OPzV2-250(2V250Ah)

OPzV series is Valve Regulated Lead Acid battery that adopts immobilized GEL and
Tubular Plate technology to offer high reliability and performance. The Battery is
designed and manufactured according to DIN standards and with die-casting positive
grid and patented formula of active material OPzV series exceeds DIN standard
values with more than 25 years floating design life at 25 ℃ and It is the best
solution for cyclic use under extreme operating
conditions.

Specification
Cells Per Unit 1
Voltage Per Unit 2 ISO 9001 ISO 14001 OHSAS 18001

Nominal Capacity 250Ah@10hr-rate to 1.80V per cell @25℃


Weight Approx. 19.5Kg (Tolerance±3.0%) MH 28539 G4M20206-0910-E-16

Internal Resistance Approx. 0.9 mΩ


Terminal F10(M8) Dimensions Unit: mm

Max. Discharge Current 1200A (5 sec) 206

Design Life 25 years


108
124
Max. Charging Current 50.0 A
C3 191.9AH
Reference Capacity C5 217.1AH C10
250.0AH C20 Φ20
266.4AH M8

2.25 V~2.30 V @ 25℃

5
Float Charging

3
5
Temperature Compensation: -3mV/℃/Cell

Cycle Use Voltage 2.37 V~2.40 V @ 25℃


Temperature Compensation: -4mV/℃/Cell

Operating Temperature Range Discharge: -40℃~60℃


Charge: -20℃~50℃ F10 TERMINAL
Storage: -40℃~60℃
Normal Operating Temperature Range 25℃±5℃
Length 124±2mm (4.88 inches)
RITAR Valve Regulated Lead Acid (VRLA) batteries can
Width 206±2mm (8.11 inches)
Self Discharge be stored for up to 6 months at 25℃ and then recharging is Height 355±2mm (14.0 inches)
recommended. Monthly Self-discharge ratio is less than 2% at
20℃.Please charged batteries before using. Total Height 390±2mm (15.4 inches)
Torque Value 10~12 N*m
Container Material A.B.S. UL94-HB, UL94-V0 Optional.

Constant Current Discharge Characteristics : A(25℃)


F.V/ Time 10min 15min 30min 1h 2h 3h 5h 8h 10h 20h
1.60V 393.2 314.7 214.2 141.5 90.26 67.21 45.15 31.19 26.13 13.72
1.65V 375.6 303.4 209.2 139.4 88.89 66.46 44.78 30.94 25.88 13.58
1.70V 350.5 288.4 201.7 135.7 87.40 65.22 44.03 30.56 25.75 13.52
1.75V 311.6 263.3 190.4 130.1 85.28 63.98 43.41 30.19 25.38 13.32
1.80V 263.8 235.7 177.9 125.1 82.42 62.62 42.54 29.69 25.00 13.13
1.85V 214.8 194.3 152.8 111.6 75.20 57.54 39.43 27.69 23.38 12.27

Constant Power Discharge Characteristics : WPC(25℃)

F.V/ Time 10min 15min 30min 1h 2h 3h 5h 8h 10h 20h


1.60V 668.3 550.4 389.5 265.2 171.3 128.6 87.44 61.13 51.63 27.10
1.65V 652.0 539.1 384.5 262.4 169.8 127.8 86.81 60.88 51.25 26.91
1.70V 618.1 517.8 373.2 257.4 167.0 125.7 86.07 60.25 50.88 26.71
1.75V 560.3 481.4 355.7 248.9 163.3 123.6 84.70 59.63 50.38 26.45
1.80V 482.4 436.3 336.9 241.0 159.9 121.5 83.21 58.76 49.63 26.05
1.85V 399.5 366.1 291.8 215.4 146.2 112.2 77.49 55.01 46.63 24.48

(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
The battery must be fully charged before the capacity test. The C10 should reach 95% after the first cycle and 100% after the third cycle.
OPzV2-250(2V250Ah)
Charge Characteristic Curve for Cycle Use(IUU)
Temperature:25℃(77℉)

Discharge Characteristics Curve

Temperature:25℃(77℉)
(V/cell) 0.24 2.50
2.16

Charge Voltage (V/Cell)


0.22 2.40
(

2.00
0.20 Charge Voltage2.30

Charge Current
1.84 0.1C 0. 05C
0 0.25C 0.17 C 0.18 2.20
After After
50% Discharge Dischar
Terminal

.50C
100%
1.68 1C
0.16 ge 2.10

1.52
0.14 2.00
Charge Current
1.36
1 2 4 6 8 10 20 40 60 24 6 8 10 20 0.12 1.90
minh 0 1 2 3 4 5 6 7 8 9 10 12 14 16 18
Charging Time(h)
0 Discharge Time

Cycle Life in Relation to Depth of Discharge Relationship Between Charging Voltage and Temperature
2.60

7000

6000 2.50
Cycle use 2.37~2.40VPC@25℃
Charge Voltage
5000 2.40
Number of

4000
2.30
Float charging 2.25~2.30VPC@25℃
3000
Expected cycle life is subject to certain charge
algorithm specified by manufacturer 2.20
2000

2.10
1000 90 100 -20 -10 0 10 20 30 40 50
Depth Of Discharge(%) Temperature(℃)
0
01020304050607080

Temperature Effects on Capacity Storage Characteristics


120 100

0℃
100 80
(

60
Capacity

10℃
80
Capaci

20℃
40
40 ℃ 3 0℃

60
20

0 0
40 -20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature(℃) Storage Time(months)

20
Effect of Temperature on Long Term Life Relationship of OCV And State of Charge(20℃)
37.5 2.20

2.15
30.0
2.10
Battery Voltage

2.05
Life Expectancy

22.5

2.00
15.0
1.95

1.90
7.5
1.85

0 1.80
0 10 20 30 40 50 0 10 20 30 40 50 60 70 80 90 100
Temperature(℃) State Of Capacity (%)

(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.

HENGYANG RITAR POWER CO.,LTD.


Add: No.1 Huagong Road, Songmu Industrial Park, Shigu District, Hengyang, Hunan, China 421001
URL: www.ritarpower.com Tel: +86-734-8595528 Fax: +86-734-8595518 E-mail: [email protected] Version 22A-0