Catalogue CPS25 UK
Catalogue CPS25 UK
Catalogue CPS25 UK
CPS25 v2 catalogue
The catalogue comprises all the necessary information in order to project and build a CUBIC CPS25
panel according to international standards within the IEC 61439 series.
When applying the catalogue please observe concordance with i.a. national regulations.
As an original manufacturer of the CPS25 system CUBIC has made a verification to the above standards.
With a correct application of the system and execution of routine verification the panel builder is able to
construct electric panels which comply with both IEC 61439-2 and -3.
[Rev: 04-06-21] Page: 02
CPS25 v2
04 Platform - floor 05 Platform - wall 06 Busbars
• Form covering
• Lift bracket
• Accessories
• DIN rail • Unique side plates to be mounted
• MCCB inserts eventually
25 Meterinserts
• Vertical or horizontal assembly of • Door with integrated hinges
MCCBs • Quick dismounting and fitting of
• Inserts for inlet switches door
• Front coverings in metal
• Unique front covering of compo-
nents
• Extensive range
Material specification:
External enclosure: 1,36 and 1.5 mm iron phosphating steel painted in a light grey colour, RAL 7035.
Mounting plates: 1.5 mm hot-galvanized steel.
Busbar holder: PC in a black and light grey colour. - Flammability: UL 94 V0, non-flammable.
Busbar covering: PC, transparent.
Internal separation: PC, transparent.
MCCB flex cover: PA6 in grey colour.
Closing device: Zinc + PA6.
Hinge: Stainless steel.
Platform - floor
A
+ + +B or +
Width (mm) Platform side Base side Base front Top A Top B Rear cover plate
400 4802-2000 x 2 4801-0046 x 2 4801-0040 4801-0041 4801-0042 4806-0240
600 4802-2000 x 2 4801-0046 x 2 4801-0060 4801-0061 4801-0062 4806-0260
4801-00X0
4801-0046
4802-2000
4801-00X1
Base side to be screwed on platform sides. Base front to be mounted. Top should be screwed on either horizontally or
when the platform has been erected.
• Heavy platforms
• At transport
• Bottom plates Width (mm) Plinth, rear
400 4801-1040
600 4801-1060
Platform - wall
A
+ B
or +
A
Width (mm) Platform side Top/Bottom Rear cover plate
400 4833-1200 x 2 4801-0041 x 2 4834-1240
600 4833-1200 x 2 4801-0061 x 2 4834-1260
Do not put on the rear
plate until all acces-
B sories have been
Width (mm) Platform side Top/Bottom Rear cover plate mounted.
400 4833-1200 x 2 4801-0042 x 2 4834-1240
600 4833-1200 x 2 4801-0062 x 2 4834-1260
Screws REMEMBER
If nothing else is indi-
50 pcs 3068-0050
cated, this screw should
1000 pcs 1030-0510q1 be applied!
4801-00X1
4833-1200
Top/bottom to be screwed on sides of the Turn the platform and screw on the second side.
platform.
Busbars
+ + +
Cu 1x5x20
Width (mm) Busbar holder Busbar carrier Locking pad
400 3063-0520 4807-0040 3063-0001 x 4
600 3063-0520 4807-0060 3063-0001 x 4
Cu 2x5x20
Width (mm) Busbar holder Busbar carrier Locking pad
400 3063-0520 4807-0040 3063-0001 x 8
600 3063-0520 4807-0060 3063-0001 x 8
Vertical: Min. 2 busbar carriers and 2 busbar holders and 4 pcs. 3063-0002 per column should be ordered
Horizontal: Min. 2 busbar carriers and 2 busbar holders and 8 pcs. 3063-0002 per column should be ordered
Max 200 mm
4807-00X0
3063-0002
3063-0520
Busbar carrier to be screwed on the platform. At least 2 units per column should be mounted. Busbar holder should be clicked on either hori-
zontally or vertically, and stop pads mounted at
the bottom of the column.
3063-0001
Copper bars should be fastened and ensured by Example of horizontal fitting, here stop pads Example of vertical fitting, here stop pads
locking pad. should be mounted at both ends. should be mounted at both ends.
