M&I LAB Manual
M&I LAB Manual
Aim of the Experiment: Measuring an unknown Resistance using Kelvin’s Double Bridge.
Device/Equipments Required:
Circuit Diagram:
Theory:
As per the design P/Q= p/q, the value of unknown resistance is,
𝑷
𝑹= 𝑺
𝑸
Above equation is the usual working equation for the Kelvin double bridge. It indicates that
the resistance of connecting lead ‘r’ has no effect on the measurement provided that the two
sets of ratio arms have equal ratios. The above equation is useful however as it shows the
error that is introduced in case the ratios are not exactly equal. It is indicated that it is
desirable to keep ‘r’ as small as possible in order to minimize the errors in case there is a
difference between ratios P / Q and p/q. In a typical Kelvin bridge, the range of resistance
calculated is 0.1Ω to 1.0 Ω.
Procedure:
Device/Equipments Required:
Circuit Diagram:
L1 = Inductor whose inductance is to be determined.
R1 = a resistance in series the inductor L1.
L3 = Fixed value inductor.
R3 = Fixed value resistance in series the inductor L3.
R4 = a standard resistor.
R2 = a variable non-inductive resistance.
From the theory of ac bridges we have at balance condition,
Substituting the values of z1, z2, z3 and z4 in the above equation and equating the real and
imaginary parts of it,
L1 = (R2/ R4). L3
R1= (R2/ R4). R3
Procedure:
1. Connect +/- 12V DC power supply at their indicated position from external
source.
2. Connect function generator probes between VIN terminals.
3. Using patch cords connect the unknown L1 and R1 to the bridge circuit.
4. Switch on power supply and function generator.
5. Set the 5Vpp, 1KHz input sinusoidal signal of function generator.
6. Rotate potentiometer R2 to find a condition for zero/minimum current.
7. Switch off the power supply and function generator.
8. Take the value of R2 using the multimeter.
9. Calculate the value of L1 and R1 using their formulae.
10. The above procedure will be repeated for different values of L1 and R1.
Objective: To measure the unknown capacitance where the balance equation is independent
of frequency.
Device/Equipments Required:
Circuit Diagram:
Cx = capacitor whose capacitance is to be determined,
rx = a series resistance representing the loss in the capacitor Cx,
Cs = a standard capacitor,
rs = a series resistance representing the loss in the capacitor Cs, of very low
value can be ignored in the equation.
A = a variable non-inductive resistance,
Cp = a variable capacitor,
B = a non-inductive resistance in parallel with the
capacitor Cp. From the theory of AC bridges we have at
balance condition,
Substituting the values of z1, z2, z3 and z4 in the above equation and equating the
real and imaginary parts of it,
Rx= (ACp)/ Cs
Cx= (BCs)/ A
The dissipation factor for the capacitor is given by the formula,
D= (2*pi*f) Cx Rx, where f= frequency of the input signal.
Procedure:
11. Connect +/- 12V DC power supply at their indicated position from
external source.
12. Connect function generator probes between VIN terminals.
13. Using patch cords connect the unknown Cx and Rx to the bridge circuit.
14. Switch on power supply and function generator.
15. Set the 5Vpp, 1KHz input sinusoidal signal of function generator.
16. Rotate potentiometer R2(A) to find a condition for zero/minimum current.
17. Switch off the power supply and function generator.
18. Take the value of R2(A) using the multimeter.
19. Calculate the value of Cx and Rx using their formulae.
20. The above procedure will be repeated for different values of Cx and Rx.
APPARATUSREQUIRED:
THEORY:
Using two wattmeter method, the power measured by the two wattcmeters i.e. the sum of the two
wattmeter readings is equal to root 3 times of the phase voltage and line voltage (√3VLIL Cosϕ)
which is the actual power consumed in a 3 phase balanced load. The connection diagram of a 3
phase balanced load connected as Star Connection is shown below.
The load is considered as an inductive load. The three voltages V RN, VYN and VBN, are
displaced by an angle of 120 degrees electrical as shown in the phasor diagram. The phase current
lag behind their respective phase voltages by an angle ϕ. Now, the current flowing through the
current coil of the Wattmeter, W1 will be given as
Potential difference across the pressure or potential coil of the Wattmeter, W1 will be
To obtain the value of VYB, reverse the phasor VBN and add it to the phasor VYN as shown in the
phasor diagram above. The phase difference between VRB and IR is (30⁰ – ϕ).
Therefore, the power measured by the Wattmeter, W1 is
CIRCUIT DIAGRAM:
Fig.5.1
PROCEDURE:
1. Make the connections as per the circuit diagram shown in Fig 5.1.
2. Switch ON 3 phase AC supply.
3. Apply load and measure the values of wattmeters, ammeter and voltmeter.
4. Switch OFF all the loads and supply.
PRECAUTIONS:
TABULAR COLUMN
Sl. No. VL (V) IL (A) W1 (W) W2 (W) W= W1+ W2 Calculated
Power
CALCULATION:
RESULT: