WL-9000 Series Sensor-Less Vector Frequency Converter

Chapter 1 Security Information


1.1 Saft Marks and Definitions
The Security clauses written in this User Manual are very important to ensure the
security using of Frequency Converter , and prevent the damage to the operator or
persons and things around. Please know these marks completely and observe the
requirement strictly .

Please must observe this mark, otherwise would bring about


casualty accident
Danger

This mark means if operating by breaking the rule would cause


minor wound or damage to the operator and things.
Warning

This mark means the instructions you should pay a attention

Attention

This mark reminds you the information useful for you

Remind

Could not do it absolutely

Forbidding

What you must do .

Forced
1.2 Range of Appliance

The frequency converter is matched with Industrial 3-phase AC


asynchronous motor .
Attention
-1-
WL-9000 Series Sensor-Less Vector Frequency Converter

The Frequency Converter should not be used with the


equipments , such as Nuclear-powered control equipments, Space
Warning navigation equipments, Traffic equipments, Security equipments,
Weapons equipments, and so on, which may cause casualty accident
because of the faults of the frequency converter . Please look into our
company in advance for the special usage of frequency converter .
Our frequency converters are made as the requirement of ISO
System .But Customers also need take any security measures for the
operating of Important equipments.

1.3 Appliance Conditions

Attention
● Install the product vertically in the place of well ventilated to get the best result of
cooling . And if installed in level position, please add the ventilation installation .
● Around Temperaturer : within the range of -10~40°C. Take away the upper cover
if over 40°C, and when be over 50°C, customers should cool forced or use by derating.
We do not suggest the application in high-temperaturer conditions, since it will shorten
the life of Frequency Converter
● Humidity should be lower than 90%, and no water coagulum.
● The vibration within the intallation place should be less than 0.5G.The Do not
allow any sudden shock happened to the frequency converter
● Installation site should far away from electromagnetic field , and should be no
inflammable and explosive dangerous goods

Ensure the product is fixed on the fireproofing material, like


Metal ,in case of fire.
Warning
Make sure no wire pieces, soldering tins or Zinc or iron sheets into
product, in case that the frequency converter to be burn up because of
short circuit

-2-
WL-9000 Series Sensor-Less Vector Frequency Converter

1.4 Security Items of Installation

Strictly forbid to operate by damp hands.


Strictly forbid to do any layout working or open the cover when
Danger the power is still open, and you should wait for 10 minutes after
breaking the power if for layout or inspection working, otherwise
would get an electric shock.

Do not use the product with failure or lack components


Make sure the cables are connected securely with the main-circuit
terminal, or else would cause damage to the poduct because of poor
Warning cantact .
The earth terminals of frequency converter must be reliable
ground connection .In case of the affect from anti-interference of earth
resistantor, several frequency converters should be earthed by one
point. See the drawing 1-1.

Drawing1-1

Strictly forbid to connect the AC power source with the ourtput


terminals U、V、W of frequency converter , otherwise would be
damage to product. See drawing 1-2.

-3-
WL-9000 Series Sensor-Less Vector Frequency Converter

Drawing 1-2

Customers must install no-fuse or leakage circuit-breaker to


protect the cicuit and avoid the broden the scope of accident because

Forced of fault of fault of product.

It not fit to install the electromagnetism Contactor at the output


circuit of frequency converter .The reason is that the open-or-close
action of contactor when the motor is runnig, will produce operation
Attention over voltage and damage to frequency converter. But it is necessary
for the following situation:
① When the frequency conversion used in energy saving
control, and the system operates under rated speed frequently, in order
to realize ecomonic operation, need to remove frequency converter.
② When for important process flow and could not stop for long
time, in order to improve the system reliability, need to transfer among
control system.
③ When one frequency converter controls multi-set of motors
Users must note that when frequency converter output, the
contactor could not act. !

-4-
WL-9000 Series Sensor-Less Vector Frequency Converter

1.5 Security items for operating

Strictly forbid to operate by damp hands。


For the frequency converter be stored over 2 years, users should
set-up to rated value by voltage regulator when be energized,
otherwise would get an electric shock or explosion.
Do not touch the inner of product or put anything into the product
Danger when power-on. Even more, could not open the cover when the
product is in the process of electrifying , otherwise would get an
electric shock or make the converter could not operate normally .
Please operate the function of “Re-start after outage” carefully,or
else will cause casualty accident.

When operating over 50Hz, must be sure the speed range of motor
bearing and machine devices when operating.
The machine devices, such as Reducer Casing or Gear Wheel
which need be lubricated,should not run for long time under low-speed.
Since the heat dissipation capacity would be poorer when
common motor running in low-frequency, should be derating, and if
Warning be constant torque load, should must adopt forced heat dissipation or
use the frequency -changer motor .
If the product was not be used for long time, user should cut off the
power source, in case of any damage to the converter or fire.
Since the output voltage is PWM Pulse wave, please do not install
capacitor or surge-current-absorber on the output end of frequency
converter, Or else would result in Fault tripping or even any damage to
power components of frequency converter. Please remove if these
products have been installed. Please see the drawing 1-3.

-5-
WL-9000 Series Sensor-Less Vector Frequency Converter

Drawing 1-3

If the Motor is put to use for first time or using again after
long time stored, should make the insulation examine and ensure
the insulating resistance is no less than 5MΩ.
If allowed to operate frequency converter over its operating
voltage range, should deploy voltage set-up transformer or voltage
reducing device.
Attention Application in the place more than 1000 meters above sea
level, because of the thin air , the heat dissipation capacity of
frequency converter would be poorer and should be used by
derating. Generally, reduce 10% rated for per 1000 meters height.
See the Drawing 1-4.

Iout

100%

90%

80%
1000 2000 3000 4000米

Drawing 1-4 Derating Curve drawing of Frequency inverter


-6-
WL-9000 Series Sensor-Less Vector Frequency Converter

● Forbid to touch the radiator section or charging resistance by


hand, or else would be burned.
● Strictly forbid to install the switch devices, like contactor, at the
input side of frequency converter and stop or start frequently. Since
the main circuit of frequency converter includes stronger charging
current and would produce heat-accumulation effect, make the
components be heat-fatigue, shorten the life of frequency converter.
See the Drawing 1-5

Drawing 1-5

● If any smoking, peculiar smell or noise happen, please cut off


the power souce immediately, and examine it or get help from agent.
Forced

1.6 Attention for Scrapped items

● The chemical condenser of frequency converter may cause


explosion when be burned. Please treat it well.
● The Operation keyboard and other plastic materials would
Warning
produce toxic gas when be burned , please treat well .

● Dispose of the frequency converter as Industrial waster


Attention

-7-
WL-9000 Series Sensor-Less Vector Frequency Converter

Chapter 2 Inspect After Buying and


Specifications of Frequency Converter
2.1 Open package Inspect
Please check-up the following items before openpackage.
z Whether the outer casing or components are damaged or fall off .
z Check the rated value on the nameplate at side of product, whether it is the
same as your order.
z Whether all things listed in packing list are well-appointed
If any questions, please contact with supplier.

2.2 Model explanation of Frequency Inverter

-8-
WL-9000 Series Sensor-Less Vector Frequency Converter

2.3 Nameplate explanation


At the riht side of frequency inverter`s outer casing, there is the nameplate which
writes the model and rated values of frequency inverter . As the following:

Drawing 2-2 Nameplate of Frequency Inverter

Chapter 3 Product illustration


3.1 Product Character
WL-9000 series Frequency Inverter is a kind of power converter which adopts the
noninductive vector technique and change the running speed of AC asynchronous
motor by controlled the output voltage and frequency. It can exactly detect the
three-phase output AC signal and the change of phase angle just by current sensor, and
correct the frequency automatically by the computing mode of noninductive vector, so
that ensure the motor fixed speed when the load changing.
z Built-in parameter auto-tuning function,can automatically identify the
characteristic of motor and set up related parameter, make the motor run
continualy steadily even when the operating parameter of motor changes as times
go by .
z Protection function in all fields: protection of under-voltage, over-voltage,
over-current, prevention of motor stall, over-load and over-heat.
z Standard V/F mode, Noninductive vector mode, Output power(torque) contol
mode.

-9-
WL-9000 Series Sensor-Less Vector Frequency Converter

z Control function special for industrial mechanic : 6 kinds of multifunction


programmable digital input function (99 kinds of functions are optional); 3
kinds of multifunction programmable digital output function (94 kinds of
function are optional); Timer and counter, Rotation speed trace function,
flip-flop function, Automatic operating function, Built-in RS485
communication interface .One or more frequency converters can be
dynamical controlled by one computer at the same time, besides that, one
computer may simultaneously control nearly 99 sets of converters (Relay
amplifier must be installed when the numbers of converters exceed 31 units );
Built-in PID function .The range of output frequency is 0.00~650.00Hz.
z Adopts low inductance structure, reduce the peak voltage of circuit,
strengthen the EMC function, improve the reliability of product greatly.

3.2 Outline dimensions


-10-
WL-9000 Series Sensor-Less Vector Frequency Converter

-11-
WL-9000 Series Sensor-Less Vector Frequency Converter

3.3 Technical parameter and specifiations


Form 3-1
Explanation form of technical parameter and specifications

-12-
WL-9000 Series Sensor-Less Vector Frequency Converter

Chapter 4 Installation and Wiring of


Frequency Inverter
4.1 Installation of frequency inverter

Customers must install no-fuse or leakage Circuit breaker to


protect the cicuit and avoid broaden the scope of accident because

Forced of fault of fault of product.

Has two installation way, units under 75KW are wall hanging type, and above
90KW are Floor cubical type.

-13-
WL-9000 Series Sensor-Less Vector Frequency Converter

z The higher ambient termperature is, the shorter frequency


converter`s life is.
z If there has thermal device near frequency converter, please
Attention
remove away. And if frequency converter is installed inside a
case, should consider the verticality and space.

Do not use the product with failure or lack components


Make sure the cables are connected securely with the main-circuit
terminals, or else would cause damage to the poduct because of poor
cantact .
Warning The earth terminals of frequency converter must be reliable
ground connection .In case of the affect from anti-interference of earth
resistant, several frequency inverters should be earthed by one point.

4.2 Dismounting and Installation for Spare parts


4.2.1 Dismounting and installation for operation key-board

-14-
WL-9000 Series Sensor-Less Vector Frequency Converter

4.3 The wiring of frequency inverter


4.3.1 Attentions :

z Only 10 minutes after the power source be cut off completely,


then allowed to open the cover of converter.
z Ensure the charging lamp at the under riht corner of main-circuit
terminals has been went out. Only the voltage value between
main-circuit terminals P+,P- is under 36VDC, then allowed to do the
innter wiring.
z Only the special and trained persons would do the Inner wiring
for frequency converter.

● Besides terminals TA, TB, TC, Strictly forbid to connect other


control terminals with 220V power source, otherwise would mak the
converter breakdown.
Declare again , could not connect the AC power source to output
terminals U,V, W .

z Check whether the rated input voltage is the same as power


source voltage. Or else would damage to frequency converter.
z Install in proper order, install the main body first,and then do
wiring ,in case of electric shock or damage to frequency converter.
z The product has been through pressure test, customer could not
do test again.
Customers must install no-fuse or leakage Circuit breaker to
protect the cicuit and avoid the broden the scope of accident because
of fault of fault of product.
z Must connect the earth terminal of frequency converter and
ourter case of motor to the earthed line. The earthed line should be
copper coil,section should larger than 4mm2 , and earthed resistance
must less than 10Ω.

-15-
WL-9000 Series Sensor-Less Vector Frequency Converter

4.3.2 Explanation of Main-circuit terminals and wiring


Form 4-2 Function Explanation of main-circuit terminals
Terminal
Function explanation
code
AC power source input terminals, when singal phase input, just connect to R
R. S. T
and T ends.
U, V, W Frequency Converter output terminals,connect to 3-phase AC motor
Connection terminals of DC Reactor,one end to P1,and another end to P+.
P, P+ (units above 18.5KW, and if no DC reactor, just connect P1, P+ as
short-circuit )
B Connection terminals of braking units.
DC power source Negative Pole, units of 18.5~75KW have this terminal, and
N-
could connect with braking unit together with P+ terminal.
E Earthed terminal
4.3.3 Main-circuit Terminals

Braking Resistant(Option)
Main-circuit terminals of 0.75-2.2KW

-16-
WL-9000 Series Sensor-Less Vector Frequency Converter

Braking Resistant (Option)


Main-circuit terminals of 3.7-15KW

Main-circuit terminals of 18.5-45KW

-17-
WL-9000 Series Sensor-Less Vector Frequency Converter

Main-circuit terminals of 55-355KW


4.3.4 Connection Diagram

-18-
WL-9000 Series Sensor-Less Vector Frequency Converter

z R. S. T. are input terminals.


z Please add a suitable circuit breaker between power-source and
frequency inverter, to ensure the system safe.
z There are many alive electronic components which would be
Warning broken down by static electricity on the control plate, so please
do not touch control plate.
z When wiring, please lock the screws on terminals.
z Please be earthed.

Output terminals from frequency inverter to motor


z Can not add any AC Contactor between frequency inverter and
motor.
Warning z Must connect U, V, W terminals to motor directly.

DC main-wire or braking unit output terminals


z Some units of frequency inverter have no braking units. Users
Attention could connect +,-ends of DC main-wire to P and N terminals
directly, and then add some braking resistants.
z Some units of frequency inverter have braking units, users could
connect P and B terminals to outer braking resistant directly.

4.3.5 Function explanation of Control-circuit Terminals

Small Control Plate


-19-
WL-9000 Series Sensor-Less Vector Frequency Converter

Big control plate

-20-
WL-9000 Series Sensor-Less Vector Frequency Converter

4.3.6 Function explanation of Control-circuit Terminals


Terminal
Type Function Explanation Remark
Code
Analog input interface 1, Ajust the minimum input value by F89.
AI1 choose 0-5V or 10V input Ajust the maximum input value by F90
by through JP2 That is ajust analog input gain.

Analog input interface 2, Ajust the minimum input value by F91.


AI2 choose 0-5V or 4-20mA Ajust the maximum input value by F92
input by through JP3 That is ajust analog input gain.

Analog input 3, choose the


third analog input interface
Analog The ex-factory value is “keyboard
or keyboard potentiometer
AI3 potentiometer input effective”, and AI3
voltage analog input effect by close.
input through jumping wire at side
of JP3

10V Supply 10V,10mA power


source to outside

1, Public end when 0-10V or


0-5V input
2,-end when 4-20mA input
ACOM 3, Public end when 0-5V
output
4, Public place of 0-10V
output
Analog output terminal
0-5V. The output voltage
wave of AM terminal is
PWM wave which is from
Analog CPU.The output voltage By through PR37 and PR38 to choose
AM
output value varies directly as the different output.
width of PWM wave. And
even PWM wave is first
filtrated by inside resistant R
and capacitor C.
Ajust the minimum input value by F89.
0-1A Ajust the maximum input value by F90
P+ pressure current signal +
current That is ajust analog input gain. P and AI1
pressure current signal _
input input to channel together, and by J3 to
P- choose P or AI1 input.

-21-
WL-9000 Series Sensor-Less Vector Frequency Converter

Ajust the minimum input value by F91.


F+ Ajust the maximum input value by F92
Flow rate current signal + That is ajust analog input gain. F and AI2
Flow rate current signal _
F- input to channel together, and by J2 to
choose F or AI2 input.
1, Public end when 0-10V or
0-5V input
2,-end when 4-20mA input
ACOM 3, Public end when 0-5V
output
4, Public place of 0-10V
output
Multi-function digital input,
X1 by through PR41 to choose
0-99 kinds of multi-function
input
Multi-function digital input,
X2 by through PR42 to choose
0-99 kinds of multi-function
input
Multi-function digital input,
X3 by through PR43 to choose
0-99 kinds of multi-function
input
Multi- Multi-function digital input,
function X4 by through PR44 to choose
0-99 kinds of multi-function
control input
terminal
X5 Multi-function digital input, by through PR45 to choose 0-99 kinds of
(RUN) multi-function input. Ex-factory value is 73, and short-circuit with
DCOM to be Forward running.

X6 Multi-function digital input, by through PR46 to choose 0-99 kinds of


(REV) multi-function input. Ex-factory value is 74, and short-circuit with
DCOM to be Reversed running.

RST RST is used to reset frequency inverter, under any situation, when RST
and DCOM are short-circuit, will reset inverter forcedly.

Digital Multi-function collector output 1, by through F45 to choose 0-99 kinds of


DO1
output multi-function output.

-22-
WL-9000 Series Sensor-Less Vector Frequency Converter

DCOM
Public end of digital place X1-X6,
RST, D01, D02+24V

TC1 Multi-function collector NO and NC output 1, by through F47 to choose


0-99 kinds of multi-function output, Ex-factory value is 4, fault warning
ouput.
TA1 Please use 24V low-voltage system in case of jamming.
Switched

output
TC2
Multi-function collector NO and NC output 2, by through F46 to choose
0-99 kinds of multi-function output.
Please use 24V low-voltage system in case of jamming.
TB2

Power
24V 24/50mA
output

4.3.6 Interface distribution of control panel and jumper-wire set


Before using the frequency converter,should correctly set all jumper-wiring
terminals on the control panel,and make sure every connection to interface fixed.The
functions of jumper-wiring terminals are as the following ,and refer to the real unit.
1. JP1 decides the characteristic of terminal AI1
If the outer analogy voltage is 0~10V input, please use input terminal AI1, and
choos the JP1 to position +10V.
If the outer analogy voltage is 0~5V input, please use input terminal AI1, and
choos the JP1 to position +5V.
【Attention】The ex-factory value of AI1 is set as +10V
2. JP2 decides the characteristic of terminal AI2
If the outer analogy voltage is 0~5V input, please use input terminal AI2, and
choos the JP2 to position +5V.
If the outer analogy current signal is 0~20mA input, please use input terminal

-23-
WL-9000 Series Sensor-Less Vector Frequency Converter

AI2, and choos the JP2 to position 20mA.


【Attention】The ex-factory value of AI2 is set as 20mA
J2 is used to choose analog input AI1 and F flow rate signal.
If is frequency inverter special for Injection Molding Machine, please choose J2 to be F
position, and make 0-1A flow rate signal as the first circuit signal input.
J3 is used to choose analog input AI2 and P pressure signal.
If is frequency inverter special for Injection Molding Machine, please choose J3 to be P
position, and make 0-1A pressure signal as the first circuit signal input.
3. JP3 decides the characteristic of terminal AI3
If you use the keyboard potentiometer, please choose JP3 to PAN position
If the outer analogy voltage is 0~5V input, could use input terminal AI3, and
choos the JP3 to position TER. (TER is for short of “terminal” )
【Attention】The ex-factory position of AI3 is PAN (PAN is for short of “panel”)
6. JP6 decides the characteristic of terminal resistance
When JP6(1~2)is short-circuit, with terminal resistance
When JP6(2~3)is short-circuit, not with terminal resistance.