Busbar: 4821-00X0 Busbar: 4821-00X0
+ + +
1
Schneider
Component Bracket
NX1X00 - NSX250 4803-1001 x 2
NSX400 - NSX630 4803-1002 x 2
ABB
Component Bracket
T3 (TS3) 4803-2002 x 2
T4 + T5 4803-2003 x 2
XT1 + XT3 4803-2004 x 2
XT2 + XT4 4803-2005 x 2
Terasaki
Component Bracket
S160-E250-S250 4803-3005 x 2
E400/S400/E630/S630 4803-3006 x 2
E125-S125 4803-3007 x 2
2 400mm
3
A
5
C
+50
4 Mounting plates
30 kg
X mm
X + 50mm
Height Pos.
150
200
A
A
C *)
4805-1540
4805-2040
4805-2040
+ X mm X mm
C
250 A 4805-2540 A
C 4805-2540
300 A 4805-3040
C 4805-3040
Front coverings MCCB fl. cov.
350 A 4805-3540
+50 Deep
+
C 4805-3540
4846-4015 4850-4015 3061-0000
400 A 4805-4040
4846-4020 4849-4025 4850-4020 3061-0000
C 4805-4040
4846-4020 4849-4025 4580-4020 3061-0000
450 A 4805-4040
(400) 4846-4025 4849-4030 4850-4025 3061-0000
C 4805-4040
4846-4025 4849-4030 4850-4025 3061-0000
4846-4030 4849-4035 4850-4030 3061-0000
*) Cannot be applied for: Schneider NSX400-
4846-4030 4849-4035 4850-4030 3061-0000
630A + ABB T4-T5
4846-4035 4849-4035 4850-4035 3061-0000
4846-4035 4849-4035 4850-4035 3061-0000
4846-4040 4849-4045 4850-4040 3061-0000
4846-4040 4849-4045 4850-4040 3061-0000
4850-4045
Screw 3061-3510 4850-4045
2 600mm
3 B
Screw 3061-3510
C 5 +50
X + 50mm
X mm
X mm X mm
D
C
4 30 kg
B D
300
C
D
C
4805-2560
4805-2560
4805-3060
+ 4846-6025
4846-6030
4849-6030 4851-6025
4850-6025
4850-6025
4850-6030
+ 3061-0000
3061-0000 x3
3061-0000
D 4805-3060 4849-6035 4851-6030 4850-6030 3061-0000
350 C 4805-3560 4846-6035 4850-6035 3061-0000
D 4805-3560 4849-6040 4851-6035 4850-6035 3061-0000 x3
400 C 4805-4060 4846-6040 4850-6040 3061-0000
D 4805-4060 4849-6045 4851-6040 4850-6040 3061-0000 x3
450 C 4805-4060 4850-6045
(400)
D 4805-4060 4851-6045 4850-6045 3061-0000 x3
2 DIN
4
400mm
30 kg 5 400mm (Opening for components = 324mm)
Mounting plates Front cov. DIN Master brack. Fastner DIN rail
Height
150
200
250
4805-1540
4805-2040
4805-2540
+ 4847-4015
4847-4020
4847-4025
4803-0010 x 2
4803-0010 x 2
4803-0010 x 4
3064-0000 x 2
3064-0000 x 2
3064-0000 x 4
4814-0040 x 1
4814-0040 x 1
4814-0040 x 2
300 4805-3040 4847-4030 4803-0010 x 4 3064-0000 x 4 4814-0040 x 2
350 4805-3540 4847-4035 4803-0010 x 4 3064-0000 x 4 4814-0040 x 2
400 4805-4040 4847-4040 4803-0010 x 6 4814-0040 x 3 4822-0002 x 4
+
150 4805-1560 4847-6015 4803-0010 x 2 3064-0000 x 2 4814-0060 x 1
200 4805-2060 4847-6020 4803-0010 x 2 3064-0000 x 2 4814-0060 x 1
250 4805-2560 4847-6025 4803-0010 x 4 3064-0000 x 4 4814-0060 x 2
300 4805-3060 4847-6030 4803-0010 x 4 3064-0000 x 4 4814-0060 x 2
350 4805-3560 4847-6035 4803-0010 x 4 3064-0000 x 4 4814-0060 x 2
400 4805-4060 4847-6040 4803-0010 x 6 3064-0000 x 6 4814-0060 x 3
4 5
Mounting plate can be
left out and DIN material
be mounted direct on the
platform.
400mm (Opening for components = 324mm)
Height Front cov. DIN Master brack. Fastner DIN rail
150 4847-4015 4803-0010 x 2 3064-0000 x 2 4814-0041 x 1
200 4847-4020 4803-0010 x 2 3064-0000 x 2 4814-0041 x 1
When ordering 1 pcs. 250 4847-4025 4803-0010 x 4 3064-0000 x 4 4814-0041 x 2
of 3064-0000, you will 300 4847-4030 4803-0010 x 4 3064-0000 x 4 4814-0041 x 2
recieve 10 fastners.
