Coordinated Control Method For Low Voltage Ride Through and Anti-Islanding Protection of Distributed PV Generation Based On Interharmonic Impedance
Coordinated Control Method For Low Voltage Ride Through and Anti-Islanding Protection of Distributed PV Generation Based On Interharmonic Impedance
Abstract—As the proportion of distributed PV interconnected Fig. 1 shows the requirements of LVRT and anti-islanding
into receiving-end grid increases, the structure and operation protection in Chinese standard GB/T 33593-2017. As for LVRT,
mode of the traditional grid will undergo crucial variations, and when the voltage is lower than 90% of the rated value, the
the safe and stable operation of grid will have been impacted. distributed photovoltaic generation system need inject reactive
However, there are conflicts and couplings in time between low current within 30ms to support the recovery of grid voltage.
voltage ride through and anti-islanding protection according to However, anti-islanding protection requires that the distributed
the grid-connected code, so that it is difficult to combine low photovoltaic generation system should be shut down from the
voltage ride through and anti-islanding protection in terms of time grid within 2 seconds after it is in an island state to ensure the
and structure. Therefore, this paper proposes a coordinated safety of the grid and personnel [6]. There are conflicts and
control method based on inter harmonic impedance. This method
couplings in time betweet LVRT and anti-islanding protection.
can accurately and quickly distinguish fault state and island state,
When the distributed photovoltaic generation system is in an
and then perform corresponding low voltage ride through and
anti-islanding protection. Finally, availability of the proposed
island state, it is meaningless to accomplish LVRT operations,
method was verified according to simulation. and it will cause damage to equipment and personnel [7].
Conversely, when the grid is fails, the shutdown operation of the
Keywords—distributed PV generation, low voltage ride through, distributed photovoltaic generation system will not be able to
anti-islanding protection, interharmonic impedance, coordinated meet the requirements of low voltage ride through [8]-[10].
control Therefore, it is necessary to accurately and quickly distinguish
fault state and island state within 30ms, and carry out
I. INTRODUCTION coordinated control strategies for low voltage ride through and
With the outbreak of the energy crisis and the increasingly anti-islanding protection to protect the safety of personnel and
serious environmental problems, the exploitation and utilization equipment.
of renewable energy has become the essential point of energy 1.0 time coupling
strategic transformation among the world nations [1]. As the
proportion of distributed PV interconnected into receiving-end Inject reactive current Island detection
grid increases, the structure and operation mode of the 0.8 within 30ms within 2s
traditional grid will undergo crucial variations, and the safe and
stable operation of the grid will have been impacted [2]. In order 0.6
Ride through zone
to improve stability of receiving-end grid that high-proportion
distributed PV interconnected into, IEEE and Chinese GB/T anti-islanding
0.4
standard both stipulate that the large-capacity inverter must have Protection
the function of low voltage ride through (LVRT) and anti-island
protection [3]-[5]. 0.2 Shall trip zone
PCC Rg Lg g U PCC ( s ) Z1 ( s ) Z g ( s )
Grid Z PCC ( s ) = =
I PCC ( s ) Z1 ( s ) + Z g ( s)
sRL ()
PLoad+jQ Load Z1 ( s ) = 2
s RLC + sL + R
C R L
Z g ( s ) = sLg + Rg
2
U PCC Set M=1/Rg+1/R, N=1/L, P=Lg/Rg, usually M>2, N>>1, P<1.
PLoad = PDG = Then there is:
R
()
Q 1
= QDG = U PCC
2
( − 2πfC )
Load 2πfL 1 + 2 P2
| Z ( j ) |= ()
( N − 2C )2 + M 2 2
where UPCC represent the point of common coupling (PCC)
voltage. According to the analysis of the amplitude-frequency
formula, when the angular frequency is equal to the angular
If the power sent by the grid is not 0 before the island occurs, frequency of the system, the trend of the amplitude-frequency
then the voltage and frequency of PCC will be offset after the curve changes. In general, the resonant frequency is greater than
island occurs. It is assumed that the inverter operates per unit the power frequency to prevent the resonance from having an
power factor, and the output active power is a constant value and impact on the power grid. At this time, the amplitude of the
the reactive power is 0. The power mismatch degree is measured equivalent impedance shows an increasing trend. In the case of
by the power variation before and after the island, then the voltage drop in the fault state, the amplitude-frequency formula
formula of active power mismatch degree and reactive power of the equivalent impedance is the same as that in normal grid-
mismatch degree is: connected operation, except that the frequency will have a large
1133
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on September 29,2023 at 11:21:54 UTC from IEEE Xplore. Restrictions apply.
instantaneous change in the case of voltage drop, so the Step 2: If it is determined to be in grid fault operation mode,
equivalent impedance in the case of fault will also increase proceed to Step 3; If the distributed photovoltaic power
instantaneously. However, after the system reaches steady state, generation system is determined to be in islanding operation
the impedance characteristics will return to the value of normal state, proceed to Step 4.
grid-connected operation.