Ex-factory set way of Jumping wire terminals

-24-
WL-9000 Series Sensor-Less Vector Frequency Converter

4.4 The Basic wiring of frequency inverter

The connection drawing among frequency inverter and optional drives

-25-
WL-9000 Series Sensor-Less Vector Frequency Converter

Circuit breaker has function of over-current protection, and avoid the fault of
following connected equipments extend. Please note the capacity when install the
circuit breaker.
Electromagnetic contactor is used to cut off the main power source when
frequency converter in trouble,and prevent power-fail or restart after fault.
Input AC Reactor could reduce influence caused by 3-phase unbalanced, raise
the input power factor of frequency converter, and reduce the damage to rectifier circuit
when the frequency converter connects with large-capacity motor. If the following
situation happen,it is necessary to match the AC Reactor:
① The degree of unbalancedness of power source over 3%
② The capacity of power source is at least 500KVA,and more ten times than the
capacity of frequency converter.
③The network voltage Suddenly changes because the power factor compensation
capacitor switch on or off.
Advice to install the Reactor of 3%(Voltage dropping under the rated current)
z Input&Output EMI filter is used to reduce electromagnetic or radio frequency
interference (RFI) produced by electric network or frequency converter.
z Braking groups are used to consume the energy which is feedback from the load
with large pontential or inertia to frequency converter, avoid the frequency converter
tripping because of pump rising voltage overtop.Even it can stop motor quickly.
z Output AC Reactor could filter the higher harmonic component in the output
current of frequency converter, and reduce the electromagnetic interference caused by
higher harmonic. At one time, could improve the current waveform, reduce operating
noise and termperature rise of motor,ensure the motor run steadily.Overmore,when the
motor cable is longer, please install output reactor.

-26-
WL-9000 Series Sensor-Less Vector Frequency Converter

Chapter 5 Opteration and Running

5.1 Operation Introduction


WL-8000 series frequency inverter supply kinds of operation and display methods
for user.
Units below 37KW select WL001 keyboard.
Units above 45KW select WL002 keyboard.
5.1.1 Introduction of Keyboard

WL-001 keyboard WL-002 keyboard

-27-
WL-9000 Series Sensor-Less Vector Frequency Converter

5.1.2 The explanation of function keys

When be keyboard control mode (F039=0), The REV key is effect

Increasing key: Increasing of datas or parameter code

Decreasing key: decreasing of datas or parameter code

Stop/Reset key: When be operating state,this key is for stopping


operation; When be Fault display state (0- -), be used to clearup
fault,and reset; When Read/Write operation, press this key to
move remending position.

Readout/writein key: for reading the parameter value or confirm


the datas write-in effectly.

5.1.3 The function explanation of state indication lamp


Hz: The lamp lighting when LED displays data of frequency
I: The lamp lighting when LED displays data of current
FWD:The lamp lighting when frequency inverter is forward running.
REV:The lamp lighting when frequency inverter is reverse running.。
5.1.4 The operational mode of keyboard
There are 4 kinds of operational mode:
① Control operating mode

Press“ ”key, Could choose one operational mode between“Control

operating mode”and “Monitor operating mode”.


When “Hz”and“I” LED is not lighting,means “Control operating mode”.
-28-
WL-9000 Series Sensor-Less Vector Frequency Converter

The user could control the running direction of frequency converter and adjust the
operation frequency.
When the jumper-wire JP3 of V3 is at the PAN position,and F040 frequency is
set as 25, means adjust speed by keyboard potentiometer.
Function of pressing keys :

For controlling forward running of frequency inverter

For controlling reverse running of frequency converter

For stopping frequency converter

When F040=3 or 8, change the operational frequency directly by pressing key.


When F040=8, the set frequency write in F000 directly.

Key,Read out information of F000.(Minimum value is set value of F016)

Key,For moving the cursor.

Key, to raise the operational frequency or change the information read out by

F000

Key to reduce the operational frequency or change the information read out by

F000
② Monitor operating mode

Press“ ”key, Choose one mode between “control operating mode”and

“Monitor operating mode”.By “Monitor operating mode”,user could monitor two kinds

of data (such as,operational frequency Hz”,”output current I”)easily, and could control

-29-
WL-9000 Series Sensor-Less Vector Frequency Converter

the forward running, reserve running and stopping of frequency converter.

When lamp of “HZ”lighting,the frequency converter is “Monitor operating

mode”and the LED display shows “Hz”information.(Or choose other information

decided by F099.Introducted in Chapte 6.2 ).

When lamp of “I”lighting,the frequency converter is “Monitor operating

mode”and the LED display shows “I”information.(Or choose other information

decided by F098.Introducted in Chapte 6.2 ).

Function of pressing keys :

Key,For controlling forward running of frequency converter

Key, For controlling reverse running of frequency converter.

Key,For stopping frequency converter

Key,Choose “Hz” or “I” information

Key,Choose “Hz” or “I” information

③ Parameter remending mode

Press“ ”key, Change over between “parameter remending mode” and “fault

display mode”. If LED display shows “Fnnn”,frequency converter is in “parameter


remending mode”, Lamps of “Hz”and“I”lighting at the same time,users could remend
or monitor all inner parameter. The operating steps to remend parameter are as the
following:

-30-
WL-9000 Series Sensor-Less Vector Frequency Converter

Step 1:Press“ ”Key, LED display shows “Fnnn”,nnn is parameter No.

Step 2:Press or key to choose parameter No.needed, press“ ”

key to move the cursor.

Step 3:Press“ ”key to read the content value of set parameter, and LED

display now shows parater content value.

Step 4:Press or key to remend the parameter value,press“ ”

key to move the cursor position.

Step 5:press“ ”key , Write the numerical value into the “EPROM”

memorizer.If need to remend, operate according to the above steps.


④ Fault display mode

Press“ ”key, Change over between “parameter remending mode” and

“fault display mode”.


If LED display shows “0. xx”, frequency converter is in “fault display mode”,
user could monitor the trouble state or execute the reset function .

Press or key to could examine reasons of the recent 4

kinds of fault.

Press“ ”key,frequency converter would reset.

-31-
WL-9000 Series Sensor-Less Vector Frequency Converter

5.1.5 Using of operation keyboard

① Change the parameter value of function code (change the parameter value of F002
from 10S to 5S)
Operation step LEDdisplay State indication
Mode before operating 0.00 HZ、I lamps go out

F000 HZ、I lamps light


press key one time

F002 HZ、I lamps light


press key to F002

10.0 HZ、I lamps light


press key one time (read out)

5.0 HZ、I lamps light


Press key to 5.0

5.0 HZ、I lamps light


press key one time (write in )

press key return to control 0.00 HZ、I lamps go out


operating mode

② The correspondence between the displayed code of parameter F063、F064、F065


and the state of outer input output terminals is as the following:

0: means terminal input is inefficient.


1:means terminal input is availability.

-32-
WL-9000 Series Sensor-Less Vector Frequency Converter

5.2 Simple operating


5.2.1 Frquency inverter reset and set the ex-factory value of parameter
If the frequency converter is used for the first time, you could initialize the data to
ex-factory value if you are not sure about the parameter value.
First set F094 = 1,then change to ALM mode, shows “0. - -”. Press STOP key,
and could recover the ex-factory value. Or, set F094 = 1, connect RST terminal to
COM terminal, then frequency converter would reset and recover to ex-factory value.

z After initializing data, please refer to the parameter form on


Chapte 6 for the ex-factory value.
z If parameter type is R/W, would recover to ex-factory value.

5.2.2 Set the parameter of motor


Before starting up frequency converter, must
1. Set parameter of V/F curve .(refer to the function description of F009、F010、
F011、F015、F016 and F088 at this manul , or refer to the set form of fixed V/F
curve at this manul)
2. Set rated capacity of motor:
F078 = 100 % * (rated current of motor) / (rated current of frequency
inverter)

z Execute the parameter auto-tuning function ,would set F009


automatically.
Reminding

-33-
WL-9000 Series Sensor-Less Vector Frequency Converter

5.2.3 Parameter Auto-tuning


WL-9000 frequency inverter could automatically examine the characteristic of
motor and set its relational parameter. Before executing the parameter auto-tuning
function, need to set the following parameter:
F001: Acceleration time
F002: Deceleration time
F010: Rated frequency of motor(50.00Hz)
F011: Rate voltage of motor % (The voltage when motor running with rated
frequency)
F015: Upper limit frequency ,≥F010
F068:Noninductive vector voltage compensation , set as “0.0”
F078: Rated capacity of motor(%) = (rated current of motor/rated current of
frequency converter)
F088:Maximum output voltage (voltage when motor running with upper limit
frequency )
Parameter auto-tuning
1. Set F094 = 155

2. Press key to enter“0.- -”,then press key,frequency

converter executes parameter auto-tuning function.

5.2.4 The parameter set of auto-tuning


After executing parameter auto-tuning, the following parameter should be set
automatically according to tuning result
F009: Torque hoisting set
F067: Operating mode optional
If auto-tuning be successful, set F067 as “3”,choose noninductive vector
mode.
If auto-tuning be fail, set F067 as “1”,choose standard V/F mode.
-34-
WL-9000 Series Sensor-Less Vector Frequency Converter

F068: Noninductive vector voltage compensation coefficient


If auto-tuning successful, F068 is for noninductive vector voltage
compensation
F069: Noninductive vector frequency compensation coefficient
If auto-tuning successful, F069 is for noninductive vector frequency
compensation

5.2.5 Gain adjustment


When auto-tuning is wrong or need more exact compensation, users could remend
F069 according to description of 5.2.5.1 and 5.2.5.2

z Parameter = F1 . F2 is divided to two coefficients of F1,F2


by the base point.
Reminding
5.2.5.1 F1:Low-voltage phase compensation coefficient
Set F067 = 1 and F054 = 3 to make the motor run under 5% low-frequency(for
example: F010=50Hz,5%=2.5Hz ), read out the power angle of this frequency

(POWER ANGLE φ ), and account the value of F1 according to F1=50/tan( φ )

5.2.5.2 F2: High-speed load compensation coefficient


Set F067=3 to make the motor run under 50Hz high-speed, use tachometer to
measure the speed change when no-load and full-load, then adjust F2 value to reduce
the speed change caused by load change.

5.2.6 Monitor the operating state of frequency converter


Parameter F099 and F098 are for selecting the parameter needed be monitored .
First inter MON MODE, when any lamp of Hz and I lamps lighting, frequency
converter is in Monitor mode. Under this mode, could monitor either two parameter
value.
▲ and ▼ keys are for choosing the parameter needed to display

-35-
WL-9000 Series Sensor-Less Vector Frequency Converter

When both Hz and I lamps are out, frequency converter is in CTL MODE.

5.2.7 Wiring, and checking before electrifying


Wiring,and check power source normally,close the circuit breaker and electrify the
frequency converter.The display will first show “2000”,as following is frequency value
“0.00”,this moment frequency converter finishes initializing. If the keyboard could not
display ,it means electrifying is fail, please open the circuit breaker and check the
reason. Drawing 5-3 is simple operating wiring.

z Please cut off power source when checking, in case of electric


shock

Simple Operating Connection

-36-
WL-9000 Series Sensor-Less Vector Frequency Converter

5.2.8 Operate on the keyboard to set frequency, FWD/REV running, start or stop

5.2.9 After simple operating, please check as following :


z Whether the motor running direction is right;
z Whether the frequency converter trips when deceleration or acceleration
running ;
z Check whether speed and frequency value are right when motor runs;
z Whether any unormal vibration or noise happens to motor;
If the above situation happens, please adjust according to the Manual or get help .

-37-
WL-9000 Series Sensor-Less Vector Frequency Converter

Reminding
Kinds of often used control ways and paratmeter set
1. Use Keyboard panel to opearate stopping , F000 set frequency :
1) Parameter set:set F039 as 0.0 set F040 as 0.08
2) Start & stop: press “FWD”is forward running,press“REV”is reverse
running,press“STOP”key to stop frequency converter.
3) Frequency set: Change value of F000 under the Control mode to change
the frequency .
2. Use Keyboard panel to operate stopping, keyboard potentiometer set frequency :
1) Parameter set :set F039 as 0.0 Set F040 as 25.08
2) Start & stop:Press“FWD”key is forward running,press“REV”keyis
reserve running,press“STOP”key to stop frequency converter.
3) Frequency set: Turn the potentiometer on keyboard to change frequency .
3. Use control terminals to operate stopping, connect external potentiometer speed
adjustment.
1) Parameter set:set F039 as 2.0 set F040 as 1.08
2) Start & stop:When FWD~COM closing is forward running,when
REV~COM closing is reserve running. When FWD~COM or REV~
COM opening is stopping.
3) Frequency set:The frequency changes as voltage between RY1 and GND
changes.

-38-
WL-9000 Series Sensor-Less Vector Frequency Converter

Chapter 6 Explanation of function parameter


6.1 Simple list of function parameter
6-1 Parameter list of HPI6000 general type of frequency converter
Funcion Minimum Ex-factory
Name Set range type
code unit set

F000 Main speed frequency set 0.00Hz~650.00Hz 0.00Hz 50.00Hz R/W

F001 Acceleration time 0.1~6553.0 S 0.1S 10.0S R/W

F002 Deceleration time 0.1~6553.0S 0.1S 10.0S R/W

FWD ( DI5 ) Input terminal


F003 0~99 0 73 FR/W
function option
REV ( DI6 ) Input terminal
F004 0~99 0 74 FR/W
function option
Stopping DC braking original
F005 0.50~650.00Hz 0.50Hz 5.00Hz R/W
frequencty

F006 Stopping DC braking voltgae 0~30 % 0 5% R/W

Action time of stopping DC


F007 0.0~25.0S 0.0 1.0S R/W
brake
Delay-time of stopping DC
F008 0.0~1.0S 0.0 0.5S R/W
brake

F009 Torque hoisting set 0~30% 0 3% FR/W

F010 Motor rated frequency 0.50~650.00 Hz 0.50 Hz 50.00 Hz FR/W

F011 Motor rated voltage 30~100% 30 % 100 % FR/W

Maximum carrier-wave
F012 frequency/ turning point of 2.0~16.9 KHz 2.0 KHz Type set FR/W
carrier-wave Frequency

F013 String interval of Modbus 3~250ms 3ms 3ms FR/W

Temperature examining form


F014 0.0~999.9 0.0 440.8 FR/W
set

F015 Upper limit frequency 0.50~650.00 Hz 0.50 Hz 50.00 Hz FR/W

-39-
WL-9000 Series Sensor-Less Vector Frequency Converter

Funcion Minimum Ex-factory


Name Set range type
code unit set

F016 Lower limit frequency 0.00~650.00 Hz 0.00 Hz 0.00 Hz FR/W

F017 Jumping frequency 0.00~650.00 Hz 0.00 Hz 0.00 Hz R/W

F018 Range of jumping frequency 0.00~5.00 Hz 0.00 Hz 0.00 Hz R/W

F019 Inching frequency 0.00~650.00 Hz 0.00 Hz 10.00 Hz R/W

Ac/deceleration time of
F020 0.1~25.0S 0.1S 10.0S R/W
inching frequency

F021 Step 1 operating frequency 0.00~650.00 Hz 0.00 Hz 0.00 Hz R/W

F022 Step 1 acceleration time 0.1~6553.0S 0.1S 10.0S R/W

F023 Step 1 deceleration time 0.1~6553.0S 0.1S 10.0S R/W

F024 Step 2 operating frequency 0.00~650.00 Hz 0.00 Hz 0.00 Hz R/W

F025 Step 2 acceleration time 0.1~6553.0S 0.1S 10.0S R/W

F026 Step 2 deceleration time 0.1~6553.0S 0.1S 10.0S R/W

F027 Step 3 operating frequency 0.00~650.00 Hz 0.00 Hz 0.00 Hz R/W

F028 Step 3 acceleration time 0.1~6553.0S 0.1S 10.0S R/W

F029 Step 3 deceleration time 0.1~6553.0S 0.1S 10.0S R/W

F030 Stop way 0~1 0 0 R/W

F031 Forbidding REV 0~1 0 0 R/W

Power factor/
F032 50.00~99.99 50.00 85.20 FR/W
filtering constant
Starting discharge
F033 0~2 0 0 R/W
braking circuit

Restart after
F034 0~1 0 0 R/W
Low (over)voltage fault

-40-
WL-9000 Series Sensor-Less Vector Frequency Converter

Funcion Minimum Ex-factory


Name Set range type
code unit set
over-current point of motor
F035 10~200 10 200 % R/W
stall

F036 Intermit output time 0.1~5.0S 0.1S 0.5S R/W

F037 Analogy output AM 0~17 0 0 R/W

F038 Analogy output AM gain 0~255 0 255 R/W

F039 Operating control way option 0.0~9.9 0.0 0.0 R/W

F040 Frequency set option 0.00~99.99 0.00 8.08 R/W

Function option of DI1 input


F041 0~99 0 0 R/W
terminal
Function option of DI2 input
F042 0~99 0 0 R/W
terminal
Function option of DI3 input
F043 0~99 0 0 R/W
terminal
Function option of DI4 input
F044 0~99 0 0 R/W
terminal
Function option of open
F045 0~99 0 0 R/W
circuit collector output DO1
Function option of open
F046 0~99 0 0 R/W
circuit collector output DO2
Function option of relay
F047 0~99 0 4 R/W
output terminal
Output current checking
F048 0~150% 0 100 % R/W
level

F049 Frequency checking level 0.00~650.00 Hz 0.00 Hz 30.00 Hz R/W

Allowed range of frequency


F050 0.00~25.0 Hz 0.00 Hz 5.0 Hz R/W
checking
Action time of electronic
F051 0~120S 0 60S R/W
thermal relay

F052 Poles of motor 2~12 poles 2poles 4poles FR/W

F053 Proportion of gear wheel 0~250% 0 100 % R/W

-41-
WL-9000 Series Sensor-Less Vector Frequency Converter

Funcion Minimum Ex-factory


Name Set range type
code unit set

F054 Monitor mode option 0~250 0 0 R/W

Analogy convertr input signal


F055 0~250 0 0 R/W
option
Analogy converter output
F056 0~1023 0 M
information

F057 Output frequency(Hz) 0.00~650.00 Hz 0.00 Hz Hz M

F058 Output speed (rpm) 0 rpm rpm/ Krpm M

F059 DC bus-bar voltage Vdc M

F060 Output voltage Vrms M

Current and others state


F061 M
display

F062 Temperature of radiator 0~100℃ ℃ M

F063 Digital input terminal state 0.0.0.0~1.1.1.1 0.0.0.0 0.0.0.0 M

F064 Control terminal state 0.0.~1.1 0.0. 0.0. M

F065 Digital output terminal state 0.0.0~1.1.1 0.0.0 0.0.0 M

F066 Keep down

F067 Operating mode option 0~4 0 1 FR/W

Noninductive vector voltage


F068 0~30 0 10 FR/W
compensation
Slippage compensation
F069 0.0~99.99 0.0 50.50 % FR/W
coefficient F1/F2

F070 Analogy input gain 0.0~100 0.0 50 % R/W

F071 Action time of TIMER 0.2~6553.0 0.2 5.0S R/W

Simple PLC auto-operating


F072 0~6 0 0 R/W
option

-42-
WL-9000 Series Sensor-Less Vector Frequency Converter

Funcion Minimum Ex-factory


Name Set range type
code unit set
The first period time set of
F073 0.1~6553.0S 0.1S 15.0S R/W
atuo-operating
The second period time set of
F074 0.1~6553.0S 0.1S 15.0S R/W
atuo-operating
The third period time set of
F075 0.1~6553.0S 0.1S 15.0S R/W
atuo-operating
The fourth period time set of
F076 0.1~6553.0S 0.1S 15.0S R/W
atuo-operating
The fifth period time set of
F077 0.1~6553.0S 0.1S 15.0S R/W
atuo-operating

F078 Rated capacity of motor 10~100 % 10 100 % FR/W

F079 Restart way option 0~3 0 0 R/W

F080 Speed searching action level 10~200 % 10 150 % R/W

Deceleration when speed


F081 0.1~25.0S 0.1S 2.0S R/W
searching
Time of voltage recovering
F082 0.1~5.0S 0.1 0.5S R/W
when speed searching

F083 IGBT protection time 2.0~25.0us 2.0us 3.0us FR/W

F084 Input AC voltage 40~1000 V 40 380V FR/W

Rated current of frequency


F085 0.5~3000.0 A 0.5 机型设定 FR/W
converter
Gain adjustment of current
F086 70~140 70 100 FR/W
displayed value
Gain adjustment of voltage
F087 70~140 70 100 FR/W
displayed value

F088 Maximum output voltage 30~100 30 100 % FR/W

Lowest value of AI1 terminal


F089 0~1023 0 12 FR/W
input
Maximum value of AI1 terminal
F090 0~1023 0 1012 FR/W
input
Lowest value of AI2 terminal
F091 0~1023 0 12 FR/W
input

-43-
WL-9000 Series Sensor-Less Vector Frequency Converter

Funcion Minimum Ex-factory


Name Set range type
code unit set

Maximum value of AI2 terminal


F092 0~1023 0 780 FR/W
input

Communication form/
F093 0.01~99.99 0.01 0.01 FR/W
Communication address

F094 Data initialize 0~250 0 0 R/W

F095 Parameter write-protect 0~2 0 0 R/W

F096 Open special parameter set 0~1 0 0 R/W

F097 Software version Type set R

Parameter needed monitor when


F098 0~99 0 61 R/W
I lamp lighting

Parameter needed monitor when


F099 0~99 0 57 R/W
Hz lamp lighting

z Parameter type R/W means this parameter is kept in


EPROM and could be written and read .
z Parameter type FR/W means this parameter is special type
controlled by factory, and is kept in EPROM and written and
Reminding read. This parameter could not be changed only allowed by
engineer.
z Parameter M means this parameter is for monitoring the state
of frequency converter,and no any influence when be written.
z Parameter type R means this parameter is fixed constant.

