CONTEG - Operating Manual v3 2 EN
CONTEG - Operating Manual v3 2 EN
230/1/50(60)
Issue 3.20en
OPERATING INSTRUCTIONS
This page is intentionally left blank.
© 2010 CONTEG. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted or stored in
any retrieval system of any nature, without the written permission of the copyright owner.
Page 2 of 94
Table of contents
1. Safety Directions ......................................................................................................................... 6
5. Installation .................................................................................................................................... 23
6. Start-up ......................................................................................................................................... 35
Page 3 of 94
7.12 System maintenance .............................................................................................. 70
7.13 Remote monitoring ................................................................................................. 73
8. Maintenance .................................................................................................................. 76
8.1 Safety instructions ................................................................................................... 76
8.2 Preventive maintenance program ........................................................................... 76
8.3 Air circuit ................................................................................................................. 77
8.4 Water circuit ............................................................................................................ 78
8.5 General appliance cleaning procedures ................................................................. 78
Page 4 of 94
IMPORTANT
These operating instructions must be read with care and fully complied with prior to
installing and using the air conditioning system.
Preserve this manual for the entire working life of the model.
This manual reflects the state of the art at the time the product is marketed. It must
not be considered unsuitable merely because it has not been updated following
developments in design and manufacturing methods.
CONTEG reserves the right to update the product and the relevant manual without
having to update products and manuals sold previously except under exceptional
circumstances.
Contact your local CONTEG partner when requesting or receiving any up-dates of
instruction manuals or corrections which are considered to be integral parts of the
manual.
Page 5 of 94
1. Safety Directions
This manual contains the basic instructions which must be respected during installation, use and
maintenance of the unit. Therefore, installer and specialized personnel / user must read and
respect these indications before mounting and commissioning the unit.
Read carefully the whole information on this manual, with particular attention to the
norms marked with the symbol on the left. Failure of conformity to these norms
might cause damages to things, people, ambient and the unit itself.
The manufacturer is not responsible for any misuse of air conditioner, as well as for non-
authorized modifications and for the inobservance of instructions on this manual.
This manual must be kept by the customer and made available to the installation,
commissioning, use and maintenance personnel.
Page 6 of 94
General information
This air conditioning unit has been designed and built for a professional use according to
applicable regulations. Please check the complete list of applicable regulations to the attached
CE conformity declaration. It has been manufactured with high quality components, tested to
certify its reliability and safety (see attached test report), and provided with warranty.
These operating instructions include the basic directions that must be complied with during
system installation, operation and maintenance. Consequently both the installer and assigned
specialized personnel/operators must read and comply with these directions before proceeding
with installation and start-up. The instruction manual must always be available at the site where
the system is being used.
• Observe the national regulations of the country where the unit will be
installed
• For transport, installation, either ordinary or extraordinary
maintenance, operators and maintenance people must wear
individual protection device (i.e. gloves, glasses, helmet, shoes),
according to the indications of safety manager and applicable
regulations. Cooling water additives have an additive effect on skin
and eyes. Wear safety glasses and safety gloves
• The unit may only be used to cool according to the CONTEG
specification.
• Before any maintenance operation, read and follow instructions in
the corresponding chapter.
Page 7 of 94
Safety and environmental requirements
The following requirements relate to the operation of refrigerating plants within the European
Community.
• The used components must correspond to the pressure equipment guide-line EC/97/23 and
EN 378 part 1-4.
• Independent of the design, the equipment and inspection before the delivery, also the
operator of such plants has duties according to EN 378 and national regulations.
This concerns the installation, the operation and the repeated inspection:
• Installation: according to EN 378
• Operation: Determination of emergency measures (accidents, malfunctions)
Creation of an abbreviated instruction and notification (template page)
a. A unit protocol must be kept.
b. To be stored in the proximity of the unit
c. Access for competent staff in case of repairs and repeated inspection must
be ensured.
• Repeated inspection: according to EN 378
The operator is responsible for the execution.
The operator must ensure that all maintenance, inspection and assembly work is carried out by
authorized and qualified specialist staff who have made an in-depth study of the operating
instructions.
It is absolutely essential to comply with the procedure for shutting down the system described in
the operating instructions. Before maintenance work, the unit must be switched off at the main
switch and a warning sign displayed to prevent unintentional switching-on.
Page 8 of 94
2. Unit identification
Name-plate parameters:
Name-plate
This unit can be identified by the name- CONTEG, spol. s r.o.
plate that includes all information Na Vítězné pláni 1719/4
regarding its correct use. 140 00 Prague 4
The name-plate is located in two copies on
the outer casing of the unit (generally on Tel.: +420 261 219 182
one of the sides) and on the panel that Fax: +420 261 219 192
closes the electric box.
The label also includes, in addition to the
manufacturer’s identification data and to the MODEL
trademarks of the product, the following Unit code and RAL color.
information: SERIES
Product identification number
DATE
Date of shipment of the product and date of start of guarantee
Rated voltage
The technical data label is printed on a Main power supply to the unit (voltage /phases/ frequency)
plastic surface to ensure long durability of Control voltage
the text even in the toughest room Voltage to auxiliary circuits
Heating absorbed current
conditions. Current absorbed in heating mode (not available).
Starting/run current
For any assistance or information Current absorbed at start / at nominal conditions.
Cooling capacity
concerning the unit Cooling capacity at nominal conditions
described in this manual, knowledge Input power
of its serial number is essential. Power absorbed by the unit at nominal conditions.
Heating input power
Power absorbed by the unit in heating mode (not
available).
Nominal conditions: Maximum pressure
Maximum operating pressure for the unit
Closed loop Protective system side ambient
Return air – temperature 45°C IP class of protection on the room side
Weight
Return air – relative humidity 15% Net weight of the unit
Intake water temperature 7°C Duty cycle
Unit capacity adjustment
Open loop
Return air – temperature 35°C
Return air – relative humidity 30% Made in EU
Intake water temperature 7°C
Page 9 of 94
Coding
A2 (12) AC-SO-CW/A2-42-30/100
A8 (16) AC-SO-CW/A8-42-30/100
B4 (20) AC-SO-CW/B4-42-30/100
A2 (12) AC-SO-CW/A2-42-30/120
A8 (16) AC-SO-CW/A8-42-30/120
B4 (20) AC-SO-CW/B4-42-30/120
Top connection of pipes with coolant: Add the suffix -T to the chosen unit’s part number
EC fans: Add the suffix -EC to the chosen unit’s part number
Open architecture side mount solutions available also in 45U design‚ more information
upon request
CLASSIC MODULAR*
(1 cooling unit per rack) (Scalable solution)
* MODULAR: Instead of xx use the required height of Cooling Unit: 42, 45 or 48U
Top connection of pipes with coolant: Add the suffix -T to the chosen unit’s part number
EC fans: Add the suffix -EC to the chosen unit’s part number
MODULAR: Modular side mount cooling units (only closed architecture) are predesigned
to achieve maximum compatibility with ROF family racks. They can be easily used in
modules that consist of racks and side mount cooling units.
Page 10 of 94
3. Components and operating principle
3.1 Intended and non-intended use
Intended use
CONTEG In-Row conditioners are designed to cool rooms containing technological equipment,
sheltered form weather. Use these conditioners to eliminate the problems caused by high
temperatures, dirt and humidity in the room subject to climate control and in which the
conditioners are to be installed.
As well, CONTEG In-Row conditioners cannot be used outside safety limits specified on the
name-plate. Conditioners must not be transported or used in positions that differ from those for
which they were designed. These units are designed to be housed in a closed metallic frame for
protection. This frame is between two racks (open loop) or beside one rack (closed loop), with
front and back panels (not included in this product). Allowed installation positions are shown in
this manual.
CONTEG is not responsible for any malfunctions caused by failure to comply with these
instructions. The operator bears the entire risk.
Non-intended use
Air conditioner cannot be installed on movable, vibrating, oscillating, tilted (non-leveled) parts.
Page 11 of 94
3.2 Component layout
CONTEG In-Row units are installed between two server racks in open loop configuration.
They take air from a hot aisle of the room, cool and deliver it to a cold aisle, where it is sucked in
by the server rack fans.
In closed loop configuration the air conditioners are beside the rack to which they are dedicated.
