Isolated converter
3104
– Isolation and conversion of standard DC signals
– Slimline housing of 6 mm
– Power supply and signal isolator for 2-wire transmitter
– Loop supply >17 V
– DIP-switch configured
Application
Applications
• Isolation and conversion of standard DC signals.
• Galvanic separation of analog current and voltage signals.
• Elimination of ground loops and measurement of floating
signals.
• A competitive choice in terms of both price and technology for
galvanic isolation of current and voltage signals to SCADA
systems or PLC equipment.
• Installation in ATEX Ex zone 2 / IECEx zone 2 / FM division 2.
• Suitable for environments with high vibration stress, e.g.
ships.
Technical characteristics
• Easy configuration via DIP-switches.
• The input is protected against overvoltage and polarity error.
• Factory-calibrated measurement ranges.
• Inputs and outputs are floating and galvanically separated.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions Output specifications
Operating temperature................................... -25°C to +70°C Current output
Storage temperature...................................... -40°C to +85°C Signal range................................................... 0...23 mA
Calibration temperature................................. 20...28°C Programmable signal ranges......................... 0 / 4...20 mA
Relative humidity............................................ < 95% RH (non-cond.) Load (@ current output)................................. ≤ 600 Ω
Protection degree........................................... IP20 Load stability.................................................. ≤ 0.002% of span / 100 Ω
Installation in.................................................. Pollution degree 2 & meas. / Current limit.................................................... ≤ 28 mA
overvoltage cat. II
Voltage output
Mechanical specifications Signal range................................................... 0...10 VDC
Dimensions (HxWxD)..................................... 113 x 6.1 x 115 mm Programmable signal ranges......................... 0/1...5 and 0/2...10 V
Weight approx................................................ 70 g Load (@ voltage output)................................ ≥ 10 kΩ
DIN rail type................................................... DIN EN 60715/35 mm of span........................................................... = of the DIP-switch selected
Wire size........................................................ 0.13...2.5 mm2 / AWG 26...12 output range
stranded wire
Screw terminal torque.................................... 0.5 Nm I.S. / Ex marking
Vibration......................................................... IEC 60068-2-6
ATEX.............................................................. II 3 G Ex ec IIC T4 Gc
2...25 Hz......................................................... ±1.6 mm
IECEx............................................................. Ex ec IIC T4 Gc
25...100 Hz..................................................... ±4 g
FM, US........................................................... Cl. I, Div. 2, Gp. A, B, C, D T4
or Cl. I, Zone 2, AEx nA IIC T4
Common specifications FM, CA........................................................... Cl. I, Div. 2, Gp. A, B, C, D T4
Supply or Cl. I, Zone 2, Ex nA IIC T4
Supply voltage............................................... 16.8...31.2 VDC EAC Ex........................................................... 2Ex nA IIC T4 Gc X
Max. required power...................................... ≤ 1.2 W
Max. power dissipation.................................. 0.55 W Observed authority requirements
EMC............................................................... 2014/30/EU
Isolation voltage
LVD................................................................ 2014/35/EU
Isolation voltage, test /
working........................................................... 2.5 kVAC / 300 VAC ATEX.............................................................. 2014/34/EU
(reinforced) RoHS.............................................................. 2011/65/EU
Zone 2 / Div. 2................................................ 250 VAC EAC................................................................ TR-CU 020/2011
EAC Ex........................................................... TR-CU 012/2011
Response time
Response time (0...90%, 100...10%)............. < 7 ms Approvals
Programming.................................................
DIP-switches ATEX.............................................................. KEMA 10ATEX0147 X
Signal / noise ratio.........................................
> 60 dB IECEx............................................................. KEM 10.0068X
Cut-off frequency (3 dB)................................. > 100 Hz c FM us.......................................................... FM17US0004X /
Signal dynamics, input................................... Analog signal chain FM17CA0003X
Signal dynamics, output................................. Analog signal chain c UL us, UL 61010-1..................................... E314307
Accuracy........................................................
Better than 0.05% of selected CCC............................................................... 2020322310003554
range EAC Ex........................................................... RU C-DK.HA65.B.00355/19
Temperature coefficient................................. < ±0.01% of span / °C DNV Marine.................................................... TAA00001RW
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE21, A criterion, burst.................................. < ±1% of span
Input specifications
Current input
Measurement range....................................... 0...23 mA
Programmable measurement ranges............ 0...20 and 4...20 mA
Input voltage drop.......................................... < 1.5 VDC
Voltage input
Measurement range....................................... 0...10.25 V
Measurement range....................................... 0...11.5 V / 0...5.75 V
Programmable measurement ranges............ 0/1...5 and 0/2...10 V
Input resistance.............................................. ≥ 500 kΩ
2-wire transmitter supply................................ > 17 V / 20 mA
3104-090221