine ECM. 20 second time delay. Default: 6 Hz, 10 seconds. Under
Fault information is communicated via the SAE-J1939 data frequency protection is disabled when excitation is
link for annunciation in the HMI. switched off, such as when engine is operating in idle
speed mode.
Alternator protection
Over frequency shutdown/warning (81o) - Genset is
AmpSentry protective relay - A comprehensive
operating at a potentially damaging frequency level.
monitoring and control system integral to the
Settings are adjustable from 2-10 Hz above nominal
PowerCommand Control System that guards the
governor set point for a 1-20 second time delay. Default: 6
electrical integrity of the alternator and power system by Hz, 20 seconds, disabled.
providing protection against a wide array of fault
conditions in the genset or in the load. It also provides Overcurrent warning/shutdown (51) - Implementation of
single and three phase fault current regulation so that the thermal damage curve with instantaneous trip level
downstream protective devices have the maximum calculated based on current transformer ratio and
current available to quickly clear fault conditions without application power rating.
subjecting the alternator to potentially catastrophic Loss of sensing voltage shutdown - Shutdown of genset
failure conditions. See document R1053 for a full size will occur on loss of voltage sensing inputs to the control.
time over current curve. The control does not included
protection required for interconnection to a utility (mains) Field overload shutdown - Monitors field voltage to
service. shutdown genset when a field overload condition occurs.
Over load (kW) warning - Provides a warning indication
when engine is operating at a load level over a set point.
Adjustment range: 80-140% of application rated kW, 0-
120 second delay. Defaults: 105%, 60 seconds.
Reverse power shutdown (32) - Adjustment range: 5-20%
of standby kW rating, delay 1-15 seconds. Default: 10%, 3
seconds.
Reverse Var shutdown - Shutdown level is adjustable: 15-
50% of rated Var output, delay 10-60 seconds. Default:
20%, 10 seconds.
Short circuit protection - Output current on any phase is
more than 175% of rating and approaching the thermal
damage point of the alternator. Control includes
algorithms to protect alternator from repeated over current
conditions over a short period of time.
Negative sequence overcurrent warning (46) – Control
protects the generator from damage due to excessive
imbalances in the three phase load currents and/or power
factors.

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 8 of 12
Custom overcurrent warning/shutdown (51) – Control Field control interface
provides the ability to have a custom time overcurrent
protection curve in addition to the AmpSentry protective Input signals to the PowerCommand control
relay function. include:
Ground fault overcurrent (51G) – Control detects a ground - Coolant level (where applicable)
fault either by an external ground fault relay via a contact - Fuel level (where applicable)
input or the control can measure the ground current from - Remote emergency stop
an external current transformer. Associated time delays - Remote fault reset
and thresholds are adjustable via InPower or HMI. - Remote start
- Rupture basin
- Start type signal
Paralleling protection
- Battle short
Breaker fail to close Warning: When the control signals a - Load demand stop
circuit breaker to close, it will monitor the breaker auxiliary - Synchronize enable
contacts and verify that the breaker has closed. If the - Genset circuit breaker inhibit
control does not sense a breaker closure within an - Utility circuit breaker inhibit
adjustable time period after the close signal, the fail to - Single mode verify
close warning will be initiated. - Transfer inhibit – prevent transfer to utility (in power
Breaker fail to open warning: The control system monitors transfer control mode)
the operation of breakers that have been signaled to open. - Retransfer inhibit – prevent retransfer to genset (in power
If the breaker does not open within and adjustable time transfer control mode)
delay, a Breaker Fail to Open warning is initiated. - kW and kVAR load setpoints
- Configurable inputs - Control includes (4) input signals
Breaker position contact warning: The controller will from customer discrete devices that are configurable for
monitor both ‘a’ and ‘b’ position contacts from the warning, shutdown or status indication, as well as
breaker. If the contacts disagree as to the breaker message displayed
position, the breaker position contact warning will be
initiated. For Lean Burn Natural Gas Engine applications:
Breaker tripped warning: The control accepts inputs to - Gearbox oil pressure/temperature protection
monitor breaker trip / bell alarm contact and will initiate a - Fire fault
breaker tripped warning if it should activate. - Earth fault
- Differential fault
Fail to disconnect warning: In the controller is unable to - DC power supply fault
open either breaker, a fail to disconnect warning is - Genset Interface Box (GIB) isolator open fault
initiated. Typically this would be mapped to a configurable - Start inhibit/enable (x3)
output, allowing an external device to trip a breaker. - Radiator fan trip
Fail to synchronize warning: Indicates that the genset - Ventilator fan trip
could not be brought to synchronization with the bus. - Ventilation louvers closed
Configurable for adjustable time delay of 10 -900 seconds, - Start system trip
120 default. - Alternator heater trip
- Alternator heater status
Phase sequence sensing warning: Verifies that the genset - Alternator winding temperature (PT100 RTDx3)
phase sequence matches the bus prior to allowing the - Alternator drive end bearing temperature (PT100 RTD)
paralleling breaker to close. - Alternator non-drive end bearing temperature (PT100
Maximum parallel time warning (power transfer control RTD)
mode only): During closed transition load transfers,
Output signals from the PowerCommand control
control independently monitors paralleled time. If time is
exceeded, warning is initiated and genset is disconnected. include:
- Load dump signal: Operates when the genset is in an
Bus or genset PT input calibration warning: The control overload condition.
system monitors the sensed voltage from the bus and - Delayed off signal: Time delay based output which will
genset output voltage potential transformers. When the continue to remain active after the control has removed
paralleling breaker is closed, it will indicate a warning the run command. Adjustment range: 0 - 120 seconds.
condition if the read values are different. Default: 0 seconds.