Therefore, they take air from the discharge of the rack and, after cooling, they deliver it to the
rack intake.
In both configurations, air suction and delivery are frontal and can be redirected with a deflector
or a plenum (not part of the supplied product).
According to the air flow through the air conditioner, the following components can be seen:
• Air filter (only in open loop configuration)
• Piping with modulating valve (3-way) and air valve on the top (2-way on the request)
• Cooling coil with condensate tray underneath
• Radial fans
Holes for water pipes are placed either on the base or on the top panel of the unit, and must be
used according to the selected version.
The electrical box is separated from the air conditioner and designed to be fixed to the rack
metallic frame above the air conditioning unit. It is closed by a protective cover.
A columnar metal bar with button switches for each fan is supplied loose, to be integrated in the
frame containing the air conditioner.
Page 12 of 94
Diagram of the internal hardware
Page 13 of 94
3.3 Working modes
Cooling
Air is sucked in by the radial fans, is filtered (only in open loop units) and then it is cooled passing
through the chilled water heat exchanger. After treatment, air is delivered through the frontal
opening. Cooling capacity is modulated by C2020 in different ways, acting on the 3-way valve
and / or on the fan speed, according to the temperature measured by the return probes.
Dehumidification
According to the signal of humidity inside the room, supplied by the humidity sensor, the air
conditioner electronic controller C2020 reduces fan speed. Consequent air flow reduction causes
a higher temperature difference between inlet and outlet air, helping condensation of humidity in
the heat exchanger.
Emergency
When a fan is blocked, temperature control is in emergency mode. The remaining fans work at
maximum speed, unless dehumidification is required.
Structure
These units are made of self-supporting galvanized sheet metal parts that offer good corrosion
resistance (suitable only for non-corrosive and non-saline environments). Electric box and fan
switch bar are powder coated with protective paint. Internal metal parts are used to strengthen
the unit and direct air flow. This system is designed for an easy inspection of the unit.
Inner components are accessible by removing the outer panels and doors of the rack where the
air conditioner is mounted.
Page 14 of 94
3.5 Hydraulic circuit components
Page 15 of 94
3.6 Motors
Fans
AC fans are radial, with backward curved blades made of galvanized sheet steel. Rotor is painted
with epoxy black RAL9011, mounted on ball bearings and dynamically balanced according to
VDI2060. Protection degree IP44; Insulation class B.
Optional EC (electronic commutation) fans are radial, with backward curved blades made of
galvanized sheet steel. Rotor is also made of galvanized sheet steel, mounted on ball bearings
and dynamically balanced according to DIN ISO1940, quality level G6.3. Protection degree IP44;
Insulation class B.
Contactors
These control motors that operate with auxiliary voltage. They comply with IEC947-4-1
standards.
Page 16 of 94
Fan speed controller (with AC fans)
This electronic module receives a PWM signal from C2020 controller and transforms it in a
change of effective voltage through a phase-cut system. Protection degree is IP20.
Temperature probes
4 PTC temperature probes are connected to analogue inputs of C2020 controller, in order to
measure following parameters:
• 2 return air probes, placed behind air intake opening, higher and lower parts
• 2 supply air probes, placed on multi-switch bar, higher and lower parts
Humidity sensor
Placed behind air intake opening, it sends a humidity analogue signal (3÷18 mA) to C2020
controller, in order to enable dehumidification mode. Measured range of humidity is 15 ÷ 90%.
Protection degree is IP54.
Page 17 of 94
C2020 electronic controller
This electronic microprocessor card is equipped with a set of terminals to connect the card to the
devices it controls (valve, fans…). The operating software and the file containing the operating
parameters are written in the EEPROM so that they remain stored even when there is a cut-off in
the power supply.
The C2020 card is housed inside the electric box and can only control one unit.
A keypad can be connected to the C2020 card to display information regarding operating
conditions, the state of the unit and any alarm. As standard, the keypad for CONTEG In-Row
is supplied mounted on the front door of the cooling unit cabinet. The keypad is provided with cable
which is connecting it to the USER socket in the e-box.
The C2020 card can also be connected to a remote monitoring / supervision system using a
serial line and ordering the necessary options. Port for serial line RS485 is available as an
accessory AC-SERC1010.
Refer to the wiring diagram given in part 2 of the manual, which is specific for each
unit, when assigning the card inputs / outputs.
Page 18 of 94
RFS dirty filter pressure switch (only in open loop models) – FL air flow alarm (only with
AC fans)
RFS gives a dirty filter signal (only with open loop units), shown both on the display and on a
voltage-free contact. It indicates when it is necessary to clean or replace the air filter. A similar
device, with an inverse logic compared to the dirty filter, gives a signal that there is insufficient air
flow on the evaporator which indicates that the evaporator fan is broken or jammed.
Range: 20 – 200 Pa
Differential pressure: 10 Pa ± 15%
P1: High pressure connection
P2: Low pressure connection
NOTE:
Adjustment must be done by authorized trained
personnel.
Technical characteristics:
Connection:
Contact 3-1 opens when the differential pressure exceeds the preset
value. At the same time contact 3-2 closes. The signal is transmitted
through this contact.
Page 19 of 94
4. Unpacking and inspection
INSPECTION
CONTEG products are delivered ex-works. All units have been individually inspected in all their
components and been carefully packaged before of the delivery. Immediately inspect the unit
upon receipt of the goods:
• Make sure that it has been transported in the correct position. Note any unsuitable shipping
conditions on the shipping document.
• Check that no components are missing, that are presents on shipping document and the
integrity of the conditioner at the moment of the receiving.
• Check that there aren’t any external damages and eventually note them on the shipping
document in the presence of deliverer.
• Remove label which protect coils.
(WARNING! FRAGILE PART! NEVER DO NOT TOUCH THE COILS
• Hidden damage, that are verified after removal the packing, must always be notified to the
shipper by registered letter within 8 days of receipt of the goods.
With ex-works delivery conditions, carrier is the sole responsible for any damage
caused during transport. CONTEG is not responsible for damages to the goods
caused by the carrier, but it will do everything in its power to assist clients on
those situations.
If delivery conditions are not ex-works: In case of damage please follow the instructions
given on the transportation documents.
The product cannot be returned without prior approval of CONTEG.
Please feel free to discuss and optimize your specific logistic needs with CONTEG. Coordination
between the CONTEG factory store, your local partner and the end-user is important.
Contact information can be found at the end of this manual.
Page 20 of 94
LIFTING AND TRANSPORT
Air conditioner must be lift without tilting or laying it on its sides (see drawing above), in safety,
using appropriate equipment.
Lifting devices with ropes can be used, securing ropes to the pallet and protecting upper edges of
the units with wooden or metallic angles.
As an alternative, when the unit is still packed with pallet, a forklift can be used, taking care that
the centre of gravity is inside fork area.
Capacity of lifting device must be appropriate for the weight of air conditioner.
Load must be balanced to avoid tilting.
Avoid offhanded or rough maneuvers.
Don’t lay other objects upon the air conditioner.
Don’t move the unit on rollers or with forklift after removing the pallet, to avoid any
structural deformation.
STORAGE
Except differently agreed, standard packing of air conditioners is composed of:
• Pallet under the unit, fixed to its lower frame
• Lateral protection panels
• Protective film around the surface (except bottom side in contact with the pallet)
• Air bag on the upper part.
Standard packing doesn’t protect air conditioner from rain and bad weather.
Standard packing is not suitable for sea-freight.
Standard packing is not suitable for air-freight.
Page 21 of 94
REMOVAL OF PACKING
• remove packing without damaging air conditioner
• recover any document or component inside the packing
• keep original packing (if composed of either pallet or carton)
Use original packing to ship the air conditioner to any other destination (if
composed of either pallet or carton).
If packing disposal is necessary, we remind to dispose different materials suitably.
Page 22 of 94
5. Installation
5.1 Positioning the unit
CONTEG In-Row air conditioners should always be ordered with plinths (DP-PDN-100-30/100 or
120). They have a compact frame and front door and a rear panel. For the open loop systems
the front and rear doors (panels) of both cooling units and the racks are perforated (see below)
while the closed loop system has solid front door and rear panels (see the next page).