-44-
WL-9000 Series Sensor-Less Vector Frequency Converter

6.2 Detailed explanation of parameter function

F000 Main speed frequency set Set range:0.00 ~ 650.00Hz


F000 is the main operational frequency set inside the CPU. When F040 is set as “0”,
this parameter is for frequency source.

z When operational set is CTL mode,the information read out or


written in always point to this parameter.
Reminding

F001 Acceleration time Set range:0~6553.0 S


F002 Deceleration time Set range:0~6553.0 S
When F000 is assigned as operational frequency, the acceleration and deceleration
time are assigned separately by F001 and F002 .

z Accerelation time is set as[The time of accerelation from


0Hz to upper limit frequency of F015 ], see t1 in the
Reminding drawing 6-1.
z Deceleration time is set as[The time of output frequency
from upper limit frequency of F015 to 0Hz. see t2 in the
drawing 6-1.

Drawing 6-1 Acceleration & deceleration time drawing

-45-
WL-9000 Series Sensor-Less Vector Frequency Converter

F003 FWD(DI5)Input terminal function option Set range:0~99


F004 REV(DI6)Input terminal function option Set range:0~99
F003 defines the function of digital input terminal X5. Ex-factory is “73”,is
defined as FWD function .
F004 defines the function of digital input terminal X6. Ex-factory is “74”,is
defined as REV function .

z DI5,DI6 terminals is marked as FWD、REV .

F005 :Stopping DC braking original frequency Set range:0.5~650.0Hz


F006 : Stopping DC braking voltage Set range:0~30%
F007 : Action time of stopping DC brake Set range:0.0~25.0 S
F008 : Delay time of stopping DC brake Set range:0~1.0 S

z This group of parameter is used to define the DC braking


function when stopping. The DC braking function could
supply zero-speed torque and be used to improve the
accuracy of stopping,but not for deceleration braking under
Reminding normal operating.
z If the DC braking voltage is over set, fault of over-current
would happen to frequency converter easily when stopping.

F005: In process of stopping,if the output frequency is lower than stopping DC


braking original frequency, the frequency converter would start up DC braking
function.Inject direct current to motor and brake motor .
F006:When DC braking is started up, use the following formulat to define the
percent of DC input voltage:
Output voltage = Rated voltage of motor × F006
F007:Means the continuous time of DC braking, and after this time,the DC
braking voltage cancels rightly. When F007 is 0, the DC braking function is close when
stopping.
-46-
WL-9000 Series Sensor-Less Vector Frequency Converter

F008: When deceleration braking,if output frequency is less than stopping DC


braking original frequency, the output voltage would fall to the stopping DC braking
voltage(F006).After the delay time of stopping DC braking , would inject DC braking
to motor.

The relation among frequency, ouput voltage and time during braking

F009 Torque hoisting set Set range:0~30%


When output frequency is lower, this parameter decides the minimum output
voltage to hoist torque.
Please use this parameter cautiously:
z After executing parameter auto-tuning,the torque hoisting would
be set automatically.
z The effect of heat-radiation of motor which runs under
low-frequency for long time would be poorer, and if torque
hoisting set over high at this moment, may burn up motor .Please
Warning must use exterior forced radiation or derating application.
z For the application of energy-saving, should set the low limit
frequency of F016, and check that the current should be Zero
when frequency converter runs under 0Hz.

-47-
WL-9000 Series Sensor-Less Vector Frequency Converter

F010 Rated frequency of motor Set range:0.50~650.00Hz


F011 Rated voltage of motor Set range:30~100%
The two parameter define the rated frequency and voltage of motor.

F012 Max carrier frequency/ turning point of carrier Set range:2.0~16.9


frequency

F012=XX.Y,includes “XX”and“Y”two groups of parameter, XX defines the


Max carrier frequency, Y defines the turning point of carrier frequency. The minimum
carrier frequency is fixed as 2KHz. For example: F012=12.5, means the max carrier
frequency is 12 KHz, and the turning point of carrier frequency is on operational
frequency of 5.00Hz. The carrier frequency could be changed over automatically when
running.

Turning point of carrier frequency

When operational more than the turning point of carrier frequency , carrier
frequency would be the set value of max carrier frequency, otherwise the carrier
-48-
WL-9000 Series Sensor-Less Vector Frequency Converter

frequency would adjust automatically between Max and Minimum carrier frequency
according to the operational frequency.

z If carrier frequency be set over low, the output current form


would be worse because the output current includes more high
harmonic, and lead to noisy, more lossing and rising termperature to
the motor. But the happened jamming and leakage current is little.
Attention z Raise the set value of carrier frequency, could reduce noise of
motor and improve the output current form. But the temperature of
frequency converter will rise because of picked-up loss of power
component switch. More leakage leads to strong jamming. If carrier
frequency is over than ex-factory value, please make frequency
converter derating used.

F013 Interval time of Modbus string Set range:3~250ms


When RS485 is defined as Modbus communication, this parameter defines the
max interval time of communication string.
F014 Examining form of termperature set Set range:0.00~999.9
Users please do not remind this parameter without allowed , which may lead
to fault of equipment.
F015 Upper limit frequency Set range:0.50~650.00Hz
F016 lower limit frequency Set range:0.00~650.00Hz
Upper limit frequency is Max output frequency within allowed range of
frequency converter (refer to F010)
Lower limit frequency is Minimum output frequency within allowed range of
frequency converter (refer to F010)
F017 Jumping frequency Set range:0.00~650.00Hz
F018 Range of jumping frequency Set range:0.00~5.00 Hz
Set F017 and F018 mainly to make frequency converter avoid from the resonance
frequency point of loading.

-49-
WL-9000 Series Sensor-Less Vector Frequency Converter

F019 Inching frequency Set range:0.00~650.00Hz


F020 Acceleration/deceleration time of Set range:0.1~25.0s
inching frequency
F019: This parameter decides the operational frequency when inching order asks for.
F020:This parameter decides acceleration/deceleration time when inching order asks
for.

z The inching frequency has the highest priority. Inching


frequency decides the operational frequency when inching
order asks for. When inching order input, frequency
Reminding converter would run under inching frequency according to
the set inching acceleration/deceleration time.

F021 Period 1 operational frequency Set range:0.00~650.00Hz


This parameter decides the operational frequency when the period 1 speed is
required.
F022 Period 1 accelereation time Set range:0.1~6553.0s
F023 Period 1 deceleration time Set range:0.1~6553.0s
This group parameter decides acceleration/deceleration time when frequency
converter executes the period 1 order.

-50-
WL-9000 Series Sensor-Less Vector Frequency Converter

F024 Period 2 operational frequency Set range :0.00~650.00Hz


This parameter decides the operational frequency when the period 2 speed is
required.
F025 Period 2 accelereation time Set range:0.1~6553.0s
F026 Period 2 deceleration time Set range:0.1~6553.0s
This group parameter decides acceleration/deceleration time when frequency
converter executes the period 2 order.
F027 Period 3 operational frequency Set range:0.00~650.00Hz
This parameter decides the operational frequency when the period 3 speed is
required.
When applying PID function, please refer to the description of Chapter 8.
F028 Period 3 accelereation time Set range:0.1~6553.0s
F029 Period 3 deceleration time Set range:0.1~6553.0s
This group parameter decides acceleration/deceleration time when frequency
converter executes the period 3 order.
F030 Stopping way Set range: 0~1
0 : When frequency converter receives stopping order, will reduce output
frequency gradually according to the set deceleration form and time, stops up to 0Hz.
1: Frequency converter stops frequency output rightly when it receives stopping
order. The loading stops freely according to mechanical inertia.
F031 Forbid reverse running Set range:0~1
0: Frequency converter could both forward run and reverse run.
1: Frequency converter could only forward run , but not reserve run.
F032 Frequency factor/ filter constant Set range:50.00~99.99
Parameter F032=aa.bb,be comparted by base point as two parameter.Normally
do not need to remend this parameter.
aa:Power factor of motor set according to name plate of motor.
bb:Noninductive vector compensation filter constant.

-51-
WL-9000 Series Sensor-Less Vector Frequency Converter

F033 Starting discharging brake circuit Set range:0~2

When F033=0, discharging brake circuit could not act .


When F033=1,the conditions of discharging brake circuit as the following:
a.Frequency inverter must in running,and
b.Have no fault warning,and
c.Frequency inverter is being deceleration,and
d.Frequency inverter examine the voltage of DC bus-bar over 117%, will
start up discharging braking module.
When F033=2, the conditions of discharging brake action as the following:
a. Frequency inverter must in running,and
b. Have no fault warning,and
c. Frequency inverter examines the voltage of DC bus-bar over 117%, will
start up discharging braking module.
F034 Reset after low(over)-voltage fault Set range: 0~1
This parameter sets the reset function after low/over-voltage of frequency
converter.
0:Frequency converter need to reset after recovering from low/over-voltage
fault.
1 : When input voltage is abnormity and causes fault trip,the frequency
converter would stop output rightly , and will start up automatically after the latency
time set by F036 when the voltage recovers to normal, then executes the speed trace
ascertained by F079.

z Should adopt speed trace function under this way (set F079 as 1, 2
or 3), otherwise will lead to over-current/voltage protection.
z Please use the reset after outage function carefully, since this
function may make frequency inverter start up automatically when
be discharged and be danger to persons and equipments.

-52-
WL-9000 Series Sensor-Less Vector Frequency Converter

F035 Stall over-current point Set range: 10~200%


Frequency inverter begins to execute auto-lowering speed to prevent motor stall,
when the current overruns the percent of F035 (frequency converter rate).
F036 Pause output time Set range:0.1~5.0 S
When UP/OP warning happens or pause-output be needed, F036 will define the
least needed time of pause output, and after this time, frequency converter could be
allowed to restart.
F037 Analogy output AM Set range:0~17
F038 Analogy output AM gain Set range:0~255
F037 choose the signal need output through AM terminal.
F038 is for adjusting size of AM signal.
Folloiwng form lists the types of signal could output through AM terminal
F037 Output signal of AM Output proportion

terminal

0 Output frequency 5V * F057 / ( F015 )

1 Keep down

2 Voltage of DC bus-bar 5V * F059 / 1000

3 Output voltage 5V * F060 / ( 2 * F084 )

4~6 Keep down

7 PID output AM=5V*(PID output)

8 PID+AI1 bias input When Xn(54)ON,5V*(PID gain *(PID output +PID


bias * AI1)),When Xn(54)OFF,5V*(PID output)
9 PID+AI2 bias input When Xn(54)ON,5V*(PID gain *(PID output +PID
bias *AI2)
),when Xn(54)OFF,5V*(PID output)
10 PID+AI3 bias input When Xn(54)ON, 5V*(PID gain *(PID output +PID
bias *AI3)
),when Xn(54)OFF,5V*(PID output)
11 PID+F028 bias input When Xn(54)ON,5V*(PID gain *(PID output +PID
bias * F028)),when Xn(54)OFF,5V*(PID output)
12 Could set output 5V * ( F038 / 255 )
voltage
13~16 Keep down

17 Radiator temperature 5V *(F062/100)

-53-
WL-9000 Series Sensor-Less Vector Frequency Converter

F039 Operating control ways option Set range:0.0~9.9


F039 is used to choose the types and ways that frequency converter receives
operaiting or stopping order
The most important step is choosing operating control ways before frequency
converter beginning to start up.
Operating control way option F039=a.b, contents two groups option of
“a”and“b”to be one parameter. When X1~X4(like: X1 is set as “89”) or X1~X4(like:
X1 is set as “90”) switch on, control order source option=“b”, orelse, control order
source option=“a”. Please refer to addenda instruction.
The control order of Forward/reverse running or stopping would be
F039=0
decided by keyboard controller.
z Press FWD key, frequency inverter is forward running.
z Press REV key, frequency inverter is reverse running.
z Press STOP key, frequency inverter will stop operating.
The control order of Forward/reverse running or stopping would be
F039=1 decided by the input state of FWD and REV terminal on the control
terminals.

z FWD terminal decides operating or stopping of frequency inverter.


z REV terminal decides running direction of frequency inverter.
The control order of Forward/reverse running or stopping would
F039=2 be decided by the input state of FWD and REV terminal on the
control terminals. But

z FWD terminal decides frequency inverter forward running.


z REV terminal decides frequency inverter reverse running.

-54-
WL-9000 Series Sensor-Less Vector Frequency Converter

Similar as F039=1 mode, but first check FWD must be OFF state
F039=3
before starting up.
Similar as F039=2 mode, but first check FWD and REV terminal
F039=4
must be OFF state before starting up.
When choose commmunitation form of WL-9000, the operating and
F039=5
stopping order are controlled by RS485 communication

F040 Frequency set option Set range:0.00~99.99


This parameter decides input source of operational frequency.
F040 = 0 Decided by numerical value of F000.
F040 = 1 Decided by input of AI1 JP1 decides(0~10V)or(0~5 V)
F040 = 2 Decided by input of AI2 JP2 decides(4~20mA)or(0~5 V)
F040 = 8 Directly decided by operation setter input.
F040 = 25 Keyboard potentiometer speed adjusting
F040 = 40 Decided by PID output

z Refer to description of section 6.3 for detailed.

F041 X1 terminal input function option Set range:0~99


F042 X2 terminal input function option Set range:0~99
F043 X3 terminal input function option Set range:0~99
F044 X4 terminal input function option Set range:0~99
X1、X2、X3、X4、FWD and REV terminals are multifunction digital input
terminals. The hardware and software function of above terminals are completely the
same. When input terminal is open-circuit, they are in “OFF”state.And when input
terminal and COM terminal are close(JP4 choose NPN),they will be “ON”state.Every
input terminal could choose special function.

-55-
WL-9000 Series Sensor-Less Vector Frequency Converter

z Refer to description of section 6.4 for detailed.

F045 Open-circuit collector output Y1 function option Set range:0~99


F046 Open-circuit collector output Y2 function option Set range:0~99
F047 Relay output terminal function option Set range:0~99

z Refer to description of section 6.5 for detailed.

F048 Output current detection level Set range:0~150%


Define the detection level of current picker module group.
F049 Frequency detection level Set range:0.00~650.00Hz
F050 Allowed range of frequency detection Set range:0.00~25.0
This group of parameter applys in digital ouput function of SPE、SPA、SPZ、SPO

z Refer to function description of section 6.5.

F051 Electronic thermal relay action time Set range:0~120S


The frequency converter contents electronic thermal relay. This parameter defines
over-load tripping time.If F051=0,the thermal relay does not act. If the rated capacitor
of frequency converter more than motor`s, adjust parameter F078 to protect the motor
exactly.
F052 Motor poles Set range:2~12P
F053 Gear wheel proportion Set range:0~100%
The set values of F052 and F053 are for computation of rpm(F058).
rpm=(120* output frequency(F057)/ motor poles(F052) * wheel
proportion(F053)%

-56-
WL-9000 Series Sensor-Less Vector Frequency Converter

F054 Monitor mode option Set range:0~250


Monitor mode(F054)uses to choose inner signal needed to monitor, and displayed
in F061 parameter.
0:Output current Irms(Ampere)
1:Output current Irms(Rated percent of frequency converter)
2:Output current Irms(Rated percent of motor)
3:Power angle θ(current phase delay angle)
4:Output powerVA= 3 ×Vrms×Irms
5:Power factor PF= COS(θ)
6:Watt(AC side)= 3 × Vrms×Irms × COSθ
7~9:keep down
10:Display the input power limit value set in advanced
11:Over-load accumulation level
32: Display time of timer when using timer function.
F055 Analogy plexer input signal option Set range:0~250
F056 Analogy plexer output information Set range :0~1023

F055 F056 Data contect after A/D transfer

0 Measured value of Vdc(DC bus-bar voltage)

1 Measured value of Iv

2 Measured value of Iw

3 Measured value of AI1

4 Measured value of AI2

5 Measured value of AI3

6 Measured value of temperature sensor

7 Keep down

8 When use RS485 communication interface to write in parameter, will display the

waited-but-be not written stroke number of EPROM .

9~31 Keep down

32 When use COUNTER function, display counter value.

-57-
WL-9000 Series Sensor-Less Vector Frequency Converter

F055 chooses the signal channel needed be detected, then transfer this analog
signal to digital signal information by the 10-bit A/D converter of CPU ,and at last
keep the transferred information into F056. The range of transferred information must
within 0~1023.
F057 Output frequency(Hz) Display range:0.00~650.00Hz
F058 Output rotate speed(rpm)
F059 DC bus-bar voltage (Vdc)
F060 Output voltage
F061 Current and other state display
F062 Temperature of radiator Display range:0~100℃
F057~F062 are used to monitor the operating state of frequency inverter.
F057: Display output frequency(Hz).Could read out the output frequency anytime.
F058: Display motor rotate speed(rpm).Output rotate speed could be computed by
frequency F057, motor poles F052, Gear wheel proportion F053 .
rpm=(120 * F057 / F052 ) * F053
When output rotate speed≥10000rpm,The display form on operational panel is
“xx.xx Krpm”
When output rotate speed≤9999rpm,The display form on operational panel is
“xxxx rpm”
F059: DC bus-bar voltage Vdc. Vdc is DC voltage Volt value measured from inner
capacitor
Vdc = 1.414 * Vac (input voltage)
F060: Output voltage Vrms. Vrms is root mean square value of frequency converter
output voltage.
F061: Output current Irms or other information. Please refer to F054 parameter set.
F062: Temperature of Raditor
Display the centigrade degree of inner radiator. When temperature overruns 45℃,
the fun operates continuely. And when be over 80℃, the frequency converter stops and
display “OH”fault.
-58-
WL-9000 Series Sensor-Less Vector Frequency Converter

F063 Digital input terminal state Set range:0.0.0.0~1.1.1.1


F064 control terminal state Set range:0.0.~1.1
F065 Digital output terminal state Set range:0.0.0~1.1.1
F063:Display X1~X4 digital input terminal state
F064: Display FWD and REV control terminal state
F065: Display Y1~Y2、TA, TC Digital output terminal state
0: Means terminal input is unavailable
1: Means terminal input is available
F066 Keep down
F067 Operating mode option Set range:0~4
F067 could choose 3 kinds of operating mode
F067=0 and F067=2 keep down
F067=1 Standard V/F mode
Frequency inverter output Sine PWM wave to motor, and sense AC output current,
and compensate distortion produced by effect of dead time, reduce the torque buffeting
of motor.
F067=3 Noninductive vector mode
Frequency inverter operates under Noninductive vector control arithmetic system,
supply extra torque compensation voltage. Could compensate slip because of load
increasing.