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 9 of 12
PowerCommand human
- Configurable relay outputs: Control includes (4) relay
output contacts (3 A, 30VDC). These outputs can be

machine interface
configured to activate on any control warning or
shutdown fault as well as ready to load, not in auto,

HMI320
common alarm, common warning and common
shutdown.
- Ready to load (genset running) signal: Operates when
the genset has reached 90% of rated speed and voltage
and latches until genset is switched to off or idle mode.
- Paralleling circuit breaker relays outputs: Control
includes (4) relay output contacts (3.5A, 30 VDC) for
opening and closing of the genset and utility breakers.
For Lean Burn Natural Gas Engine applications:
- Start inhibit/enable event
- Emergency stop event
- Ventilator fan run control
- Louvre control Description
- Radiator fan control
- Alternator heater control This control system includes an intuitive operator interface
- Engine at idle speed event panel that allows for complete genset control as well as
system metering, fault annunciation, configuration and
Communications connections include: diagnostics. The interface includes five genset status LED
- PC tool interface: This RS-485 communication port lamps with both internationally accepted symbols and
allows the control to communicate with a personal English text to comply with customers needs. The
computer running InPower software. interface also includes an LED backlit LCD display with
tactile feel soft-switches for easy operation and screen
- Modbus RS-485 port: Allows the control to navigation. It is configurable for units of measurement and
communicate with external devices such as PLCs using has adjustable screen contrast and brightness.
Modbus protocol.
The run/off/auto switch function is integrated into the
Note - An RS-232 or USB to RS-485 converter is interface panel.
required for communication between PC and control.
All data on the control can be viewed by scrolling through
- Networking: This RS-485 communication port allows screens with the navigation keys. The control displays the
connection from the control to the other Cummins current active fault and a time-ordered history of the five
Power Generation products. previous faults.

Mechanical drawing Features:


• LED indicating lamps
- genset running
- remote start
- not in auto
- shutdown
- warning
- auto
- manual and stop
- Circuit breaker open (if equipped)
- Circuit breaker closed (if equipped)
• 320 x 240 pixels graphic LED backlight LCD.
• Four tactile feel membrane switches for LCD defined
operation. The functions of these switches are defined
dynamically on the LCD.
• Seven tactile feel membrane switches dedicated screen
navigation buttons for up, down, left, right, ok, home and
cancel.