In open loop system the cooling units must be installed between two server racks. Installation at
an end of a row is not recommended because there is a mix of hot and cold air. Furthermore it is
recommended to install them near the racks with highest heat load.
In the front the cooling units and CONTEG racks are joined together using the universal
mounting kit (DP-DR-UNI) and sealing tape, in case of closed architecture.
Note: When using the cooling unit at the end of the row (for example in a contained cold aisle
arrangement) there is a special way of joining the CONTEG cooling unit with the rack. A floating
nut on the cooling unit must be removed and then a screw must be preinstalled in the rack before
joining the units.
To minimize the influence to the air flows of units installed in neighboring parallel rows it is highly
recommended to offset the cooling units (as indicated in layout below). Using this method
assures that the cooling units don’t impede or overly influence the other units air-streams and
allows for more efficient air flows.
Page 23 of 94
In closed loop version the cooling unit is installed beside a rack. A closed air circuit is created
between the rack and the unit. Hot and cold zone are created inside the closed module which
has solid front and rear doors. A system for emergency opening of doors is required.
There’s room enough for an easy installation and maintenance of the unit: please
check dimensional drawings, with particular attention to the accessibility of water
connections and wiring. There must be a free space of 1 m from both front and back
sides of the unit for installation and maintenance.
Air circulates correctly, both inside and outside the frame, avoiding any short circuit,
re-circulation or by-pass.
Additionally: check that air suction and discharge are correctly separated inside the
frame. Separate the air suction from discharge placing sealing material (gaskets)
suitably.
In open loop version, avoid placing of two units such as their air supplies are one in
front of the other.
Avoid any obstacle to the air flow.
Measures (i.e. deflectors) to separate hot and cold aisles increase the efficiency of
the system, and are highly recommended.
Units should be installed on flat and perfectly horizontal bases so that they will
operate correctly and that condensate will drain properly.
The piping and wiring to the cooling unit and its electrical parts must be connected
by authorized personnel only.
Before the start-up please observe position of condensate water discharge and
water connection passages in the following drawings.
Page 24 of 94
General dimensions of the unit
Width: 300 mm
Depth: Open loop system: 1000 mm or 1200
Closed loop system: 1200 mm
Height: Open loop system: 1978 (42U)
Closed loop system: 1978 (42U), 2111 (45U), 2245 (48U)
Page 25 of 94
Position of the electronic box (under the top panel)
and the control panel (from the front)
Detail of a fixing hole with floating nut for side connection to a rack
(for joining into a row of racks use mounting kit DP-DR-UNI)
Page 26 of 94
TOP VIEW
BOTTOM VIEW
Page 27 of 94
SIDE VIEW (FROM THE LEFT SIDE)
AND THE DETAIL OF 3-WAY VALVE PIPING
Page 28 of 94
5.2 Hydraulic connection
CONTEG In-Row air conditioners must be connected to a circuit with chilled water, including
either a chiller or a dry cooler or a cooling tower. For chilled water circulation pumps have to be
provided. These pumps must be selected according to total pressure losses through the
hydraulic circuit.
Pressure losses through CONTEG In-Row air conditioners are shown in the
technical data sheet at the end of this manual. Pressure losses are referred to pure
water. Correction factor for pressure losses in case of monoethylene glycol
addition is shown in the following diagram.
An important requirement for hydraulic circuit is quality of water. In case its cleanliness is
inadequate, a fine mesh filter in the circuit is recommended.
In the following table, substances which must be added in particular working conditions to
ensure correct functioning:
(*) Dose following the prescription and working temperatures of antifreeze supplier,
according to minimum ambient and working temperatures.
An excess of additive worsens chiller performance. For any doubt please consult chiller
manufacturer.
Maximum total (static + dynamic) pressure in water circuit = 8 bar for every
standard CONTEG model.
Page 29 of 94
Coefficient of correction for pressure
losses through the hydraulic circuit
using monoethylene glycol
Hydraulic connections in CONTEG In-Row units are screw type, with 1” diameter for all models.
Connect corresponding nipple (not supplied with the unit) as a terminal of external chilled water
circuit. Then screw it to the female connector on the unit, respecting water inlet and outlet
positions.
Select hydraulic pipes with diameter suitable to their equivalent length (considering
pressure losses through curves, unions, etc.) to the water flow, to the circulation
pump head. The following minimum diameters are suggested:
WATER FLOW < 2500 l/h From 2500 From 3000 From 4000
to 3000 l/h to 4000 l/h to 5500 l/h
PIPE DIAMETER 1“ 1 1/2 “ 2“ 2 1/2 “
Female
(unit side)
Nipple
In case some gaskets are missing, use always glycol-proof rubber gaskets. Apply
teflon-gasket on the nipple and tighten it to the female connector on the unit.
Page 30 of 94
Application of teflon-gasket (not supplied) to the nipple
Insulate water pipes with anti-diffusion material, to avoid heat exchange with ambient air and
consequent condensation of humidity in it on the pipes.
Once water circuit is closed, open the red water cocks and the 3-way valve manually (if
closed). Then, de-ventilate the circuit through the valve on the top part of internal piping.
Page 31 of 94
Condensate discharge: Syphon installation (Air-trap)
Ensure that there is a sufficient height difference between the fan pan and the upper bow of the
syphon or the highest part of the drain tube, in order to avoid a water column in the drain syphon
caused by the pressure in the suction area of the A/C unit, which prevents the draining of the
condensate water
Unit limit
Possible installation at
the customer side:
funnel
Connect the condensate water drains to the local waste water system. Condensate discharge
connector with a diameter if 15 mm is on the unit base (position is shown in drawings in
paragraph 5.1).
Page 32 of 94
5.3 Electrical connections
The electrical connection to the climate-control system must comply with the following
regulations:
Machine safety directive (2006/42/CE)
Low voltage directive (2006/95/CE)
Electromagnetic compatibility directive (2004/108/CE)
National mechanical and electrical systems regulations
CONTEG In-Row units are provided with an additional terminal to connect emergency
power supply.
Page 33 of 94
• The electrical box is supplied pre-installed on the top of the unit. It is provided with 4 lateral
fixation inserts. The electrical box is plugged to internal components of the unit. When
inserting the unit into the cooling unit cabinet, it is possible to unplug the electrical box and
put it into the cabinet in a second moment. Then electrical connections must be restored
following the wiring diagram.
• Electrical cables are connected from each single fan to the multi-switch bar following the
wiring diagram.
• Power supply and signal cables from electrical box are connected to multi-switch bar
following the wiring diagram.
• Main power supply cables from the distribution panel of the site are connected to the unit
power terminal board located inside its electrical box. In the following drawing the lay-out of
cable passage and connectors is shown.
• The emergency power supply, if available, is connected in the same way.
Dirty filter +
E-box rear side
humidity sensor
Emergency
power supply
Power supply
to multi-switch
bar
Page 34 of 94
6. Start-up
The start-up must be done exclusively by authorized technical personnel. Before
the first start-up the system must be installed and connected as described in the
“Installation” chapter.
• Make sure the main switch is turned off and that the system is isolated from power mains.
• Check that all power switches in the electric system have been turned off.
• Check that the main electrical supply cable and the terminals, including the PE terminals, are
correctly hooked up.
• Check that contactors are free to move.
• Use the main switch to turn the air climate control system on.
• Activate fan power switches for the fans one after another.
• Check the supply voltage on all phases.
• At this point the electronic card is powered and the single components of the system can be
activated to check for proper operation. The fundamental procedures to follow during
installation are described in the following paragraph. Other guidelines are found in the
manual for the C2020 electronic card.
• Set the desired recovery air temperature on the conditioner display.
• Start the climate control system by pressing the ON-OFF push-button on the display.
• Check the current absorbed by the fans, comparing these values with those indicated in
technical specifications.
• When the system is operating at normal capacity: 1) check that there are no alarms; 2) check
that the fans work properly; 3) check, with the unit operating, that power supply voltages
remain inside the values indicated on the technical data label for the unit; 4) check that the
unit operates according to the logic described in the following chapter.
Shutdown
To shut the unit down, disconnect it from all its power supplies using the related isolating
switches.
The ON-OFF key on the C2020 display (if present) is only used to put the unit on
stand-by. It must not be thought to be a safety component to turn the unit off prior
to performing maintenance.
Page 35 of 94
7. Software features
7.1 Keypad and menus
Air conditioners are provided with keypad for displaying working conditions, unit state and
eventual alarms. The keypad is on board the air conditioner, on its front side panel. The keypad
can be also used to modify working parameters of the unit (e.g. set points). Here below a
picture of keypad.
Page 36 of 94
In the following paragraphs only menus and functions available for user and service will be
described.
** STULZ C2020
CONTROLLER
STURKSXX.YY
CCC
After the initialization phase a new screen appears where some system parameters are
indicated. Use UP/DOWN ARROW keys to scroll the screens and display the measured and set
parameters, like for example: external and internal temperature, external and internal humidity,
fans on/off, etc….
In the following figure all main screens are represented. If a component is not connected, the
corresponding value doesn’t appear (---).
Page 37 of 94
Page 38 of 94
Screen a)
Room temp. A: Internal temperature point A (TIA). Connected to supply air probe A.
Room temp. B: Internal temperature point B (TIB). Connected to supply air probe B.
Screen b)
Ret. temp.A: return temperature A (TRA)
Ret. temp.B: return temperature B (TRB)
Screen c)
Ext. temp.: external temperature (TAE)
CoolMode: mode of cooling
Screen d)
RH room: relative humidity of the room (IRH)
Set RH: setpoint of humidification (S02)
Screen e)
Water temp.: water temperature (WT)
Water flow: water flow (WF)
Screen f)
IN wat. pr.: inlet water pressure (IWP)
OUT wat. pr.: outlet water pressure (OWP)
Screen g)
IN air pr.: inlet air pressure (IAP)
OUT air pr.: outlet air pressure (OAP)
Screen h)
AC fan speed: speed of the fans
EC: state of the enable cooling (digital out R1)
Valve: percentage of opening valve
Screen i)
F1: speed of FAN1; if “---“ is shown, FAN1 is absent
F2: speed of FAN2; if “---“ is shown, FAN2 is absent
F3: speed of FAN3; if “---“ is shown, FAN3 is absent
F4: speed of FAN4; if “---“ is shown, FAN4 is absent
F5: speed of FAN5; if “---“ is shown, FAN5 is absent
F6: speed of FAN6; if “---“ is shown, FAN6 is absent
Screen l)
Up: proportional part of water flux management
Ui: integral part of water flux management
Water flow: opening of the valve for managing the water flux
Screen m)
Software version
Page 39 of 94
7.3 Entering menus and modifying values
Menus are protected by 3 levels of password: user, maintenance, manufacturer
(there are 2 manufacturer passwords for manufacturer setup menu and I/O setup
menu). With user password only a limited number of functions and parameters can
be entered. With maintenance password more functions and parameters can be
entered. With manufacturer password all parameters are accessible. If typed
password is not correct for the menu which has to be entered, nothing happens and
menu name will still be flashing.
User password is set at 0. So, no password is needed to enter user setup menu.
Maintenance password is set at 0111.
In case of necessity, to know manufacturer passwords, please contact after sales
department of CONTEG (see last chapter of this manual: Contacts).
Pressing ESC key in any phase of password typing is equivalent to typing 0000.
Page 40 of 94
Page 41 of 94
Page 42 of 94
7.4 USER SETUP menu - This section from page 43 to
This menu is entirely accessible with user password (required only if set value is different from 0).
In user setup menu temperature and humidity set points, alarm thresholds and configuration
parameters like language and clock can be set. The parameter list of this menu is shown here
below.
S07. Differ. temperature Band for the control (DELTA_T) based 0/30 5 °C
Band on differential temperature
S08. Differ. pressure Setpoint for the control (DELTA_P) 0/20 10 bar
Set point based on differential pressure
S09. Differ. pressure Band for the control (DELTA_P) based 0/5 2 bar
band on differential pressure
S10. Water flow Setpoint of the water flow control 0/200 50 l/min
Set point
Page 43 of 94
Id Screen Description Range PreSet Unit
Code
S11. Water flow Proportional band for PI control of the 0/50 5 l/min
Proportional band water flow
S12. Water flow Integral time for PI control of water flow 0/200 60 sec
Integral time
S18. Alarm limit Set point for the low temperature alarm -999/ 10 °C
low temperature 999
S20. Alarm limit Set point for the high temperature alarm -999/ 50 °C
high temperature 999
Page 44 of 94
Id Screen Description Range PreSet Unit
Code
S22. Alarm limit Set point for the minimal temperature -999/ 5 °C
min temperature alarm 999
S24. Alarm limit Set point for the maximal temperature -999/ 60 °C
max temperature alarm 999
S26. Alarm limit Set point for the high humidity alarm 0/100 80 %
high humidity
S29. Alarm limit min Set point for the alarm min water flow 0/200 5 l/min
water flow
S30. Alarm limit max Set point for the alarm max water flow 0/200 50 l/min
water flow
S31. Alarm limit Set point for the low pressure of water 0/10 1 bar
Low pressure when the valve is opened
S32. Limit humidity for Set point of humidity for the request of 0/100 75 %
Opening door the opening door
Page 45 of 94
Id Screen Description Range PreSet Unit
Code
S34. Max fan speed with Max speed of the fans, when the door 0/100 30 %
opened door is opened
Concrete PreSet values are different for each type of cooling unit CW or DX and are
descripted in other file.
User password is also between parameters of manufacturer setup menu (M136), accessible with
maintenance password. To change password, enter manufacturer setup menu with 0111, go to
parameter M88 “password user setup” and modify value.
Note down the new user password value and make it available for future access to
this menu. If accidentally lost, user setup menu can be accessed also with
maintenance password 0111.
Page 46 of 94
7.5 MANUFACTURER SETUP menu
This menu contains all parameters for managing cooling cycles (e.g. cycle hysteresis), correct
working of the unit (e.g. minimum on-off time for compressor working), alarm delays, etc.
This menu is protected by maintenance password, useful to access only some parameters.
Default value of this password is 0111.
Parameters not accessible with maintenance password are reserved to the manufacturer of the
air conditioner and accessible with manufacturer password.
Use of maintenance password to configure or maintain air conditioner is restricted
to personnel skilled for installation and maintenance operations.
M06. Cooling set point Minimum limit for cooling set point -99.9/ 20 °C
minimum limit 99.9
Page 47 of 94
Id Screen Description Range PreSet Unit
Code
M07. Cooling set point Maximum limit for cooling set point -99.9/ 30 °C
maximum limit 99.9
M08. Humidity set point Lower limit of humidity set point 0/100 35 %
minimum limit
M09. Humidity set point Upper limit of humidity set point 0/100 80 %
maximum limit
M10. Low pressure Delay time of low pressure alarm 0/9999 120 sec
alarm delay
M11. High pressure Delay time of high pressure alarm delay 0/255 0 sec
alarm delay
M12. Air flow Delay time of air flow alarm delay 0/255 0 sec
Alarm delay
M14. External ambient Pressure of the external ambient. It 0/2000 1013 mbar
pressure depends on altitude (meters from sea
level) of installation.
M15. Delay time for Delay time of start fan 0/999 30 sec
starting fan
M16. Delay time for Delay time of stop fan 0/999 90 sec
stopping fan
M17. Min. switching on The fan has to be on for this time 0/999 10 sec
for fan
M18. Min switching off The fan has to be off for this time 0/999 10 sec
for fan
Page 48 of 94
Id Screen Description Range PreSet Unit
Code
M19. Minimal Min speed of the fan 0/100 30 %
fan speed
M21. Min fan speed for Min speed for management of the fan 0/100 10 %
fan blocked alarm blocked alarm
M27. Integral time for Integral time used for the calculation of 0/999 120 sec
fans control proportional-integral control
M28. Coeff. for control of Coefficient for the control of the third 0/100 50 %
fan couple 2 fan couple (fan couple C).
Page 49 of 94
Id Screen Description Range PreSet Unit
Code
M31. Real Time Clock Enable for real time clock YES / NO YES
Enable
M37. DELAY FOR Time to wait after switch on the system 0/255 30 min
DEHUMIDIFICATION before to check dehumidification
conditions
M38. MIN TIA FOR Min value for Tia to enable -100/100 30 °C
DEHUMDIFICATION dehumidification
Concrete PreSet values are different for each type of cooling unit CW or DX and are
descripted in other file.