Step 3: Determine whether to perform fault mode based on
0.6 voltage and frequency. If implementing fault mode, it is
Impedance(Ω)
III. COORDINATED CONTROL METHOD FOR LOW VOLTAGE RIDE Islanding operation
THROUGH AND ANTI-ISLANDING PROTECTION BASED ON
INTERHARMONIC IMPEDANCE
From the analysis in the Section II, there may exist coupling Y Whether the fault has
between distributed photovoltaic power generation LVRT and Resume operation
recovered
anti-islanding protection control. Therefore, a coordinated
control strategy for LVRT and anti-islanding protection in N
distributed photovoltaic power generation is proposed in this N Is it located in the
Disconnection
section. LVRT zone
1134
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on September 29,2023 at 11:21:54 UTC from IEEE Xplore. Restrictions apply.
proposes a fault and islanding identification method based on
Voltage(V)
the impedance characteristics of harmonics between grid
connected points, and selects high-frequency harmonics as
injected harmonics.
The design of the inter harmonic impedance discrimination
Current(A)
threshold is also important. The threshold should be adjusted
under different load capacity. The transient change time of
voltage drop will not exceed 0.02s, so when the percentage of
impedance change exceeds 50% after 20ms, the operation mode
is determined as islanding. Otherwise, the operation mode id
determined as fault. Since the impedance of the inverter is
(W,var)
Power
difficult to obtain through theoretical calculation, it can be
approximated by the system impedance obtained through
simulation.
System
State
IV. SIMULATION VERIFICATION AND ANALYSIS
In order to verify the coordinated control method based on
interharmonic impedance proposed in this paper, the distributed Time(s)
PV interconnected into receiving-end grid in Fig. 1 is built by
using Matlab/Simulink. Fig. 8. Waveform diagram after grid failure occurs.
0.5
0
0 500 1000 1500 2000
Current(A)
Frequency (Hz)
Time(s)
1135
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on September 29,2023 at 11:21:54 UTC from IEEE Xplore. Restrictions apply.
method based on interharmonic impedance is proposed. The Three-Phase Inverters Connected to Low-Voltage Grids,” IEEE Trans.
proposed method consists of two parts, which are the fault and Energy Convers., vol. 32, no. 2, pp. 505-515, June 2017.
islanding cooperative control technology based on sequential [5] J. Joshi, A. K. Swami, V. Jately and B. Azzopardi, “A Comprehensive
Review of Control Strategies to Overcome Challenges During LVRT in
logic control, and fault and islanding discrimination method PV Systems,” IEEE Access, vol. 9, pp. 121804-121834, August, 2021.
based on interharmonic impedance. This method can accurately [6] M. Talha, S. R. S. Raihan and N. A. Rahim, “A Grid-tied PV Inverter with
and quickly distinguish fault state and island state with in 30ms, Sag-severity-independent Low-voltage Ride Through, Reactive Power
and then perform corresponding low voltage ride through and Support, and Islanding Protection,” J. Mod. Power Syst. Cle., vol. 9, no.
anti-islanding protection. Finally, availability of the proposed 6, pp. 1300-1311, November 2021.
method was verified according to simulation. [7] D. Sivadas, V. V. Surkod, A. K. Haridas, A. Chithrabhanu and K.
Vasudevan, “Adaptive Active Islanding Detection Strategy Enhanced
REFERENCES with Fault Ride-Through Capability for Grid-Tied Inverters,”2022 IEEE
International Conference on Power Electronics, Smart Grid, and
[1] Y. Sun, Z. Zhao, M. Yang, D. Jia, W. Pei, et al., "Overview of energy Renewable Energy (PESGRE), Trivandrum, India, 2022, pp. 1-7.
storage in renewable energy power fluctuation mitigation," CSEE J.
Power Energy Syst., vol. 6, no. 1, pp. 160-173, March 2020. [8] R. Rai and B. Singh, “Converter Control During Low Voltage Ride
Through Operation for Grid-Interfaced Solar PV Battery Assisted System,”
[2] M. K. Behera and L. C. Saikia, "A Novel Resilient Control of Grid- IEEE Trans. Ind. Electron., vol. 70, no. 9, pp. 9181-9191, Sept. 2023.
Integrated Solar PV-Hybrid Energy Storage Microgrid for Power
Smoothing and Pulse Power Load Accommodation," IEEE Trans. Power [9] M. A. Khan, A. Haque and V. S. B. Kurukuru, “Dynamic Voltage Support
Electron., vol. 38, no. 3, pp. 3965-3980, March 2023. for Low-Voltage Ride-Through Operation in Single-Phase Grid-
Connected Photovoltaic Systems,” IEEE Trans. Power Electron., vol. 36,
[3] P. P. Das and S. Chattopadhyay, “A voltage-independent islanding no. 10, pp. 12102-12111, Oct. 2021.
detection method and low-voltage ride through of a two-stage PV inverter,”
IEEE Trans. Ind. Appl., vol.54, no.3, pp. 2773-2783, May-June 2018. [10] B. K. Choudhury and P. Jena, “Superimposed Impedance-Based Passive
Islanding Detection Scheme for DC Microgrids,” IEEE J. Em. Sel. Top.
[4] M. Dietmannsberger, F. Grumm and D. Schulz, “Simultaneous Power Electron., vol. 10, no. 1, pp. 469-483, Feb. 2022.
Implementation of LVRT Capability and Anti-Islanding Detection in
1136
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on September 29,2023 at 11:21:54 UTC from IEEE Xplore. Restrictions apply.