Grid Solutions
Multilin
EPM 9650 & 9450
High Performance Power Quality Metering Monitoring & Metering
Ideal for industrial, commercial, and utility applications, the performance enhanced EPM 9650 & 9450 • Current, voltage, real and reactive power,
Power Quality Meters provide a comprehensive set of features required for the highest levels of Power energy use, cost of power, power factor and
Quality analysis and communications. frequency
The Multilin™ EPM 9650 & 9450 meters provide the total picture of power usage and power quality for • Laboratory grade 0.04% Watt-Hour accuracy
metered points within a distribution network, allowing users to make power related decisions quickly • Flicker and waveform recording
and effectively. • Real-time PQ monitoring and harmonic
magnitude analysis to 255th order
Key Benefits
• High-performance power quality and revenue class metering for critical power applications Control
• EN50160 flicker with up to 512 waveform samples per cycle and high-speed transient recording for • Programmable setpoints for alarms and 90
complete power quality monitoring millisecond relay activation for high speed
• Fast response time to power quality events for diagnostics and maintenance updates and control
• Built-in GPS clock sync capability for accurate time stamping of events and alarms for synchronized • Expandable external outputs
system monitoring • 8 built-in, high-speed, digital inputs
• Exceeds ANSI C-12 and IEC 687 specifications for accuracy with auto calibration using temperature • Multiple analog, digital and relay outputs
compensation
• Software and hardware triggers record waveform events, allowing the meter to be used for fault
analysis, system apparatus monitoring and many other applications Communications
• Real time phasor analyzer monitors phase angles between the voltages and currents • On-board Ethernet and Modbus/TCP capability
• Able to record THD to the 255th order peak and real-time harmonic magnitudes analysis to the 128th • High-speed RS485 and RS232 Com Ports
order for every channel for accurate power quality analysis • Multiple protocols including Modbus and
• Simplified system integration with communication option for 10/100 BaseT Ethernet with Modbus/TCP DNP3.0 level 2
• Expandable analog and digital output modules, simplifying the polling, logging, and transfer of data • Built-in modem with dial-out capability
to master station devices • Web Server & Gateway
Applications
• Revenue class metering and load aggregation for energy management
• Transformer loss compensation
• High-performance power quality monitoring of critical loads
EPM 9000 Series Power Quality Meter
2 GEGridSolutions.com
EPM 9000 Series Power Quality Meter
User Interface
3 Communication Ports 8 High-Speed IRIG-B Input
Status Inputs
Heartbeat
(Test Pulse)
On-Board Modem
RS-232 or Ethernet TCP/IP
Rugged
Metal Case
4 Current Inputs
Universal Power
Supply
4 Voltage Inputs
Revenue Metering Max/Min Integration and Recording: The unit • Bi-directional consumption and demand
offers time stamped max and min values for quantities
Accuracy in Billing Measurements:
every measured reading. kW readings are • 20-year calendar - 4 seasons/yr, 2 holidays/yr
Dual 16 Bit A/D converters provide supreme
integrated using:
sampling accuracy and resolution. The unit • 4 TOU schedules/seasons
far exceeds ANSI C-12 and IEC 687 accuracy • Block (fixed) window • Prior month, prior season storage
standards offering 0.04% watt-hour accuracy. • Thermal window
• Present month, present season storage
To ensure optimum accuracy the unit auto- • Rolling (sliding) window
Transformer Loss and Line Loss Compensation:
adjusts to dual internal references accurate to 1
• Predictive window The unit compensates for transformer and
part per million. In addition, the EPM 9000 uses
Time of use (TOU) Capability: EPM 9000 offers line losses. Power reading compensation is
an auto-calibration technique that recalibrates
comprehensive time of use capability. Standard conducted for both iron and copper losses.
the unit on the fly when the temperature changes
more than 5 degrees Celsius for improved features include: Load Aggregation/Universal Metering: Using the
accuracy over the full temperature range. status inputs, EPM 9000 has the ability to count
pulses and aggregate different loads providing a
total picture of the load and its component parts.
This can be used to accumulate and aggregate
other utilities such as water and gas data.