Page 50 of 94
7.6 SETUP I/O menu
In this menu parameters to manage inputs and outputs to / from the C2020 can be modified.
Access to this menu is protected. Some parameters, concerning calibration of analogue channels
and polarity of digital I/O, are accessible with maintenance password (default value 0111).
Parameters not accessible with maintenance password are reserved to the manufacturer of the
air conditioner and accessible with manufacturer password.
Parameters relevant for the units explained on this manual are listed here below. The
correspondence between number of analogue channel and probe of the unit to which it is
connected is shown on the specific wiring diagram of the air conditioner.
I21. Select Relay Select the relay linked to enable R1-R13 / No R1 (**) -
Enable cooling cooling conn.
Page 51 of 94
Id Mask Description Range PreSet Unit
Code
I22. Select Relay Select the relay linked to water valve R1-R13 / No R8 (**) -
Water valve conn.
I23. Select Relay Select the relay linked to emergency R1-R13 / No R13 -
Emergency open open door conn. (**)
door
I27. Select Relay Select the relay linked to leakage (R1-R13)+ R6 (**)
Leakage (CW) or (CA) /
No conn.
I28. Select Relay High Select the relay activated by high (R1-R13)+ R7 (**) -
pressure al. pressure alarm (CW) or (CA) /
No conn.
I29. Select Relay Low Select the relay activated by high (R1-R13)+ R8 -
pressure al. temperature Resonator alarm (CW) or (CA) / (**)
No conn.
I30. Select Relay High Select the relay activated by High (R1-R13)+ R9 -
humidity al. humidity alarm (CW) or (CA) / (**)
No conn.
Page 52 of 94
Id Mask Description Range PreSet Unit
Code
I34. Select Relay Select the relay activated by (R1-R13)+ CA -
Max temperature al. maximal temperature alarm (CW) or (CA) / (**)
No conn.
I39. Select Relay Select the relay activated by air flow (R1-R13)+ CA -
Air flow al. alarm (CW) or (CA) / (**)
No conn.
Page 53 of 94
Id Mask Description Range PreSet Unit
Code
I46. Select Relay Select the relay linked to FAN6 (R1-R13)+ CA -
FAN6 blocked al. blocked alarm (CW) or (CA) / (**)
No conn.
I47. Select Relay Broken Select the relay activated by broken (R1-R13)+ CA (**) -
Probe Al.IC1 probe alarm IC1 (CW) or (CA) /
No conn.
I48. Select Relay Broken Select the relay activated by broken (R1-R13)+ CA (**) -
Probe Al.IC2 probe alarm IC2 (CW) or (CA) /
No conn.
I149. Select Relay Broken Select the relay activated by broken (R1-R13)+ CA (**) -
Probe Al.IC3 probe alarm IC3 (CW) or (CA) /
No conn.
I50. Select Relay Broken Select the relay activated by broken (R1-R13)+ CA (**) -
Probe Al.T1 probe alarm T1 (CW) or (CA) /
No conn.
I51. Select Relay Broken Select the relay activated by broken (R1-R13)+ CA (**) -
Probe Al.T2 probe alarm T2 (CW) or (CA) /
No conn.
I52. Select Relay Broken Select the relay activated by broken (R1-R13)+ CA (**) -
Probe Al.T3 probe alarm T3 (CW) or (CA) /
No conn.
I53. Select Relay Broken Select the relay activated by broken (R1-R13)+ CA (**) -
Probe Al.T4 probe alarm T4 (CW) or (CA) /
No conn.
I55. Select relay Opened Select the relay activated by the (R1-R13)+ CA (**)
door alarm opened door alarm (CW) or (CA) /
No conn.
I57. Select Relay Select the relay activated by the (R1-R13)+ CA (**) -
XYZ communicat. al. XYZ communication alarm (CW) or (CA) /
No conn.
Page 54 of 94
Id Mask Description Range PreSet Unit
Code
I58. Select Relay Select the relay activated by R1-R13/ No R11 -
Common Warning common warning conn. (**)
I60. – Polarity digit input Select the polarity of digital input A1 0/1 1
I72. A1 – A13 – A13:
0 = normally opened
1= normally closed
I73. – Polarity digit out Select the polarity of digital outputs 0/1 0
I85. R1 – R13 R1 -R13:
0 = normally opened
1 = normally closed
I93. PASSWORD
Concrete PreSet values are different for each type of cooling unit CW or DX and are
descripted in other file.
Page 55 of 94
CONTEG A2 open loop and CONTEG A4 closed loop have 3 fans. Each fan has its
own output from the C2020 board (FAN1 upper, FAN2 middle, FAN3 lower).
CONTEG A8 / B4 open loop and CONTEG B2 / C4 closed loop have 5 fans. An
expansion board (IE2) is necessary to control them in couples.
The fans of upper couple (couple A) will have the same speed SP_A.
The same is for the lower couple (couple B) with speed SP_B.
The fan in the middle will have its own speed SP_C.
The fan speed control depends on the temperature probes TIA, TIB, TRA and TRB
as shown in the following paragraphs.
The temperatures TIA and TRA manage the fan couple A. If the TIA probe is
absent, the fan couple A will not run.
The temperatures TIB and TRB manage the fan couple B. If the TIB probe is
absent, the fan couple B will not run.
The fan couple C will run at:
SP_C = (SP_A * (100 - M28)) + SP_B * M28) /100
Fan speed is different only when the unit is provided with EC fans. AC fans are all
controlled by the same phase-cut output so they rotate at the same speed.
In general the speed of all AC fan is the highest between SP_A and SP_B.
Page 56 of 94
COOLING MODE WITH WATER VALVE ON-OFF
In this configuration, water valve is connected to relay R8. Control of capacity is therefore ON-
OFF, not modulated.
Parameters:
S01 COOLING SET POINT (cool set point - CS): pre-set = 25°C
S03 COOLING BAND: (B): pre-set = 5°C
The cooling mode can be managed by the modulation of fan speed or by the modulation of water
valve opening. Either fan speed or water valve opening depends on the combination of different
way of control. In the following table possible control combinations are shown.
FAN DELTA_T Temperature is controlled modulating fan speed and it is the weighted
average between two different managements.
FI logic is based on TIA and TIB.
FD logic is based on temperature differential (TRA, TRB, TIA, TIB).
The final result is RES = (FI*(100-S15) + FD*S15) / 100
If the FAN control fails ---> RES = FI
If the DELTA_T control fails ---> RES = FD
Valve is open at 100% unless max(TIA, TIB)< (S01 - S05). If so, valve is
closed.
VALVE DELTA_T Temperature is controlled modulating valve opening and it is the weighted
average between two different managements.
VI is based on TIA and TIB.
VD is based on temperature differential (TRA, TRB, TIA, TIB)
The final result is RES = (VI*(100-S15) + VD*S15) / (100)
If the VALVE control fails ---> RES = VI
If the DELTA_T control fails ---> RES = VD
Fan speed is S17.
Page 57 of 94
FI: COOLING MODE BY FAN SPEED MODULATION
FI control logic is enabled when S13 = FAN
Parameters:
S01 COOLING SET POINT (cool set point - CS): pre-set = 25°C
S03 COOLING BAND: (B): pre-set = 5°C
S16 MAX FAN SPEED IN FAN MODULATION MODE: pre-set = 80%
M19 MINIMAL FAN SPEED: pre-set = 30%
M27 INTEGRAL TIME FOR FANS CONTROL: pre-set = 120
Analog channels
TIA: internal temperature in point A
TIB: internal temperature in point B
The reference temperature (Tref) for the control of fan couple A is TIA. The
reference temperature (Tref) for the control of fan couple B is TIB.
