Read this document carefully before using this device.

The guarantee will be expired by device demages if you don't


attend to the directions in the user manual. Also we don't accept any compensations for personal injury, material damage
or capital disadvantages.

EA54 PROGRAMMABLE AC/DC AMMETER


Thank you for choosing EA54 programmable AC/DC ammeter.
54 x 94mm sized. 1 2 3 4 5 6 7 8 9

4 digits display.
Easy to use with front panel keypad.
5A or 60 mV , CT20/30 current transformer or 60 mV input feature (Please Specify at Order).
Programmable scale range between 5A and 9999A.
Multifunctional alarm output (NO+NC) for upper and lower limits.
Communication feature over isolated RS485, using ModBus RTU protocol (Optional). OUT AC DC ACDC A
Measuring type can be selected as AC, DC or true RMS.
Keylock feature.
0-20mA, 4-20mA, 0-10V or 1-5V output selection (Specified devices with output type 'A' only).
CE marked according to European Norms.
CT20/30 should be ordered separately if required.
SET
EA54
Order Code : EA54
1 2 3 4
1- Supply Voltage 2 - Input 3 -Output 4 - Isolated Modbus
UV......... 90-250V AC CT........................... CT20/30 R......... 08A Relay RSI........ RS485 Modbus Available
Current Transformer input OR 60mV. A........... Analog ( Specify at order)
LV......... 10-30V DC / X1........................... 1A
8-24V AC Default (Blank)...... 5A or 60mV. 10 11 12 13 14 15 16 17 18

TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
Ambient/Storage Temperature 0 ... +50°C/-25 ... 70°C
Max. Relative Humidity 80% Relative humidity for temperatures up to 31°C, decreasing linearly to 50% at 40°C.
Rated Pollution Degree According to EN 60529 Front panel : IP65 , Rear panel : IP20
Height Max. 2000m

KEEP AWAY device from exposed to corrosive, volatile and flammable gases or liquids and DO NOT USE the device in similar hazardous locations.

ELECTRICAL CHARACTERISTICS

Supply 90-250V AC 50/60Hz ;10-30V DC / 8-24V AC SMPS


Power Consumption Max. 5VA
Wiring 2.5mm² screw-terminal connections
If input type is 5A / 60mV, scale 0A 9999A : ( Specified by c.tr.r parameter. i.e : scale is... 0A...5A for c.tr.r = 5 )
If input type is 1A, scale 0A 9999A : ( Specified by c.tr.r parameter. i.e : scale is 0A...... 1A for c.tr.r = 1 )
If input type is CT20/30 / 60mv :
AC and RMS
If ityp = Ct20 , 0A...300A or Ct30 , 0A...120A ( Specified by turn parameter. i.e : scale is 0A..300A / 0A..120A for turn = 1 )
If ityp = 5Hnt , 0A... 9999A ( Specified by c.tr.r parameter. i.e : scale is 0A...5A for c.tr.r = 5 )
Scale
If input type is 5A / 60mV, scale : -999A...9999A ( Specified by c.tr.r parameter. i.e : scale is -5A...5A for c.tr.r = 5 )
If input type is 1A, scale : -999A...9999A ( Specified by c.tr.r parameter. i.e : scale is -1A...1A for c.tr.r = 1 )
DC If input type is CT20/30 / 60mV :
DC measurement can not be performed by using CT.
If ityp = 5Hnt , scale : 0A...9999A ( Specified by c.tr.r parameter. i.e : scale is -5A ...5A for c.tr.r=5 )
Sensitivity 0.002A x c.tr.r ( i.e. : 0.01A for c.tr.r = 5 )
AC ± %1 (full scale) (± 2% For square wave form)
±
Accuracy DC %1 (full scale)
± %1 (full scale) (± 2% For square wave form)
RMS
-1A...1A ( Device may be damaged at 2A and above currents )
2 and 3 -5A...5A or CT20/30 input, 0 ... 150 mA ( Device may be damaged at 10A and above currents )
Input Range 1 and 4 -60mV...60mV ( Device may be damaged at 50V and above voltages )
2 and 3 12mΩ (For 5A input) , 90mΩ (For 1A input)
Input Impedance
1 and 4 40kΩ (For 5A input) , 600mΩ (For CT20/30 input)
Frequency Range DC , 10Hz - 200Hz (10Hz - 70Hz For square wave form)
EMC EN 61326-1: 2013
Safety Requirements EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)

OUTPUTS
Analog Output 0-20mA DC, 4-20mA DC, 0-10V DC or 1-5V DC can be selected on program. ( Load resistance for current outputs Max. 500Ω ).
Output Relay : 250V AC, 8A (for resistive load), NO+NC
Life Expectancy For Relay Mechanical 30.000.000; Electrical 100.000 operation. 250V AC, 8A (resistive load).

HOUSING
Housing Type Suitable for EN60715 Standards, TH35 rail type.
Dimensions W54xH94xD68mm
Weight Approx. 250g (after packing)
Enclosure Material Self extinguishing plastics.

Avoid any liquid contact when the device is switched on.


DO NOT clean the device with solvent (thinner, gasoline, acid etc.) and / or abrasive cleaning agents.

TM
EN

1/5 EA54-EN-04-220103
1 2 3 4 5 6 7 8 9

EA54 PROGRAMMING DIAGRAM


OUT AC DC ACDC A
Increment Used for increasing the setpoint value and changing parameters. LOCKING & UNLOCKING KEYPAD
Measured Value Measured Value
OUT AC DC ACDC A key When held down for a few seconds, configured numeric value increases faster.
Used for decreasing the setpoint value and changing parameters. L0C 0.00 UL0C 0.00.
Decrement
When held down for a few seconds, configured numeric value decreases faster.
EN
EA54
SET
key
In “Running Mode” , by pressing to key for 3 seconds, keypad locked or unlocked.
EN
EA54
SET Programming
SET Used for displaying and configuring the selected parameter value.
10 11 12 13 14 15 16 17 18
key QUICK MENU
Measured Value

If these keys are pressed and held for 3 seconds, “Programming Mode” is entered or it returns to “Running Mode”. If and keys SET UPLL LOLL
&
are pressed respectively while parameter names are displayed, than it returns to measured value. +0.00
SET

PROGRAMMING MODE By pressing to key for 3 seconds, quick menu is entered.

SET
SET
Out1 REVISION NUMBER
ConF
SET Day.Month Year Measured Value
This menu available for specified devices with & &
i " R " ( R E L AY ) i n o r d e r c o d e o n l y. SET
01.01 2015 0.00
& &
Please check "Output Type" in the order code.
& If these keys are pressed and held together, revision
&

Current Conversion Ratio Out1 Output date appears as day, month and year.
While revision information displayed and if one of the pressed
It can be adjusted between 5(/5) and 9999(/5). If this parameter OtYp It can be adjusted as n.o. or N.c. If n.o is selected, incase of key is released, measured value is displayed again.
changes, upper limit value is set to maximum scale, minimum limit alarm, out relay is activated.
value is set to minimum scale and hysteresis values are set to 0.1
SETTING UP THE PARAMETERS
Measuring Method Upper Limit Value SET SET

ACdC
tYpE It can be adjusted to ac , dc or acdc. LEDs on the top of the UPLL It can be adjusted between minimum and maximum scale that tYPE dC
display indicates the adjusted measurement method. is specified with c.tr.r parameter. SET

This parameter can’t be lower than (l0ll - HY5U - HY5U ) If key is pressed, the current value of the parameter appears by flashing on the display.

Decimal Indicator By using “UP” or “DOWN” navigation keys, selected parameter can be adjusted to
d.pnt If measured value is lower than 10, it will be displayed as Hysteresis Value for Upper Limit the desired value.
(0.000) , (0.00) , (0.0) or (0) or (0). HY5U It can be adjusted between 0 and ctrr /5 parameter. This SET

