Nordcold N41x - N51x - Service Manual
Nordcold N41x - N51x - Service Manual
Nordcold N41x - N51x - Service Manual
Gas Electric
Refrigerators
MODELS
N41X Series
N500 Series
N51X Series
Questions? 1-800-444-7210
© 2015 NORCOLD, INC. All rights reserved. Part No. 626800 Rev. B 07.12.2015
TABLE OF CONTENTS
Table of contents ............................................................ 2 Ventilation ..................................................................... 25
Introduction ..................................................................... 4 Roof Exhaust Venting ................................................ 25
About This Manual ...................................................... 4 Double Sidewall Venting ........................................... 25
Model Identification ..................................................... 4 Propane Gas System - N500........................................ 27
Information Label ........................................................ 4 Components .............................................................. 27
Cooling Unit Serial Number ......................................... 4 Propane Gas System - N41X/N51X ............................. 28
Certification and Code Requirements ......................... 4 Components .............................................................. 28
About Installation ......................................................... 4 Propane Gas System - All Models ................................ 29
Replacement Parts ...................................................... 4 Components Continued - All Models ......................... 29
Technical Assistance ................................................... 4 Handling of Propane Gas Lines and Fittings ............. 29
Safety Awareness ........................................................... 6 Propane Gas Pressure .............................................. 30
Safety Notice ............................................................... 6 Testing for Gas Leakage ........................................... 30
Attention Statements ................................................... 6 Burner Cleaning Procedure ....................................... 31
Specifications ................................................................. 7 Electrical Requirements and Components ................... 32
N41X Models ............................................................... 7 AC Power .................................................................. 32
N500 Models ............................................................... 8 DC Power ................................................................. 32
N51X Models ............................................................... 9 AC Power Cord ......................................................... 34
Troubleshooting - Quick Reference Guide ................... 10 N500 Terminal Block ................................................. 34
N41X /N51X Displayed Fault Codes .............................11 AC/DC Converter as Power Source .......................... 34
Troubleshooting Flowcharts - N500 Units .................... 12 Cooling Unit .................................................................. 35
Burner Will Not Maintain Flame - N500 Units ........... 12 Description ................................................................ 35
No AC Operation - N500 Units .................................. 13 Gradual Decrease in Cooling Efficiency .................... 35
No DC Operation - N500.3 (3-Way Units Only)......... 14 Cooling Monitoring - N510 Units Only ...................... 35
No Gas Operation - N500 Units ................................ 15 Refrigerant Leakage - All Models .............................. 36
Thermocouple and Interrupter Malfunctioning Disposal of Cooling Unit - All Models ........................ 36
- N500 Units ........................................................... 16 Cooling System Diagnostic Flowchart ....................... 37
Troubleshooting flowcharts - N41X/N51X Units ........... 17 Electronic Components - All Models ............................. 39
Blank Display - Refrigerator does not turn on Spark/Sense Electrode - All Models .......................... 39
- N41X/N51X .......................................................... 17 Electronic Components - N500 Models ........................ 39
Optical Display Does Not Turn On Relighter - N500 Models ........................................... 39
- Power is available - N41X/N51X .......................... 17 Flame Indicator - N500 Models ................................. 39
On-Off Theory of Operation - N41X / N51X .............. 17 Electronic Components - N41X/N51X Models.............. 40
“F” Fault Code - Burner failed to ignite or reignite Power Board - N41X/51X Models ............................. 40
- N41X/N51X .......................................................... 19 Controls ........................................................................ 41
“E” Fault Code - DC voltage high - N41X/N51X ........ 20 N500 Controls ........................................................... 41
“C” Fault Code - DC voltage low - N41X/N51X ......... 20 N41X/N51X Controls ................................................. 42
“A” Fault Code - No AC power available N41X/N51X Modes of Operation ............................... 43
- N41X/N51X .......................................................... 21 N41X/N51X Diagnostic Mode ....................................... 46
“S” Fault Code - Flame sense circuit failure Diagnostic Mode ....................................................... 46
- N41X/N51X .......................................................... 21 Wiring Pictorials and Diagrams .................................... 49
“H” Fault Code - AC heater failed open
- N41X/N51X .......................................................... 22
“r” Fault Code - AC relay stuck closed
- N41X/N51X .......................................................... 22
Thermistor Failure Fault - Controls in Backup
Operating System Mode - N41X/N51X .................. 23
Backup Operating System - N41X/N51X Models ...... 23
“N” Fault Code - No cooling detected by the
controls - N41X/N51X ............................................ 24
Power Board Resetting Procedure ............................ 24
NORCOLD. INC.
