CGL - Instruction & Maintenance Manual Current Transformer Live Tank
CGL - Instruction & Maintenance Manual Current Transformer Live Tank
Smart solutions.
Strong relationships.
INSTR UCTIO N
&
MAIN TENA NCE MANU AL
PRODUCT : CURRENT TRANSFORMER - LIVE TANK
3 Erectio n
3.1 Lifting & Keeping The CT in _Position 8
3.2 Mountin g of CT 8
3.3 Electric al Connec tions 8
Commi ssionin g
4 11
4.1 Pre Commi ssionin g Checks
4.2 Commi ssionin g 12
Mainte nance
5 13
5.1 Periodi c Mainten ance
5 .2 Checkin g of "Oil Level" in Bellows 15
5.3 Tan Delta of CT 16
1] HOOD
2) METALLIC BELLOW
3) CORE WITH SECONDARY WINDING
4) PRIMARY TERMINALS
5] HOUSING
6] 'PORCELAIN FLANGE
7] PORCELAIN INSULATOR
8] CONDENSER GRADED BUSHING
9] BASE
1OJ OIL FILLING PLUG
11] SHELL
12] ELECTRICAL LEAD THROUGH
13] SECONDARY BOX
14] SECONDARY BOX COVER
15] RATING/ SCHEMATIC PLATE
16) SECONDARY TERMINALS
17] GLAND PLATE
18] MOUNTING HOLES
19] OIL SAMPLING VALVE
20] EARTHING TERMINALS
21) CT LIFTING HOLES
FIG. 1
1
1.2 General Construction :
• Primary Winding :
• Secondary Windin g:
This is torroidal winding. The core (either of High quality Silicon steel or
of Mu-Metal) is wound in a ring form. The second ary winding of
enamelled copper wire is uniformly distributed over the circumf erence
of the core. The uniform distribution minimises the reactan ce of the
second ary winding and in turn helps the accura te transfo rmation of
primary current to secondary side. The relevant leads of the second ary
winding are brought to terminal block through the Alumin ium tube.
• Insulation :
• Primary Terminals :
• Secondary Terminals :
• Earthing Terminals :
I
P1
~I+--+- - - - +--- -
I
I
P2
FIG . 2
4
Primary Terminals Type 2 (P1 - P2 Change over)
P2
FIG. 3
PARALLEL SERI ES
FIG . 4 FIG. 5 .
5
C,
2.1 Packin g:
Unless otherwise agreed upon, the CTs are packed in wooden crates,
with M. S. angle iron frame to hold the basic unit. Fig. 6 shows a typical
packed CT. The packed CTs are transported in horizontal position.
72.5 kV CT's are transported in vertical position.
• Please scrutinize the shipping documents with your Purchase Order and
the markings on the packing case.
• In case goods are insured by you, and any damage is noticed, please
inform your insurance company and proceed further as per Standard
practice.
6
2. 1 Typ ical Packed CT
REMOVE BOLT S
FIG. 6
7
3.0 ERECT ION
• Please refer to fig. 6 and follow the instruct ions given therein correctl y .
• Open the packing case and unscrew all nuts and bolts used for
clampin g the CT in packing case.
• For lifting the CT from packing case and keeping it on platform use two
ropes as shown in the fig. 7.
• Four mountin g holes are provided to hold the CT firmly on the support
structur e at your site.
• Earthing Connection
• Secondary Connections
Use Second ary Termina l Blocks for connect ing instrum ents relays etc.
Connec tions to be done as per rating & Schema tic Plate.
Ensure that VA values given on the rating plate are adhered to.
8
-
(
ENSURE WOODEN SUPPORTS IS
FIRM ON GRO UND TO AVOID
HEAVY SWING ING Of TH l CT
DUR ING LI FTIN C
FIG.7
9
C,
• Caution:
• Primary Connections :
iii) As screw/bolts shall be used with correct washers in order to ensure the
clamping pressure.
10
>
C,
4.1 Pre - Commissioning checks :
Table No. 1 :
Sr. No. A B
1 Tightness of all
Secondary connections.
2 Porcelain insulator
is clean.
3 Base structure
is firmly earthed.
5 No secondary winding is
open and "CX" lead is
connected to earth inside
terminal box. *
* Caution:
11
5.0 MAINTENANCE C,
Sr. No. A B
4.2 Commissioning :
12
a
13
C,
Table No. 1
What
Check for rated value. •
To 5 Secondar y Current
Be
Checked
Check for rated value. • • •
6 Metal Bellows
Check for correct min; max positions. • • • •
(refer Section 5.2 - table 2).
7 Oil Leakage
Check for oil traces. • • • •
8 Terminal Box
Check whether the secondary connections are firm. • •
9 Porcelain Insulator
Check for cleanliness. • • --
10 Metal Parts
Check for corrosion • • ·-
11 "Tan Delta" of CT
12
Refer Section 5.3 •
Typical character istics of Oil Sample
Refer Section 5-4 •
A B C D E F G
Tests 11 & 12 are recommened after 10 years of service & thereafter
every five years.
-
14
11
C,
5.2 Checking of Oil Level" in Bellows :
Table ~o. 2
15
11
5.3 Tan Delta 11 of CT :
5.3.1 Procedure
• Disconnect CT from tan delta test set & source & reconnect primary in
the transmission line & Cx must be earthed.
(Caution - During normal operations always ensure that Cx is firmly
connected to earth.)
16
Notes:
1)
Capacitanc e & tan delta measurem ents at site are most sensitive &
can also be affected by the atmospher ic conditions & electrical
envfronme nt are carried out under dry atmospheric conditions.
2) We recommen d the CT to be tested for tan delta before
commissio ning and the value obtained shall be considered as a
reference value for further monitoring during service. Tan delta
should be 0.005 before commissioning.
17
5.4 Dissolved Gas Analysis of Oil :
The oil sample from CT is to be collected at the frequency mentione d in
Table No. 1.
The complete procedure for testing of samples is as below.
♦ Break the sealing wire and remove the steel plug from oil sampling
valve.
♦ Utmost cleanliness is essential when taking out oil sample as the test
result can also be affected by atmospheric conditions & electrical
environm ent at site.
♦ Replace the sampled oil quantity with a freshly filtered new oil of BDV
higher than 60 kV . (The oil used in the CT is Napthene based
uninhibited mineral oil, hence it is recommended to use oil of same
quality.)
We recomme nd DGA of oil sample done after every five years of service
period. The limits to be used for analysis shall be as specified in
"Reliability, Surveillance & Maintenance of High Voltage Insulatio ns in
Power Systems " State of Technique Report of Study Committ ee 15,
published by CIGRE Study Committee 15 in 1991.
18
c,
Smjrl solutions.
Strong relationships.
_,,,,,,