After the setting up the parameters, if set key is pressed again, adjusted
If measured value between 10 and 100, it will be displayed as parameter can’t be higher than ( Upll - l0ll - HY5L ). When parameter name appears on display.
(0.00) ,(0.0) or (0). ctrr changed, HY5U gets the value of 0.1 .
If measured value between 100 and 1000, it will be displayed
DEFAULT SETTINGS
as (0.0) or (0).
Delay Time for Upper Limit Alarm
dPnt type may change according to relay parameters value. Powered on device by pressing key. dPAr message appears
dLYU It can be adjusted between 0 and 900 .
Samping Time on display and device resets to default settings.
Optn If 1 ( 1 ) is selected ; sampling time of the measurement is 250ms,
If 2 ( 2 ) is selected, it is 500ms. ERROR MESSAGES
If 3 ( 3 ) is selected, it is 750ms. Lower Limit Value
If 4 ( 4 ) is selected, it is 1 second. LOLL It can be adjusted between lower scale and upper scale that is Measured current value is higher than maximum scale.
specified with c.tr.r parameter.
Device Address This parameter can’t be higher than (UPLL - HY5U -

Adr5 It can be adjusted between 1 - 247 . HY5L) value. Measured current value is lower than minimum scale.

Hysteresis Value for Lower Limit


Baud Rate HY5L It can be adjusted between 0 and Ctrr /5 . CT20/30 Current Transformer & Windings Chart
This parameter can’t be higher than ( UPLL - L0LL -
bAUd It can be adjusted as OFF, 1200, 2400, 4800, 9600, 19200, 38400,
turn 1 2 3 4 5 6 7 8 9 10
57600 and 115200 . HY5U ) value. When ctrr is changed, HY5U gets the value
of 0.1 . CT20 Iin max(A) 300 150 100 75 60 50 42,8 37,5 33,3 30
Input Type ( In devices with input type "CT" ) CT30 Iin max(A) 120 60 40 30 24 20 17,1 15 13,3 12
itYp Can be adjusted to Ct20 , CT30 , 5HNt values. Delay Time for Lower Limit Alarm
If 5Hnt is selected, 60mV input terminals must be used. dLyL It can be adjusted between 0 and 900 seconds.
Terminal inputs : 1 and 4 Note :
Number of Windings ( In devices with input type "CT" ) If ityp = 5hnt , turn parameter is not appears.
Delay Time for Initial Upper Limit Alarm If ityp = Ct20 or Ct30 , ctrr parameter is not appears.
turn Number of windings of the current cable getting through the CT20/30 current
5dly It can be adjusted between 0 and 900 seconds.
transformer. Note :
Please see "CT20/30 Current Transformer & Windings" chart on
Before setting the relay parameters, the operating scale must
the right side of this page. be determined from dpnt parameter.
If dpnt , typE and Ityp parameters are changed (if applicable), Upll , loll
Analog Output Status ( In devices with output type "Analog"
atYp Can be adjusted to 0-20 , 4-20 , 0-10 , 1-5 values. , Hy5U and Hy5l values must be checked.

2/5 EA54-TR-02-180509
DIMENSIONS & CONNECTION DIAGRAM
Input
46m For mounting the device on rail :
m
Push the device to rail in direction 1 and UP.l1 + HYS.U
make sure that rail-lock is interlocked to rail. UP.l1
UP.l1 - HYS.U
68mm

For removing the device from rail : LO.l1 + HYS.L

m
m
direction 2 and pull the device in direction 3.

4
6

5
,
LO.l1
Push the rail-lock with a flat tip screwdriver in
LO.l1 - HYS.L

t
dly.U dly.U dly.l dly.l
Out

A.out = n.o.
3 t
Equipment is protected throughout by Out
2 DOUBLE INSULATION
94m m
m 5
4
m
A.out = n.c.
1 t
Holding screw 0.4-0.5Nm.

Rail-lock
(rms)
ac dc Ac.dc
EN EA54 ammeters are rail mounted control devices. Device must be used to according to instructions. Mounting and electrical A
connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations. During an 1 1
installation, all of the cables that are connected to the device must be free of electrical power. The device must be protected 0 A 0.000 A
T/2 T 3T/2 2T
against inadmissible humidity, vibrations and severe soiling. Make sure that the operation temperature is not exceeded. The cables 2 2
should not be close to the power cables or components. -A