TESTED FOR LP GAS: EQUIPPED FOR PROPANE / Teste
pourle GPL, equipped por le propan
D
TI FIE
Degagement minimum pour I'installation R R
0" cotes, haut,bas, arriere, Installer
uniquement avec latrousse n_5
Voir les instructions d'installation.
CSA-1.10-2003 ANZI Z221.19-2003
618860 REFRIGERATORS REFRIGERATORS
Attention Statements
The safety alert symbol ! followed by the word
WARNING or CAUTION identifies potential safety ! CAUTION: This heading identifies
hazards or conditions. hazards, which if ignored can cause injury and/or
property damage.
N41X Models
Storage volume
N41X ---------------------------------------------------------------------------------------------------------------------------------- 5.5 ft3.
Controls
Type ------------------------------------------------------------------------------------- Electronic with built-in diagnostic function
ON/OFF/MODE/TEMP SET switches -------------------------------------------------------------------Flush pushbutton style
Temperature settings ---------------------------------------------------------------------------------------------- 1=cold, 5=coldest
Temperature sensor ---------------------------------------------------------------------------- Thermistor, fin-mounted on 5th fin
DC power
Controls operating voltage ----------------------------------------------------------------------------------------- 10.5 to 15.4 Vdc
Controls DC fuse (F2 in power board) ------------------------------------------------------------------------------- 3 A type 3AG
DC operation voltage (3-way models only)-------------------------------------------------------------------12 VDC to 15 Vdc
DC heater rating (3-way models only) ------------------------------------10.7 amps @12 VDC (resistance is 1.3 ohms)
AC power
AC heater operating voltage requirements ----------------------------------------------------------------------- 108 to 132 Vac
Fuse AC heater circuit (F3 in power board) ------------------------------------- 5 A, 1/4 in. x 1 1/4 in. AGC type fast acting
AC heater rating ----------------------------------------------------------------- 200 W @ 110 VAC (resistance of 61.3 ohms
Propane gas
Operating pressure ----------------------------------------------------------------------------------------------- 10.5 to 11.5 in. w.c.
Heat input ---------------------------------------------------------------------------------------------------- 1200 Btu/h @ 11 in. w.c.
Orifice -----------------------------------------------------------------------------------------------------------------------------------LP14
N500 Models
Storage volume
N500 ---------------------------------------------------------------------------------------------------------------------------------- 5.5 ft3.
Controls
Type -------------------------------------------------------------------------------------------------------------------------- Top mounted
Temperature settings ---------------------------------------------------------------------------------------------- 1=cold, 5=coldest
Temperature sensor ----------------------------------------------------------------------------------------------------- Capillary tube
DC power
Ignition circuit operating voltage ---------------------------------------------------------------------------------- 10.5 to 15.4 Vdc
Relighter---------------------------------------------------------------------------------------------------------------1.3 amp type 3AG
DC operation voltage (3-way models only)-------------------------------------------------------------------12 VDC to 15 Vdc
DC heater rating (3-way models only) ------------------------------------10.7 amps @12 VDC (resistance is 1.3 ohms)
AC power
AC heater operating voltage ---------------------------------------------------------------------------------------- 108 to 132 Vac
AC heater circuit fuse -------------------------------------------------------- 5A, 1/4 in. x 1 1/4 in. AGC type fast acting, inline
AC heater rating ----------------------------------------------------------------- 200 W @ 110 VAC (resistance of 61.3 ohms
Propane gas
Operating pressure ----------------------------------------------------------------------------------------------- 10.5 to 11.5 in. w.c.
Heat input ---------------------------------------------------------------------------------------------------- 1200 Btu/h @ 11 in. w.c.
Orifice -----------------------------------------------------------------------------------------------------------------------------------LP14
Gas ignition --------------------------------------------------------------------------------------------------- 12 VDC ignition module
Electrode-to-burner air gap ----------------------------------------------------------------------------------------------------- 3/16 in.
N51X Models
Storage volume
N51X ---------------------------------------------------------------------------------------------------------------------------------- 5.5 ft3.
Controls
Type ------------------------------------------------------------------------------------- Electronic with built-in diagnostic function
ON/OFF/MODE/TEMP SET switches -------------------------------------------------------------------Flush pushbutton style
Temperature settings ---------------------------------------------------------------------------------------------- 1=cold, 5=coldest
Temperature sensor ---------------------------------------------------------------------------- Thermistor, fin-mounted on 5th fin
DC power
Controls operating voltage ----------------------------------------------------------------------------------------- 10.5 to 15.4 Vdc
Controls DC fuse (F2 in power board) ------------------------------------------------------------------------------- 3 A type 3AG
DC operation voltage (3-way models only)-------------------------------------------------------------------12 VDC to 15 Vdc
DC heater rating (3-way models only) ------------------------------------10.7 amps @12 VDC (resistance is 1.3 ohms)
AC power
AC heater operating voltage requirements ----------------------------------------------------------------------- 108 to 132 Vac
Fuse AC heater circuit (F3 in power board) ------------------------------------- 5 A, 1/4 in. x 1 1/4 in. AGC type fast acting
AC heater rating ----------------------------------------------------------------- 200 W @ 110 VAC (resistance of 61.3 ohms
Propane gas
Operating pressure ----------------------------------------------------------------------------------------------- 10.5 to 11.5 in. w.c.
Heat input ---------------------------------------------------------------------------------------------------- 1200 Btu/h @ 11 in. w.c.
Orifice -----------------------------------------------------------------------------------------------------------------------------------LP14
The refrigerator does not cool Ventilation obstructed. Check enclosure for air flow obstructions.
efficiently on AC power. AC voltage low. Check AC voltage input.
DC voltage low.
DC voltage high.
Flashing
Temp Backup operating system in operation.
Setting
YES
YES
YES
YES
NO
Wiring OK? Repair or replace selector switch wiring.
Check selector switch wiring.
YES
Interrupter
terminals
YES
YES
YES
YES
AC
Set selector switch to "AC." voltage
NO
Replace selector switch.
Check voltage out of present?
selector switch terminal 1b.
YES
YES
YES
Resistance NO
Check DC heater resistance. Replace DC heater.
1.2 to 1.4
ohms?
YES
YES
YES
YES
YES
mV
V mA
OFF
4. Set selector knob to LP GAS operation.
A mA mA COM
!
V
Thermocouple
disconnect wires from interrupter.
7. Press and hold gas safety valve and turn selector
knob to LP GAS to ignite burner. Hold the valve open
Figure 4. Checking thermocouple voltage output to to maintain the flame lit while following procedure
interrupter below.
Check thermocouple
voltage output. See
Figure 4.
Voltage NO
10 to 30 Replace thermocouple.
mlV?
YES
No voltage (0)
reading from
angled interrupter Replace thermocouple.
terminal to ground.
See Figure 5.
10-30 mlV
Check thermocouple voltage across interrupter
Replace gas safety valve.
output to interrupter. terminals.
See Figure 6.
No voltage (0)
reading from
straight interrupter Check control switch connections.
terminal to ground.
See Figure 7.
Angled Angled
terminal terminal
Straight
Straight terminal Angled Straight
terminal terminal terminal
Interrupter Interrupter
Interrupter
Figure 5. Checking angled terminal Figure 6. Checking voltage across Figure 7. Checking straight
to ground terminals terminal to ground
00.0
4 1/2 DIGITS
1 Seconds
MIN MAX
REL
HOLD
Hz
H
mA
V A
μA
V
OFF
A mA μA COM V
NOTE
Figure 8. Checking DC fuse continuity K3 is a latching relay. Once the relay coil is energized the
contacts close and remain closed even when the 12VDC
is removed, hence the term “latching relay”. With the
Optical Display Does Not Turn On - Power is K3 contacts now closed, 12VDC is passed back to the
Display Board via the white-red wire [L] between P1-9
available - N41X/N51X of the Power Board and P1-2 [M] of the Display Board.
This 12VDC will remain at P1-2 [M] until the latching relay
Verify: is “unlatched”, which will not take place until the On-Off
■ There is 10.5 - 15.4 volts DC between power board terminals button is depressed again. This 12VDC is termed the
12VDC and GND1. If not, correct DC input to power board. switched 12-volts and is used to power on the display.
■ There is 10.5 - 15.4 volts DC between the white / red wire
and the white / violet wire of the optical control wire harness
connector.
■ The 5 amp fuse (F1) on the power board is intact. If not,
NOTE
replace fuse.
■ There is 10.5 - 15.4 volts DC between the white / red wire and The On-Off switch [E] is a momentary push-button
the white / violet wire of the power board wire harness con- switch. The operation described above takes place
nector. If not, replace power board. during the “split second” the On-Off button is depressed
■ While pressing and holding the ON/OFF button, there are to power the refrigerator on. If for some reason the
10.5 - 15.4 volts DC between the blue and the white / violet display does not turn on, the On-Off button can be
wires at the optical display connector. If the connectors and pushed and held down to aid in troubleshooting.
the terminals are secure and undamaged, replace the optical EXAMPLE: Verify you have 12VDC between P1-1 (GND)
control display assembly.
and P1-6 (continuous 12-volts) of the Power Board.
■ After releasing the ON/OFF button, there are 10.5 - 15.4 volts
DC between the green wire and the white/violet wire of the
Leave the meters black ground lead connected to P1-1
wire harness optical display connector. If not, replace power and move the red positive lead from P1-6 to P2-3 of
board. the Power Board. Have someone press and hold the
■ That the optical display LED is illuminated, If not, replace the On-Off button. You should measure 12VDC as long as
optical control display assembly. the On-Off button is held in. When the On-Off button is
released you should see the 12VDC go away.
1
P4
K6
2
- YL-GN/JN-VE
1
-
K4
2
K3
3
K1
K5
-
4
K4
+
U1
5
+
K5
6
AND MAKE SURE RIBBON CABLE IS SECURELY
AND PROPERLY CONNECTED TO P2. SILVER
+ CONTACTS OF RIBBON CABLE SHOULD BE
7
K2
8 +
K6
P2
+
9
+
10
K1
P1
WH-BK/BC-NR
LIMIT_OUT
+
P1
LIMIT_IN
1
AC_HT_HI
RD-YL/RG-JN
CABLE
RIBBON
3
K2
AC_HT_LO_2
4
AC_HT_LO
D
5
BU-BL
WT-VT/BC-VT P1
GN/VE
P2
6
1
WH-RD/BC-RG 2 Vreg 1
TEMP MODE ON-OFF
F2 8-Amp
BU-BL M
P2
2
L2 3 i
c
WT-VT/BC-VT 4 r 3
5
o
4 EE
WT/BC 6 5
7
L1 OVERLAY
POWER BOARD/PANNEAUD’ALMENTATION
GND
P4
- YL-GN/JN-VE
1
J
K4
2
K3
3
K1
K5
4
K4
U1
+
K5
6
7
K2
K3
K
+
9
10
K1
P1
LIMIT_OUT
+
LIMIT_IN
1
AC_HT_HI_2
2
WH-RD/BC-RG
AC_HT_HI
H
3
L
K2
AC_HT_LO_2
M
4
AC_HT_LO
F D
5
BU-BL G
WH-VT/ BC-VT GN/VE P1
RIBBON CABLE
6
1 P2
WH-RD/BC-RG 1
TEMP MODE ON-OFF
2 Vreg
F2 8-Amp
BU-BL M
P2
2
L2 3 i
c
WH-VT/ BC-VT 4 r 3
5
o
4 EE
WH/BC 6 5
L1 7
OVERLAY
POWER BOARD/PANNEAUD’ALMENTATION
DISPLAY BOARD / CARTE D’AFFICHAGE
Burner NO
and orifice Clean and service burner and orifice.
clean?
