3% AFFF

Foam Concentrate

Chemguard 3% AFFF is a specially formulated, • Bladder tank balanced pressure proportioning


synthetic, aqueous film forming foam concentrate. systems
A vapor suppressing aqueous film is formed by the
• Around the pump proportioners
foam solution draining from the expanded foam
blanket. It is intended for use at a proportioning • Handline, air-aspirating nozzles with fixed
rate of 3% (3 parts AFFF concentrate to 97 parts eductor pickup tube
water) on Class B hydrocarbon type fuels such as
gasoline, kerosene, diesel, etc. Chemguard 3% DISCHARGE DEVICES
AFFF is not intended for use on fuels, which are
polar solvent/water miscible such as alcohols, • Foam Chambers
ketones, esters, etc.
• Air-aspirating and non air-aspirating sprinkler
FEATURES heads or spray nozzles
• Standard water fog nozzles for handlines and
• U.L. Listed, Foam Liquid Concentrates monitors
• U.L. recommended application rate on • Air-aspirating foam nozzles
hydrocarbon type fuels is .10/gpm ft².
• Foam makers for use with either Floating Roof
• U.L. Canada Listed storage tanks or Dike/Bund protection systems
• Performance to ICAO, Doc. #9137, Part 1, • High back pressure foam makers for sub-
Chapter 8, Level “B” verified surface base injection system (hydrocarbon type
fuels only)
• Suitable for use with fresh or salt water
• Excellent wetting characteristics when used in APPLICATIONS
combating Class “A” fuel fires
• Crash Fire Rescue
• Suitable for use with both aspirating foam and
standard water fog nozzles • Storage Tanks(non-polar solvent type fuels only)
• Suitable for use with deluge or closed head • Truck/Rail Loading or Unloading Facilities
foam water sprinkler systems
• Processing/Storage Facilities
• If inadvertently frozen, thawing will render
• Docks/Marine Tankers
product completely serviceable again
• Flammable Liquid Containment Areas
• Suitable for use with carbon steel, fiberglass,
polyethylene or stainless steel. Chemguard 3% • Mobile Equipment
AFFF is not compatible with galvanized pipe or
fittings in an undiluted form. FOAMING PROPERTIES
• Suitable for use with siliconized dry chemical
extinguishing agents Aspirating type discharge devices typically generate
expansion ratios between 6-10 to 1 when 3% AFFF
PROPORTIONING is mixed with water at the correct ratio. Non-
aspirating type devices will typically generate
• Fixed or portable in-line eductors expansion ratios of between 2-4 to 1. Expansion
• In-line balanced pressure and pump pressure ratios are dictated by the type of discharge devices,
proportioning skid flow rate and discharge pressure.

CHEMGUARD
th
204 S. 6 Ave • Mansfield, Tx 76063 • (817) 473-9964 • FAX (817) 473-0606
www.chemguard.com
DATA SHEET #D10D03015R2
REVISION: 09/2005
TYPICAL PROPERTIES AT 77ºF (25ºC)

Appearance....………………….Clear Slightly Yellow


Specific Gravity….……………………………….1.020
pH….…………………………………………………7.7
Viscosity....……………………………………..1.5 cps

ENVIRONMENTAL IMPACT

Chemguard 3% AFFF is biodegradable, low in


toxicity and can be treated in sewage treatment
plants. Please refer to Chemguard Technical
Bulletin regarding foam products and the
environment.

STORAGE

If kept in the original unopened and airtight


Chemguard supplied container and stored within
the temperature range of 35ºF-120ºF (2ºC - 49ºC) a
shelf life of between 20-25 years can be expected.
When stored in other than the manufacturers
supplied container, please check with Chemguard
for storage guidelines.

ORDERING INFORMATION & WEIGHT

Part No: Container Weight


C303P 5-Gallon Pail / 19 Liters 45 lbs.
C303D 55-Gallon Drum / 208 Liters 495 lbs.
C303BD 330-Gallon Tote / 1249 Liters 3000 lbs.

CHEMGUARD
th
204 S. 6 Ave • Mansfield, Tx 76063 • (817) 473-9964 • FAX (817) 473-0606
www.chemguard.com
DATA SHEET #D10D03015R2
REVISION: 09/2005
MATERIAL SAFETY
DATA SHEET

CHEMGUARD 3% AFFF C-303 Revision Date: 1/25/2006

1. PRODUCT IDENTIFICATION
Chemical Family: Surfactant mixture; fire fighting foam concentrate
Aqueous Film Forming Foam

Product name: Chemguard 3% AFFF C-303

Manufacturer: Chemguard, Inc.