350 4847-4035 4803-0010 x 4 3064-0000 x 4 4814-0041 x 2
400 4847-4040 4803-0010 x 6 3064-0000 x 6 4814-0041 x 3
4847-XX25 4847-XX30
4847-XX35 4847-XX40
3 Not relevant
4 30 kg 5 400mm
400mm
Front coverings
Mounting plates
50 4845-4005
Height
150 4845-4015
150 4805-1540
200 4845-4020
200 4805-2040
250 4845-4025
250 4805-2540
300 4845-4030
+
300 4805-3040
350 4845-4035
350 4805-3540
400 4845-4040
400 4805-4040
600mm 600mm
Height 50 4845-6005
Screw 3061-3510
4805-XXXX
3064-0000
4803-0010
4803-0010
The mounting plate can be displaced either back- The bottom of the mounting plate should be
wards or forward with brackets, which dislocate placed in holes on the platform and be tilted in
with 20mm and then in leaps of 10mm up to place.
80mm.
4803-XXXX
The mounting plate should be fastened with Brackets should be mounted in pre-defined The covering is fixed with screws to the brack-
screws. holes and slits and fastened with screws, then ets.
the switch selected should be installed.
+ 15
2 x ø6
Sealing screw
25
M5x10 4830-0510
4822-0005
Bracket is mounted, and tap is bended. The tap should penetrate the hole, and the Ready for sealing.
screw fastened.
or
+ +
Width (mm) Side profile FLOOR Side profile WALL Fitting for wall Screw
400 4840-2015 4838-1215 4836-0000 x 2 3041-0812 x 4
600 4840-2015 4838-1215 4836-0000 x 2 3041-0812 x 4
To cover hinge holes not applied, use
To cover holes, use blind plugs 3066-4452s (40 pcs.).
grey blind plugs 3069-0855s
(40 pcs.).
4840-2015
At first the small chip with a hole is bended, so The side plates are fastened to the platform.
the side plates can be mounted.
4836-0000
4836-0000
3041-0812
3041-0812
4836-0000
4836-0000
3041-0812
3041-0812
Reinforced hinge is mounted (2 pcs.) The back plate is fastened with a screw. The bracket can also be used to hold two plat-
forms together.
+ + + + + +
Floor
Width (mm) Door Soft close device Reinfor. hinge Cap
400 4806-2040 3067-0001 3060-0005 x 2 3060-0395 x 2
600 4806-2060 3067-0001 3060-0005 x 2 3060-0395 x 2
Wall
Width (mm) Door Soft close device Reinfor. hinge Cap
400 4835-1240 3067-0001 3060-0005 3060-0395
600 4835-1260 3067-0001 3060-0005 3060-0395
4806-20X0
4815-0003
At first the door is mounted at the bottom. The hinge is tilted a little at the top, before the The closing clamp is mounted on the platform.
door is moved into place.
3067-0001
2176-0000 1190-0000
The closing device is mounted on the door by Soft close devices 3060-0395 are mounted Soft close devices are put on as illustrated, 4
means of the lock nut. under each of the 2 reinforced hinges. pcs. per door, the sheet consists of 54 pcs.
Accessories
Brackets to be mounted in the platform. DIN, PE rail and wiring channel can be mounted.
Width (mm) Bracket, cable
area
400 & 600 4803-0004
+ +
Width (mm) Special nut Screw DIN933 Dish washer Mounting of e.g. Cu-flex on busbars.
400 & 600 4807-0008 2009-0840 2018-0800
Accessories
+ +
Width (mm) Busbar cover, side Busbar cover, front/ Busbar cover, top/
back bottom
400 & 600 4816-0200 x 2 4817-0200 x 2 4818-0000 x 2
4816-0250 x 2 4817-0250 x 2 4818-0000 x 2
At more spaces above each
4816-0300 x 2 4817-0300 x 2 4818-0000 x 2 other, covering is made with
4816-0350 x 2 4817-0350 x 2 4818-0000 x 2 4818-0001, and each column is
concluded with top/bottom.
4816-0400 x 2 4817-0400 x 2 4818-0000 x 2
Accessories
Or be ass. before
side pl.
Width (mm) Bottom plate with small flange Bottom plate with big flange Side section
400 4804-0040 4804-0042 4804-0001 x 2 Plinth must be
mounted first.