YES
YES
YES
YES
YES
NOTE
YES
YES
Check that fuse holder clips NO Adjust clips to ensure fuse contacts are
are making full contact with Clips okay?
firm in clips and making full contact.
fuse.
YES
Replace power board.
YES
YES
Replace power board.
AC heater resistance 58 to 64 W.
Temperature* Resistance*
(oF) (k )
85 8.1– 9.0
80 9.1–10.0
16 pin connector
75 10.1–11.0
70 11.1–12.0
5th Fin 60 12.1–13.0
50 15.5–16.5
40 22.5–23.5
35 24.5–25.5
33 28.5–29.5
32 30.0–32.0
*Approximate Values Pin 13
Thermistor
packed in
ice bath Pin 8
Thermistor wiring
(to 16 pin connector)
Backup Operating System - N41X/N51X the cooling cycle. For example, if the temperature setting
Models is set to 4, raising the setting to 5 will lengthen the cooling
The backup operating system (BOS) is an electronically cycle, making the cabinet colder.
controlled duty cycle. It maintains the refrigerator in When a warmer temperature is desired, changing the
operation if the thermistor is disconnected or fails. The temperature setting to a lower number shortens the cooling
BOS maintains cooling by controlling the heat source cycle. For example, if the temperature setting is set to 5,
selected. When the refrigerator is operating in BOS, the lowering the setting to 4 will shorten the cooling cycle.
length of the cooling cycle is regulated not by temperature,
but by time. When the N41X/N51X controls shift to BOS operation,
the temperature setting flashes for ten seconds when the
To accomplish this, the BOS adjusts the length of the TEMP button is pressed. After ten seconds, the selected
cooling cycle according to the temperature setting selected operation mode indicator displays.
by the user-the higher the temperature setting, the longer
YES
NOTE
A jumper wire to short Pin 15 to ground can be made
from a six inch long insulated 22 AWG wire with a 1/2
inch of insulation stripped from each end.
Insulated wire jumper
8. Turn OFF the refrigerator. Pin 16 Pin 15 Ground Lug
White/violet wire
9. Turn ON refrigerator. If “n” code displays, repeat 22 AWG with 1/2" long stripped ends
steps 7 - 9.
Figure 12. Resetting the power board
Minimum Maximum
Bottom 0 inch 0 inch
Absorber coils
Sides (each) 0 inch 1/8 inch
Air intake vent
Gas safety
valve
Flue tube
Canister
A
Mounting
bracket
Flue baffle
Electrode
Mounting
bracket Burner
Manual shut-off
Components The orifice meters the flow of gas to the burner. The
Manual Shutoff Valve N500 model requires the LP14 orifice. See Figure 19.
The manual shutoff valve controls the flow of propane gas A restricted, clogged, or damaged orifice will affect the
from the RV propane supply to the gas valve-thermostat burner’s heat output, which in turn affects the performance
assembly. See Figure 18. of the cooling unit when the refrigerator is operating on
propane gas. The orifice should be checked and cleaned
Orifice annually to maintain the propane gas combustion system
at peak performance. It should also be checked before
and after seasonal storage, and before the recreational
! WARNING: Do not separate the orifice vehicle is placed in service. See “Burner Cleaning” section
from its threaded adaptor! The orifice and its adap- for more information on cleaning the burner and its
tor are a sealed assembly. Separating the orifice components.
from the threaded adaptor can cause propane
gas leakage. A propane gas leak can ignite and L P
Manual shut-off
Canister
Flue tube
DC connections
Gas valve Flue baffle
Burner tube
Components
Solenoid Gas Valve
The solenoid gas valve, shown in Figure 22, controls DC power connections Mounting bracket
the flow of gas from the RV gas supply to the burner.