GEGridSolutions.com 3
EPM 9000 Series Power Quality Meter
The units offer an independent out of limit log. • Waveform record capture
This allows a user to download out of limit • CBEMA power quality event
information to obtain a sequence of events for • Control output change
any occurrence. Utilizing the 1 millisec clock
• Filling of meter memory
resolution, the logs can be combined with
different metered points through a distribution • Cycling of control power
system to provide an accurate system-wide • Password failure on a call coming into the
depiction of a power disturbance. modem
• Meter communication failure
Event-Triggered Waveform Recording Log
EPM 9000 records waveforms with a resolution
of up to 512 samples per cycle. The amount of
waveform recording is based on the amount of
memory installed.
EnerVista Viewpoint Monitoring - Access real-time system values and track energy consumption
4 GEGridSolutions.com
EPM 9000 Series Power Quality Meter
EnerVista Viewpoint Monitoring - Monitor the status of digital inputs and review the magnitude of system highs and lows
GEGridSolutions.com 5
EPM 9000 Series Power Quality Meter
Typical Wiring
Ia HI Ib HI Ic HI In HI Ia HI Ib HI Ic HI In HI
L+ N- CHASIS Vaux. Vref. Va Vb Vc L+ N- CHASIS Vaux. Vref. Va Vb Vc
LO LO LO LO LO LO LO LO
FUSES
FUSES 0.25A
0.25A
LOAD
CTs LINE
N LOAD CTs LINE
C C
B B
A A
6 GEGridSolutions.com
EPM 9000 Series Power Quality Meter
Technical Specifications
DEMAND MONITORING INPUTS OUTPUT MODULES
Measured values: Phase A/B/C/N current (A) INPUT VOLTAGE RANGE ANALOG TRANSDUCER SIGNAL OUTPUT
3 phase real power (kW) 150V phase to neutral, 300V phase to phase* 4 Analog Outputs, 0–1mA, self-powered, scalable, bi-direc-
3 phase reactive power (kvar) 300V phase to neutral, 600V phase to phase tional
3 phase apparent power (kVA) *To be used also with PTs for extended input voltage. 8 Analog Outputs, 0–1mA, self-powered, scalable, bi-direc-
Measurement Thermal exponential INPUT CURRENT RANGE tional
type: 1 – 9999 sec, steps of 1 sec 5 amp inputs 2x continuous programmable to any CT range 4 Analog Outputs, 4–20mA, self-powered, scalable
Block interval/rolling demand time Fault current recording to 60 amps peak secondary based on 8 Analog Outputs, 4–20mA, self-powered, scalable
in interval (programmable): 5 amp full scale
Wiring: Common Mode
1 – 9999 sec, steps of 1 sec Note: 1 amp current inputs available as special order
Accuracy: 0.1% of Full Scale
ISOLATION
All inputs and outputs are isolated to 2500 Volts Calibration: Self-Calibrating
POWER SUPPLY Scaling:
FREQUENCY RANGE Programmable
CONTROL POWER Fundamental 45-75 Hz Ordering Up to 4 Analog Output modules can be
Input options: 90–276 Volts AC/DC BURDEN Specifics: used with each unit
18–60 Volts DC Voltage inputs: 0.05VA Max
Frequency: 20–400Hz Current inputs: 0.005VA Max DIGITAL DRY CONTACT RELAY OUTPUTS
Burden: 20 VA max SENSING METHOD 4 Relay Outputs, 5 amps, 125, AC/DC, Form C
Up to 512 samples per cycle (programmable)
16 Bit A/D resolution – dual converters ORDERING SPECIFICS: MULTIPLE MODULES CAN BE USED
METERING True RMS
UPDATE TIME DIGITAL SOLID STATE PULSE OUTPUTS
MEASURED VALUES 200 millesec — high speed instant readings 4 Solid State Pulse, Outputs, Form A or C KYZ Pulses
MEASUREMENTS 200 1 Sec Display 1 second — Revenue accurate
Millisec* Resolution
Voltage (L-N) 0.10% 0.05% 5 Digit Maximum Pulse
Voltage (L-L) 0.10% 0.05% 5 Digit COMMUNICATIONS Speed: 20 pulses per second
Current 0.10% 0.025% 5 Digit Ordering Up to 4 modules can be used
Format: Programmable parity and stop bits
Frequency 0.03 Hz 0.01 Hz 00.001 Hz Specifics:
KW @ Unity PF 0.10% 0.06% 5 Digit Ports: 4 Communication ports BUILT-IN DIGITAL INPUTS
2 slave ports
KW @ .5 PF 0.10% 0.1% 5 Digit 8 Digital Status Inputs Wet/Dry Auto-Detect Up to
KVA 0.40% 0.08% 5 Digit Port 1: RS-232 or RS-485 selectable 300 Volts DC
VAR 0.10% 0.0% 5 Digit Protocol: Modbus®
PF 0.10% 0.08% 3 Digit Modbus ASCII/RTU and DNP 3.0
DISPLAY
Harmonics N/A 0.2% 3 Digit
KW/Hours N/A 0.04% 16 Digit Media: All ports use 2-wire RS-485 TOUCH SCREEN LCD DISPLAY
KVA/Hours N/A 0.08% 16 Digit communication Touch screen graphical display
320 x 240 pixels CCFL backlit
KVAR/Hours N/A 0.08% 16 Digit Baud rate: 56K bps Displays data from up to 8 meters
Note: Readings are in percent of reading where applicable Modem: 56K Modem with dial-out capability 4.7” x 3.5” aperture (12.1cm x 9.1cm)
(more accurate standard), not in percent of full scale (less
Ethernet: 10/100 base T with Modbus/TCP Protocol
accurate standard). LED DISPLAY
Functions: Read/write setpoints 3-line multi-function LEDs
Accuracy: ANSI C12.20 Class 0.2 and IEC687 Read actual values RS-485 master
harmonics: Measures harmonic magnitudes to the Isolation: All Com Ports are additionally Displays data from a single meter
255th order for each voltage and current isolated from each other
channel
Real-time harmonics resolved to the 128th TYPE TESTS
order ENVIRONMENTAL TYPE TESTS AS PER UL® & CE®
Humidity: Up to 95% non-condensing Emissions: EN55011
WAVEFORM Immunity: EN50082
Temperature: -40° C to +80° C ambient
Samples No of **Max. No No of Accuracy ANSI C12.20 Class 0.2 and IEC687
CONSTRUCTION
per Cycle Cycles of Cycles Channels Communication:
Constructed in a metal case. All hardware is stainless steel.
Record per Record per Isolation: 2500 volts AC 60 Hz
Screen* Event PACKAGING
Voltage Input Optically isolated to 2500VDC
16 8 Pre / 56 6080 7 Shipping box: 16” x13” x11” withstand:
32 4 Pre / 28 3040 7 (40.64cm x 33.02cm x 27.94cm)
Current Input 100 amps for 10 Seconds
64 4 Pre / 12 1520 7 Ship weight: Approx. 12 lbs (5.4 kgs) withstand: 300 amps for 1 Second
128 1 Pre / 7 760 7 Surge withstand: ANSI/IEEE C37.90.1
256 1 Pre / 3 760 3
Surge: ANSI C62.41
512 1 Pre / 3 760 1
* Post Event Screen (Calculations at 60Hz.) ESD: IEC 1000-4-2
Radiated Immunity: IEC 1000-4-3
DATA LOGGING Fast Transient: IEC 1000-4-4
EPM 9450 Surge Immunity: IEC 1000-4-5
Log Storage Options 512K RAM 512K Record Size Flicker Meter: IEC 868
Historical Log 1 176K 58 Days Flicker Meter: IEC 61000-4-15
Historical Log 2 256K 42 Days
Out of Limit 48K 512
CBEMA Log 16K 256 TYPE TESTS
Relay Output Log N/A N/A Emissions: EN55011
Input Status Log N/A N/A ISO: Manufactured to an ISO9001 registered
Waveform Recording N/A 8Number of Events program
UL & cUL: Recognized under e200431
EPM 9650
CE: Conforms to EN 55011/ EN 50082
Log Storage Options 2 Meg RAM 2 Meg Record Size 4 Meg RAM 4 Meg Record Size
Industry Canada Approval:#AE-1069
Historical Log 1 176K 58 Days 1808K 602 Days Revenue Metering:
Historical Log 2 256K 42 Days 400K 66 Days
Out of Limit 48K 512 96K 1024
CBEMA Log 16K 256 64K 1024
Relay Output Log N/A N/A 32K 512
Input Status Log N/A N/A 32K 512
Waveform Recording N/A 8 1568K 96
Number of Events
GEGridSolutions.com 7
Ordering
Meters
EPM 9450 - High performance power quality metering with logging
PL9450 * * * A * * 0 0 0 0 Description
Frequency 0 60 Hz
1 50 Hz
4 400 Hz
System Voltage A 120/208 volts connection
B 277/480 volts connection
Control Power 0 90-276 volts AC/DC power supply
1 18-60 volts DC power supply
Features Options A Basic unit with 512 K memory, 8 digital inputs,
8 cycle of waveform (up to 512 samples/cycle), 100 days data log.
