Lecture 2 - Single Phase Transformers
Lecture 2 - Single Phase Transformers
Lecture 2: Single-phase
Transformers
Instructor:
Dr. Ferchichi Noureddine
2
I- Some history
The second generation of power distribution systems (what we are still using)
was proposed by TESLA few years later. His idea was to generate AC power of
any convenient voltage, step up the voltage for transmission (higher voltage
implies lower current and, thus, lower losses), transmit AC power with small
losses, and finally step down its voltage for consumption. Since power loss is
proportional to the square of the current transmitted, raising the voltage, say, by
the factor of 10 would decrease the current by the same factor (to deliver the
same amount of energy) and, therefore, reduce losses by factor of 100.
The step up and step down voltage conversion was based on the use of
transformers.
3
The invention of a transformer can be attributed to Faraday, who in 1831 used its
principle to demonstrate electromagnetic induction.
Russian engineer Yablochkov in 1876 invented a lighting system based on a set of
induction coils, which acted as a transformer.
4
Gaulard and Gibbs first exhibited a device with an open iron core called a
'secondary generator' in London in 1882 and then sold the idea to a company
Westinghouse. They also exhibited their invention in Turin in 1884, where it was
adopted for an electric lighting system.
In 1885, William Stanley, an engineer for Westinghouse, built the first
commercial transformer after George Westinghouse had bought Gaulard and
Gibbs' patents. The core was made from interlocking E-shaped iron plates. This
design was first used commercially in 1886.
Hungarian engineers Zipernowsky, Bláthy and Déri created the efficient "ZBD"
closed-core model in 1885 based on the design by Gaulard and Gibbs. Their
patent application made the first use of the word "transformer".
Another Russian engineer Dolivo-Dobrovolsky developed the first three-phase
transformer in 1889.
Finally, in 1891 Nikola Tesla invented the Tesla coil, an air-cored, dual-tuned
resonant transformer for generating very high voltages at high frequency.
5
Windings are wrapped around two Windings are wrapped around the
sides of a laminated square core. center leg of a laminated core.
Usually, windings are wrapped on top of each other to decrease flux leakage
and, therefore, increase efficiency.
6
Lamination
types
V- Ideal transformer
vS (t ) N
2 a
v P (t ) N1
Ideal transformer
The relationship between the primary i1(t) and secondary i2(t) currents is
i1 N 2
a
i2 N1
In the phasor notation:
V2 N 2
a
V 1 N1
I1 N 2
a
I 2 N1
The phase angles of primary and secondary voltages are the same. The phase
angles of primary and secondary currents are the same also. The ideal
transformer changes magnitudes of voltages and currents but not their angles.
10
Ideal transformer
If the voltage is positive at the dotted end of the primary winding at some
moment of time, the voltage at the dotted end of the secondary winding will also
be positive at the same time instance.
If the primary current flows into the dotted end of the primary winding, the
secondary current will flow out of the dotted end of the secondary winding.
11
Assuming that p and s are the angles between voltages and currents on the
primary and secondary windings respectively, the power supplied to the
transformer by the primary circuit is:
Pin Vp I p cos p
The power supplied to the output circuits is
Pout Vs I s cos s
Since ideal transformers do not affect angles between voltages and currents:
p s
Both windings of an ideal transformer have the same power factor.
12
1 1
V1 V2 V2 aV1 I1 aI 2 I 2 I1
a a
Therefore:
1
Pout V2 I 2 cos aV1 I 1 cos V1 I 1 cos Pin
a
The output power of an ideal transformer equals to its input power – to be
expected since assumed no loss. Similarly, for reactive and apparent powers:
Sout Vs I s Vp I p Sin
13
Next, we exclude the transformer from the circuit and solve it for voltages
and currents.
The solutions obtained for the portion of the circuit that was not replaced
will be the correct values of voltages and currents of the original circuit.
Finally, the voltages and currents on the other side of the transformer (in
the original circuit) can be found by considering the transformer’s turn ratio.