Integrated in the valve’s body are a manual shutoff and
pressure tap. The valve’s manual shutoff is a spring- Solenoid
The orifice meters the flow of gas to the burner. The N41X/
N51X models require the LP14 orifice. See Figure 23.
A restricted, clogged, or damaged orifice will affect the Figure 23. LP14 orifice
burner’s heat output, which in turn affects the performance
of the cooling unit when the refrigerator is operating on
propane gas. The orifice should be checked and cleaned
annually to maintain the propane gas combustion system
at peak performance. It should also be checked before
and after seasonal storage, and before the recreational
vehicle is placed in service. See Burner Cleaning for more
information on cleaning the burner and its components.
Figure 24. Gas flame appearance. ! WARNING: When working on or near the
Flue Tube propane gas system:
The flue tube channels hot exhaust gases towards the Do not smoke or light fires! Extinguish all open
exhaust vent. It should be cleaned annually to maintain the flames!
combustion system at peak performance. Do not use an open flame to leak test any of the
Flue Cap propane gas system components. Propane gas is
The flue cap maintains a slight back pressure of hot highly flammable and explosive.
combustion exhaust gases in the flue tube. This slight back Do not connect the refrigerator directly to the propane
pressure helps to establish and maintain a good draft of gas tank. Always use an approved pressure regulator
ventilation air through the cooling unit. between the propane gas tank and the refrigerator
Flue Baffle propane gas system.
The flue baffle is located inside the flue tube and helps Always use two wrenches to tighten or loosen
distribute the heat to the generator section of the cooling connections to prevent damage to connections,
unit. The flue baffle must never be permanently removed. piping, and components. Damaged connections,
The flue baffle should be cleaned annually to maintain the piping, and components create the potential for gas
combustion system at peak performance. leaks.
1. Turn OFF refrigerator. 11. Visually inspect the orifice. If dirty, wash the
2. Close the propane gas tank valve(s). assembly with alcohol, then allow to air dry. If
cleaning fails to remove dirt or if the condition of the
For Steps 3 - 5, refer to Figure 18 (N500), or Figure 22 orifice assembly is questionable, replace the orifice
(N41X/N51X). assembly.
12. Clean dirt or debris from the burner box base.
3. Close the gas valve manual shutoff.
13. Reinstall the burner. Do not overtighten the retaining
4. Remove the drip cup retaining screw, then remove screw.
the drip cup.
AC Power Cord
N500 AC Power Cord
Wire leads identification
N500 models are supplied AC power through the AC
power cord, which connects to the terminal block (see Smooth: Line (hot) lead ( to terminal block terminal 2)
Ribbed: Neutral lead (to terminal block terminal 1)
Figure 28). The cord’s grounding prong on the AC outlet Green: Ground to metal plate
connector must be left intact and never be modified or
cut. The cord’s ground wire (green wire) must always be
fastened to the refrigerator cabinet metal plate.
N41X/N51X AC Power Cord
N41X/N51X models are supplied AC power through the AC
Figure 28. N500 AC power cord
power cord. See Figure 29. Do not modify or cut the cord’s
grounding prong. Always make sure that ground wire
(green wire) is tightly fastened to the refrigerator cabinet
metal plate. The rounded side of the AC cord’s power
board connection must be connected to the power board
with the rounded side facing left.
Wire leads identification
N500 Terminal Block Smooth: Line (hot) lead (to power board connector)
Ribbed: Neutral lead (to power board connector)
The terminal block is located on the back of the refrigerator Green: Ground to metal plate
in the lower left corner. See Figure 30. The terminal block
receives AC power from the RV’s AC outlet and DC power
from the RV’s DC power supply and distributes the power
to the refrigerator’s electrical components.