F067=4 Output power(torque) control mode


The operation characteristic is similar with F067=1, when output power overruns
the set upper limit, frequency inverter would reduce automatically its output frequency.

z Under this mode, F073~F077 defines output power limit


curve which is controlled by AI2 or AI3.

-59-
WL-9000 Series Sensor-Less Vector Frequency Converter

20% 40% 60% 80% 100%

Since auto-operating mode function is cancelled, must set F072 as “0”.


PL20(F073):is the output power limit value when output frequency is 20% of
upper limit frequency(F015).
(output frequency=F015 * 20%)
PL40(F074):is the output power limit value when output frequency is 40% of
upper limit frequency(F015).
(output frequency=F015 * 40%)
PL60(F075):is the output power limit value when output frequency is 60% of
upper limit frequency(F015).
(output frequency=F015 * 60%)
PL80(F076):is the output power limit value when output frequency is 80% of
upper limit frequency(F015).
(output frequency=F015 * 80%)
PL100(F077):is the output power limit value when output frequency is upper
limit frequency(F015).
(output frequency=F015)
PL20~PL100 are all expressed as “W.n”,the expression is :PL = W·10n
For example:F015=60Hz,PL20(F073)=15.2, means the output power limit
value is PL20=15·102=1500Watt when output frequency is 12Hz(60*20%)

Actual output power:compute according to P(Watt)= 3 ·Vout·Iout· cosθ


The monitor of output current and power is descripted detailed in F054.
-60-
WL-9000 Series Sensor-Less Vector Frequency Converter

F068 Noninductive vector voltage compensation Set range:0~30


F068 the compensation coefficient when frequency inverter operates under
Noninductive vector mode.
This parameter could be set by parameter auto-tuning function automatically, and
normally no need to be remended. Please refer to parameter set of auto-tuning at 5.2.4.
F069 Slip compensation coefficient F1/F2 Set range:0.00~99.99
F069: Motor inner parameter of R1、R2、L1、L2 become to this parameter
F1: Low-speed phase compensation coefficient
Set F067=1 and F054=3, make the frequency converter operate under 5%
lowe-speed (like F010=60Hz,5%=3Hz), read out power angle of this frequency, then
compute F1 value according to F1=50/RY1n(Φ).
F2: High-speed load compensation coefficient
Set F067=3,make frequency converter operate under 60Hz high-speed,use a
tachometer to measure the speed change when no-load and full-load, and adjust the F2
value to reduce speed change caused as load change.

F070 Analogy input gain Set range:0.0~100%


F071 Timer action time Set range:0.2~6553.0 S

z Please refer to function description of section 6.4.

F072 Simple PLC auto-operating option Set range:0~6


F073 The first period time of auto-operating set Set range:0.1~6553.0S
F074 The second period time of auto-operating set Set range:0.1~6553.0S
F075 The third period time of auto-operating set Set range:0.1~6553.0S
F076 The fourth period time of auto-operating set Set range:0.1~6553.0S
F077 The fifth period time of auto-operating set Set range:0.1~6553.0S

-61-
WL-9000 Series Sensor-Less Vector Frequency Converter

z Please refer to instruction of F073~F077 when use torque


control mode.

Reminding z Please refer to detailed introduction in setion 6.6

F078 Motor rated capacitor Set range:10~100%


F078 defines the percent of motor current and rated current of frequency inverter,
please refer to description of F051.
F079 Resart may option Set range:0~3
F080 Action level when speed searching Set range:10~200%
F081 Deceleration time when speed searching Set range:0.1~25.0S
F082 Voltage restoring time when speed searching Set range:0.1~5.0 S
The frequency converter has the speed trace function. When restart after pause,
could first sense the current rotate speed of motor, then output right starting frequency
to reduce impulse current.
Parameter F079~F082 are used to define the speed trace characteristic of
frequency inverter when restarting after pause.
1. Set digital input function terminal to start up speed trace program.
Set the input terminal function option mode Xn=8,when input terminal is “ON”,
frequency converter will make IGBT intermit to output. When input terminal recovers
to be“OFF”, frequency converter will still keep intermit stopping state for a period of
time decided by F036, then begins to execute the speed trace .
2. Restore normal voltage (F034=1) after the fault of instantaneous voltage
over-lower or over-high.
When input voltage is unormal and lead to fault tripping, frequency inverter will
rightly stop output.And when input voltage restores, the frequency converter will still
keep stopping output state within a period of time decided by F036. Then begins to
execute the speed trace.
There are 4 parameters to decide the characteristic of speed trace as the following,
F079 Restart way option.
-62-
WL-9000 Series Sensor-Less Vector Frequency Converter

Do not track, begins to operate Begins speed trace from operating


0 1
from minimum speed. frequency before stopping
Begins speed trace from upper Begins speed trace from set frequency
2 3
limit frequency
F081 Deceleration time when speed searching
(refer to action sequential drawing)
F082 Voltage restoring time when speed searching

As above drawing, after the time decided by F036, the process of speed trace
could fall into four steps:
Step 1: According to option of F079, first ouput frequency, this moment, the
output voltage is 0 volt.
Step 2:。Keep the operational frequency set just now.Then increase gradually the
output voltage according to voltage acceleration time appointed by F082.In the process
of voltage increasing, monitor whether the output current overruns the defined value
defined by F080 at the same time .
Step 3: If output current overruns the set value of F080, then reduce the output
frequency according to the deceleration time set by F081, up to the output current is
less than set value of F080. This means the output frequency of frequency converter is
equal as motor speed.
Step 4: From now on, the ouput frequency of frequency converter could be
increased to the former set frequency.

-63-
WL-9000 Series Sensor-Less Vector Frequency Converter

F083 IGBT protection time Set range:2.0~25.0us


F083 is used to prevent the two groups of IGBT of up and down breakover at the
same time.

z Only the factory could remend this parameter. If need when


remending, please contact with factory.

F084 Input AC voltage Set range:40~1000V


F084 defines the standard input power source voltage of frequency inverter.
According to this parameter, frequency inverter computes all the related voltage
a) OP over-high voltage tripping level = 1.414 * F084 * 130%
b) UP over-low voltage tripping level = 1.414 * F084 * 70%
c) OP after over-high voltage tripping,
voltage restoring level= 1.414 * F084 * 120%
d) UP after over-low voltage tripping,
voltage restoring level = 1.414 * F084 * 80%
e) when contactor is put into use,
the voltage level = 1.414 * F084 * 69%
f) When contactor switching off,
the voltage level = 1.414 * F084 * 65%
g) Discharging starting voltage= 1.414 * F084 *117%
(refer to function description of F033)

z Contactor is used to make the charging resistor shirt-circuit

F085 Rated current of frequency covnerter Set range:0.5~3000.0A


F085 defines rated output current of frequency inverter
F086 Gain adjustment of current shown value Set range:70~140

-64-
WL-9000 Series Sensor-Less Vector Frequency Converter

F087 Gain adjustment of voltage shown value Set range:70~140


F086 adjusts the shown value of output current.
F087 adjusts shown value of DC bus-bar voltage (Vdc)
F088 Max output voltage Set range:30~100%
F088 defines the max voltage when frequency converter operates under upper
limit frequency. Refer to F010、F011 and F015。
F089 AI1 terminal input minimum value Set range:0~1023
F090 AI1 terminal input maxmum value Set range:0~1023
F089 and F090 define the minimum and maxmum value of AI1.
【Adjustment way of the minimum value of AI1 input】 set F055=3, Connect
the input terminal of AI1 to GND terminal: at the moment , the minimum value of AI1
input is information read by F056, and input this information to F089 parameter.(JP1
choose at +10V position)
【Adjustment way of the maxmum value of AI1 input】 set F055=3, Connect
AI1 input terminal to the +10V terminal: at the moment, the maxmum of AI1 input is
the information read by F056, and input this information to F090.(JP1 choose at
+10V position)

z This parameter has been adjusted , please do not adjust it


again if not necessary.

F091 AI2 terminal input minimum value Set range:0~1023


F092 AI2 terminal input maxmum value Set range:0~1023
F091 and F092 define the minimum and maxmum value of AI2.
【Adjustment way of the minimum value of AI2 input】 set F055=4, Connect
the input terminal of AI2 to GND terminal: at the moment , the minimum value of AI2
input is information read by F056, and input this information to F091 parameter.(JP2
choose at +5V position)
【Adjustment way of the maxmum value of AI2 input】set F055=4, Connect AI2
-65-
WL-9000 Series Sensor-Less Vector Frequency Converter

input terminal to the +5V terminal: at the moment, the maxmum of AI2 input is the
information read by F056, and input this information to F092.(JP2 choose at +5V
position)

z This parameter has been adjusted , please do not adjust it


again if not necessary.

F093 Communication form/communication address Set ragne:0.01~99.99


When applying the computer communication control, this parameter is used to
define the communication address code and communication rate of frequency inverter .
please refer to RS485 communication function of Chapte 7.
F094 Data initialize Set range:0~250
1) The R/W type of parameter initialize to ex-factory value, the steps as
following:
Step 1:write in F095=0,F094=1。
Step 2:After the execution software(press RESET key in ALM mode) or
hardware of frequency converter reset action, the information of R/W type
in EPROM memorizer would be to ex-factory value.
2) All parameter auto-initialize to ex-factory value, the steps as
following(please operate carefully):
Step 1:write in F094=249。
Step 2:After the execution software (press RESET key in ALM mode) or
hardware of frequency converter reset action, the information of R/W type
in EPROM memorizer would be to ex-factory value.

F095 Parameter write-protect Set range:0~2


F096 Open special parameter set Set range:0~2
If set F095=1,all the parameter(except F000 and F095)are not allowed to be
remended.
-66-
WL-9000 Series Sensor-Less Vector Frequency Converter

If set F095=0,The parameter of R/W type are allowed to be remended.


If set F095=0 and F096=1, All the parameter of R/W and FR/W type are could
be remended.
If set F095=2,All the parameter are only written in RAM memorizer , and not
stored into EPROM memorizer.
F097 software version
This parameter shows the software version of frequency converter.
F098 The parameter needs monitor Set range:0~99
when I lamp lighting
F099 The parameter needs monitor Set range:0~99
when Hz lamp lighting
Under the monitor mode, set F098 和 F099 could choose two groups of important
parameter to monitor.
Set these two groups of parameter, could monitor other important parameter. Refer
to set value of F057~F062.
F098: Assign the parameter that frequency converter need to monitor when 【I】
lamp lighting.
F099:Assign the parameter that frequency converter need to monitor when 【Hz】
lamp lighting.
Example:F099=57,parameter F057 stands for output frequency,therefore, will
show output frequency on the seven periods display
.
6.3 The way of set operational frequency
F040 is the parameter of frequency set option, could be from operation setter,
memorizer, analogy input, up/down counter, or the combination of above source.
Frequency set option F040=cc.dd,contents“cc”和“dd”two groups of option as
one parameter,refer to Xn(88) and Xn(90)。When Xn(88) and Xn(90) starting, control
command source option=“dd”,otherwise, control command source option =“cc”.

-67-
WL-9000 Series Sensor-Less Vector Frequency Converter

6-3 parameter form of WL-9000 series general frequency inverter


F040 Frequency set option Operation control way decision

0 Decided by number value of F000 Refer to instruction of F039

1 Decided by AI1 input Refer to instruction of F039

2 Decided by AI2 input Refer to instruction of F039

3 Input by operational setter Refer to instruction of F039

(increasing key / decreasing key )

4 Operational frequency and direction decided by size of AI1.

5 Operational frequency and direction decided by size of AI2.

6 Decide by built-in up/down counter Refer to instruction of F039

7 Similar as F040=6,but when open the frequency converter, will input the value of

F000 to up/down counter.

Similar as F040=3, but when open the frequency converter, will input the value of
8 F000 to the operation panel, and could write-in F000 automatically after remending
frequency.
9 Similar as F040=4, after operating, even the output frequency is lower than F016,
could keep operating under low-speed.
10 Similar as F040=5, after operating, even the output frequency is lower than F016,
could keep operating under low-speed.
11 The same as F040=6。

Frequency set = AI1 * ( 1 ± ( F070 * AI2 ) ),after operating, even the output
12
frequency is lower than F016, could keep operating under low-speed.
13 Frequency set = AI2 ± ( F015 * ( F070 * AI1 ) ),after operating, even the output
frequency is lower than F016, could keep operating under low-speed.
14~16 Keep down

17 Similar as F040=1,after starting to operate,even the output frequency is lower than


F016, could keep operating under low-speed.
18 Similar as F040=2,after starting to operate,even the output frequency is lower than
F016, could keep operating under low-speed.
19 Similar as F040=11,could write in F000 automaticaly after the value of up/down
counter be remended.

-68-
WL-9000 Series Sensor-Less Vector Frequency Converter

20 Contrary to action of F040=18.


+5V(or 20mA)---> low-speed; 0V---> high-speed
21 Frequency set =operation setter set * ( 1± ( F070 * AI2 ))。

Frequency set =panel set ± ( F015 * ( F070 * AI1 )),after operating, even the output
22
frequency is lower than F016, could keep operating under low-speed.
23~24 Keep down

25 Similar as F040=2,frequency set is decided by input of AI3.


( i.e:keyboard potentiometer )
26 Similar as F040=5,frequency set is decided by input of AI3

( i.e:keyboard potentiometer )

Similar as F040=5, frequency set is decided by input of AI3. after operating, even the
27
output frequency is lower than F016, could keep operating under low-speed.
Frequency set = AI1 * ( 1 ± ( F070 * AI3 )),after operating, even the output frequency
28
is lower than F016, could keep operating under low-speed.
Frequency set = AI3 ± ( F015 * ( F070 * AI1 )),after operating, even the output
29
frequency is lower than F016, could keep operating under low-speed.
Similar as F040=2,frequency set is decided by input of AI3. after starting to operate,
30
even the output frequency is lower than F016, could keep operating under low-speed.
31 Contrary to action of F040=30, +5V(or +10V)---> low-speed, 0V---> high-speed

32 Contrary to action of F040=17, +5V(or +10V)---> low-speed, 0V---> high-speed

33 Frequency set = panel set * ( 1± ( F070 * AI1 ))

34 Frequency set = panel set * ( 1± ( F070 * AI3 ))


Frequency set = panel set ± ( F015 * ( F070 * AI2 ) ),after operating, even the output
35
frequency is lower than F016, could keep operating under low-speed.
Frequency set = panel set ± ( F015 * ( F070 * AI3 ) ),after operating, even the output
36
frequency is lower than F016, could keep operating under low-speed.
37 AI1 control forward running,AI2 control reverse running

38 AI2 control forward running,AI1 control reverse running

Similar as F040=0,frequency set is decided by number value of F000. after operating,


39
even the output frequency is lower than F016, could keep operating under low-speed.
40 Frequency set is decided by PID output

41~45 Keep down

46 Frequency set is decided by RS485 communication interface(only suit for when


HPI6000 communication form)
-69-
WL-9000 Series Sensor-Less Vector Frequency Converter

47 Keep down

48 Frequency set=PID gain *(PID output+PID bias * AI1)


,refer to chapte 8

49 Frequency set=PID gain *(PID output+PID bias * AI2)


,refer to chapte 8

50 Frequency set=PID gain *(PID output+PID bias * AI3)


,refer to chapte 8

51 Frequency set=PID gain* PID output+PID bias * F028),refer to chapte 8

z JP1 chooses the configuration of analogy input AI1.could


choose 0 ~ +5V or 0 ~+10V 。
Reminding z JP2 chooses the configuration of analogy input AI2. could
choose 0 ~ +5V or 0 ~ 20mA。
z JP3 is used to choose that analogy input signal source is AI3 or
keyboard potentiometer speed-adjustment.

F040 = 0 Output frequency is decided by information of F000.


Under this mode, frequency information is stored in F000.When starting to
operate, is used to decide the output frequency of frequency converter. But the
operation direction is controlled by F039.
Parameter F000 is the main-speed set frequency which is saved in memorizer. As
soon as the frequency data is written into F000, would be saved forever, unless users
write in new value.

z Under this mode, if change F000,will rightly change the output


frequency when the frequency inverter is operating.

F040 = 1 Output frequency is decided by voltage of AI1


Under this mode, the voltage signal of AI1 terminal will decide the output
frequency when frequency converter is operating, but the operating direction is decided
by F039.
When the input signal is the maxmum value, the output frequency is equal as the
frequency set by F015.The relation between input voltage and output frequency is as
the following drawing.

-70-
WL-9000 Series Sensor-Less Vector Frequency Converter

z Use JP1 to choose suitable input voltage range.if necessary,


could use F089 and F090 to remend input range.

F040 = 2 Output voltage is decided by input of AI2.


Under this mode, the voltage (or current) signal of AI2 terminal decides the output
frequency when frequency converter is operating.but the operating direction is
controlled by F039.
When the input signal is the maxmum value, the output frequency is equal as the
frequency set by F015.The relation between input voltage and output frequency is as
the following drawing.

z JP2 decides input voltage or current signal.If necessary, could


use F091 and F092 to remend the input range.

F040 = 3 Output frequency is decided directly by operational setter input.


Output frequency is decided directly by the operational setter. If use sequence
communication control, the output frequency would be decided by RS485
communication command input. But the operating direction is controlled by F039.
-71-
WL-9000 Series Sensor-Less Vector Frequency Converter

z After staring to operate, even set frequency is lower than


F016, will keep the frequency of F016 and operating under
low-speed.

F040 = 4 Output frequency and operating direction are controlled by


voltage of AI1.

Under this mode, the voltage signal of AI1 terminal will decide the output
frequency and operating direction when frequency converter is operating. When input
signal is the maxmum value, frequency converter is forward running under the
frequency set by F015. when input signal is “0”, frequency converter is reverse running
under the frequency set by F015. when input signal is near to center point, frequency
converter will stop output. Please compare the function of F040=9 .

z Use JP1 to choose suitable input voltage range. If necessary,


could use F089 and F090 to remend the input range.

F040 = 5 Output frequency and operating direction are controlled by input


of AI2.

-72-
WL-9000 Series Sensor-Less Vector Frequency Converter

Under this mode, the voltage signal of AI2 terminal will decide the output
frequency and operating direction when frequency converter is operating. When input
signal is the maxmum value, frequency converter is forward running under the
frequency set by F015. when input signal is “0”, frequency converter is reverse running
under the frequency set by F015. when input signal is near to center point, frequency
converter will stop output. Please compare the function of F040=10.

z JP2 decides input voltage or current signal. if necessary,


could use F091 and F092 to remend the input range.