204 South 6th Ave.
Mansfield, TX 76063
emergency phone: 817-473-9964

2. COMPOSITION / INFORMATION ON INGREDIENTS


ACGIH/PPM OSHA/PPM
CAS NO. Common Name TWA STEL PEL % by wt
7732-18-5 water 85% - 90%
57018-52-7 propylene glycol t-butyl ether not established 2% - 4%
7487-88-9 magnesium sulfate N/A N/A N/A 1% - 2%
proprietary mixture proprietary hydrocarbon surfactant N/A N/A N/A proprietary
proprietary mixture proprietary fluorosurfactant N/A N/A N/A proprietary

3. HAZARDS IDENTIFICATION
Routes of entry: Dermal, inhalation and ingestion
Potential Health Effects: May cause skin and eye irritation.

Carcinogenicity: Not a carcinogen.

4. FIRST AID MEASURES


Ingestion: Do not induce vomiting. Call a physician.
Inhalation: Remove to fresh air.
Skin: Rinse with water. Wash with soap and water. Contaminated clothing should be washed
before re-use.
Eyes: Rinse with water. Call a physician.

Page 1 of 4
5. FIRE FIGHTING MEASURES

Flash Point: >150°F


Flammable Limits in air (lower % by volume): not evaluated
Flammable Limits in air (upper % by volume): not evaluated
Auto-ignition Temperature: not evaluated

General Hazards: None known.


Fire Fighting Equipment: Self contained breathing apparatus
Fire Extinguishing Media: Water, Foam, Carbon Dioxide, Dry Chemical, Halon
Fire and Explosion Hazards: Decomposition products may be toxic.
Hazardous Combustion Products: oxides of nitrogen, sulfur and carbon

6. ACCIDENTAL RELEASE

Contain spills. Vacuum or pump into storage containers, absorb smaller quantities
with absorbent materials, and dispose of properly. Washing area with water will create large
amounts of foam.

Dispose of released and contained material in accordance with local, state, and federal
regulations. Release to local waste treatment plant only with permission.

7. HANDLING AND STORAGE

Store in original container, or appropriate end-use device. Store at temperatures of 35 - 120


degrees F. If the material freezes, it may be thawed without loss of performance.

8. EXPOSURE CONTROLS, PERSONAL PROTECTION

Eye Protection: Wear side-shield safety glasses.


Skin Protection: Wear latex gloves.
Respiratory Protection: Use organic vapor respirator if needed.

9. PHYSICAL AND CHEMICAL PROPERTIES

Boiling Point: 205° - 212°F


Melting Point: 30° F
Specific Gravity: 1.012 g/ml
Vapor Pressure (mm Hg): N/A
pH 7.0 - 8.5
Flash Point (PMCC): >150°F
Vapor Density (air = 1) N/A
Solubility in water: 100%
Appearance: clear amber liquid
Odor: slight solvent odor

Page 2 of 4
10. STABILITY AND REACTIVITY

Stability: Stable
Incompatibility: Strong oxidizers
Hazardous Polymerization: Will not occur.
Decomposition Products: Oxides of nitrogen, sulfur, carbon.

11. TOXICOLOGICAL INFORMATION

Eye Irritation: (Rabbits) mild irritant


Skin Irritation: (Rabbits) minimal irritant
Inhalation Toxicity: not evaluated
Sensitization: not evaluated
Teratology: not evaluated
Mutagenicity: not evaluated
Reproduction: not evaluated
Acute Oral Effects (Rats): not evaluated

12. ECOLOGICAL INFORMATION


CONCENTRATE SOLUTION (AS USED)
Chemical Oxygen Demand: 210,000 mg/l 6,300 mg/l
Biological Oxygen Demand (20 day): 79,800 mg/l 2,394 mg/l
Biodegradability (B.O.D./C.O.D.) 38% 38%
Total Organic Carbon: 33,600 mg/l 1008 mg/l
LC50 (96 hour pimephales promelas) 233 ppm 7767 ppm
LC50 (48 hour, daphnia magna) 1110 ppm 37,000 ppm

13. DISPOSAL CONSIDERATIONS

Dispose in accordance with local, state, and federal regulations. Discharge to waste treatment
plants only with permission. Anti-foam agents may be used to reduce foaming in waste streams.

14. TRANSPORTATION INFORMATION

Department of Transportation proper shipping name: not regulated

15. REGULATORY INFORMATION

All ingredients are on the TSCA inventory.


No components are reportable under SARA Title III, sec. 313
No components are priority pollutants listed under the U.S. Clean Water Act Section 307 (2)(1)
Priority Pollutant List (40 CFR 401.15).
No components are reportable under CERCLA.

16. OTHER INFORMATION

NFPA Hazard Ratings HMIS Identification System


1 Health Hazard Rating 1
1 Flammability Rating 1
0 Instability/Reactivity Rating 0

CHANGE LOG:
Page 3 of 4
Revision 2 - Revision date changed.

Page 4 of 4
MATERIAL SAFETY
DATA SHEET

CHEMGUARD 3% AFFF C-303 Revision Date: 1/25/2006

1. PRODUCT IDENTIFICATION
Chemical Family: Surfactant mixture; fire fighting foam concentrate
Aqueous Film Forming Foam

Product name: Chemguard 3% AFFF C-303

Manufacturer: Chemguard, Inc.