600 4804-0060 4804-0062 4804-0001 x 2 See page 4
Bottom plates should be mounted with screws. Side sections close gap at the back of the
platform.
05
A
All flanges can be applied for the
top and bottom plates.
05
B
Accessories
4841-0009
+ +
Width (mm) 400 and 600
Barrier Support bracket Assembly fitting
Gulv 4840-2000 4803-0002 x 5 4803-0003 x 2
Væg 4839-1200 4803-0002 4803-0003 x 2
Accessories
+
Cables are led through as required, after making a hole and
mounting a joint.
Width (mm) Cable entry
400 4805-0540
600 4805-0560
Width (mm) Lift bracket Screws are removed from the platform,
and lift brackets are mounted in the
400 4802-0040 holes with the screws.
600 4802-0060
Accessories
+
4854-XXXX only
mounted towards the
Without ventilation With ventilation cable compartment.
Width Height Inner cov. vert. Inner cov. top/bot. Bredd Height Inner cov. vert. Cover with ventilla. Inner cov. top/bot.
400 150 4853-1500 x 2 4828-0040 400 150 4853-1500 4854-1500 4828-0040
200 4853-2000 x 2 4828-0040 200 4853-2000 4854-2000 4828-0040
250 4853-2500 x 2 4828-0040 250 4853-2500 4854-2500 4828-0040
300 4853-3000 x 2 4828-0040 300 4853-3000 4854-3000 4828-0040
350 4853-3500 x 2 4828-0040 350 4853-3500 4854-3500 4828-0040
400 4853-4000 x 2 4828-0040 400 4853-4000 4854-4000 4828-0040
600 150 4853-1500 x 2 4828-0060 600 150 4853-1500 4854-1500 4828-0060
200 4853-2000 x 2 4828-0060 200 4853-2000 4854-2000 4828-0060
250 4853-2500 x 2 4828-0060 250 4853-2500 4854-2500 4828-0060
300 4853-3000 x 2 4828-0060 300 4853-3000 4854-3000 4828-0060
350 4853-3500 x 2 4828-0060 350 4853-3500 4854-3500 4828-0060
400 4853-4000 x 2 4828-0060 400 4853-4000 4854-4000 4828-0060
4853-0XX0
4828-00X0
Coverings for side are clicked on. Top/bottom is clicked on the sides. Holes must be drilled in the metal plate for
mounting of screws for fastening of top and
bottom.
CUBIC-Modulsystem A/S Tel +45 9882 2400
Skjoldborgsgade 21 E-mail: [email protected]
9700 Broenderslev www.cubic.eu
Denmark
[Rev: 04-06-21] Page: 22
Accessories
+ +
Order an extra top/bot-
Used for cable entry pl: 4805-0540 & 4805-0560 +50 tom per column
Width Height Inner cov. vert. Cov. extension Inner cov. top/bot.
400 200 4853-1500 x 2 4853-0500 x 2 4828-0040
250 4853-2000 x 2 4853-0500 x 2 4828-0040
300 4853-2500 x 2 4853-0500 x 2 4828-0040
350 4853-3000 x 2 4853-0500 x 2 4828-0040
400 4853-3500 x 2 4853-0500 x 2 4828-0040
450 4853-4000 x 2 4853-0500 x 2 4828-0040
600 200 4853-1500 x 2 4853-0500 x 2 4828-0060
250 4853-2000 x 2 4853-0500 x 2 4828-0060
300 4853-2500 x 2 4853-0500 x 2 4828-0060
350 4853-3000 x 2 4853-0500 x 2 4828-0060
400 4853-3500 x 2 4853-0500 x 2 4828-0060
450 4853-4000 x 2 4853-0500 x 2 4828-0060
4828-0040
Extension and side coverings are put together. The sides with extension are clicked on. Top/bottom is clicked on the sides.
2088-0611
The box is closed in the corners. Holes must be drilled in the metal plate for
mounting of screws for fastening of top and
bottom.
CUBIC-Modulsystem A/S Tel +45 9882 2400
Skjoldborgsgade 21 E-mail: [email protected]
9700 Broenderslev www.cubic.eu
Denmark
[Rev: 04-06-21] Page: 23
Accessories
IP43
17mm
2080-0855
1029-0002
- Max 3 sections
- Max 250 kg
- Plinth in back must be mounted
Mount bracket for lifting Use transport device to lift panel from the floor Use as shown here
Screws REMEMBER
If nothing else is indi-
50 pcs. 3068-0050
cated, this screw should
1000 pcs. 1030-0510q1 be applied!