Communications 0 4 communication port
User-selectable RS 485 Modbus and DNP - no modem or Ethernet connection
1 10/100 BaseT Ethernet, web server and gateway capability
2 Internal 56k modem connection with pass-through port
Current Inputs 0 5 Amps
1 1 Amps
EPM 9650 - High performance power quality metering with advanced logging
PL9650 * * * A * * 0 0 0 0 Description
Frequency 0 60 Hz
1 50 Hz
System Voltage A 120/208 volts connection
B 277/480 volts connection
Control Power 0 90-276 volts AC/DC power supply
1 18-60 volts DC power supply
Features Options A Advance unit includes basic unit, with 2 Meg memory,
Up to 96 days of data logging, up to 64 cycles of waveform recording
B Flicker includes advance unit plus Flicker with 4 Meg memory, 602 days of data logging
Communications 0 4 Communication ports
User-selectable RS 485 Modbus and DNP - no modem or Ethernet connection
1 10/100 BaseT Ethernet, web server and gateway capability
2 Internal 56k modem connection with pass-through port
Current Inputs 0 5 Amps
1 1 Amps
Accessories
PL9000
*
* * * * * * 0 0 Analog Output Modules
1 M A O N 4 O 4 Channel 0-1 mA Analog Outputs
1 M A O N 8 O 8 Channel 0-1 mA Analog Outputs
2 O M A O N 4 4 Channel 4-20 mA Analog Outputs
2 O M A O N 8 8 Channel 4-20 mA Analog Outputs
PL9000
* * * * * * * 0 0 Analog Input Modules
8 A I 1 0 0 0 8 Channel 0–1mA Analog Inputs
8 A I 2 0 0 0 8 Channel 0–20mA Analog Inputs
8 A I 3 0 0 0 8 Channel 0–5V DC Analog Inputs
8 A I 4 0 0 0 8 Channel 0–10V DC Analog Inputs
PL9000
*
* *
0 *
0 0 0 0 Digital Output Modules
4
R O 1 4 Channel Control Relay Outputs
4
P O 1 4 Channel kyz Solid State Pulse Outputs
PL9000
* * * * 0 0 0 0 0 Digital Input Modules
8 D I 1 0 0 0 0 0 8 Channel Digital Status Inputs
PL9000
M B I O 0 0 0 0 0 Auxiliary Mounting Bracket (One set per module group)
PL9000
*
* * * * * * * * 9000 Series Meter Display Module
P
4 0 N P L U S 0 Three line LED Display
P
6 0 N 0 0 0 0 0 Touch-Screen LCD Display with 6-ft cable
P
6 0 N 1 0 0 0 0 Touch-Screen LCD Display with 15-ft cable
PLSOFT
9000 Series Meter Software
COMS Communicator Software, Single User License
COM3 Communicator Software, Three User License
GEGridSolutions.com
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General Electric
Company.
GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.