The load impedance when referred to the transmission line (while the
transformer T2 is eliminated) is:
1 1
Z '
Load 2 Z Load 2
.(4 j.3) 400 j.300
a2 (0,1)
The total impedance on the
transmission line level is
Z eq Zline Z Load
'
0,18 j.0,24 400 j.300 400,18 j.300,24
The total impedance is now referred across T1 to the source’s voltage level:
1 1
Z eq (400,18 j.300,24) 4,0018 j.3,0024 5,00336,87
'
2
Z eq 2
a1 10
18
N
Therefore: d
eind N
dt
20
p m Lp
average primary flux mutual flux
s m Ls
Average secondary flux
21
Therefore:
eS (t ) N 2
a
e P (t ) N1
That is, the ratio of the primary voltage to the secondary voltage both caused by
the mutual flux is equal to the turns ratio of the transformer.
v S (t ) N 2
a
v P (t ) N1
23
Ignoring flux leakage and assuming time-harmonic primary voltage, the average
flux is:
1 1 Vm
sin tWb
Np Np
v (t ) dt V cos tdt
p m
N p
If the values of current are comparable to the flux they produce in the core, it is
possible to sketch a magnetization current. We observe:
1. Magnetization current is not sinusoidal: there are high frequency components;
2. Once saturation is reached, a small increase in flux requires a large increase
in magnetization current;
3. Magnetization current (its fundamental component) lags the voltage by 90o;
4. High-frequency components of the current may be large in saturation.
Assuming a sinusoidal flux in the core, the eddy currents will be largest when
flux passes zero.
25
Core-loss current
The total no-load current in the core is called the excitation current of the
transformer:
iex im ihe
26
Fnet N pi p N sis 0
27
Lp P N pi p
permeance of flux path
Therefore:
eLp (t ) N p P N pi p N pP
d 2
di p
dt dt
30
di p
Primary coil: eLp (t ) Lp
dt
dis
Secondary coil: eLs (t ) Ls
dt
The leakage flux can be modeled by primary and secondary inductors.
The magnetization current can be modeled by a reactance XM connected across
the primary voltage source.
The core-loss current can be modeled by a resistance RC connected across the
primary voltage source.
Both currents are nonlinear; therefore, XM and RC are just approximations.
31
The transformer’s
equivalent circuit
However, the exact circuit is not
very practical.
From this information, the power factor of the input current and the magnitude and
the angle of the excitation impedance can be determined.
To evaluate RC and XM, we determine the conductance of the core-loss resistor is:
1
GC
RC
The susceptance of the magnetizing inductor is:
1
BM
XM
33
Since both elements are in parallel, their admittances add. Therefore, the total
excitation admittance is:
1 1
YE GC jBM j
RC XM
The magnitude of the excitation admittance in the open-circuit test is:
I oc
YE
Voc
The angle of the admittance in the open-circuit test can be found from the circuit
power factor (PF):
Poc
cos PF
Voc I oc
34
In real transformers, the power factor is always lagging, so the angle of the current
always lags the angle of the voltage by degrees. The admittance is:
I oc I oc
YE cos1 PF
Voc Voc
Therefore:
VSC 0 VSC
Z SE
I SC I SC
Since the serial impedance ZSE is equal to
Z SE Req j. X eq
1 1
Z SE ( RP 2
R S ) j.( X P 2
XS)
a a
it is possible to determine the total series impedance referred to the primary side
of the transformer. However, there is no easy way to split the series impedance
into primary and secondary components.
The same tests can be performed on the secondary side of the transformer. The
results will yield the equivalent circuit impedances referred to the secondary
side of the transformer.
37
1 1
Therefore: RC 159k ; X M 38.3k
0.0000063 0.0000261
The power factor during the short-circuit test is
PSC 240
PF cos 0.196lagging
VSC I SC 489 2.5
The series impedance is given by
VSC 489
Z SE cos 1 PF 78.7
I SC 2.5
38.4 j192
Therefore:
Req 38.3; X eq 192
The equivalent circuit
39
The voltages, currents, powers, impedances, and other electrical quantities are
measured as fractions of some base level instead of conventional units.
actualvalue
Quantity perunit
basevalueof quantity
Usually, two base quantities are selected to define a given per-unit system. Often,
such quantities are voltage and power (or apparent power). In a 1-phase system:
Pbase ,Qbase ,orSbase Vbase I base
Vbase Vbase
2
Zbase
I base Sbase
40
I base
Ybase
Vbase
Ones the base values of P (or S) and V are selected, all other base values can
be computed form the above equations.