Figure 29. N41X/N51X AC power cord
AC/DC Converter as Power Source
! WARNING: Do not
Check cooling unit. operate the refrigerator if the
cooling unit is leaking or a leak
is suspected.
Signs of leak(s):
YES · Yellow residue inside or at the rear of the
Replace cooling unit. Any signs of leak? refrigerator.
· Ammonia smell.
NO
NO Ventilation as YES
Correct ventilation to meet
per installation Check heat input.
installation requirements.
instructions?
! WARNING: Do
Continued from previous page.
YES
YES
NO
Spark/sense electrode
Orange wire
Spark/sense
Relighter electrode
(orange)
Retaining
screw
DC power
supply
(white)
Ground
(green)
NOTE
Because the wire harness is “foamed” into the cabinet,
it is not a replaceable component.
N500 Controls
5
1
5 2
4 3
N41X/N51X Controls
controls shift to propane gas, the controls second priority AUTO LED on to indicate AUTO mode AUTO
2. The AC LED comes on as the 2. Shut off power to the solenoid gas valve.
controls search for AC power AC LP GAS
availability. AUTO
3. Set “gas lock-out”.
3. The AC LED turns off when AC
power is detected by the controls. AC LP GAS
NOTE
Mode operation is indicated by the AUTO
AUTO LED. In AUTO mode, the controls maintain “gas lock-out”
until a full cooling cycle on AUTO AC is completed.
NOTE Turning the refrigerator OFF and back ON also clears
“gas lock-out.”
In AUTO mode, pressing the MODE push-button
momentarily displays the heat energy source in use. 4. Provide a visual warning by flashing alternating “A”
For example, in AUTO AC, the AC LED will come on (no AC) and “F” (no flame) fault codes, shown below.
and stay on for approximately 10 seconds.
NOTE
AUTO DC and DC Manual Mode Maintain cooling only.
3 DC voltage low
4 DC voltage high
AC mode selected
but not available
5 6
AC relay stuck closed
7
Press the MODE button to bring up screen 8. Press the button to return to screen 1.
MODE
9 BLK/NOIR
BLK/NOIR
15 ORN/ORANGE
14 16
BLK/NOIR
L T2
13 T1 T3
BLK/NOIR
BLK/NOIR
5
12 BLK/NOIR
3
BLK/NOIR
4a 3b 2
4b 3a
BLK/NOIR 2a 1b
11
2b 1a
7
BLK/NOIR
10 BLK/NOIR
BLK (RIB)
BLK/NOIR /NOIR
4 GRN-YEL/
GRN/VERT
VERT/JUANE
8 1
6 BLK/NOIR
3 17 9
TB-2 TB-1
1a AC/CA
1 1b 1
Off/Arret
15
12 DC/CC
TB-3
TB-4
4b
10
4a
11
16 14
3a
Gas/Gaz
3b
2a
Gas/Gaz 8
2b
18 20
19
U1
P2
6 5 4 3 2 1
K5
K2
K4
K3
K1
WH/BC
BU-BL
P3 1 2
4
WH/BC
3
WH-VT/BC-VT
F2 8-Amp
K1
F1 5-Amp
OR-OR
K3
K2
K5
K4
AC_HT_LO_2
AC_HT_HI_2
LIMIT_OUT
AC_HT_LO
AC_HT_HI
P1
LIMIT_IN
P4
12VDC
GND
L2
10
L1
9 8 7 6 5 4 3 2 1
+
-
+
+
+
+
-
-
-
BK/NR
BK/NR
+ 12 VDC/VCD
RD/RG
WH/BC
- 12 VDC/VCD
BK/NR
YL-GN/JN-VE
7
WH/BC
G
WH/BC
A
120 VCA
120 VAC
C
B
WH/BC
5
WH/BC
D
1
WH-RD/BC-RG
WH-VT/BC-VT 4
2
WH/BC
GN/VE
BU/BL
5
1
2
6
7
P1
E
Vreg
RD/RG
BK/NR
M
o
c
r
i
P2
3
5
1
4
F
TEMP
MODE
ON-OFF
H