F040 = 6 Output frequency is decided by innter up/down counter

F040 = 7 Similar as F040=6, but will input the value of F000 in up/down
counter when power-on .

z After starting to operate, even set frequency is lower than F016,


will keep the frequency of F016 and operating under low-speed.

-73-
WL-9000 Series Sensor-Less Vector Frequency Converter

The structure of inner up/down counter is as the following:

1. When F040=6, 7, 11 or 19, the output of up/down counter


decides operating frequency.
2. When F040=7 or 19,when opening frequency converter,
will input the value of F000 in up/down counter.
Reminding 3. When F040=19 , will write the frequency value after
amending into F000;
4. Re the input signal, such as: up, down, upload, clearup and
keeping, please refer to description of multifunction digital
input terminal.
5. Could most use four input at the same time.

Application of Up/Down counter


F040 = 8 Similar as F040 = 3 ,but when opening frequency converter,
could read out the F000 value in advanced.
Similar as F040=3,The different points as follwing:
-74-
WL-9000 Series Sensor-Less Vector Frequency Converter

a. Could read out F000 value in advanced when power-on, and be treated as
advanced set frequency.
b. F000 When use the operational settor, and set frequency modifying, will
write in automatically F000.

z After starting to operate, even set frequency is lower than


F016, will keep the frequency of F016 and operating under
low-speed.

Output frequency and operating direction are decided by AI1


F040 = 9 voltage, and do not stop when output frequency is lower than
F016.

Under this mode, the voltage signal of AI1 terminal will decide the output
frequency and operating direction when frequency converter is operating. When input
signal is the maxmum value, frequency converter is forward running under the
frequency set by F015. when input signal is “0”, frequency converter is reverse running
under the frequency set by F015. when input signal is near to center point, frequency
converter will operate under the frequency set by F016, Please compare the function of
F040=4 .

-75-
WL-9000 Series Sensor-Less Vector Frequency Converter

z Use JP1 to choose suitable input voltage ragne. If necessary,


could use F089 and F090 to modify the input range.

Output frequency and operating direction ard controlled by AI2


F040 = 10
input; but do not stop when frequency is lower than F016.

Under this mode, the voltage signal of AI2 terminal will decide the output
frequency and operating direction when frequency converter is operating. When input
signal is the maxmum value, frequency converter is forward running under the
frequency set by F015. when input signal is “0”, frequency converter is reverse running
under the frequency set by F015. when input signal is near to center point, frequency
converter will operate under the frequency set by F016, Please compare the function of
F040=5 .

z JP2 decides input voltage or current signal.If necessary, could


use F091 and F092 to modify the input range.

F040 = 11 The same as F040=6


F040 = 12 Set frequency = AI1 *(100% ± (F070*AI2) )
(suit for proportion interlocking operating)

-76-
WL-9000 Series Sensor-Less Vector Frequency Converter

Under this mode,set frequency = AI1 * ( 100% ± ( F070 * AI2 ) )。Normally,


AI1 analogy signal is treated as main set frequency, and AI2 analogy signal is treated
as multiplication rate input.
When signal AI2 input is the maxmum value,changing rate is ( 100 % + F070 );
When signal AI2 input is the minimum value,changing rate is ( 100 % - F070 )。

z When set frequency is less than F016, frequency converter will


continuely operate according to F016 set.

The application as following, AI1 decides the basic speed of every frequency
converter.and the percent of every unit is controlled by AI2.

F040 = 13 Set frequency= AI2 ± ( F015 * (F070*AI1) )


(suit for synchronization interlocking operating)
Under this mode, set frequency = AI2 ± ( F015 * (F070 * AI1) )。Normally, AI2
analogy signal is treated as main set frequency, and AI1 analogy signal is treated as
addition or subtraction compensation input.
When signal AI1 input is the maxmum value,changing rate is +( F015 * F070 );
When signal AI1 input is the minimum value,changing rate is -( F015 * F070 )。

z When set frequency is less than F016, frequency converter


continue to operate according to F016 set

-77-
WL-9000 Series Sensor-Less Vector Frequency Converter

The typic application is as following, AI2 decides basic linear velocity.If there
difference between speed of M2 and M1,the output of position detector will input
directly AI1 terminal of frequency converter 2, then modify the speed of M2 to keep
two units synchronization.

F040 = 14~16 Keep down


F040 = 17 Similar as F040 = 1, after operating,even output frequency is
lower than F016, could keep operating under low-speed.

z Use JP1 to choose proper input voltage range.If necessary, could


use F089 and F090 to modify input range.

Similar as F040 = 2, after operating,even output frequency


F040 = 18
Is lower than F016, could keep operating under low-speed.

-78-
WL-9000 Series Sensor-Less Vector Frequency Converter

z JP2 decides input voltage or current signal, if necessary, could


use F091 and F092 to modify the input range.

Similar as F040 = 6, but could write in F000 automatically after


F040 = 19
remending the value of up/down counter.
Similar as F040=6,the different points as the following;
a. Could read out F000 value in advanced when power-on.
b. When set frequency changing, will write in F000 automatically.
F040 = 20 Similar as F040 = 18,but the definition of high and low
speed are diffenent.

Under this mode, the voltage or current signal of AI2 terminal will decide output
frequency when frequency converter is operating. But the operating direction is
controlled by F039.
When input signal is the maxmum value, frequency converter is forward running
under the frequency set by F016; Contrarily,when input signal is zero, frequency
converter will operate under frequency set by F015
-79-
WL-9000 Series Sensor-Less Vector Frequency Converter

z JP2 decides input voltage or current signal.If necessary, could


use F091 and F092 to modify input range.
z Please refer to the instruction of F040=18, and note the
difference from above drawing.

F040 = 21 Frequency set = set frequency of operational settor* ( 100% ±


(F070*AI2) )
This mode is similar as F040 = 12,but AI1 input is set frequency of operational
settor.
Under this mode,set frequency = set frequency of operational settor * ( 100 %
±(F070 * AI2)), The set frequency of settor is as main set frequency, and analogy
signal from AI2 is as multiplication rate input.
When signal AI2 input is the maxmum value, changing rate is (100 % + F070)
When signal AI2 input is the minimum value, changing rate is (100% - F070)。

z When set frequency is less than F016, frequency converter


continues to operate according to F016 set.

This function is applicated in multi-unit proportion interlocking control of


computer online. Refer to instruction of F040=12, and note compare the difference
from the following drawing:

-80-
WL-9000 Series Sensor-Less Vector Frequency Converter

F040 = 22 Set frequency =set frequency of operational settor ± ( F015 *


(F070*AI1) )
This mode is similar as F040 = 13,But AI2 input is set frequency of
operational settor.
Under this mode,set frequency = set frequency of operational settor ± ( F015 *
(F070 * AI1) ),The set frequency of settor is as main set frequency;and the analogy
signal from AI1 is treated as addition or subtraction compensation input.
When signal AI1 input is the maxmum value,changing rate is ( F015 * F070 )
When signal AI1 input is the minimum value,changing rate is -( F015 * F070 )。

z When set frequency is less than F016, frequency converter


continues to operate according to F016 set.

This function is applicated in multi-unit synchronization interlocking control of


computer online. Refer to instruction of F040=13, and note compare the difference
from the following drawing:

-81-
WL-9000 Series Sensor-Less Vector Frequency Converter

F040 = 23~24 Keep down

F040 = 25 Output frequency is decided by AI3 input


(keyboard potentiometer adjust speed)
This mode is similar as F040 = 2,but the voltage signal of AI3 terminal will
decide output frequency when frequency converter is operating. And the operating
direction is controlled by F039.Refer to function of F040=2.

z If necessary, could use F091 and F092 to modify the input


range of AI3.

F040 = 26 Output frequency and operating direction are controlled by AI3 input
This mode is similar as F040 = 5, But the voltage signal of AI3 terminal will
decide the output frequency and operating direction when frequency converter is
operating. Refer to function description of F040=5.

z If necessary, could use F091 and F092 to modify input range


of AI3.
Input voltage range is 0~+5V

-82-
WL-9000 Series Sensor-Less Vector Frequency Converter

Output frequency and operating direction are controlled by AI3


F040 = 27
input.But do not stop when frequency is lower than F016.
This mode is similar as F040 = 10, But the voltage signal of AI3 terminal will
decide the output frequency and operating direction when frequency converter is
operating, and do not stop when frequency is lower than F016. Refer to the function
description of F040=10.

z If necessary, could use F091 and F092 to modify input range


of AI3.
Input voltage range is 0~+5V

F040 = 28 Set frequency = AI1*(100% ± (F070*AI3) )


(suit for proportion interlocking operating)
This mode is similar as F040 = 12,But the signal of AI2 terminal changes to the
signal of AI3 terminal.Refer to the function description of F040=12.

z If necessary, could use F091 and F092 to modify input range of


AI3. Input voltage range is 0~+5V

F040 = 29 Set frequency = AI3 ± (F015 * (F070*AI1))


(suit for synchronization interlocking operating)
This mode is similar as F040 = 13,But the signal of AI2 terminal changes to the
signal of AI3 terminal.Refer to the function description of F040=13

z If necessary, could use F091 and F092 to modify input range


of AI3. Input voltage range is 0~+5V

-83-
WL-9000 Series Sensor-Less Vector Frequency Converter

Output frequency is decided by AI3 input,after operating, even


F040 = 30 output frequency is lower than F016, could keep operating under
low-speed.
This mode is similar as F040 = 18,But the signal of AI2 terminal changes to the
signal of AI3 terminal.Refer to the function description of F040=18.

z If necessary, could use F091 and F092 to modify input range of


AI3. Input voltage range is 0~+5V

F040 = 31 Similar as F040 = 30 , but is contrary to the definition of high


and low-speed.
This mode is similar as F040 = 30, Under this mode, when the input signal of
AI3 terminal is maxmum value, frequency converter is forward running under
frequency set by F016.Contrarily, when input signal is zero, frequency converter is
operating under frequency set by F015. Refer to the function description of F040=20.

z If necessary, could use F091 and F092 to modify input


range of AI3. Input voltage range is 0~+5V

F040 = 32 Similar as F040 = 17 , but the definition of high-speed and


low-speed .

-84-
WL-9000 Series Sensor-Less Vector Frequency Converter

This mode is similar as F040 = 20,but the signal of AI2 terminal changes to
be the signalof AI1 terminal.Under this mode,the voltage signal of AI1 terminal will
be used to decide the output frequency when frequency converter is operating.And the
operating direction is controlled by F039.
When input signal is Maxmum value, frequency converter is forward running under the
frequency set by F016. Contrarily, when inupt signal is zero, frequency converter will
operate under the frequency set by F015.

z Use JP1 to choose proper input voltage range.If necessary,


could use F089 and F090 to modify the input range.

F040 = 33 Set frequency = set frequency of operational settor * ( 100% ±


(F070*AI1) )
Similar as F040 = 21,multiplication rate input will be AI1.
F040 = 34 Set frequency = set frequency of operational settor * ( 100% ±
(F070*AI3) )
Similar as F040 = 21,multiplication rate input will be AI3.
F040 = 35 Set frequency = set frequency of operational settor ± ( F015 *
(F070*AI2) )
Similar as F040 = 22,addition or subtraction compensation input will be AI2.
F040 = 36 Set frequency = set frequency of operational settor± ( F015 *
(F070*AI3) )
Similar as F040 = 22,addition or subtraction compensation input will be AI3.
F040 = 37 AI1 forward running,AI2 reverse running
Controlled by AI1 when be forward running,the same as F040 = 17
Controlled by AI2 when be reverse running,the same as F040 = 18
F040 = 38 AI2 forward running,AI1 reverse running
Controlled by AI2 when be forward running,the same as F040 = 18
Controlled by AI1 when be reverse running,the same as F040 = 17
-85-
WL-9000 Series Sensor-Less Vector Frequency Converter

Output frequency is controlled by the information of F000,after


F040 = 39 operating, even output frequency is lower than F016, could keep
low-speed operating.
This mode is similar as F040= 0, But after operating, even output frequency is
lower than F016, could keep operating under low-speed.

z Under this mode, when frequency converter is operating,


changing F000 will change the output frequency rightly.

F040 = 40 Output frequency is decided by PID output


Please refer to PID function of Chapte 8.
F040 = 41~45 Keep down
F040 = 46 Output frequency is decided by RS485 communication
interface command.(refer to chapte 7.)

F040 = 47 Keep down


F040 = 48 Frequenc set=PID gain*(PID output +PID bias * AI1)
F040 = 49 Frequenc set =PID gain*(PID output +PID bias * AI2)
F040 = 50 Frequenc set =PID gain*(PID output +PID bias * AI3)
F040 = 51 Frequenc set =PID gain*(PID output +PID bias * F028)
Please refer to the PID function on Chapte 8.

6.4 Multifunction digital input terminal option


Terminal of X1、X2、X3、X4、FWD(X5)、REV(X6)are multifunction digital
input terminal.
F003: for choosing the function of FWD terminal
F004: for choosing the function of REV terminal
F041: for choosing the function of X1 terminal

-86-
WL-9000 Series Sensor-Less Vector Frequency Converter

F042: for choosing the function of X2 terminal


F043: for choosing the function of X3 terminal
F044: for choosing the function of X4 terminal

z On the control terminal, FWD is DI5,REV is DI6


z Xn( n=1~6,is X1 X2 X3 X4 X5 X6)

6-4 Parameter form of WL-9000 series General frequency inverter


F003 、 F004 、 Function Function explanation
F041~F044 code
0 NULL No any action
1 EMS emergency stopping
2 SPD3 Operating under period 3 frequency set in advanced
3 SPD2 Operating under period 2 frequency set in advanced
4 SPD1 Operating under period 1 frequency set in advanced
5 JOG Operating under inching frequency set in advanced
6 OH Motor over-heat protection function (Normal open type of
detector )
7 TMIA Timer(counter) input (delay-time close type)
8 ON_BB Pause output and speed trace (close action type)
9 FJR Forward inching operating
10 RJR Reserve inching operating
11 TMIB Timer(counter) input (delay-time close type)
12~14 Keep down
15 U/D CLEAR Carry F016 into up/down counter
16 U/D LOAD Carry F015 into up/down counter
17 U/D HOLD Keep up/down counter

18 OFF_BB Pasue output and speed trace (open-circuit action type)


19 UP up/down counter increasing
20 DOWN up/down counter decreasing
21 ALARM Fault reset
CLEAR
22 SET1(FF1) Set flip-flop(1)
23 CLR1(FF1) Clear away flip-flop (1)
24 SET2(FF2) Set flip-flop(2)
25 CLR2(FF2) Clear away flip-flop (2)
26 SET(FF1&FF2) Set flip-flop(1) and (2) at the same time
27 CLR(FF1&FF2) Clear away flip-flop(1) and (2) at the same time
28 CLK Input Input pulse of timer (counter)

29 Keep down
30 /OH Motor over-heat protection function (Normal close type of
detector )
-87-
WL-9000 Series Sensor-Less Vector Frequency Converter

31 Normal/Auto Transfer switch between normal operating and


SW auto-operating
32~35 Keep down
36 TMIC Timer(counter) input (switching type and loop type )
37~47 Keep down
48 Speed Hold Keep former speed operating
49 Keep down
50 PID Enable PID start-up
51 PID Hold PID integrating keeping
52 PID Clear PID integrating cleanup
53 PID Preset Set PID input value in advanced
54 PID Bias PID bias starting up
55 PID Boost PID gain starting up
56~68 Keep down

69 DC-BRAKE1 DC braking voltage controlled by AI1


70 DC-BRAKE2 DC braking voltage controlled by AI2
71 DC-BRAKE3 DC braking voltage controlled by AI3

72 SENSOR _ option between vector and non-vector


LESS
SELECTION
73 FWD Forward operating
FUNCTION
74 REV Reverse operating
FUNCTION
75 POWER _ Source option of manual output power limit
CONTROL
SELECT
76 FORWARD Forbid forward operating
INHIBIT
77 REVERSE Forbid reverse operating
INHIBIT
78 PANEL SET UP Increase panel set frequency

79 PANEL SET Decrease panel set frequency


DOWN
80 SPEED SW1
81 SPEED SW2
16 periods of speed option
82 SPEED SW3
83 SPEED SW4

84 JOG ACC/DEC
Accelereation/deceleration time option
TIME
85 SPD1 ACC/DEC
TIME
86 SPD2 ACC/DEC
TIME

-88-
WL-9000 Series Sensor-Less Vector Frequency Converter

87 SPD3 ACC/DEC
TIME
88 SPEED Speed order change over
COMMAND
SW
89 CONTROL Control order change over
COMMAND
SW
90 SPEED & Source of speed and control order change over
CONTROL
SW
Timer(counter) input (delay-time switch-off type)
91 /TMIA
(inverter input)
Timer(counter) input (delay-time close type)
92 /TMIB
(inverter input)
Timer(counter) input (switching and loop type)
93 /TMIC
(inverter input)
94 TMIAX The same as X=7,delay time=F071*AI2

95 TMIBX The same as X=11,delay time =F071*AI2

96 TMICX The same as X=36,delay time =F071*AI2

97 /TMIAX The same as X=91,delay time =F071*AI2

98 /TMIBX The same as X=92,delay time =F071*AI2

99 /TMICX The same as X=93,delay time =F071*AI2

Xn=0 No any function


Do not act whatever the state of input terminal
Xn=1 EMS: Emergency stopping function
Choose this function, If input terminal ON when the frequency converter is
operating,the converter will output DC voltage into motor to instead of AC voltage and
stop the motor quickly.(Refer to the function description of F005~F008).
Xn=2 Period 3 operational frequency
Xn=3 Period 2 operational frequency
Xn=4 Period 1 operational frequency
Xn=5 Inching
F000 can set the main operational frequency, and other four parameters could set

-89-
WL-9000 Series Sensor-Less Vector Frequency Converter

other normal operational frequency in advanced.


F000: Main-speed frequency, acceleration /deceleration time is set by F001 and
F002.
F019:Inching frequency, acceleration /deceleration time is set by F02
F021: Period 1 operational frequency. acceleration /deceleration time is set by F022
and F023.
F024:Period 2 operational frequency. acceleration /deceleration time is set by F025
and F026.
F027:Period 3 operational frequency. acceleration /deceleration time is set by F028
and F029.
When the terminal decides the operational speed, the preference order is as the
following:
Inching > Period 1 speed >Period 2 speed >Period 3 speed>16 periods of
speed > Normal operational speed
Normal operational speed: Means the frequency set option decided by F040.

z The above functions are effect when having operating order,


but would also be effect without operational signal when be
inching operating of Xn=9 or Xn=10.
z Multi-periods of speed according to this manual

Xn=6 OH Motor over-heat protection function(refer to Xn=30)


When input terminal is open-circuit, means be normal to operate.
When input terminal is close, frequency inverter will stop input and display OH
fault information.
Xn=7 TMIA delay-time switching-off type of timer(/counter)input

-90-
WL-9000 Series Sensor-Less Vector Frequency Converter

When the timer is being used, The signal of 0.1S rated time is choosed as timer
(/counter) function input. And when time is being used, the input terminal of X2 or X4
which is assigned as Mode 28 would be pulse input terminal of timer (/counter)
function. If need to remend by hand, please refer to function of Xn=94~99 .

z The frequency converter contents timer (/counter) function.


When digital input terminal X2 and X4, this function must
be used as counter, otherwise be used as timer.

When any one of digital input terminal Xn is assigned with TMIA function, could
choose Y1 or Y2 or TA, TC to be output function of TMOA, and add with the
timer(/counter) module to make up to a delay-time switch-off relay, and the delay-time
is decided by F071.