In a power system, a base apparent power and voltage are selected at the
specific point in the system. Note that a transformer has no effect on the
apparent power of the system, since the apparent power into a transformer
equals the apparent power out of a transformer. As a result, the base apparent
power remains constant everywhere in the power system.
On the other hand, voltage (and, therefore, a base voltage) changes when it
goes through a transformer according to its turn ratio. Therefore, the process
of referring quantities to a common voltage level is done automatically in the
per-unit system.
41
Sbase1 10000
I base1 20.83 A
Vbase1 480
Vbase1 480
Zbase1 23.04
I base1 20.83
The turns ratio of the transformer T1 is a1 = 10; therefore, the voltage in the
transmission line region is
Sbase2 10kVA
10000
I base2 2.083 A
4800
4800
Z base2 2304
2.083
The turns ratio of the transformer T2 is a2 = 0,05; therefore, the voltage in the
load region is
Sbase 10kVA
10000
I base 41.67 A
240
240
Z base 5.76
41.67
b. To convert a power system to a per-unit system, each component must be
divided by its base value in its region. The generator’s per-unit voltage is
4800
VG , pu 1.00 pu
480
The transmission line’s per-unit impedance is
20 j 60
Zline, pu 0.0087 j 0.026 pu
2304
45
1030
Zload , pu
5.76
1.73630 pu
The per-unit
equivalent circuit
Vpu 10
I pu 0.569 30.6 pu
Ztot , pu 0.0087 j 0.026 1.73630
46
Pload , pu I pu
2
Rpu 0.5692 1.503 0.487
The actual power on the load is
Pline, pu I pu
2
Rline, pu 0.5692 0.0087 0.00282
The actual power lost in the transmission line
When only one device (transformer or motor) is analyzed, its own ratings are used
as the basis for per-unit system. When considering a transformer in a per-unit
system, transformer’s characteristics will not vary much over a wide range of
voltages and powers. For example, the series resistance is usually from 0.02 to
0.1 pu; the magnetizing reactance is usually from 10 to 40 pu; the core-loss
resistance is usually from 50 to 200 pu. Also, the per-unit impedances of
synchronous and induction machines fall within relatively narrow ranges over quite
large size ranges.
If more than one transformer is present in a system, the system base voltage and
power can be chosen arbitrary. However, the entire system must have the same
base power, and the base voltages at various points in the system must be related
by the voltage ratios of the transformers.
System base quantities are commonly chosen to the base of the largest
component in the system.
48
Where Vs,nl and Vs,fl are the secondary no load and full load voltages.
Note, the VR of an ideal transformer is zero.
49
a.V1 V2 Req 2 I 2 jX eq 2 I 2
Pout Pout
100% 100%
Pin Pout Ploss
Note: the same equation describes the efficiency of motors and generators.
Considering the transformer equivalent circuit, we notice three types of losses:
1. Copper (I2R) losses – are accounted for by the series resistance
2. Hysteresis losses – are accounted for by the resistor Rc.
3. Eddy current losses – are accounted for by the resistor Rc.
a. Find the equivalent circuit of this transformer referred to the high-voltage side.
b. Find the equivalent circuit of this transformer referred to the low-voltage side.
c. Calculate the full-load voltage regulation at 0.8 lagging power factor, at 1.0
power factor, and at 0.8 leading power factor.
d. Plot the voltage regulation as load is increased from no load to full load at
power factors of 0.8 lagging, 1.0, and 0.8 leading.
e. What is the efficiency of the transformer at full load with a power factor of 0.8
lagging?
53
a. The excitation branch values of the equivalent circuit can be determined as:
Poc 50
oc cos 1 cos 1 84
Voc I oc 2300 0.21
The excitation admittance is:
I oc 0.21
YE 84 84 0.0000095 j 0.0000908S
Voc 2300
The elements of the excitation branch referred to the primary side are:
1
Rc 105k
0.0000095
1
XM 11k
0.0000908
54
p a VS , fl
Va.Vp
VR 100% a.Vp
VS , fl
234.85 230
100%
230
2.1%
57
p a VS , fl
Va.Vp 232.94 230
VR 100% 100% 1.28%
VS , fl 230
a.Vp
58
p a VS , fl
Va.Vp 229.85 230
VR 100% 100% 0.062%
VS , fl 230
a.Vp
59
Pout
100% 98.03%
PCu Pcore Pout