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 10 of 12
• Six tactile feel membrane switches dedicated to control The HMI is designed for proper operation in ambient
for auto, stop, manual, manual start, fault reset and lamp temperatures from -20 ºC (-4 ºF) to +70 ºC (158 ºF), and for
test/panel lamps. storage from -30 ºC (-22 ºF) to +80 ºC (176 ºF).
• Two tactile feel membrane switches dedicated to control The control board is fully encapsulated to provide superior
of circuit breaker (where applicable). resistance to dust and moisture. Display panel has a
• Allows for complete genset control setup. single membrane surface, which is impervious to effects of
• Certifications: Suitable for use on gensets that are dust, moisture, oil and exhaust fumes. This panel uses a
designed, manufactured, tested and certified to relevant sealed membrane to provide long reliable service life in
UL, NFPA, ISO, IEC, Mil Std. and CE standards. harsh environments.
• LCD languages supported: English, Spanish, French, The control system is specifically designed and tested for
German, Italian, Greek, Dutch, Portuguese, Finnish, resistance to RFI/EMI and to resist effects of vibration to
Norwegian, Danish, Russian and Chinese Characters. provide a long reliable life when mounted on a genset. The
control includes transient voltage surge suppression to
Communications connections include: provide compliance to referenced standards.
- PC tool interface - This RS-485 communication port
allows the HMI to communicate with a personal Certifications
computer running InPower. PowerCommand meets or exceeds the requirements of the
- This RS-485 communication port allows the HMI to following codes and standards:
communicate with the main control board.
- NFPA 110 for level 1 and 2 systems.
- ISO 8528-4: 1993 compliance, controls and switchgear.
Mechanical drawing - CE marking: The control system is suitable for use on
generator sets to be CE-marked.
- EN 50081-1,2 residential/light industrial emissions or
industrial emissions.
- EN 50082-1,2 residential/light industrial or industrial
susceptibility.
- ISO 7637-2, level 2; DC supply surge voltage test.
- Mil Std 202C, Method 101 and ASTM B117: Salt fog
test.
- UL 508 recognized or Listed and suitable for use on UL
2200 Listed generator sets.
- CSA C282-M1999 compliance
- CSA 22.2 No. 14 M91 industrial controls.
- PowerCommand control systems and generator sets are
designed and manufactured in ISO 9001 certified
Software facilities.
InPower (beyond 6.5 version) is a PC-based software
service tool that is designed to directly communicate to Warranty
PowerCommand gensets and transfer switches, to All components and subsystems are covered by an
facilitate service and monitoring of these products. express limited one year warranty. Other optional and
extended factory warranties and local distributor
Environment maintenance agreements are available.
The control is designed for proper operation without
recalibration in ambient temperatures from -40 ºC (-40 ºF)
to +70º C (158 ºF), and for storage from -55 ºC (-67 ºF) to
+80 ºC (176 ºF). Control will operate with humidity up to
95%, non-condensing.

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 11 of 12
See your distributor for more information

Cummins Power Generation

Americas Europe, CIS, Middle East and Africa Asia Pacific


rd
1400 73 Avenue N.E. Manston Park Columbus Ave. 10 Toh Guan Road #07-01
Minneapolis, MN 55432 USA Manston Ramsgate TT International Tradepark
Phone: 763 574 5000 Kent CT 12 5BF United Kingdom Singapore 608838
Fax: 763 574 5298 Phone 44 1843 255000 Phone 65 6417 2388
Fax 44 1843 255902 Fax 65 6417 2399
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system
except through an approved device or after building main switch is open.

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570b (5/10) Page 12 of 12
PI734F - Winding 312
APPROVED DOCUMENT
Technical Data Sheet
PI734F
SPECIFICATIONS & OPTIONS
STANDARDS TERMINALS & TERMINAL BOX
Stamford industrial generators meet the requirements of BS Standard generators feature a main stator with 6 ends
EN 60034 and the relevant sections of other national and brought out to the terminals, which are mounted on the
international standards such as BS5000, VDE 0530, NEMA frame at the non-drive end of the generator. A sheet steel
MG1-32, IEC60034, CSA C22.2-100, AS1359. terminal box contains the AVR and provides ample space
Other standards and certifications can be considered on for the customers' wiring and gland arrangements. It has
request. removable panels for easy access.