When input TMIA switching on, output


TMIA
TMOA will switch on rightly. But when TMIA
TMOA FO71 is switching off, the TMOA must switch off
/TM0A after a period of time defined by F071.

z The max input pulse of timer/counter is 1000Hz.


z The frequency inverter has only one time/counter module.

-91-
WL-9000 Series Sensor-Less Vector Frequency Converter

Xn=8 ON_BB Pause output and speed trace(close action type), please
refer to function of Xn=18
When the selected input terminal is “ON”, all IGBT will stop output rightly; And
when be “OFF”, the frequency converter will execute the function of speed trace after a
period of time (decided by F036).
Xn=9 FJR Forward inching operating
When the selected input terminal is “ON”, the frequency converter would be
forced to forward operate under inching frequency. (execute without extra operating
order)
Xn=10 RJR Reverse inching operating
When the selected input terminal is “ON”, the frequency converter would be
forced to reverse operate under inching frequency. (execute without extra operating
order)
Xn=11 TMIB Delay-time close type of timer(/counter) input
Please first refer to function description of Xn=7 timer (/counter) module

When any one of digital input terminal Xn is assigned with TMIB function,
could choose Y1 or Y2 or TA、TC to be output function of TMOB, and add with the
timer(/counter) module to make up a delay-time switch-off relay, and the delay-time is
decided by F071.

TMIB
FO71
TMOB

/TM0B
When input TMIB is “OFF”, the
TMOB would recover to state of“OFF”rightly, But when input TMIB is “ON”,the
output TMOB would must be “on”after a period of time defined by F071.
The max input pulse of timer/counter is 1000Hz.
WL-9000 frequency inverter has only one timer/counter module.
-92-
WL-9000 Series Sensor-Less Vector Frequency Converter

Xn=12~14 Keep donw.


Xn=15 CLEAR : carries the F016 to up/down counter
Xn=16 LOAD : carries the F015 to up/down counter
Xn=17 HOLD : Keep up/down counter

z If use the output of up/down counter for frequency set, the


F040 must choose one number from 6,7,11 or 19.
z Please refer to function description of F040 about the
Reminding difference among these four types.

If the function option of input terminal is Xn=15( CLEAR ):and when this
terminal is “ON”,will carry the frequency of F016 into up/down counter, at this
moment, the change of output frequency must be according to the feedback of F002.
If the function option of input terminal is Xn=16( LOAD ):and when this
terminal is “ON”,will carry the frequency of F015 into up/down counter, at this
moment, the change of output frequency must be according to the feedback of F001.
If the function option of input terminal is Xn=16( LOAD ):and when this
terminal is “ON”,will carry the frequency of F015 into up/down counter, and will keep
the former operating speed.
Xn=18 OFF_BB Pause output and speed trace(open-circuit action type)
When the selected terminal is “OFF”, all IGBT will stop ouput rightly;
And when the terminal recovers to “ON”, the frequency converter will execute the
speed trace function after a period of time decides by F036.
Xn=19 UP: up/down counter increasing
When the selected input-terminal is “ON”, up/down counter will increases
according to the acceleration time of F001.
Xn=20 DOWN: up/down counter decreasing
When the selected input-terminal is “ON”, up/down counter will decrease
according to the deceleration time of F002.
-93-
WL-9000 Series Sensor-Less Vector Frequency Converter

Xn=21 Fault reset


Only the frequency converter in trouble, the terminal with above function could be
used as reset terminal.When the frequency converter is normal, this terminal has no any
function.

z Standard RST terminal could reset frequency converter in


any situation.

Xn=22 Set Flip-Flop(1)


Xn=23 Clear away Flip-Flop(1)
XIn=24 Set Flip-Flop(2)
Xn=25 Clear away Flip-Flop(2)
Xn=26 Set Flip-Flop(1)and(2)at the same time
Xn=27 Clear away Flip-Flop(1)and(2)at the same time

The above drawing is two groups of built-in flip-flop with normal function.Every
flip-flop could be set or cleared away by two input terminals, and be monitored by two
output terminals of Y1 or Y2 or TA, TC
F041=22 F042=23 F043=23 F045=4

-94-
WL-9000 Series Sensor-Less Vector Frequency Converter

Xn=28 Input pulse of timer (counter).

z When input terminal X2 or X4 set as this mode,


timer(counter) module would be function of counting
Reminding automatically
z Refer to the description of Xn=7.

When X1 choose(28), keep down.


When X2 choose(28), applys in normal timer/counter, refer to Xn=7、Xn=11、Xn=36
set.
When X3 choose(28),No function.
When X4 choose(28), applys in normal timer/counter, refer to Xn=7、Xn=11、Xn=36
set.

z Max limit of input pulse is 1000Hz

Xn=29 No function
Xn=30 /OH Motor over-heat protection function
( Refer to function description of parameter Xn=6.
When input terminal is close, means normal and could operate.
When input terminal is open-circuit, frequency convertor will stop ouput and
disply OH fault information.
Xn=31 Transfer switch between normal operating and auto operating
(refer to the function description of 6.6)
Generally, if just need normal operating mode, make F072=0 .If need
auto-operating function, F072 could choose different auto-operating modes.
If need to change over between normal operating mode and auto-operating mode
regularly, could set F072 as the needed auto-operating mode,then change over by
handle by the appointed input terminal,so that no need to change F072 parameter
regularly.
-95-
WL-9000 Series Sensor-Less Vector Frequency Converter

When the oppointed input terminal choose this mode, if input is “OFF”state, will
execute auto-operating mode.If input is“ON”state, will return to normal operating
mode, which is the same as the state when F072=0. If input recovers to be “OFF”state
again, the frequency converter will also recover to auto-operating mode.
Xn=32~35 Keep down
Xn=36 Switching loop type timer(counter) input

When input TMIC is “OFF”, TMOC output always keeps “ON”. If TMOC output
Y1 or Y2=92, output always keeps “OFF”. When input TMIC is “ON”,TMIC output
will do “ON/OFF”transfer rightly according to the time set by F071, time of ON/OFF
is half and half. Refer to instruction of Xn=94.
Xn=37~47 Keep down
Xn=48 Keep former operating speed
If the function option of input terminal is Xn=48, when this input terminal is
“ON”, frequency converter stops acceleration or deceleration rightly and keep former
operating speed. When input terminal is “OFF”, the frequency converter keeps on
acceleration or deceleration.
Xn=49 Keep down
Xn=50 PID starting

-96-
WL-9000 Series Sensor-Less Vector Frequency Converter

Xn=51 PID integrating keeping


Xn=52 PID integrating clear up
Xn=53 PID output value set in advanced
Xn=54 PID bias starting
Xn=55 PID gain starting
PID Function , refer to function of Chapter 8.
Xn=56~68 keep down
Xn=69 DC braking voltage is controlled by AI1
Xn=70 DC braking voltage is controlled by AI2
Xn=71 DC braking voltage is controlled by AI3
If the function option of input terminal is Xn=69,70 or 71,when this input
terminal is “ON”,the frequency converter will output DC braking voltage to motor.The
voltage value is controlled by AI1、AI2 or AI3

z DC braking voltage=F006 * Vn(i:AI1、AI2、AI3)

Xn=72 Vector or non-vector transfer option


If input terminal function is Xn=72:
If F067=1, when input terminal is close, the operating mode of frequency inverter
will change over from normal mode to noninductive vector mode.
If F067=3, when input terminal is close, the operating mode of frequency inverter
will change over from noninductive vector mode to normal mode
Xn=73 Forward running
When choose this function, this terminal is set as FWD function . Refer to
description of F003.
Xn=74 Reverse running
When choose this function, this terminal is set as REV function . Refer to
description of F004
DIn=75 Source option of Manual output power limit (Refer to function
description of F067)

-97-
WL-9000 Series Sensor-Less Vector Frequency Converter

This function is effect only when F067=4 output power limit mode.
If input terminal function is Xn=75, when input terminal is “ON”,the power limit
curve is controlled by AI2.
If input terminal function is other value, or this terminal is “OFF”, the power limit
curve is controlled by AI3.
Xn=76 Forbid forward running
When the selected input terminal is “ON”, frequency converter forbids forward
running.
Xn=77 Forbid reverse running
When the selected input terminal is “OFF”, frequency converter forbids reverse
running.
Xn=78 Increase panel set frequency
Xn=79 Decrease panel set frequency
When control panel set frequency is speed command source (F040=8),
If input terminal function is X=78, and when this terminal is “ON”,will increase
panel set frequency. If input terminal function is X=79, and when this terminal is “ON”,
will decrease panel set frequency.
Xn=80~83 16 periods speed option
When all terminals of Xn=2~5 are “OFF”(have no function of inching, SPD1,
SPD2, SPD3)
If terminals of Xn=80~83 are “ON”, and the set frequency is as the following:
Set frequency=Xn(83)* F027+Xn(82)* F024+Xn(81)* F021+Xn(F080)
* F019
Xn=84~87 Acceleration/deceleration time option
When all terminals of Xn=2~5 are “OFF”(have no function of inching, SPD1,
SPD2, SPD3)
When Xn=84 terminal is “ON”, the acceleration time =F020,
deceleration time =F020
When Xn=854 terminal is “ON”, the acceleration time =F022,
-98-
WL-9000 Series Sensor-Less Vector Frequency Converter

deceleration time =F023


When Xn=86 terminal is “ON”, the acceleration time =F025,
deceleration time =F026
When Xn=86 terminal is “ON”, the acceleration time =F028,
deceleration time =F029
Xn=88~90 Choose control command and speed command
Please refer to instruction of F039 and F040 .
F039=a.b,has two groups option a and b
F040=cc.dd,has two groups option cc and dd
If terminal Xn=88 is “ON”, speed source=dd
If terminal Xn=88 is “OFF”, speed source=cc
If terminal Xn=89 is “ON”, speed source=b
If terminal Xn=89 is “OFF”, speed source=a
If terminal Xn=90 is “ON”, speed source=b
If terminal Xn=90 is “OFF”, speed source=a

If any Xn=90, could not set Xn=88 or 99 again.

Xn=91 /TMIA delay-time switching-off timer(counter) reverse input


Xn=92 /TMIB delay-time close type timer(counter) reverse input
Xn=93 /TMIC Switching loop type timer(counter) reverse input

Please refer to function description of Xn=7 Xn=11 Xn=36

Xn=94~99 adjustable timer time


Xn(94)=TMIAX
Xn(95)=TMIBX
Xn(96)=TMICX
Xn(97)=/TMIAX
Xn(98)=/TMIBX
Xn(99)=/TMICX

-99-
WL-9000 Series Sensor-Less Vector Frequency Converter

Similar as TMIA~TMIC, but time of timer is adjusted by AI2。

6.5 Digital output function option


Parameter F045 choose output function of Y1
Parameter F046 choose output function of TC2, TA2
Parameter F047 choose output function of TC1, TB1

Every output could choose the function listed in the following form
F045、F046、F047 Function Code Function instruction

0 OFF Output is alwaysOFF

1 STOP Frequency converter is stopping

2 SPE Output frequency is equal

3 SPNE Output frequency is not equal

4 ALM Be in trouble

5 NALM No trouble

6 BRAKING Frequency converter is in braking

7 RUNNING Frequency converter is operating

8 SPO Output frequency overrun

9 SPNO Output frequency not over

10 SPA Output frequency is arrival

11 SPNA Output frequency is not arrival

-100-
WL-9000 Series Sensor-Less Vector Frequency Converter

12 DIR Derection of running

13 Irms LEVELO Irms>F048

14 TMOA Delay-time switching-off type timer output

15 SPZ Output frequency is zero-speed

16 SPNZ Output frequency is not zero-speed

17 SRY1LLING Stall preventing deceleration

18~19 Keep down

20 TMOB Delay-time close type timer output

21 STEP1 Auto-operating under period 1

22 STEP2 Auto-operating under period 2

23 STEP3 Auto-operating under period 3

24 STEP4 Auto-operating under period 4

25 STEP5 Auto-operating under period 5

26 STEP6 Auto-operating under period 6

27 STEP7 Auto-operating under period 7

28 STEP8 Auto-operating under period 8

29 STEP9 Auto-operating under period 9

30 STEP10 Auto-operating under period 10

31 Keep down

32 Q1(FF1) Flip-flop(1)output

33 /Q1(FF1) Flip-flop(1)reverse output

34 Q2(FF2) Flip-flop(2)output

35 /Q2(FF2) Flip-flop(2)reverse output

36~37 Keep down

38 Output ON ON Output is always ON

39 Keep down

40 /TMOA Delay-time switching-off timer reverse ouput

41 /TMOB Delay-time close timeer reverse output

-101-
WL-9000 Series Sensor-Less Vector Frequency Converter

42 TMOC Switching loop type timer

43 /TMOC Switching loop type timer reverse output

44 ×32CLK(only DO1) Output pulse frequency =32×F057(Hz)

45 ×16CLK(only DO1) Output pulse frequency =16×F057(Hz)

46 ×8CLK(only DO1) Output pulse frequency =8×F057(Hz)

47 ×4CLK(only DO1) Output pulse frequency =4×F057(Hz)

48 ×2CLK(only DO1) Output pulse frequency =2×F057(Hz)

49 ×1CLK(only DO1) Output pulse frequency =1×F057(Hz)

50~53 Keep down

54 Irms LEVEL1 Irms>AI1

55 Irms LEVEL2 Irms>AI2

56 Irms LEVEL3 Irms>AI3

57 Power-Limit Output power is limit

58~69 Keep down

70 RUN &(AI1>F074) In operating and AI1>F074 comparision output

71 RUN &(AI1<F074) In operating and AI1<F074 comparision output

72 RUN &(AI2>F075) In operating and AI2>F075 comparision output

73 RUN &(AI2<F075) In operating and AI2<F075 comparision output

74 RUN &(AI3>F076) In operating and AI3>F076 comparision output

75 RUN &(AI3<F076) In operating and AI3<F076 comparision output

76~77 Keep down

78 OL-WARNING Over-load accumulation>50%

79 /OL-WARNING Over-load accumulation<50%

80 AI1>F074 AI1>F074 comparision output

81 AI1<F074 AI1<F074 comparision output

82 AI2>F075 AI2>F075 comparision output

83 AI2<F075 AI2<F075 comparision output

84 AI3>F076 AI3>F076 comparision output

-102-
WL-9000 Series Sensor-Less Vector Frequency Converter

85 AI3<F076 AI3<F076 comparision output

86 ACC In acceleration

87 DEC In deceleration

88 DISCHARGE In discharging

89 Keep down

90 FWD In forward running

91 REV In reverse running

92 TMOC Similar with Yn(42)but act after TMIC is ON

93 /TMOC The same as Yn(43)

When in action of open and reset, all output are in “OFF”state

F045~F047=0 OFF(Output is always OFF)


When output-terminal function chooses this mode, this terminal is always in
“OFF”state. Please refer to description of F045~F047=38
F045~F047=1 STOP Frequency converter is stopping
(Please refer to content of F045~F047=7)
If output terminal function choose this mode, the frequency converter is in
stopping state, and this terminal would be“ON”. As soon as frequency converter begins
to operate, the output would be “OFF”state.

z Frequency converter is braking, and is still in operating


state.

F045~F047=2 SPE Output frequency is equal


F045~F047=3 SPNE Output frequency is not equal
First, assign anyone frequency to exsit in the object frequency compared with
F049, then assign the allowed error frequency to exist in F050. As the following

-103-
WL-9000 Series Sensor-Less Vector Frequency Converter

drawing: If output terminal function chooses SPE, and when the error between output
frequency of frequency converter and F049 is less than the range of F050, it is
regarded as frequency equal. This moment, the output terminal would be “ON”state.
But if the function chooses SPNE, the action is completely contrary to SPE.

F045~F047=4 ALARM In trouble


When frequency converter is normal, output terminal is in“OFF”state, and if
frequency converter is in trouble, the output terminal would be “ON”state rightly.
F045~F047=5 NOT ALARM not in trouble
When frequency converter is normal, output terminal is in“ON”state, and if
frequency converter is in trouble, the output terminal would be in “OFF”state rightly.
F045~F047=6 BRAKING Frequency converter is braking
If output terminal chooses this function mode, and when frequency converter is
braking, this output terminal is “ON”, orelse is in “OFF”state.

z The DC braking mentioned in this function means add the DC


current to the coil of motor, and does not mean outer resistor
discharge braking.
z When in the process of DC braking, the frequency converter is
operating.

-104-
WL-9000 Series Sensor-Less Vector Frequency Converter

F045~F047=7 RUNNING frequency converter is operating


(refer to F045~F047=1)
If output terminal choose this mode, when frequency converter is operating, this
output terminal will be “ON”, and when frequency converter stops operating, the
output terminal would be “OFF”.
F045~F047=8 SPO output frequency overruns
F045~F047=9 SPNO output frequency does not overrun
Please refer to the time sequencial drawing of F045~F047=2.
First, assign anyone frequency to exsit in the object frequency compared with
F049, refer to the drawing: If output terminal function chooses SPO, and when the
output frequency overruns the frequency set by F049, it is regarded as frequency
overruns. This moment, the output terminal would be “ON”state. But if the function
chooses SPNEO, the action is completely contrary to SPEO.
F045~F047=10 SPA output frequency arrival
F045~F047=11 SPNA output frequency not arrival
Please refer to the time sequencial drawing of F045~F047=2
First, assign the allowed error frequency stored in F050, if output terminal
function chooses SPA, and when the error between the output frequency of frequency
converter and set frequency is less than the range of F050, it is regarded as frequency
arrival, at the moment, output terminal would be at “ON”state.
If choose SPNA function, the action is completely contrary to SPA.
F045~F047=12 DIRECTION operating direction
If output terminal choose this function, and when frequency converter output is
forward direction, the output terminal is “ON”state.and when output is reverse
direction, output terminal would be “OFF”state.

z When frequency converter is stopping, output terminal is at


“ON” state.