CAUTION :
1
A2
A
If 5A / CT20-30 and 60mV inputs are connected at the same time, the measurement will be incorrect. 0.308 A A
0
p
EN INDUSTRIAL ELECTRONICS EN INDUSTRIAL ELECTRONICS EN INDUSTRIAL ELECTRONICS T/2 T 3T/2 2T
2
EA54-LV-A-RSI EA54-UV-R EA54-UV-CT-R-RSI

A1 A1
A
AC/DC AMMETER AC/DC AMMETER AC/DC AMMETER CT20
Measurement Input
0.386 A
0
8 680407 723256 8 680407 719631 8 680407 723270 0-300A T/2 T 3T/2 p2
10-30V DC/8-24V AC 90-250V AC 90-250V AC
50/60Hz 4,5VA
1

1
50/60Hz 5VA
1

50/60Hz 5VA
A

CTt2
Max. Max.
0
1
10 11 12 13 14

Max. Max. Max. CT


0 11
1

2
60mV 5A 60mV 5A 60mV 20/30
11
3

0
A 0.000 A

2000
AC/DC AC/DC + +
3

AC/DC AC/DC AC/DC AC/DC


3 4

+ T/2 T 3T/2 2T
2
1

+ + +
4
4

OUTPUT OUTPUT -A
13

250V AC 8A 250V AC 8A
RESISTIVE RESISTIVE
4
1

COM COM
7

LOAD
7

LOAD
A
15 16

B B
A 1 A 1 A 1
ANLG OUT
CAT II
8

CAT II
GND CAT II A Made in Turkey A
9

Made in Turkey
9

Made in Turkey
SN: XXXXXXXXX
SN: XXXXXXXXX SN: XXXXXXXXX 0 T/2 T 3T/2 2T 2 2 2

NOTE : Fuse
A
F 100mA
SUPPLY: 250V AC Switch A d d2 A d A d
90-250V AC
veya 10 Line UV/LV Please see page 5 for Modbus Connection Diagram 0 d d T T 2 T T
10-30V DC /
8-24V AC T 2T
50/60Hz 7VA 11 Neutral Supply
1) Mains supply cords shall meet the requirements of IEC 60227
or IEC 60245. A

A 1 A 1
2) In accordance with the safety regulations, the power supply
switch shall bring the identification of the relevant instrurment 0 0.000
and it should be easily accessible by the operator. T/2 T 3T/2 2T
3 3
Fuse should be connected. Cable size: 1,5mm² -A

3/5 EA54-TR-02-180509
EN EA54 DIGITAL AMMETER MODBUS PROTOCOL ADDRESS MAP
HOLDING REGISTERS FOR OUTPUT TYPE UNIT “R” (RELAY) DEVICES
Holding Register
Data Read/Write Default
Adresleri Data Content Parameter
Decimal Hex Type Name Permission Value
0000d 0x0000 word Alarm output status 0tyP R/W no
0001d 0x0001 word Current replacement rate ctrr R/W 5
0002d 0x0002 word The upper limit of the setpoint UPLL R/W 5.00
0003d 0x0003 word The upper limit of the hysteresis value HY5U R/W 0.10
0004d 0x0004 word Delay time for the upper limit alarm dlyU R/W 0
0005d 0x0005 word The lower limit of the setpoint L0Ll R/W 0.00
0006d 0x0006 word The lower limit of the hysteresis value HY5L R/W 0.10
0007d 0x0007 word Delay time for the lower limit alarm dLyl R/W 0
0008d 0x0008 word Measurement method (0=AC, 1=DC, 2=ACDC) typE R/W aCdC
0009d 0x0009 word Decimal point. ( 0 = 0 , 1 = 0.0 , 2 = 0.00 , 3 = 0.000 ) dpnt R/W 0.00
Sampling time of the measurement value. If 1 is selected, it is
0010d 0x000A word 250ms. If 2 is selected, it is 500ms. If 3 is selected, it is 750ms. 0PTN R/W 4
If 4 is selected, it is 1 second.
Device address for RS485 network connection.
0011d 0x000B word Adjustable between 1-247. aDr5 R/W 1
Baudrate (0=Off;1=1200;2=2400; 3=4800; 4=9600; 5=19200
0012d 0x000C word 6= 38400; 7= 57600; 8= 115200) BAUD R/W oFF

0013d 0x000D word Delay Time for Initial Upper Limit Alarm 5dly R/W 0

*0014d 0x000E word Input Type (0 = Ct20 , 1= Ct30 , 2 = 5Hnt ) ityp R/W Ct20
*0015d 0x000F word Number of windings for transformer turn R/W 1
* 14d and 15d addresses are available for only in CT20/30 input type devices.