• If Tref < S01 -> Fan speed will be at minimum value M19
• If S01 < Tref < S01+S03, the speed of the fan couple A and B is the result of a proportional
integral control with:
Setpoint: S01
Proportional band: S03
Integral time: M27
• If Tref > S01+S03 -> Fan speed will be at maximum value S16
Page 58 of 94
VI: COOLING MODE BY WATER VALVE OPENING
VI control logic is enabled when S13 = WATER VALVE
Parameters:
S01 COOLING SET POINT (cool set point - CS): pre-set = 25°C
S03 COOLING BAND: (B): pre-set = 5°C
S17 FAN SPEED IN WATER VALVE MODE: pre-set = 50%
M22 MIN WATER VALVE OPENING: pre-set = 0%
M23 MAX WATER VALVE OPENING: pre-set = 100%
Analog channels
TIA: internal temperature in point A
TIB: internal temperature in point B
• If max(TIA,TIB) < S01 -> water valve opening will be at minimum value M22
• If S01 < max(TIA,TIB) < S01+S03 -> water valve opening will be calculated proportionally
to the temperature = M22 + ((max(TIA,TIB)- S01)/ S03) * (M23 - M22)
• If max(TIA,TIB) > S01+S03 ---> water valve opening will be at maximum value M23
Page 59 of 94
FD: COOLING MODE BY FAN SPEED ON TEMPERATURE DIFFERENTIAL
FD control logic is enabled when S13 = FAN and S14 = DELTA_T
Parameters:
S06 DIFFER. TEMPERATURE SET POINT: pre-set = 10°C
S07 DIFFER. TEMPERATURE BAND: pre-set = 5°C
S16 MAX FAN SPEED IN FAN MODULATION MODE: pre-set = 80%
M19 MINIMAL FAN SPEED: pre-set = 30%
M27 INTEGRAL TIME FOR FANS CONTROL: pre-set = 120
Analog channels
TIA: internal temperature in point A / TIB: internal temperature in point B
TRA: return temperature in point A / TRB: return temperature in point B
• If DIFF_Tref < S06 -> Fan speed will be at minimum value M19
• If S06 < DIFF_Tref < S06+S07, the speed of the fan couples A and B is the result of a
proportional integral control with:
Setpoint: S06
Proportional band: S07
Integral time: M27
• If DIFF_Tref > S06+S07 -> fan speed will be at maximum value S16
Page 60 of 94
VD: COOLING MODE BY OPENING VALVE ON TEMPERATURE DIFFERENTIAL
VD control logic is enabled when S13 = WATER VALVE and S14 = DELTA_T
Parameters:
S06 DIFFER. TEMPERATURE SET POINT: pre-set = 10°C
S07 DIFFER. TEMPERATURE BAND: pre-set = 5°C
S17 FAN SPEED IN WATER VALVE MODE: pre-set = 50%
M22 MIN WATER VALVE OPENING: pre-set = 0%
M23 MAX WATER VALVE OPENING: pre-set = 100%
Analog channels
TIA: internal temperature in point A /TIB: internal temperature in point B
TRA: return temperature in point A / TRB: return temperature in point B
• If DIFF_T< S06 -> water valve opening will be at minimum value M22
• If S06< DIFF_T< S06+S07 -> water valve opening will be calculated proportionally to the
temperature = M22 + (DIFF_T-S06)/ S07) * (M23 - M22)
• If DIFF_T> S06+S07 -> water valve opening will be at maximum value M23
Page 61 of 94
ENABLING COOLING
When FI and FD capacity modulation systems are enabled, C2020 can close the valve via R1
digital output in case supply air temperatures fall below a certain limit when fans are running at
minimum speed.
Parameters:
S01 COOLING SET POINT (cool set point - CS): pre-set = 25°C
S05 ENABLING COOLING BAND (ECB): pre-set = 2°C
Analog channels
TIA: internal temperature in point A
TIB: internal temperature in point B
Page 62 of 94
HOT SPOT MODE
The digital input A6 enables / disables the hot spot mode control.
Parameters:
S02 HUMIDITY SET POINT (HS): pre-set= 80%
S04 HUMIDITY BAND(HB): pre-set= 40%
M20 MAXIMUM FAN SPEED: pre-set= 100%
Analog channel:
- IRH: internal relative humidity
When the hot spot mode is active the maximum fan speed is M20. The status of the hot spot
mode depends on the internal relative humidity. When humidity is too high, hot spot mode is
disabled to allow fan speed reduction for dehumidification.
Page 63 of 94
DEHUMIDIFICATION
Parameters:
S02 HUMIDITY SET POINT (HS): pre-set= 80%
S04 HUMIDITY BAND(HB): pre-set= 40%
M37 DELAY DEHUMIDIFICATION: pre-set= 30 min
M38 MINTIA: preset = 30°C
Analog channel:
IRH: Internal relative humidity
TIA: Room temp A
Dehumidification starts if
System on for at least M37 minutes
TIA>M38+1
IRH>S02 +S04
Dehumidification stops if
System is not on.
TIA< M38
IRH<S02 -S04
During dehumidification
Fans rotate at minimum value
Cooling at maximum
EMERGENCY MODE
Parameters:
S02 HUMIDITY SET POINT (HS): pre-set= 80%
S04 HUMIDITY BAND(HB): pre-set= 40%
M19 MINIMAL FAN SPEED: pre-set = 30%
M20 MAXIMUM FAN SPEED: pre-set= 100%
Analog channel:
- IRH: internal relative humidity
Page 64 of 94
WATER FLOW CONTROL
Parameters:
S10 WATER FLOW SET POINT: pre-set=50 l/min
S11 WATER FLOW BAND: pre-set=5 l/min
S12 WATER FLOW INTEGRAL TIME: pre-set= 60sec
Analog channels
WF: water flow
Analog output
ANOUT2
By the analog output ANOUT2, a pump manages the water flow. The regulation of the pump
speed is integral-proportional (PI) type and it is based on WF analog channel. If nothing is
connected to the WF analog channel, the water flow control is absent.
Page 65 of 94
7.9 Alarms
Each alarm has a corresponding message on the display. Alarm messages are displayed on
LCD alternatively (few seconds) with the standard display.
Press ESC button for more than 5 seconds to reset the alarm with manual reset.
In the fourth line of the LCD display, “EMERGENCY” will appear when an alarm is active and the
machine is blocked. This doesn’t mean that the emergency control is enabled.
Alarms are summarized in the table below, which contains the following details:
ENABLE: condition to enable the alarm
DISABLE: condition to disable the alarm
DELAY: some alarms are delayed for a time adjustable with the specified parameter
RESET: kind of reset, automatic or manual
OUT: alarms can be addressed to a dedicated digital output and / or grouped in “Common
warning” and “Common alarm” setting the specified parameter. The “common warning” can be
connected to any relay by parameter I58. The “common alarm” can be connected to any relay by
parameter I59. Both “common warning” and “common alarm” aren’t displayed.
NOTES:
* All temperature and humidity alarms are delayed of M24 hours from C2020 power on.
** C2020 checks the number of fans indicated by M25 FAN CONFIGURATION FOR SBX
BOARD: pre-set and by M26 FAN CONFIGURATION FOR IE2 BOARD
This alarm works only with EC fans. Every EC fan has its own tachometric signal as a
feedback to C2020. When the analogue output to the fan is > M21 but the tachometric signal
is absent for more than 1 minute, the alarm appears.
*** “Request opening door” is a warning which appears when a door opening signal goes to
C2020 trough digital input A1, but ambient humidity is too high, so there is a risk of water
condensation on cold heat exchangers.