-105-
WL-9000 Series Sensor-Less Vector Frequency Converter

F045~F047=13 Irms LEVEL0


When the output current “root mean square value”of frequency converter (Irms)
>F048, this output terminal would be “ON”.
F045~F047=14 TMOA delay-time switching-off timer output
F045~F047=15 SPZ output frequency is zero-speed
F045~F047=16 SPNZ output frequency is not zero-speed
Please refer to the time sequencial drawing of F045~F047=2
First , must define the error range of zero-speed , and store it into F050.
If output terminal function choose SPZ, and when output frequency is less than
F050, is regarded as frequency in zero-speed; at this moment, output terminal would be
“ON”state.
If choose SPNZ function, the action is contrary completely to SPZ.
F045~F047=17 SRY1LLING In stall preventing deceleration.
When the frequency converter is operating, if output current overruns the
limit(150%) of hardware, frequency converter will reduce the output frequency
automatically and prevent motor stall ,so that could reduce output current.
If output terminal choose this function, when the frequency converter is executing
deceleration action for preventing motor stall, output terminal would be “ON”.
F045~F047=18 Keep down
F045~F047=19 Keep down
F045~F047=20 TMOB delay-time close timer output

z Please refer to the function description of section of 6.4

F045~F047=21 STEP1 auto-operating under step 1


F045~F047=22 STEP2 auto-operating under step 2
F045~F047=23 STEP3 auto-operating under step 3
F045~F047=24 STEP4 auto-operating under step 4

-106-
WL-9000 Series Sensor-Less Vector Frequency Converter

F045~F047=25 STEP5 auto-operating under step 5


F045~F047=26 STEP6 auto-operating under step 6
F045~F047=27 STEP7 auto-operating under step 7
F045~F047=28 STEP8 auto-operating under step 8
F045~F047=29 STEP9 auto-operating under step 9
F045~F047=30 STEP10 auto-operating under step 10

F045~F047=31 Keep down


F045~F047=32 Q1 flip-flop(1)output
F045~F047=33 /Q1 flip-flop(1)anti-phase output
F045~F047=34 Q2 flip-flop(2)output
F045~F047=35 /Q2 flip-flop(2)anti-phase output

z Refer to the function description of Xn=22

F045~F047=36 Keep down


F045~F047=37 Keep down
F045~F047=38 ON(output is always ON)
When output terminal function chooses this mode, this terminal is always in
“ON”state.This function could be self-detection and while could be used as normal
digital output contact by the computer. Please refer to the description of F045~F047=0.
F045~F047=39 Keep down
F045~F047=40 /TMOA delay-time switching-off timer anti-phase output
F045~F047=41 /TMOB close timer anti-phase output
F045~F047=42 TMOC Switching loop type timer
F045~F047=43 /TMOC Switching loop type timer anti-phase output

-107-
WL-9000 Series Sensor-Less Vector Frequency Converter

z Refer to the function description of Xn=7 and Xn=36 at


section 6.4

F045~F047=44 ×32CLK output pulse frequency =32×F057(Hz)


F045~F047=45 ×16CLK output pulse frequency =16×F057(Hz)
F045~F047=46 ×8CLK output pulse frequency =8×F057(Hz)
F045~F047=47 ×4CLK output pulse frequency =4×F057(Hz)
F045~F047=48 ×2CLK output pulse frequency =2×F057(Hz)
F045~F047=49 ×1CLK output pulse frequency =1×F057(Hz)
Output terminal function mode 44~49 are set output pulse frequency. When
using this mode, the user must execute frequency converter reset, and strart up XnCLK
function. In the same way, when changing the XnCLK function , also must execute
reset action.

z This function is only effect for Y1 terminal, and the max


output frequency is 3KHz

F045~F047=50 Keep down


F045~F047=51 Keep down
F045~F047=52 Keep down
F045~F047=53 Keep down
F045~F047=54 Irms LEVEL1
When the output current “root mean square value”of frequency converter (Irms%)
> 150% * AI1, this output terminal will be “ON”.
F045~F047=55 Irms LEVEL2
When the output current “root mean square value”of frequency converter (Irms%)
> 150% * AI2, this output terminal will be “ON”.
F045~F047=56 Irms LEVEL3

-108-
WL-9000 Series Sensor-Less Vector Frequency Converter

When the output current “root mean square value”of frequency converter (Irms%)
> 150% * AI3, this output terminal will be “ON”.
F045~F047=57 is output power limiting
Frequency converter operates under the output power (torque) control mode, when
the output power overruns the upper limit of set frequency, the frequency converter will
reduce its output power automatically, and this output terminal will be “ON”.
F045~F047=58~69 Keep down
F045~F047=70 Comparing output with AI1>F074 during operating
F045~F047=71 Comparing output with AI1<F074 during operating
When the frequency converter is operating, and AI1 analogy input signal>F074,
Yn(70)will be “ON”, and Yn(71)will be “OFF”.(F074 value must be defined within
0.0~1023.0, the point leaves out of account ). Set F055=3, and F056 could monitor the
size of AI1 analogy input signal.
F045~F047=72 Comparing output with AI2>F075 during operating
F045~F047=73 Comparing output with AI2<F075 during operating
When the frequency converter is operating, and AI2 analogy input signal>F075,
Yn(72)will be “ON”, and Yn(73)will be “OFF”.(F075 value must be defined within
0.0~1023.0, the point leaves out of account ). Set F055=4, and F056 could monitor the
size of AI2 analogy input signal.
F045~F047=74 Comparing output with AI3>F076 during operating
F045~F047=75 Comparing output with AI3<F076 during operating
When the frequency converter is operating, and AI3 analogy input signal>F076,
Yn(74)will be “ON”, and Yn(75)will be “OFF”.(F076 value must be defined within
0.0~1023.0, the point leaves out of account ). Set F055=5, and F056 could monitor the
size of AI3 analogy input signal.
F045~F047=76 Keep down
F045~F047=77 Keep down
F045~F047=78 OL- WARNING over-load accumulation warning

-109-
WL-9000 Series Sensor-Less Vector Frequency Converter

F045~F047=79 /OL- WARNING over-load accumulation warning


When F054 =11, F061 could monitor the accumulation value of overload(OL).
(refer to description of F054)
When output terminal choose mode 78, if over-load accumulation value (OL) >
50%, this output terminal will be “ON”.
When output terminal choose mode 79, if over-load accumulation value (OL) <
50%, this output terminal will be “ON”.
F045~F047=80 AI1>F074 comparing output
F045~F047=81 AI1<F074 comparing output
When AI1 analogy input signal>F074, Yn(80)will be “ON”, and Yn(81)will
be “OFF”.(F074 value must be defined within 0.0~1023.0, the point leaves out of
account ). Set F055=3, and F056 could monitor the size of AI1 analogy input signal.
F045~F047=82 AI2>F075 comparing output
F045~F047=83 AI2<F075 comparing output
When AI2 analogy input signal>F075, Yn(82)will be “ON”, and Yn(83)will
be “OFF”.(F075 value must be defined within 0.0~1023.0, the point leaves out of
account ). Set F055=4, and F056 could monitor the size of AI2 analogy input signal.
F045~F047=84 AI3>F076 comparing output
F045~F047=85 AI3<F076 comparing output
When AI3 analogy input signal>F076, Yn(84)will be “ON”, and Yn(85)will
be “OFF”.(F076 value must be defined within 0.0~1023.0, the point leaves out of
account ). Set F055=5, and F056 could monitor the size of AI3 analogy input signal.
F045~F047=86 In acceleration
If output terminal chooses this function, and when frequency converter is
acceleration, output terminal would be “ON”state.
F045~F047=87 In deceleration
If output terminal chooses this function, and when frequency converter is
deceleration, output terminal would be “ON”state.

-110-
WL-9000 Series Sensor-Less Vector Frequency Converter

F045~F047=88 In discharging
If output terminal chooses this function, and when the voltage of the capacitor
inside frequency converter is over high, output terminal would be “ON”state.
F045~F047=89 Keep down
F045~F047=90 In forward running
If output terminal chooses this function, and when frequency converter output is
forward running direction, output terminal will be “ON”state.
F045~F047=91 In reverse running
If output terminal chooses this function, and when frequency converter output is
reverse running direction, output terminal will be “ON”state.
F045~F047=92 TMOC switching loop type timer
(starting up control)
If output terminal chooses this function, and when DIn =36 and DIn ON, the
function is the same as Yn = 42. But when DIn is OFF, the output is always in
“OFF”state.(refer to description of DIn=36 ).
F045~F047=93 /TMOC switching loop type timer anti-phase output
The function is the same as Yn = 43.

6.6 Simple PLC auto-operating option


6.6.1 The related parameter and function of simple PLC operating option
Parameter Function
F072 Choose the simple PLC auto-operating option

F073 Auto-operating the first (sixth) step time set

F074 Auto-operating the second (seventh) step time set

F075 Auto-operating the third (eighth) step time set

F076 Auto-operating the fourth (ninth) step time set

F077 Auto-operating the fifth (tenth) step time set

-111-
WL-9000 Series Sensor-Less Vector Frequency Converter

6.6.2 Simple PLC auto-operating option is controlled by F072, the auto-operating


function could be chosen as the following:
F072 Function description

0 Normal operating, stop the auto-operating function

1 After stagewise auto-operating, keep constant-speed operating

2 After stagewise auto-operating, Stop, then repeat continually

3 After stagewise auto-operating, Stop, reverse, then repeat continually

4 After stagewise auto-operating, then repeat continually

5 After stagewise auto-operating, reverse, then repeat continually

6 Similar as mode 4;but every time will repeat from the second step.

Could use digital input terminal to transfer normal operating/simple PLC


auto-operating, refer to description of Xn=31.
F072=1 After stagewise auto-operating, keep constant-speed operating
Step1: Frequency converter operates under inching frequency, operating time is
controlled by F073.
Step2: Frequency converter operates under the step 1 operating frequency,
operating time is controlled by F074.
Step3: Frequency converter operates under the step 2 operating frequency,
operating time is controlled by F075.
Step4: Frequency converter operates under the step 3 operating frequency,
operating time is controlled by F076.
Step5: Frequency converter operates continually under the main set frequency
(F040 choose)

-112-
WL-9000 Series Sensor-Less Vector Frequency Converter

F072=2 After stagewise auto-operating, Stop, then repeat continually


Step1: Frequency converter operates under inching frequency, operating time is
controlled by F073.
Step2: Frequency converter operates under the step 1 operating frequency,
operating time is controlled by F074.
Step3: Frequency converter operates under the step 2 operating frequency,
operating time is controlled by F075.
Step4: Frequency converter operates under the step 3 operating frequency,
operating time is controlled by F076.
Step5: Frequency converter stops operating, stopping time is controlled by F077
After the step5, begins to repeat again from step1

F072=3 After stagewise auto-operating, Stop, reverse, then repeat


continually
Step1: Frequency converter operates under inching frequency, operating time is
controlled by F073.
Step2: Frequency converter operates under the step 1 operating frequency,
operating time is controlled by F074.
Step3: Frequency converter operates under the step 2 operating frequency,
operating time is controlled by F075.
Step4: Frequency converter operates under the step 3 operating frequency,
operating time is controlled by F076.
Step5: Frequency converter stops operating, stopping time is controlled by F077
After the step 5, reverse
Step6: Frequency converter operates under inching frequency, operating time is
controlled by F073.
-113-
WL-9000 Series Sensor-Less Vector Frequency Converter

Step7: Frequency converter operates under the step 1 operating frequency,


operating time is controlled by F074.
Step8: Frequency converter operates under the step 2 operating frequency,
operating time is controlled by F075.
Step9: Frequency converter operates under the step 3 operating frequency,
operating time is controlled by F076.
Step10: Frequency converter stops operating, stopping time is controlled by F077
After the step 10, reverse; and begins to repeat again from the step 1.

F072=4 After stagewise auto-operating, then repeat continually.


Similar as mode F072=2。Just step 5 is difference.
Step1: Frequency converter operates under inching frequency, operating time is
controlled by F073.
Step2: Frequency converter operates under the step 1 operating frequency,
operating time is controlled by F074.
Step3: Frequency converter operates under the step 2 operating frequency,
operating time is controlled by F075.
Step4: Frequency converter operates under the step 3 operating frequency,
operating time is controlled by F076.
Step5: Frequency converter operates under main set frequency (F040 choose),
operating time is controlled by F077
After the step 5, begins to repeat again from the step 1.
F072=5 After stagewise auto-operating, reverse, then repeat continually
Similar as mode F072=32。Just step 5 and 10 are difference.
Step1: Frequency converter operates under inching frequency, operating time is
controlled by F073.
Step2: Frequency converter operates under the step 1 operating frequency,
-114-
WL-9000 Series Sensor-Less Vector Frequency Converter

operating time is controlled by F074.


Step3: Frequency converter operates under the step 2 operating frequency,
operating time is controlled by F075.
Step4: Frequency converter operates under the step 3 operating frequency,
operating time is controlled by F076.
Step5: Frequency converter operates under main set frequency (F040 choose),
operating time is controlled by F077
After the step 5, reverse.
Step6: Frequency converter operates under inching frequency, operating time is
controlled by F073.
Step7: Frequency converter operates under the step 1 operating frequency,
operating time is controlled by F074.
Step8: Frequency converter operates under the step 2 operating frequency,
operating time is controlled by F075.
Step9: Frequency converter operates under the step 3 operating frequency,
operating time is controlled by F076.
Step10: Frequency converter operates under main set frequency (F040 choose),
operating time is controlled by F077
After the step 10, reverse; then repeat from the step 1.

F072=6 Similar as mode 4;but every time will repeat from the second step.
At the beginning, from step 1 to step 5 are the same as F072=4
But every time will repeat from the step 2.
At the beginning:step1→step 2→……step 5→step 2……step 5……

1 2 3 4 5 2 3 4 5 2 3 4 5

T1 T2 T3 T4 T5 T2 T3 T4 T5 T2 T3 T4 T5

Application drawing of F072=6


-115-
WL-9000 Series Sensor-Less Vector Frequency Converter

6.6.3 Output signal when auto-operating under the special step.


During the auto-operating, could choose the special digital output terminal (Yn)
function. When auto operating under the special step, could output signal to cooperate
the action of ancillary equipments.
Application: when frequency is in auto-operating, if hope that there all having
output signal when operating under step 2.3.4 , the set method as the following :
Make F045=22, choose that Y1 will act when be step 2.
Make F046=23, choose that Y2 will act when be step 3.
Make F047=24, choose that TA、TC will act when be step 4.
The action sequencial drawing of output terminal is the following:

Chapter 7 RS485 communication function


7.1 RS485 communication interface parameter
When controlled by computer communication, F093 defines the communication
address, former and rate of frequency converter.
7.1.1 WL-9000 series communication interface parameter set
F093=PB.ID ( P:communication form,B:communication rate,
ID:communication address)
1. The set range of communication address:ID=01~99
2. The explanation of communication form set is as the following:
-116-
WL-9000 Series Sensor-Less Vector Frequency Converter

Communication Explanation
form
P=0 WL-9000 communication form,parameter No. is two-digit “nn”
P=1 WL-9000 communication form,parameter No. is three-digit“nnn
P=2 Modbus,no parity, 8 bit binary
P=3 WL-9000 Modbus, no parity , 8bit binary

3. The explanation of communication rate set is as the following:


Communication Explanation
rate
B=0 4800bps,2stopbits
B=1 9600bps,2stopbits
B=2 19200bps,2stopbits
B=3 Keep down
B=4 4800bps,1stopbits
B=5 9600bps,1stopbits
B=6 19200bps,1stopbits
B=7 Keep down

7.2 The interface specification of RS485 hardware.


WL-9000 series Noninductive frequency converter is buit-in RS485
communication interface, CON6 output. The pin definition is as the following:

5V 0V A+ B- OPEN
NO TR

JP6

-117-
WL-9000 Series Sensor-Less Vector Frequency Converter

z RS485 interface allows the signal terminal of multi-pieces frequency


converter connected in parallel directly.
(do not connect CON6 PIN3(+5V)in parallel )
z when communicate with computer, could transfer to be standard 9pin
Dsub(male) computer terminal. The definition after transfer is as the
following :
Dsub(mail )9pin position Definition con6
PIN1~3 N.C.
PIN4 A(SIG+) PIN3A+
PIN5 B(SIG-) PIN2B-
PIN6 0V PIN4(GND)
PIN7~9 N.C.

7. 3 WL-9000 communication form


7. 3 .1 The command for frequency converter
The signal communicate between RS485 interface and frequency converter
by ASCII string, at the end should add up CR code(0x0D).
The communication interface of computer must be defined as:7Bit data,
Even Parity。

7. 3 .1.1 Operating control command:(frequency converter has no apply


information)
Command form:【 C,uu,cc,fffff 】
C:The original character of operating control command.
uu:communication address,assign that the uu channel receiving this string.uu
(ID)could be appointed as the 00~99 channel.
If uu=00, All frequency converters must receive command.
cc:decimalist operating control command code(00~15), made up by four
binary-system signal.
-118-
WL-9000 Series Sensor-Less Vector Frequency Converter

cc=8 * Bit-3 (inching)+4*Bit-2(reverse running)+2*Bit-1(forward running)


+Bit-0(reset)
fffff:speed set value

Control code CC Function


cc=00 Stop
cc=01 Reset
cc=02 Forward running
cc=06 Reverse running
cc=10 Inching forward running
cc=14 Inching reverse running

7. 3 .1.2 Parameter writing command:


(frequency converter has no reply information)
Command form:【 W,uu,nn, ddddd 】or 【 W,uu,nnn,ddddd 】
W :The original character of parameter writing command.
uu :Communication address,assign that the uu channel receiving this string.uu
(ID)could be appointed as the 00~99 channel.
If uu=00, All frequency converters must receive command.
nn(n):If communication form P=0, parameter No. is two-digit“nn”,parameter No.
is 00~99。
If communication form P=1,parameter No. is three-digit “nnn”,parameter No.
is 000~099。
ddddd:the parameter value that wants to write in, is 00000~65535。

7. 3 .1.3 Parameter reading out command:


(frequency converter will reply about parameter value and operating state)
Command form:【 R,uu,nn 】or【 R,uu,nnn 】
R :The original character of parameter reading out command.
-119-
WL-9000 Series Sensor-Less Vector Frequency Converter

uu :Communication address,assign that the uu channel receiving this string.uu


(ID)could be appointed as the 00~99 channel.
If uu=00, All frequency converters must receive command.

nn(n): If communication form P=0, parameter No. is two-digit“nn”,parameter No.


is 00~99。
If communication form P=1,parameter No. is three-digit “nnn”, parameter
No. is 000~099。

7. 3 .2 The reply information of frequency converter to computer


As soon as frequency converter receiving the parameter reading out command,
will reply rightly about this parameter and operating information of the time.
Reply information form【 P,uu,nn,tt,ddddd,s,aaaa 】 or
【 P,uu,nnn,tt,ddddd,s,aaaa 】
P :The original character of parameter reply information.
uu :Point out this string is the reply information of the uu.
Parameter F093 of every frequency converte decides the
communication address itself.
nn(n):if communication form P=0,parameter No.is two-digit “nn”,parameter
No.is 00~99。
if communication form P=1,parameter No.is three-digit “nnn”,
parameter No.is 000~099。
tt :The information type of reply parameter
Information Information Keyboard controller
Information type
type tt range display form
Can read-wirte
0 00000~65535 point two-digit
and store
Can read-wirte
1 00000~65535 point one-digit
and store
-120-
WL-9000 Series Sensor-Less Vector Frequency Converter

Can read-wirte
2 00000~65535 Integer
and store
Can read-wirte
3 00000~00255 point two-digit
and store
Can read-wirte
4 00000~00255 point one-digit
and store
Can read-wirte
5 00000~00255 Integer
and store

Can read-wirte
6 00000~00001 Interge
and store
Can read-wirte
7 00000~65535 Interge
but can not store
point two-digit,
-if number value
8 Only read 00000~65535 greater than 32767,
need to remend to
(65536~ddddd)
9 Only read 00000~65535 point two-digit
10 Only read 00000~65535 point one-digit
11 Only read 00000~65535 Interge
12 Only read 00000~00255 point two-digit
13 Only read 00000~00255 point one-digit
14 Only read 00000~00255 Interge
15 Only read 00000~00001 Interge
16 Only read 00000~00015 Interge,Binary
17 Only read 00000~00007 Interge,Binary
18 Only read 00000~00003 Interge,Binary
19 Only read 00000~01023 Interge

-121-
WL-9000 Series Sensor-Less Vector Frequency Converter

20 Only read 00000~FFFF Interge,Hex


22 Only read 00000~FFFF Interge,Hex

ddddd: Parameter value of reply(00000~65535)。


S : reply about the output state of frequency converter
S=1: frequency converter is reverse running output
S=2: frequency converter is forward running output
S=3: frequency converter stops
S= other value,undefinition
aaaa: reply about the cureent four times of fault record of frequency converter
(0000~9999)
four numbers stand for the code record of current four times of fault:
a of thousand-digit: The code stands for the present fault state.
a of hundred-digit: The code stands for the first time fault state.
a of ten-digit:The code stands for the second time fault state.
a of unit-digit:The code stands for the third time fault state.

z The meaning of fault code is in Chapte 9.