HOLDING REGISTERS FOR OUTPUT TYPE UNIT “BLANK” (NO RELAY) OR “A” (ANALOG) DEVICES

0000d 0x0000 word Current Conversion Ratio ctrr R/W 5


0001d 0x0001 word Measurement method (0=AC, 1=DC, 2=ACDC) typE R/W aCdC
0002d 0x0002 word Decimal point ( 0 = 0 , 1 = 0.0 , 2 = 0.00 , 3 = 0.000 ) dpnt R/W 0.00
0003d 0x0003 word Sampling time of the measurement value OPTN R/W 4
Device address for RS485 network connection.
0004d 0x0004 word Adjustable between 1-247. aDr5 R/W 1
Baudrate (0=Off;1=1200;2=2400; 3=4800; 4=9600; 5=19200
0005d 0x0005 word 6= 38400; 7= 57600; 8= 115200) BAUD R/W off

*0006d 0x0006 word Input Type ( 0 = Ct20 , 1 = Ct30 , 2 = 5Hnt ) ityp R/W Ct20

*0007d 0x0007 word Number of windings for transformer turn R/W 1


Analog output type.
**0008d 0x0008 word (0=0-20,1=4-20,2=0-10,3=1-5) atyp R/W 0-20

* 6d and 7d addresses are available for only in CT20/30 input type devices.
** Address 8d is available for only in “A” (Analog) input type devices.
NOTE :
In devices with input type CT20/30, following parameter settings will change automatically if the ityp parameter is changed.
If ityp = Ct20 ; UpLL = 300.0 , LoLL = 0 , Hy5U = 0.10 , Hy5L = 0.10
If ityp = Ct30 ; UpLL = 120.0 , LoLL = 0 , Hy5U = 0.10 , Hy5L = 0.10

TM
EN

4/5 EA54-EN-04-220103
EN EA54-xx-x-xxx-RSI INPUT REGISTERS DEVICES
Input Register Read / Write
Addresses Data Parameter Permission
Decimal Hex Type Data Content Name

0000d 0x0000 word Measured current value -- Read Only


0001d 0x0001 word Decimal point of measured current value -- Read Only
DISCRETE INPUTS FOR OUTPUT TYPE UNIT “R” (RELAY) DEVICES
Discrete Input
Addresses Data Data Content Parameter Read/Write Permission
Decimal Hex Type Name

00d 0x00 Bit Relay output state (0=OFF; 1=ON) -- Read Only
COILS FOR OUTPUT TYPE UNIT “R” (RELAY) DEVICES
Coil Addresses Data Parameter Read/Write
Data Content Default
Decimal Hex Type Name Permission Value

00d 0x00 Bit Output state (0=no; 1=nc) 0typ R/W no

Note 1 : Coil and Discrete input parameters are not available in the devices those have no relay

Note 2 : 0tyP menu parameters can be used as “Holding Register” or “Coil.

Note 3 : Value read in 0th address of input register gives the measured value. Also, the 1st address of the input register specifies
the decimal part of the measured current value.
For example ;
Value read in 0th address of input register is 2842, if value read in 1st address from input register as 1, it is 284.2
Value read in 0th address of input register is 2842, if value read in 1st address from input register as 2, it is 28.42
Value read in 0th address of input register is 2842, if value read in 1st address from input register as 3, it is 2.842

* MODBUS CONNECTION DIAGRAM


120

Slave - 2 120 Ohm


Master Slave - 1
Up to 127 slave devices Slave - 127
Ohm

B A B A B A can be controlled. B A
+ - + - - -
+

+
Termination should be accomplished by
attaching 120 Ohm resistors to the start
and at the end of the communication line.
* Applies to devices with Modbus function.

TM
EN

5/5 EA54-EN-04-220103