Page 66 of 94
DISPLAYED ENABLE DISABLE DELAY RESET OUT UNIT
ALARM BEHAVIOUR
High temperature TI > S20 TI <S20-S21 S28 and Auto I32 No changes
M24 *
Max temperature TI > S24 TI <S24-S25 S28 and Auto I34 No changes
M24 *
Low temperature TI <S18 TI>S18 + S19 S28 and Auto 131 No changes
M24 *
Min temperature ON: TI < S22 TI > S22 + S23 S28 and Auto I33 No changes
M24 *
Max water flow Flow meter present WF < S30 - 2 Auto I36 No changes
and WF > S30 l/min
Min water flow Flow meter present WF > S29 + 2 Auto I35 No changes
and WF < S29 l/min
Fire-smoke Dig in A7 enabled A7 disabled Manual I37 Unit off,
door closed
Air flow Dig in A9 enabled A9 disabled M12 Auto I39 No changes
Power failure AC to C2020 AC to C2020 Auto I40 No changes,
absent present door open
High humidity IRH > S26 IRH < S26 - S27 S28 and Auto I30 No changes
M24 *
Fan x thermic Automatic switch of Automatic switch Manual Fan1 I24 Emergency
fan x open of fan x closed Fan2 I25 mode
Fan3 I26
Fan x blocked Only EC fans Only EC fans Manual Fan1 141 Emergency
Output fan speed > Tachometric Fan2 I42 mode
M21 signal present Fan3 I43
Tachometric signal Fan4 I44
absent for more Fan5 I45
than 1 min ** Fan6 I46
Request opening Dig in A1 enabled IRH < S32 - S33 Auto I54 No changes
door and IRH > S32 and A1 disabled only
warning***
Opened door Dig in A2 enabled A2 disabled Auto I55 Fan speed at
S34 or
stopped if
door opened
by other
alarms
Warning Clock memory lost Manual No changes
Check date and (low C2020
time battery)
Warning C2020 reset with Manual No changes
Hardware reset RES jumper
Page 67 of 94
Unit management in case of sensor failure:
ALARM ACTION
Internal humidity probe broken (IRH) No function tied to IRH will be used
Internal temperature point A probe broken Opening valve at 100% and fan speed at 100%, if also
(TIA) TIB is broken
Internal temperature point B probe broken Opening valve at 100% and fan speed at 100%, if also
(TIB) TIA is broken
External temperature probe broken (TAE) No action
Water flow (WF) The pump speed will be the last calculated one
When a probe, connected to one of the seven analog channel, is broken, the correspondent alarm
will be on.
Each analog channel can be connected to a different type of sensor, so the action of the alarm
depends on the sensor (TBD).
When the alarm is on, its description and the sensor connected are displayed on the screen, for
example:
This message indicates that there’s a broken probe alarm in IC1 channel which is connected to
the internal relative humidity probe (IRH).
On the second line and on the third one of the screen the description of the alarm is displayed.
On the fourth line of the screen the probe connected is displayed.
It’s possible to connect the alarms to a relay and/or to associate them to “common warning” or
“common alarm” relay by I47, I48, I49, I50, I51, I52 and I53.
The reset is automatic.
Pressing SET key from “COUNTERS MENU” the hours of activity of the fans (or couple of fans)
are shown. The displayed parameters are:
Page 68 of 94
7.11 Alarm history menu
Pressing SET key from “ALARM MENU” you can enter the “ALARM HISTORY MENU” where all
details about the last 50 happened alarms are displayed.
This menu is accessible by the user.
Details of each alarm are displayed in two screens.
First screen:
xx/yy: “xx” is a number in progress while “yy” is the total number of happened alarms
dd/mm/yy: date when the alarm has happened
1/2: first page of two
hh:mm : time when the alarm has happened
DESCRIPTION OF ALARM: which type of alarm has happened
Second screen:
• xx/yy : “xx” is a number in progress while “yy” is the total number of happened alarms
• dd/mm/yy : date when the alarm has happened
• 2/2: second page of two
• TIA=: value of the internal temperature at point A, when the alarm became active
• TIB=: value of the internal temperature at point B, when the alarm became active
• IRH=: value of internal relative humidity, when the alarm became active
• TAE=: value of the external temperature, when the alarm became active
Press UP/DOWN ARROW keys to scroll alarms, their description and the relative analog
channel values. Press ESC key to come back the previous menu.
Page 69 of 94
7.12 System maintenance
This menu is composed of three submenus:
• Manual control
• Reset counter
• HW Key programming
RESET DATA
One screen is for the history of alarms and the others for the counters. Press UP/DOWN
ARROW keys to scroll the screens. Press SET key to reset a counter. Press ESC key, to come
back to the previous menu without resetting anything.
Page 70 of 94
MANUAL CONTROL
It allows controlling manually the devices of the unit, overriding the automatic control, but keeping
software functions for protection, to guarantee safety and integrity of all components.
It’s possible to get a manual control even if the unit is OFF.
To carry out the manual control you have to enter “MANUAL CONTROL” menu from “SYSTEM
MAINTENANCE” menu. Maintenance password 0111 is required.
Page 71 of 94
To scroll the submenus use UP/DOWN ARROW keys.
To enter every submenu press SET key. After that the status of the control can be modified
pressing UP/DOWN ARROW keys. To come back there are two ways:
Press the SET key: in this way the new status is stored
Press the ESC key: in this way the new status isn’t stored
ON/OFF MANAGEMENT : in this menu it’s possible to switch off the unit for a fixed time of 30
minutes. After 30 minutes the unit will switch on automatically.
Once inside this menu, to switch off the machinery, it’s necessary typing the right password and
pressing the SET key. The following screen will appear:
where “xx” is a countdown to automatic restart of the unit. Pressing the ON key it’s possible to
switch on the unit before time is over.
COOLING in this menu it’s possible to control the status of cooling mode. Temperature control
rules are bypassed, fans are forced to their max speed and the valve is forced to its
maximum opening.
ON: FANS = max speed, Valve= max opening (UP key)
OFF: the cooling has an automatic control (DOWN key)
FANx SPEED: this is the speed of fan x which can be controlled by this menu
INC: to increase the value use the UP key
DEC: to decrease the value use the DOWN key
VALVE OPENING: this is the opening of the water valve which can be controlled by this menu
INC: to increase the value use the UP key
DEC: to decrease the value use the DOWN key
TIMER: this is a parameter indicating how long it’s possible to stay under manual control. The
following screen is displayed:
When time is over, all manual controls will be switched off and automatic control of the unit will
be restored. This time can be set from 0 to 255 minutes.
Page 72 of 94
Timer is preset at 1 minute. After that automatic control is restored. Before starting
manual control, it is recommended to increase this parameter as much as
necessary to complete the test on the unit. If it is required to go out of manual
control before set time elapses, restore the modified parameter of manual control
to the original value. For instance: if manual control is on cooling, restore OFF on
the corresponding parameter to return to automatic control. If fan speed has been
forced to 30%, restore value to 0%.
STULZ PROTOCOL
Involved parameters:
To allow the connection of a C2020 controller to the RS485 serial line, the serial 485 adapter
ACTSERC1010 (IS485) is required.
The C2020 controller can communicate (through the RS485 serial port) with Stulz TeleCompTrol
software installed on host computer which displays the setup parameters, the controller states
and alarms.
The parameter M02 selects which protocol manages the communication:
In case of STULZ PROTOCOL it must be = 1. The baudrate is 9600kbit/sec.
The parameter M03 sets the protocol for the connector SLAVE of the board, in case of STULZ
PROTOCOL it must be =1.
In the system (see figure below) there is a gateway (MIB) which manages the communication
according to the STULZ protocol specifications.
• The connection between the RS485 serial port (named PRG) of two different C2020
controllers;
Page 73 of 94
• The connection between the PRG port of the C2020 controller to the MIB gateway;
• The connection between the RS232 serial port of gateway to the RS232 serial port of the
host computer.
MODBUS PROTOCOL
Involved parameters:
To allow the connection of a C2020 controller to the RS485 serial line, the serial 485 adapter
ACTSERC1010 (IS485) is required.
The C2020 controller can communicate (through the RS485 serial port) with the software
installed on host computer which displays the setup parameters, the controller states and alarms.
The parameter M02 selects which protocol manages the communication:
In case of MODBUS PROTOCOL it must be = 2. The baudrate is 9600kbit/sec.
The parameter M03 set the protocol for the connector SLAVE of the board, in case of STULZ
PROTOCOL it must be = 2.
In the system (see figure below) there is no gateway managing the communication.
The connection between the RS485 serial port (named PRG) of two C2020 controllers;
Page 74 of 94
The connection between the PRG port of a C2020 control board and the RS485 serial port of the
host computer:
Page 75 of 94
8. Maintenance
8.1 Safety instructions
Installation and intervention on air conditioners must be made in full compliance with specific
national regulations for accident prevention, with particular reference on electrical and refrigerant
equipment. Failure to comply with these regulations might be dangerous to people and
environment.
Before any intervention on the unit, refer to instructions on this manual, check data on the name-
plate and take any other precaution in order to guarantee optimal safety.