7.3.3Modbus communication form


HPI6000 series built-in standard Modbus communication form, and HPI6000
Modbus communication form,by through Modbus communication interface and
human,PC,PLC will be connected directly.

Chapter 8 PID function


8.1 PID parameter
The adjustment function of PID: The PID controller built-in frequency converter
will detect the physical quantity (feedback quantity) by through the sensor of control
-122-
WL-9000 Series Sensor-Less Vector Frequency Converter

object, then make this physical quantity compare with system specified rate. If there is
bias, it will make the bias as zero by through PID adjustment function. This is normal
process control way for keep the feedback quantity and specified rate as the same .

z When using PID function, could not use other function


related to F073~F077.

F073 PID input option


Made up by two groups of interge X and point Y .Interge X will choose the source
of PID set value, point Y will choose the source of PID feedback value. The optional
source of PID set value and PID feedback value as the following:
Set value Instruction

0 Fixed value, F027 set(0.00~100.00%)

1 Analogy input AI1 is source ,0~+5V→0~0DI7FFF

2 Analogy input AI2 is source,0~+5V→0~0DI7FFF

3 Analogy input AI3 is source,0~+5V→0~0DI7FFF

4 Analogy input AI1 is source,+5V~0→0~0DI7FFF

5 Analogy input AI2 is source,+5V~0→0~0DI7FFF

6 Analogy input AI3 is source,+5V~0→0~0DI7FFF

X2(28)pulse input,computation way :0 DI 7FFF*(per 13.2ms total pulse number


10
/F071)

F028 PID bias set(0.1~100.0%)


F029 PID gain set(0.0~500.0%)
F074 PID output value set in advanced(0.1~100.0%)
F075 PID`s P gain
F076 PID`s I gain
F077 PID`s D gain

-123-
WL-9000 Series Sensor-Less Vector Frequency Converter

8.2 PID digital input function option


Xn Function Instruction

PID function When input terminal Xn(50)is ON,start up PID function


50
starting When input terminal Xn(50)is OFF,stop PID function

PID integrating When input terminal Xn(51)is OFF, integrating normal treatment 。
51
keeping When input terminal Xn(51)is ON,integrating keeping

PID integrating When input terminal Xn(52)is ON, clear up PID integrating value.
52
clearup

PID output value set in When input terminal Xn(53)is ON,set PID integrating value
53
advanced in advanced as the set value of F074.

When input terminal Xn(54)is ON,bias quantity = bias input starting

54 PID bias starting (refer to 8.3)

When input terminal Xn(54)is OFF,bias quantity =0

When input terminal Xn(55)is ON ,PID special gain = F029 set value

(0.0~500.0%)

55 PID gain starting When input terminal Xn(55)is OFF,PID special gain =100.0%

When input terminal Xn(55)is ON,PID output will keep former output

value, is similar as Xn(51)function.

8.3 PID speed source option


F040 Frequency set option

40 Frequency set =PID output (F040=40)

When input terminal Xn(54)is ON,frequency set= PID gain* (PID output +PID bias *

48 AI1)

When input terminal Xn(54)is OFF,frequency set =PID output

When input terminal Xn(54)is ON,frequency set = PID gain *(PID output +PID bias *

49 AI2)

When input terminal Xn(54)is OFF,frequency set =PID output

-124-
WL-9000 Series Sensor-Less Vector Frequency Converter

When input terminalXn(54)is ON,frequency set = PID gain *(PID output +PID bias *

50 AI3)

When input terminal Xn(54)is OFF,frequency set =PID output

When input terminal Xn(54)is ON,frequency set = PID gain *(PID output +PID bias *

51 F028)

When input terminal Xn(54)is OFF,frequency set =PID output

8.4 Analogy output function


F037 AM terminal AM output

output signal

7 PID output AM=5V*(PID output)

PID+AI1 When Xn(54)ON,5V*(PID gain *(PID output +PID bias *AI1)


),
8
bias input When Xn(54)OFF,5V*(PID output)

PID+AI2 When Xn(54)ON,5V*(PID gain *(PID output +PID bias *AI2)


),
9
bias input When Xn(54)OFF,5V*(PID output)

PID+AI3 When Xn(54)ON,5V*(PID gain *(PID output +PID bias *AI3)


),
10
bias input When Xn(54)OFF,5V*(PID output)

PID+F028 When Xn(54)ON,5V*(PID gain *(PID output +PID bias * F028))



11
bias input When Xn(54)OFF,5V*(PID output)

8.5 PID simple application example


8.5.1 If feedback channel choose AI1(0~10V),the range ability of remote pressure
meter is 0~1Mpa.
8.5.2 Wiring
1) X1 is short-circuit with common port COM
8.5.3 The set parameter as following :
1) F039 is according to actual requirement, normally be set as outer terminal
control, that is F039=2;
2) F040=40 output frequency is decided by PID output;
3) F041=50 PID starting up,that is, X1 function option is PID stating
-125-
WL-9000 Series Sensor-Less Vector Frequency Converter

function ;
4) F073=0.1 PID input option,
0 means the PID set value source,decided by F027
1 means PID feedback value source,analogy input AI1 is source;
5) F027=50% set value source PID(system required voltage is 0.5Mpa)。
8.5.4 Test running:close operational signal, that is, X6(REV)~DCOM
are close, frequency converter is operating under PID state.

-126-
WL-9000 Series Sensor-Less Vector Frequency Converter

8.6 PID Basic structure chart

-127-
WL-9000 Series Sensor-Less Vector Frequency Converter

Chapter 9 Normal Fault、Abnormity and


Countermeasure
9.1 Fault code and countermeasure
Form 9-1 Normal fault code and countermeasure
ERROR Fault
Fault explanation Countermeasure
display code

-- 0 Normal,no fault

①Extend acceleration time


②Reduce load inertia
over-current in ③Reduce torque hoist
CA 1
acceleration ④Examine input power source
⑤Choose the starting way as speed
trace starting
①Deceleration time too short
over-current in
CD 2 ②Load inertia over great
deceleration
③Frequency conveter`s power samller
①Examine input power source
over-current in
OC 3 ②Reduce load breaking
operating
③Change a greater power unit
Frequency converter ①Examine load current
OH 4
over-heat ②Reduce carrier frequency
①Examine input power source
Power source ②Check the set value of F084 input
OP 5
voltage over-high AC power-source voltage
③Extend deceleration time
①Check input power source
Power source
UP 6 ②Check the set value of F084 input
voltage over-low
AC power-source voltage

OL 7 Over-load Examine load current

over-current in DC
CB 8 Amend parameter F005~F008
braking
software detecting
CS 9 Examine current sensor
over-current
Memorizer self-detection
SE Change the main CPU panel
fault

-128-
WL-9000 Series Sensor-Less Vector Frequency Converter

9.2 Abnormity and Countermeasure

Form 9-2 Abnormity and Countermeasure

Abnormity Conceivable reasons Countermeasure


① network over-low voltgae or
① Check the network voltage;
No any display failure-phase ;
② Looking for service ;
after power-on ② DC auxiliary power fault ;
③ Looking for service;
③ Charging resistor damaged;
①Input side of frequency ① Examine wiring or looking for
Power source converter short-circuti; service;
trip ② Capacitor of circuit breaker too ② Enlarge the capacitor of circuit
small; breaker;
① Wrong wiring;
① Check wiring;
Motor not ② Operating way is set wrong;
② Reset the operating way;
running ③ Over-load or motor blockage
③ Reduce load or adjust motor state;
running;
Motor reverse ① Adjust any two phase output
① Wiring phase of motor wrong;
running wiring of U,V,W;
①Acceleration/deceleration time set
① Reset acceleration/
illsuited ;
deceleration time;
②Stall over-current point is set
Motor could ② Enlarge the set value of stall
over-low;
not accelerate over-current point;
③Carrier frequency set
or decelerate ③ Reduce carrier frequency;
illsuited or appears surge ;
④ Reduce load or change greater
④over-heavy load;
power of frequency converter;

rotate speed ① Load wave over greatly; ① Reduce load wave;


wave when ② Motor over-load protection ② Enlarge motor over-load
motor is coefficient is set too small; protection coefficient;
steady-state ③ Frequency set potentiometer is ③ Change the potentiometer or
running poor contact; looking for service;

z When be Error warning state, must check the system


carefully and parameter according to the Manual. Press
“STOP/RESET” to reset

-129-
WL-9000 Series Sensor-Less Vector Frequency Converter

Chapter 10 Examining and Maintenance


10.1 Notices of examining and maintenance
It is necessary to do the daily and regular inspection and maintenance to the
frequency converter, because that frequency converter operates for a long time and
influenced by ambient temperature, humidity, dust or vibration, or the reason of
compontents aging and abrasion, all will make the frequency converter be in latency
trouble.

● Only special technical operator could do the inspection,


maintenance,in case of accident.
● At least 10 minutes after cutting off the power source, could
do the inspection and maintenance,in case of electric shock
accident.
● Make sure indication lamp of control keyboard go out. Open
the panel, then make sure that the charging lamp on the right
side of main-circuit terminal go out.
● Must use insulated tools when inspecting, and please do not
operate by the dank hands, in case of accident.
变频器检查项目一览表
● Keep the equipment neat and clean.
● Do not use the product in the situation of dank or oily. The
dust or other things will break down the isolation and lead to
unexpected accident. Must be carefull!

-130-
WL-9000 Series Sensor-Less Vector Frequency Converter

10.2 Daily inspected items


Form 10-1 Daily inspected items

Inspected Inspected Inspection


Inspection method Eligibility standard Used instrument
object items period

●Ambient ●Thermometer
temperature ●Thermometer ●Ambient ●Hygrometer
●Humidity, examine Temperature
Operating dust, corrodibility ●Smell is -10~40℃ no frost
and oil mist Daily
enviroment examine ●Humidity
●Vision 20-90%,
examine no peculiar smell

●Vibrate stable
● Vibration ●Touch cover ●Normal
Frequency
● Heat Daily ●Auditory temperature
converter
● Noise examine ●No abnormal
noise
●Vibrate stable
● Vibration ●Touch cover ●Normal
Motor ● Heat Daily ●Auditory temperature
● Noise examine ●No abnormal
noise
●Moving-iron
●Every electric voltmeter
●Input voltage
Electric ●Ammeter parameter within ●Rectifier
●Output voltage Daily
parameter examine range voltmeter
●Output current
rated value ●Clip-on
ammeter

10.3 Regular inspection items

z During inspection, could not dismount or shake compontents,


even could not take away connectors, otherwise will lead to
damage to frequency converter.
z Please do not leave the inspection tools (likes screwdriver) into
the product after inspection, or else will damage to frequency
converter.

-131-
WL-9000 Series Sensor-Less Vector Frequency Converter

Form 10-2 Regular inspected items

Inspected Inspected Inspection Eligibility


Inspection period Used instrument
object items method standard

● Whether ●The connection no


connection and loosened and terminal is
terminal firm.
● Vision
The whole Loosened Regular
examine
● Whether ●No compontents be
compontents be burned
burned
Main power ● Whether Regular ●Vision ● No damaged
module damaged examine
● whether leak ● No leak
Filter ●Vision
Regular
capacitor ● whether examine ● No swelled up
swelled up
● Whether the ● Voice is normal
Main circuit

voice of ●Auditory
switching on is examine
Contactor Regular
abnormal
● Dust clearup ●Vision ● Clean and neat
examine
●whether has cleft ● No cleft
●Vision
Resistor ● whether Regular ● Normal colour
examine
colour is
abnormal
●whether ●Normal voice, vibrate
●Auditory
noise and steady
examine
vibration is
Fan Regular
abnormal
●Vision
● Dust clearup examine ● Clean and neat

● Dust clearup ●Vision ●Clean and neat


PCB panel Regular
examine
● whether ● Firm and no
FPC Regular
loosened loosened
Control circuit

●whether has ●Normal smell, no colour


abnormal smell ●Vision changing
or colour examine
The whole changing Regular
● whether has cleft ●No cleft
● Smell
examine
● whether ●Vision ●Display normal and clear
LED Regular
K
e display normal examine
y ● whether ● No scratched
scratched
b
Connection ● Vision
o
a Regular
r
d wires ● whether firm examine ● Firm and no
loosened

-132-
WL-9000 Series Sensor-Less Vector Frequency Converter

10.4 The storing of frequency inverter


Please pay the following attentions for the storing of frequency inverter

z Do not store the product at the place of high-temperature, dank


and dusty, and make sure well airiness.
z The frequency converter not used for long time will cause
the filter characteristic of electroanalysis capacitor poorer, must make
Attention
sure one power-on within 2 years, and time of power-on is not less
than 5 hours. Must use voltage regulator to raise the input voltage to
the rated value, and check whether the function is normal, circuit is
short-circuit. If above problems happen to, please remove earlily or
look fro service.

10.5 The guarantee to frequency inverter

-133-
WL-9000 Series Sensor-Less Vector Frequency Converter

Chapter 11 Application example


The following application example is for reference .

11.1 Example 1: Keyboard controls the frequency converter starting and stopping,
keyboard potentiometer set the frequency.

Drawing 11-1 The connection drawing of example1

— F039 control way option:set as “0”——keyboard operation;

— F040 frequency set option:set as “25”——keyboard potentiometer set;

— Use the 、 keys for starting up to operate and decelerating to

stop;

— Turn the keyboard potentiometer to adjust speed.

11.2 Example 2: Outer terminals control frequency converter starting and stopping,
outer potentiometer sets the frequency.

-134-
WL-9000 Series Sensor-Less Vector Frequency Converter

Drawing 11-2 Connection drawing of example 2

— F039 control way option:set as 2——Outer terminals control;


— F040 frequency set way:set as 1——Outer voltage signal AI1(0 ~ 10V)
— FWD~DCOM close,motor is forward running;REV~DCOM close,
motor is reverse running;
— FWD~DCOM or REV~DCOM switch off ,frequency converter stops;
— Adjust the AI1 potentiameter for speed adjustment.
— Please note the set of jump-wire terminal, the ex-factory value could meet
the requirement.

-135-
WL-9000 Series Sensor-Less Vector Frequency Converter

11.3 Example 3:Outer terminals control frequency converter starting and stopping,
multi-step speed operating way.

Drawing 11-3 The connection drawing of example

— F041=80,F042=81,F043=82,F044=83——(X1~X4 function option)


—— set as “multi-step speed control”;
— F019,F021,F024,F027---- multi-step speed frequency set, total 16 steps
of frequency:
— FWD~COM close, motor is forward running;REV——COM close,
motor is reverse running;FWD、REV~COM switch off ,frequency
converter stops;
— Any one or severls of X1~X4 and COM close(total 15 kinds of
combination ), the frequency converter will operate according to the
multi-step speed frequency set by X1~X4.

-136-
WL-9000 Series Sensor-Less Vector Frequency Converter

— The function form of X1~X3 making up to 8-step speed:


Frequency Step speed X3(F024) X2(F021) X1(F019)
F000 1 0 0 0
F019 2 0 0 1
F021 3 0 1 0
F024 4 1 0 0
F019+F021 5 0 1 1
F019+F024 6 1 0 1
F024+F021 7 1 1 0
F019+F021+F024 8 1 1 1

11.4 Example 4 : The proportion interlocking operating control of


Multi-pieces frequency converter

11-4 Example 4 wiring drawing


For example:ask the three motors to run according to the proportion of 1:0.5:
0.2. When AI2 input is minimum value, output frequency =100%-F070*F015,the
number “1” is corresponding to frequency 50Hz,and need having fine-tuning function.
Frequency 1 set as the following:
— F039 control way option:set as 2—as outer terminal control;
— F040 frequency set option:set as 12— proportional inlocking input;
— F070 proportional interlocking set:set as 0—choose the proportional input

-137-
WL-9000 Series Sensor-Less Vector Frequency Converter

of AI2 input as “zero”,i.e, AI1 input is “1”,(note: F015=50Hz “1” value


is corresponding to frequency 50HZ);
Frequency 2 set as the following:
— F039 control way option:set as 2—as outer terminal control;
— F040 frequency set option:set as 12— proportional inlocking input;
— F070 proportional interlocking set:set as 50——choose the proportional
input of AI2 input as 50%,i.e, AI1 input is 50%(note F015=50Hz “0.5”
value is corresponding to frequency 25Hz);
Frequency 2 set as the following:
— F039 control way option:set as 2—as outer terminal control;
— F040 frequency set option:set as 12— proportional inlocking input;
— F070 proportional interlocking set:set as 80——choose the proportional
input of AI2 input as 80%,i.e, AI1 input is 20%(note F015=50HZ “0.2”
value is corresponding to frequency 10Hz);
— Potentiameter 1,Potentiameter 2,Potentiameter 3,Could do the exact
fine-tuning to every frequency converter.
11.5 Example 5 The special using of F039

-138-
WL-9000 Series Sensor-Less Vector Frequency Converter

F039 Operational control way option F039 = 0.2


F041 DI1 terminal input function option F041=89

— F039 =a.b F039 in above example is set as 0.2


F039=0.2 the integer part is the content of a:in above parameter, a=0 means
operating control command is decided by keyboard. Press“FWD”key to control
frequency converter forward running, press“REV”key,frequency converter is
reverse running, press“STOP”key,frequency converter stops operating.
F039=0.2 the point part is the content of b:in above parameter , b=2 means
the operating control command is decided by FWD terminal to control frequency
converter operating or stopping; and by REV terminal to control frequency
converter reverse running.
Well then, when the F039 execute “a” function and “b” function?
— F041=89 means DI1 terminal function chooses “89”function,
When X1~DCOM are switching off,F039 operating control command=a
When X1~DCOM are close,F039 operating control command =b
In above example: when X1~COM are switching off, press FWD or REV
key on the keyboard to realize forward or reverse running, press STOP key to
stop;when X1~COM are close, use FWD~COM or REV~COM close or
switching off to decide frequency converter operating or stopping.
11.6 Example 6 The special using of F040

-139-
WL-9000 Series Sensor-Less Vector Frequency Converter

F040 Frequency set option F040 = 8.25


F042 terminal input function option F041=88

— F040 =cc.dd the F040 in above example is set as 8.25


F040=8.25, The integer part is the content of cc: in above parameter,cc=8
means the frequency set option function is “8”, that is, the frequency is set by F000
value when power-on.
F040=8.25, The point part is the content of dd: in above parameter, dd=25
means the frequency set option function is “25”, that is, the frequency is set by
keyboard potentiometer after operating.
Well then, when the F040 execute “cc” function and “dd” funcgtion?
— F042=88 means X2 terminal function chooses “88”function,
When X2~DCOM are switching off,F040 operating control command=cc
When X2~DCOM are close,F040 operating control command =dd
In above example: when X2~COM are switching off,frequency set is
decided by F000 parameter;when X2~COM are close, frequency is decided by
keyboard potentiometer.
— If F040 is set as 8.25, when if such X2、X5、X6、DCOM multifunction
digital input terminal function is not set as “option control command and speed
command ” function,then frequency is decided by integer part 8, and at this moment
the function of point part could realize.

-140-
WL-9000 Series Sensor-Less Vector Frequency Converter

11.7 Example 7 Use UP/DOWN terminal to decide operational


Frequency

Parameter set :F040=6 F41=19 F42=20


Parameter explanation:when F040=6,the operational frequency is decided by the
built-in up/down counter.
When X1 and DCOM are close,the operational frequency increasing;
When X2 and DCOM are close,the operational frequency decreasing;

-141-