DESCRIPTION SHAFT & KEYS


The STAMFORD PI range of synchronous ac generators are All generator rotors are dynamically balanced to better
brushless with a rotating field. They are separately excited than BS6861:Part 1 Grade 2.5 for minimum vibration in
by the STAMFORD Permanent Magnet Generator (PMG). operation. Two bearing generators are balanced with a
This is a shaft mounted, high frequency, pilot exciter which half key.
provides a constant supply of clean power via the Automatic
Voltage Regulator (AVR) to the main exciter. The main INSULATION/IMPREGNATION
exciter output is fed to the main rotor, through a full wave The insulation system is class 'H', and meets the
bridge rectifier, protected by surge suppression. requirements of UL1446.
All wound components are impregnated with materials
VOLTAGE REGULATORS APPROVED DOCUMENT and processes designed specifically to provide the high
The PI range generators, complete with a PMG, are available build required for static windings and the high mechanical
with one of two AVRs. Each AVR has soft start voltage build strength required for rotating components.
up and built in protection against sustained over-excitation,
which will de-excite the generator after a minimum of 8 QUALITY ASSURANCE
seconds. Generators are manufactured using production
Underspeed protection (UFRO) is also provided on both procedures having a quality assurance level to
AVRs. The UFRO will reduce the generator output voltage BS EN ISO 9001.
proportional to the speed of the generator below a pre-
settable level. NOTE ON REGULATION
The stated voltage regulation may not be maintained in
The MX341 AVR is two phase sensed with a voltage the presence of certain radio transmitted signals. Any
regulation of ± 1 %. (see the note on regulation). change in performance will fall within the limits of Criteria
'B' of EN 61000-6-2:2001. At no time will the steady-state
The MX321 AVR is 3 phase rms sensed with a voltage voltage regulation exceed 2%.
regulation of 0.5% rms (see the note on regulation). The
UFRO circuit has adjustable slope and dwell for controlled DE RATES
recovery from step loads. An over voltage protection circuit All values tabulated on page 8 are subject to the following
will shutdown the output device of the AVR, it can also trip an reductions
optional excitation circuit breaker if required. As an option,
short circuit current limiting is available with the addition of 5% when air inlet filters are fitted.
current transformers. 10% when IP44 Filters are fitted.
3% for every 500 metres by which the operating altitude
Both the MX341 and the MX321 need a generator mounted exceeds 1000 metres above mean sea level.
current transformer to provide quadrature droop 3% for every 5°C by which the operational ambient
characteristics for load sharing during parallel operation. temperature exceeds 40°C.
Provision is also made for the connection of the STAMFORD
power factor controller, for embedded applications, and a Note: Requirement for operating in an ambient
remote voltage trimmer. temperature exceeding 60°C must be referred to the
factory.
WINDINGS & ELECTRICAL PERFORMANCE
All generator stators are wound to 2/3 pitch. This eliminates
triplen (3rd, 9th, 15th …) harmonics on the voltage waveform
and is found to be the optimum design for trouble-free supply
of non-linear loads. The 2/3 pitch design avoids excessive
neutral currents sometimes seen with higher winding pitches. Note: Continuous development of our products entitles us to
A fully connected damper winding reduces oscillations during change specification details without notice, therefore they must
paralleling. This winding, with the 2/3 pitch and carefully not be regarded as binding.
selected pole and tooth designs, ensures very low levels of
voltage waveform distortion. Front cover drawing is typical of the product range.

2
PI734F
WINDING 312
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.

A.V.R. MX341 MX321

VOLTAGE REGULATION ± 1% ± 0.5 % With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

INSULATION SYSTEM CLASS H

PROTECTION IP23

RATED POWER FACTOR 0.8

STATOR WINDING DOUBLE LAYER LAP

WINDING PITCH TWO THIRDS

WINDING LEADS 6

MAIN STATOR RESISTANCE 0.00076 Ohms PER PHASE AT 22°C STAR CONNECTED

MAIN ROTOR RESISTANCE


APPROVED DOCUMENT 2.31 Ohms at 22°C

EXCITER STATOR RESISTANCE 17.5 Ohms at 22°C

EXCITER ROTOR RESISTANCE 0.063 Ohms PER PHASE AT 22°C

R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others

WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%

MAXIMUM OVERSPEED 2250 Rev/Min

BEARING DRIVE END BALL. 6232 C3

BEARING NON-DRIVE END BALL. 6319 C3

1 BEARING 2 BEARING

WEIGHT COMP. GENERATOR 3840 kg 3807 kg

WEIGHT WOUND STATOR 1908 kg 1908 kg

WEIGHT WOUND ROTOR 1609 kg 1565 kg


2
WR² INERTIA 49.3409 kgm 48.424 kgm2
SHIPPING WEIGHTS in a crate 3913kg 3876kg

PACKING CRATE SIZE 216 x 105 x 154(cm) 216 x 105 x 154(cm)

50 Hz 60 Hz

TELEPHONE INTERFERENCE THF<2% TIF<50

COOLING AIR 2.69 m³/sec 5700 cfm 3.45 m³/sec 7300 cfm

VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
kVA BASE RATING FOR REACTANCE
2020 2080 2080 2040 2345 2500 2550 2600
VALUES
Xd DIR. AXIS SYNCHRONOUS 2.93 2.73 2.53 2.21 3.55 3.38 3.16 2.96