204 South 6th Ave.
Mansfield, TX 76063
emergency phone: 817-473-9964

2. COMPOSITION / INFORMATION ON INGREDIENTS


ACGIH/PPM OSHA/PPM
CAS NO. Common Name TWA STEL PEL % by wt
7732-18-5 water 85% - 90%
57018-52-7 propylene glycol t-butyl ether not established 2% - 4%
7487-88-9 magnesium sulfate N/A N/A N/A 1% - 2%
proprietary mixture proprietary hydrocarbon surfactant N/A N/A N/A proprietary
proprietary mixture proprietary fluorosurfactant N/A N/A N/A proprietary

3. HAZARDS IDENTIFICATION
Routes of entry: Dermal, inhalation and ingestion
Potential Health Effects: May cause skin and eye irritation.

Carcinogenicity: Not a carcinogen.

4. FIRST AID MEASURES


Ingestion: Do not induce vomiting. Call a physician.
Inhalation: Remove to fresh air.
Skin: Rinse with water. Wash with soap and water. Contaminated clothing should be washed
before re-use.
Eyes: Rinse with water. Call a physician.

Page 1 of 4
5. FIRE FIGHTING MEASURES

Flash Point: >150°F


Flammable Limits in air (lower % by volume): not evaluated
Flammable Limits in air (upper % by volume): not evaluated
Auto-ignition Temperature: not evaluated

General Hazards: None known.


Fire Fighting Equipment: Self contained breathing apparatus
Fire Extinguishing Media: Water, Foam, Carbon Dioxide, Dry Chemical, Halon
Fire and Explosion Hazards: Decomposition products may be toxic.
Hazardous Combustion Products: oxides of nitrogen, sulfur and carbon

6. ACCIDENTAL RELEASE

Contain spills. Vacuum or pump into storage containers, absorb smaller quantities
with absorbent materials, and dispose of properly. Washing area with water will create large
amounts of foam.

Dispose of released and contained material in accordance with local, state, and federal
regulations. Release to local waste treatment plant only with permission.

7. HANDLING AND STORAGE

Store in original container, or appropriate end-use device. Store at temperatures of 35 - 120


degrees F. If the material freezes, it may be thawed without loss of performance.

8. EXPOSURE CONTROLS, PERSONAL PROTECTION

Eye Protection: Wear side-shield safety glasses.


Skin Protection: Wear latex gloves.
Respiratory Protection: Use organic vapor respirator if needed.

9. PHYSICAL AND CHEMICAL PROPERTIES

Boiling Point: 205° - 212°F


Melting Point: 30° F
Specific Gravity: 1.012 g/ml
Vapor Pressure (mm Hg): N/A
pH 7.0 - 8.5
Flash Point (PMCC): >150°F
Vapor Density (air = 1) N/A
Solubility in water: 100%
Appearance: clear amber liquid
Odor: slight solvent odor

Page 2 of 4
10. STABILITY AND REACTIVITY

Stability: Stable
Incompatibility: Strong oxidizers
Hazardous Polymerization: Will not occur.
Decomposition Products: Oxides of nitrogen, sulfur, carbon.

11. TOXICOLOGICAL INFORMATION

Eye Irritation: (Rabbits) mild irritant


Skin Irritation: (Rabbits) minimal irritant
Inhalation Toxicity: not evaluated
Sensitization: not evaluated
Teratology: not evaluated
Mutagenicity: not evaluated
Reproduction: not evaluated
Acute Oral Effects (Rats): not evaluated

12. ECOLOGICAL INFORMATION


CONCENTRATE SOLUTION (AS USED)
Chemical Oxygen Demand: 210,000 mg/l 6,300 mg/l
Biological Oxygen Demand (20 day): 79,800 mg/l 2,394 mg/l
Biodegradability (B.O.D./C.O.D.) 38% 38%
Total Organic Carbon: 33,600 mg/l 1008 mg/l
LC50 (96 hour pimephales promelas) 233 ppm 7767 ppm
LC50 (48 hour, daphnia magna) 1110 ppm 37,000 ppm

13. DISPOSAL CONSIDERATIONS

Dispose in accordance with local, state, and federal regulations. Discharge to waste treatment
plants only with permission. Anti-foam agents may be used to reduce foaming in waste streams.

14. TRANSPORTATION INFORMATION

Department of Transportation proper shipping name: not regulated

15. REGULATORY INFORMATION

All ingredients are on the TSCA inventory.


No components are reportable under SARA Title III, sec. 313
No components are priority pollutants listed under the U.S. Clean Water Act Section 307 (2)(1)
Priority Pollutant List (40 CFR 401.15).
No components are reportable under CERCLA.

16. OTHER INFORMATION

NFPA Hazard Ratings HMIS Identification System


1 Health Hazard Rating 1
1 Flammability Rating 1
0 Instability/Reactivity Rating 0