Safety procedures
Cut of the power supply to the unit before making any maintenance operation. A
“DO NOT SWITCH ON” warning sign must be clearly visible. ON-OFF key on C2020
display (if present) is only used to put the unit is stand-by. It must not be
considered as a safety device to switch off the unit before maintenance.
Live electrical components have to be switched to de-energized and checked to
ensure that they are in the de-energized state.
Some verification must be effected with the unit in operation (measuring current,
pressures and temperatures). In such a case, the unit must only be switched on at
the master switch after all mechanical connections have been carried out. The unit
must be switched off immediately after the measuring procedure.
The electrical box might be hot.
Very little routine maintenance is necessary to keep the unit in reliable operating order and
protect its moving parts. This maintenance, however, must be performed at the prescribed
maintenance intervals. Failure to perform due maintenance both decreases the working life and
efficiency of the unit and also invalidates guarantee coverage.
Every 3 months
• AIR FILTERS (only in open loop models): check the condition of the filters and replace them
if necessary (dirty filter alarm). When you decide to replace the filter the new filter must have
a filter element with the same thickness and density as the original filter. Sets of spare filters
can be ordered from the STULZ service department.
• HEAT EXCHANGERS: check that the heat exchangers are efficient and not clogged or dirty.
• CONDENSATE DRAIN: check that the condensate drain system is perfectly clean and
efficient.
Page 76 of 94
Every year
• FANS: check that fans do not show signs of overheating or abnormal vibrations and that they
are free to rotate. Also check the remote condenser.
• ELECTRICAL CIRCUIT: check that electrical connections are tight, that switches, remote
control switches and isolating switches are operating and in good condition. Also check that
the control card operates and perform a test of alarm signals.
• MECHANICAL PARTS: clean the inner components of the system.
Heat exchanger
Heat exchanger consists of copper tubes with aluminum fins. Particles of internal and external air
passing through the filter might nest between the fins, reducing heat transmission efficiency and
increasing air flow resistance. The latter shows when the fan current increases.
For cleaning, proceed as follows: blow compressed air through the heat exchanger in the
direction opposite the direction of air flow during normal operation.
Do not distort the fins while cleaning - this also increases the air resistance.
Fan
The bearings of the fans are lifetime lubricated and do not need maintenance. Check the
operation current. An increased operation current indicates either a higher air resistance by a
clogged pre-filter or a winding short circuit in the fan motor.
Fan is automatically controlled with variable speed. To make measurements at nominal speed,
use manual control.
Filter
Page 77 of 94
Loosen the fixing screws at the sides of the
brackets. Push the bracket up and extract it.
Then the filter can be removed.
Spare filters must have filtering medium with the same thickness and
density as the original one. A set of spare filters can be ordered at CONTEG
sales dept.
Page 78 of 94
9. Uninstalling the unit
This unit must be uninstalled by specialized and authorized persons.
Cut off power supply. Switch off power conducting cables to the unit and secure them against
being switched on again. Disconnect the A/C unit from the de-energized network.
Disconnect the unit from external water circuit, closing water valves and emptying hydraulic
circuit of the unit.
If either glycol or similar additives have been used, also this mixture must be
collected and disposed in a suitable way avoiding to pour it into the sewer.
Move the unit as described in paragraph “lifting and transport”, with a lifting device of suitable
capacity.
Dispose of the unit in accordance with the disposal and safety regulations applicable on site. We
recommend a recycling company for this. Basically, the unit contains the following raw materials:
aluminum (heat exchanger and condensate tray), copper (heat exchanger, water collector and
electrical cables), zinc plated iron and steel (panels and metallic frame), rubber (water pipes).
Page 79 of 94
10. Appendix: technical data
Notes on technical data sheets:
* Nominal conditions
Closed loop: return air temperature 45°C / RH 15%
Open loop: return air temperature 30°C / RH 30%
EWT (all models) = 7°C
Water dT (all models) = 5°C
Gross cooling capacities (including power dissipated by fans)
Refrigerant: water without additives
** Total pressure losses through the water circuit inside the unit.
*** Air flow in closed loop models refers to the unit not installed in the rack.
Notes on diagrams:
• Return air conditions: T = 26°C RH = 40% / T = 30°C RH = 30% /
T = 35°C RH = 25% / T = 40°C RH = 20% / T = 45°C RH = 15%
• For all models in all working conditions listed above, SHF = 1 (total cooling
capacity sensible cooling capacity)
• Refrigerant: water without additives
Page 80 of 94
CONTEG OPEN LOOP AC-SO-CW AC-SO-CW AC-SO-CW
A2 A8 B4
Total cooling capacity* kW 12.5 16.2 19.3
Sensible cooling capacity* kW 12.5 16.2 19.3
Power supply V/ph/Hz 230/1/50
Air flow m3/h 2500 | 3600 | 3600
FAN
AC FAN version
Number of fans 3 5 5
Fan motor max (each) W 160
A 0.7
EC FAN version
Number of fans 3 5 5
Fan motor max (each) W 178
A 1.4
AIR-TO-WATER HEAT EXCHANGER
Type COPPER TUBE / ALUMINUM FIN
Face area m2 0.40
Air face velocity m/s 2.3 2.8 2.8
WATER CIRCUIT
Water flow l/h 2150 2790 3330
Water pressure drop (total)** kPa 62 91 75
Water valve type 3-way modulating valve
FILTER - WASHABLE (STANDARD)
Quantity and shape 3 zigzag
Size mm 600x180
Depth mm 100
Efficiency EU3
PHYSICAL DATA
Cooling module
Height1) mm 1978 (42U)
Width mm 300
Depth mm 1000 or 1200
Weight (empty) – depth 1000 kg 169 173 173
Weight (empty) – depth 1200 kg 179 183 183
Weight (with coolant) – d.1000 kg 175 179 179
Weight (with coolant) – d.1200 kg 185 189 189
WATER CONNECTION SIZES
Supply line diameter in 1" female
Return line diameter in 1" female
1)
Indicated height includes the plinth 100 mm;
Height 2111 mm (45U) is available on special request
Page 81 of 94
CONTEG CLOSED LOOP AC-SC-CW AC-SC-CW AC-SC-CW
A4 B2 C4
CONTEG CLOSED LOOP – AC-SM-CW AC-SM-CW AC-SM-CW
MODULAR SYSTEM A4 B2 C4
Total cooling capacity* kW 21.6 29.5 36.0
Sensible cooling capacity* kW 21.6 29.5 36.0
Power supply V/ph/Hz 230/1/50
Air flow*** m3/h 2600 4000 4000
FAN
AC FAN version
Number of fans 3 5 5
Fan motor max (each) W 160
A 0.7
EC FAN version
Number of fans 3 5 5
Fan motor max (each) W 178
A 1.4
AIR-TO-WATER HEAT EXCHANGER
Type COPPER TUBE / ALUMINIUMFIN
Face area m2 0.40
Air face velocity m/s 2.3 2.8 2.8
WATER CIRCUIT
Water flow l/h 3700 5070 6200
Water pressure drop (total)** kPa 81 122 142
Water valve type 3-way modulating valve
PHYSICAL DATA
Cooling module
Height1) mm 1978 (42U), 2111 (45U), 2245 (48U)
Width mm 300
Depth mm 1200
Weight (empty) – height 42U kg 179 183 183
Weight (with coolant) kg 185 189 189
WATER CONNECTION SIZES
Supply line diameter in 1" female
Return line diameter in 1" female
1)
Indicated height includes the plinth 100 mm.
Page 82 of 94
CONTEG A2 open loop: cooling capacity
Page 83 of 94
CONTEG A2 open loop: total pressure losses
Page 84 of 94
CONTEG A8 open loop: water flow
Page 85 of 94
CONTEG B4 open loop: cooling capacity
Page 86 of 94
CONTEG B4 open loop: total pressure losses
Page 87 of 94
CONTEG A4 closed loop: water flow
Page 88 of 94
CONTEG B2 closed loop: cooling capacity
Page 89 of 94
CONTEG B2 closed loop: total pressure losses
Page 90 of 94
CONTEG C4 closed loop: water flow
Page 91 of 94
Page 92 of 94
Page 93 of 94
11. Contacts
CONTEG, spol. s r.o.
Na Vítězné pláni 1719/4
140 00 Prague 4
Czech Republic
www.conteg.com
[email protected]
Page 94 of 94