X'd DIR. AXIS TRANSIENT 0.18 0.17 0.15 0.13 0.21 0.20 0.19 0.18

X''d DIR. AXIS SUBTRANSIENT 0.13 0.12 0.11 0.10 0.16 0.15 0.14 0.13

Xq QUAD. AXIS REACTANCE 1.89 1.75 1.63 1.42 2.28 2.18 2.03 1.90

X''q QUAD. AXIS SUBTRANSIENT 0.26 0.25 0.23 0.20 0.32 0.31 0.29 0.27

XL LEAKAGE REACTANCE 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.03
X2 NEGATIVE SEQUENCE 0.19 0.17 0.16 0.14 0.23 0.22 0.20 0.19
X0 ZERO SEQUENCE 0.02 0.02 0.02 0.02 0.03 0.03 0.02 0.02

REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.154s
T''d SUB-TRANSTIME CONST. 0.02s
T'do O.C. FIELD TIME CONST. 2.54s
Ta ARMATURE TIME CONST. 0.02s
SHORT CIRCUIT RATIO 1/Xd

3
PI734F
50 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT

4
PI734F
60 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT

5
PI734F
Winding 312

Locked Rotor Motor Starting Curve


50
30
Hz 346V 380V 400V 415V 440V

25
.

20
PER CENT TRANSIENT VOLTAGE DIP

15 APPROVED DOCUMENT

10

0
0 1000 2000 3000 4000 5000 6000
LOCKED ROTOR kVA

60
30
Hz 380V 416V 440V 460V 480V

25
.

20
PER CENT TRANSIENT VOLTAGE DIP

15

10

0
0 1000 2000 3000 4000 5000 6000 7000
LOCKED ROTOR kVA

6
PI734F
Winding 312
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.
50
Hz
100000

SYMMETRICAL

ASYMMETRICAL
CU RR E NT (Am p s)

10000

APPROVED DOCUMENT

1000
0.001 0.01 0.1 1 10
TIME (secs)
Sustained Short Circuit = 6,850 Amps

60 100000
Hz

SYMMETRICAL

ASYMMETRICAL
CU RR E NT (Am p s)

10000

1000
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 8,900 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable
time 0.001 seconds and the minimum current to the various types of short circuit :
point in respect of nominal operating voltage :
50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v x 1.00 416v x 1.00 Minimum x 1.00 x 1.80 x 3.20
400v x 1.05 440v x 1.06 Sustained x 1.00 x 1.50 x 2.50
415v x 1.09 460v x 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v x 1.16 480v x 1.15 All other times are unchanged
The sustained current value is constant irrespective
of voltage level
Note 3
Curves are drawn for Star (Wye) connected machines.

7
PI734F
Winding 312 / 0.8 Power Factor

RATINGS

Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C

50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

kVA 1880 1935 1935 1900 2020 2080 2080 2040 2105 2170 2170 2125 2165 2250 2250 2185

kW 1504 1548 1548 1520 1616 1664 1664 1632 1684 1736 1736 1700 1732 1800 1800 1748

Efficiency (%) 96.1 96.2 96.3 96.4 96.0 96.0 96.1 96.3 95.9 95.9 96.0 96.2 95.8 95.8 96.0 96.2

kW Input 1565 1609 1607 1577 1683 1733 1732 1695 1756 1810 1808 1767 1808 1878 1876 1817

60Hz Star (V) 416 440 460 480 416 440 460
APPROVED DOCUMENT 480 416 440 460 480 416 440 460 480

kVA 2190 2325 2370 2420 2345 2500 2550 2600 2435 2600 2650 2705 2505 2675 2730 2785

kW 1752 1860 1896 1936 1876 2000 2040 2080 1948 2080 2120 2164 2004 2140 2184 2228

Efficiency (%) 96.0 96.1 96.1 96.2 95.9 95.9 96.0 96.1 95.8 95.8 95.9 96.0 95.7 95.8 95.9 95.9

kW Input 1825 1935 1973 2012 1957 2086 2125 2164 2033 2171 2211 2254 2094 2234 2277 2323

DIMENSIONS

8
APPROVED DOCUMENT

Head Office Address:


Barnack Road, Stamford
Lincolnshire, PE9 2NB
United Kingdom
Tel: +44 (0) 1780 484000
Fax: +44 (0) 1780 484100

www.cumminsgeneratortechnologies.com

Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved


Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.

PI7F-312-TD-EN-SG-A