4824-0000
Position of the insert for meter is determined by Universal bracket and bearer to be mounted in Please note the position of the universal bracket
measuring with the side covering the third slot from the side covering. in the depth.
4823-0045
4823-0041
2 bearers are mounted at this distance. Coverings are clipped on the house. Then fasten to the platform in the 2 coverings.
4823-0002
3046-5512
2062-0032 4823-0005
4823-0003
Top/bottom are clipped on. The foam plate is mounted. The foam plate is fastened from the back.
4826-0041
4826-0041
Horizontal covering back is mounted. Transformer field is fastened. Horizontal covering is mounted below the
transformer field.
4824-0001
4826-0040
After mounting the components, they are pro- Put together the chips of the 2 plates and fasten Side coverings are mounted in both sides.
tected with horizontal covering front. the covering to the platform.
Width (mm)
400 4823-0000s
REMEMBER
Screws
If nothing else is indi-
50 pcs. 3068-0050 cated, this screw should
be applied!
1000 pcs. 1030-0510q1
1180 mm
Universal bracket and bearer to be mounted in Please note the position of the universal bracket 2 bearers are mounted at this distance.
the third slot from the covering. in the depth.
4823-0045
4823-0041
Coverings are clipped on the house. Then fasten to the platform in the 2 coverings.
2023-0516
4506-0006 4823-0004
Screws and plate are put on the table. The meter plate is placed on top of the parts. The meter plate is fastened with screws.
4506-0011
4506-0012
Then the fastening plate is screwed on the Stiffener parts are assembled. Stiffener ready for mounting.
meter plate.
Stiffeners are mounted on the meter plate. Preassembled meter plate with stiffeners ready The back is clipped into place.
to be fastened to house.
4823-0003
Top and bottom are clipped into place. Then they are fastened with screws.
4823-0006 4823-0008
4823-0007
Mount the support plate - remember that the Covering for terminal strips should now be The sides are clipped on.
membrane should go through both plastic assembled.
layers.
4506-0008
Put the top into position in the slots. Covering for terminal strips is now assembled. The covering is clipped over the stiffeners, and
sealing can be effected.
Sides for the platform are mounted with It is covered, and is now ready for meter and
screws. seal.
+ + +
4843-3500 4843-0040
4843-4035
Mounting plate is mounted with 4 screws. The sides are mounted in sloths. Top/bottom are also mountes in sloths.
2030-0600
3068-0050
The covering is screwed together with washers Both in top and in bottom.
and screws.
+ + + +
Size (mm) Mounting plate Isolator 40x50 M12 Distance piece Busbar Screw Screw Screw
600x800 4842-6060 2045-4050 3064-0001 4821-0400 2009-1225 2009-1240 2009-1035
4821-0500
4821-0600
Sides are mounted in bouth sides. Inner top/bottom are mounted. Inner top/bottom are mounted.
Outer top/bottom are mounted. Outer top/bottom are mounted. Parts are mounted on the mounting plate.
+ +
Swivelling front Hinge bracket Screws Hinge
4852-4040 4852-0040 3041-0608 & 3047-0406 x 2 0570-0000 x2
4852-4080 4852-0080 3041-0608 & 3047-0406 x 2 0570-0000 x2
4852-6040 4852-0040 3041-0608 & 3047-0406 x 2 0570-0000 x2
4852-6080 4852-0080 3041-0608 & 3047-0406 x 2 0570-0000 x2
Swing frame is mounted. Hinge must be mounted in the front with Front with swing frame is mounted.
brackets
On pages 34 to 36 we have a representative list of different groups of functional units in the range from DIN material, MCCBs and up to 800A incoming
device. The power loss for each group is calculated on the basis of values given by device manufactures.
On page 37 we have a representative list with power loss of CPS25 busbars, Cu-flex and wires.
The power loss of e.g. a busbar or device with a load different from the rated current can be calculated by using this formula: P = Pn x (I/In)2
NOTE!
External cables are not included in the power losses given in this manual.
The power loss for external cables is estimated to be about 20% of the calculated power loss from devices, busbars and internal wires.
The Total Power Loss (TPL) can be found by using the following formula [TPL = power loss from installed parts x RDF2].
The total power loss from the parts installed consists of:
• The calculated power loss for functional units from pages 34 to 36.
• The calculated power loss for busbars from page 37.
• The estimated power loss for cables.
Rated Diversity Factor (RDF) is subject to an agreement between the user and manufacturer.
