Fisa Tehnica SUN2000 en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Smart Energy Controller

SUN2000-3-10KTL-M1 (High Current Version)

Active Safety Higher Yields Battery Ready Flexible Communication

AI Powered Up to 30% More Energy Plug & Play battery interface 2 WLAN, Fast Ethernet, 4G
Active Arcing Protection with Optimizer 1 Communication Supported

Efficiency Curve Circuit Diagram


Efficiency [%]
DC
100% Switch

PV1+
98%
DC/AC Output
PV1- EMI Converter Isolation Relay
Filter
96% PV2-
L1
PV2+
94% Output EMI L2
Filter Filter
L3
92% SPD
N
BAT+ PE

90% BAT-
SPD
0% 20% 40% 60% 80% 100%
470 V 600 V 850 V
Load [%] SUN2000-3/4/5/6/8/10KTL-M0/M1

*1 Only applicable to SUN2000-3/4/5/6/8/10KTL-M1 smart energy center.


*2. SUN2000-3/4/5/6/8/10KTL-M0 will be compatible with HUAWEI smart string ESS in Q1, 2021

11
SOLAR.HUAWEI.COM/MEA
SUN2000-3/4/5/6/8/10KTL-M1 (High Current Version)
Technical Specification
SUN2000 SUN2000 SUN2000 SUN2000 SUN2000 SUN2000
Technical Specification -3KTL-M1 -4KTL-M1 -5KTL-M1 -6KTL-M1 -8KTL-M1 -10KTL-M1

Efficiency
Max. efficiency 98.2% 98.3% 98.4% 98.6% 98.6% 98.6%
European weighted efficiency 96.7% 97.1% 97.5% 97.7% 98.0% 98.1%

Input (PV)
Recommended max. PV power 1 4,500 Wp 6,000 Wp 7,500 Wp 9,000 Wp 12,000 Wp 15,000 Wp
Max. input voltage 2 1,100 V
Operating voltage range 3 140 V ~ 980 V
Start-up voltage 200 V
Rated input voltage 600 V
Max. input current per MPPT 13.5 A
Max. short-circuit current 19.5 A
Number of MPP trackers 2
Max. input number per MPP tracker 1

Input (DC Battery)


Compatible Battery HUAWEI Smart String ESS 5kWh – 30kWh
Operating voltage range 600 V ~ 980 V
Max operating current 16.7 A
Max charge Power 10,000 W
Max discharge Power 3,300 W 4,400 W 5,500 W 6,600 W 8,800 W 10,000 W

Output (On Grid)


Grid connection Three-phase
Rated output power 3,000 W 4,000 W 5,000 W 6,000 W 8,000 W 10,000 W
Max. apparent power 3,300 VA 4,400 VA 5,500 VA 6,600 VA 8,800 VA 11,000 VA 4
Rated output voltage 220 Vac / 380 Vac, 230 Vac / 400 Vac, 3W / N+PE
Rated AC grid frequency 50 Hz / 60 Hz
Max. output current 5.1 A 6.8 A 8.5 A 10.1 A 13.5 A 16.9 A
Adjustable power factor 0.8 leading ... 0.8 lagging
Max. total harmonic distortion ≤3%

Output (Off Grid)


Backup Box Backup Box – B1
Maximum apparent power 3,000 VA 3,300 VA 3,300 VA 3,300 VA 3,300 VA 3,300 VA
Rated output voltage 220 V / 230 V
Maximum output current 13.6 A 15 A 15 A 15 A 15 A 15 A
Power factor range 0.8 leading ... 0.8 lagging

Features & Protections


Input-side disconnection device Yes
Anti-Islanding protection Yes
DC reverse polarity protection Yes
Insulation monitoring Yes
DC surge protection Yes, compatible with TYPE II protection class according to EN/IEC 61643-11
AC surge protection Yes, compatible with TYPE II protection class according to EN/IEC 61643-11
Residual current monitoring Yes
AC overcurrent protection Yes
AC short-circuit protection Yes
AC overvoltage protection Yes
Arc fault protection Yes
Ripple receiver control Yes
Integrated PID recovery 5 Yes
Battery reverse charging from grid Yes

General Data
Operating temperature range -25 ~ + 60 °C (-13 °F ~ 140 °F)
Relative operating humidity 0 %RH~100 %RH
Max. operating altitude 4,000 m (13,123 ft.) (Derating above 2000 m)
Cooling Natural convection
Display LED Indicators; Integrated WLAN + FusionSolar App
Communication RS485; WLAN/Ethernet via Smart Dongle-WLAN-FE; 4G / 3G / 2G via Smart Dongle-4G (Optional)
Weight (incl. mounting bracket) 17 kg (37.5 lb)
Dimension (incl. mounting bracket) 525 x 470 x 146.5 mm (20.7 x 18.5 x 5.8 inch)
Degree of protection IP65
Nighttime Power Consumption < 5.5 W 6

Optimizer Compatibility
DC MBUS compatible optimizer SUN2000-450W-P

Standard Compliance (more available upon request)


Certificate EN/IEC 62109-1, EN/IEC 62109-2, IEC 62116
G98, G99, EN 50438, CEI 0-21, VDE-AR-N-4105, AS 4777, C10/11, ABNT, UTE C15-712, RD 1699, TOR D4, NRS 097-2-1,
Grid connection standards
IEC61727, IEC62116, DEWA
*1 Inverter max input PV power is 20,000 Wp when long strings are designed and fully connected with SUN2000-450W-P power optimizers.
*2 The maximum input voltage is the upper limit of the DC voltage. Any higher input DC voltage would probably damage inverter.
*3 Any DC input voltage beyond the operating voltage range may result in inverter improper operating. *4 C10 / 11: 10,000 VA
*5 SUN2000-3~10KTL-M1 raises potential between PV- and ground to above zero through integrated PID recovery function to recover module degradation from PID. Supported module types include: P-type (mono, poly).
12
*6. <10 W when PID recovery function is activated.