In lack of an agreement, the RDF can be found in IEC 61439-2 table 101 or IEC 61439-3 table 101.
The power loss for 5 groups of functional units is calculated to a total of 500W
Busbar: 1 meter 1-5x20 loaded 400A => P = Pn x (I/In)2 => 52 x (400/440)2 = 43W
Cables: 15% of 543W = 81.5W
RDF for the circuits (e.g. 15) in the 5 groups according to IEC 61439-2, table 101 = 0.6
The temperature rise in both the middle and the top of the panel can be found in the curves on page 38 (floor model) / page 39 (wall model).
For a 400mm wide panel the temperature rise in the middle is measured to 17K and in the top to 26K.
With an ambient temperature of 25 ºC that gives an actual temperature of 42 ºC and 51 ºC.
The devices installed in the top half of the panel shall then be capable of withstanding 51 ºC, and in the bottom half 42 ºC. If not, the temperature must be
lowered, either by selecting a larger panel, or by installing lower power loss (larger devices / thicker cables).
Type of load Assumed loading factor Number of outgoing circuits Assumed loading factor
Distribution – 2 and 3 circuits 0.9 2 and 3 circuits 0.8
Distribution – 4 and 5 circuits 0.8 4 and 5 circuits 0.7
Distribution – 6 to 9 circuits 0.7 6 to 9 circuits 0.6
Distribution – 10 or more circuits 0.6 10 or more circuits 0.5
Electric actuator 0.2 IEC 61439-3, table 101
Motors ≤ 100 kW 0.8
Motors > 100 kW 1.0
IEC 61439-2, table 101
Component: 80 A MCCB
Connection: 1 x 25 mm2 wire per pole (300 mm)
Power loss: 55W
Component: 63 A MCCB
Connection: 1 x 16 mm2 wire per pole (300 mm)
Power loss: 53W
Component: 80 A MCCB
Connection: 1 x 25 mm2 wire per pole (300 mm)
Power loss: 55W
Components:
2 x 63A, 4 pole RCD relay
6 x 16A, 4 pole MCB
12 x 10A, 2 pole MCB
Connection:
16 mm2 wire for 63A
6 mm2 wire for up to 16A
Total power loss: 291W
Components:
2 x 63A, 4 pole RCD relay
2 x 16A, 4 pole MCB
9 x 10A, 2 pole MCB
Connection:
16 mm2 wire for 63A
6 mm2 wire for up to 16A
Total power loss: 185W
Components:
1 x 63A, 4 pole RCD relay
1 x 16A, 4 pole MCB
6 x 10A, 2 pole MCB
Connection:
16 mm2 wire for 63A
6 mm2 wire for up to 16A
Total power loss: 82W
Busbars
Busbar 1 - 5x20, 440A = 52W per meter
Busbar 2 - 5x20, 800A = 88W per meter
Note! A busbar typically has some outgoings, and the power loss should be adjusted accordingly.
Cu-flex
Cu-flex Current [A] Power loss [W]
FB25288 165 7
FB50288 260 9
FB100288 400 10.5
FB240288 670 13
2 x FB240288 1035 15.5
Further Cu-flex data can be found in the CUBIC Cu-flex brochure. Please download from www.cubic.eu
Conductor arrangement
Single-core cables in a cable trun- Single-core cables, touching free in Single-core cables, horizontally
king on a wall, horizontally run. air or on a perforated tray. spaced
6 of the cables 6 cables in free air
(2 three-phase circuits) continuous- (2 three-phase circuits) continuous-
ly loaded ly loaded
Cross- Resistance of Max. operating Power losses Max. operating Power losses Max. operating Power losses
sectional area of conductor at current per conductor current per conductor current per conductor
conductor 20°C, R20 Imax Pv Imax Pv Imax Pv
50
riseΔt [K]
40
Temperaturerise
30 Mell
Temperature
Top
20
10
0
50 100 150 200 250 300 350 400 450 500 550 600
Power loss
50
Temperature rise Δt [K]
40
Temperature rise
30 M
T
20
10
0
50 100 150 200 250 300 350 400 450 500 550 600 650 700
Power loss
Power loss
Power loss
50
riseΔt [K]
40
Temperaturerise
30 M
Temperature
To
20
10
0
50 100 150 200 250 300 350
Power loss
50
rise Δt [K]
40
Temperature rise
30 Me
Temperature
Top
20
10
0
50 100 150 200 250 300 350 400 450
Power loss
Power loss
Power loss