The document contains tables with static and dynamic force data for overhead power line conductors and suspension strings. Table 1 lists static forces for various conductor spans under different temperature, wind velocity, and angle conditions. Table 2 provides similar static force data for shield wire spans. Table 3 shows dynamic forces during short circuits for some conductor spans. Table 4 gives the suspension string load values for 220kV and 132kV lines.

Uploaded by

Mian M Khurram
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views

Loading Output

The document contains tables with static and dynamic force data for overhead power line conductors and suspension strings. Table 1 lists static forces for various conductor spans under different temperature, wind velocity, and angle conditions. Table 2 provides similar static force data for shield wire spans. Table 3 shows dynamic forces during short circuits for some conductor spans. Table 4 gives the suspension string load values for 220kV and 132kV lines.

Uploaded by

Mian M Khurram
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 6

Table 1: STATIC FORCES DUE TO CONDUCTOR SPANS

SR. DESIGNATION SPAN T V θ D TO TH TV LC


o
C m/s deg m kN kN kN m
1 32 m DOUBLE CONDUCTOR 75 0 0 1.300 22.74 0.00 3.81 21.434
2 32 m DOUBLE CONDUCTOR 0 45 0 1.048 28.20 0.00 3.81 21.360
F1
3 32 m DOUBLE CONDUCTOR 0 45 45 0.804 36.75 3.34 3.81 21.300
4 32 m DOUBLE CONDUCTOR 0 45 90 0.682 43.35 4.73 3.81 21.280
5 37 m DOUBLE CONDUCTOR 75 0 0 1.300 27.28 0.00 3.94 26.394
6 37 m DOUBLE CONDUCTOR 0 45 0 0.960 36.93 0.00 3.94 26.320
F2
7 37 m DOUBLE CONDUCTOR 0 45 45 0.750 47.29 3.47 3.94 26.280
8 37 m DOUBLE CONDUCTOR 0 45 90 0.644 55.11 4.90 3.94 26.260
9 37 m DOUBLE CONDUCTOR (132 kV SWITCHYARD) 75 0 0 1.050 22.57 0.00 2.64 29.534
10 37 m DOUBLE CONDUCTOR (132 kV SWITCHYARD) 0 45 0 0.617 38.42 0.00 2.64 29.470
F3
11 37 m DOUBLE CONDUCTOR (132 kV SWITCHYARD) 0 45 45 0.504 46.97 2.26 2.64 29.460
12 37 m DOUBLE CONDUCTOR (132 kV SWITCHYARD) 0 45 90 0.444 53.34 3.20 2.64 29.450
13 37 m SINGLE CONDUCTOR 75 0 0 1.050 12.81 0.00 1.49 29.534
14 37 m SINGLE CONDUCTOR 0 45 0 0.626 21.49 0.00 1.49 29.470
F4
15 37 m SINGLE CONDUCTOR 0 45 45 0.427 31.52 2.09 1.49 29.450
16 37 m SINGLE CONDUCTOR 0 45 90 0.357 37.63 2.96 1.49 29.450
17 53 m DOUBLE CONDUCTOR 75 0 0 1.050 35.52 0.00 2.87 45.499
18 53 m DOUBLE CONDUCTOR 0 45 0 0.418 89.20 0.00 2.87 45.440
F5
19 53 m DOUBLE CONDUCTOR 0 45 45 0.389 95.78 2.60 2.87 45.440
20 53 m DOUBLE CONDUCTOR 0 45 90 0.369 101.17 3.67 2.87 45.440
21 54 m DOUBLE CONDUCTOR 75 0 0 1.050 36.35 0.00 2.88 46.497
22 54 m DOUBLE CONDUCTOR 0 45 0 0.414 92.11 0.00 2.88 46.440
F6
F6
23 54 m DOUBLE CONDUCTOR 0 45 45 0.387 98.50 2.61 2.88 46.440
24 54 m DOUBLE CONDUCTOR 0 45 90 0.367 103.77 3.68 2.88 46.440
Table 2: STATIC FORCES DUE TO SHIELD-WIRE SPAN
SR. DESIGNATION SPAN T V θ D TO TH TV
o
C m/s deg m kN kN kN
1 16 m SPAN 75 0 0 0.528 0.21 0.00 0.10
2 16 m SPAN 0 45 0 0.452 0.24 0.00 0.10
F7
3 16 m SPAN 0 45 45 0.199 0.55 0.06 0.10
4 16 m SPAN 0 45 90 0.148 0.74 0.08 0.10
5 24 m SPAN 75 0 0 0.792 0.32 0.00 0.11
6 24 m SPAN 0 45 0 0.674 0.38 0.00 0.11
F8
7 24 m SPAN 0 45 45 0.297 0.86 0.09 0.11
8 24 m SPAN 0 45 90 0.222 1.15 0.13 0.11
9 29 m SPAN 75 0 0 0.957 0.40 0.00 0.12
10 29 m SPAN 0 45 0 0.813 0.47 0.00 0.12
F9
11 29 m SPAN 0 45 45 0.359 1.05 0.11 0.12
12 29 m SPAN 0 45 90 0.269 1.41 0.16 0.12
13 32 m SPAN 75 0 0 1.056 0.44 0.00 0.13
14 32 m SPAN 0 45 0 0.896 0.52 0.00 0.13
F10
15 32 m SPAN 0 45 45 0.397 1.17 0.12 0.13
16 32 m SPAN 0 45 90 0.297 1.56 0.17 0.13
17 37 m SPAN 75 0 0 1.221 0.51 0.00 0.14
18 37 m SPAN 0 45 0 1.035 0.60 0.00 0.14
F11
19 37 m SPAN 0 45 45 0.459 1.36 0.14 0.14
20 37 m SPAN 0 45 90 0.345 1.81 0.20 0.14
21 41 m SPAN 75 0 0 1.353 0.57 0.00 0.15
22 41 m SPAN 0 45 0 1.146 0.67 0.00 0.15
F12
23 41 m SPAN 0 45 45 0.510 1.51 0.16 0.15
24 41 m SPAN 0 45 90 0.383 2.01 0.22 0.15
25 44 m SPAN 75 0 0 1.452 0.61 0.00 0.15
26 44 m SPAN 0 45 0 1.230 0.72 0.00 0.15
F13
27 44 m SPAN 0 45 45 0.548 1.62 0.17 0.15
28 44 m SPAN 0 45 90 0.412 2.16 0.24 0.15
29 53 m SPAN 75 0 0 1.749 0.74 0.00 0.17
30 53 m SPAN 0 45 0 1.480 0.88 0.00 0.17
F14
31 53 m SPAN 0 45 45 0.662 1.96 0.21 0.17
32 53 m SPAN 0 45 90 0.499 2.60 0.29 0.17
33 56 m SPAN 75 0 0 1.848 0.79 0.00 0.17
34 56 m SPAN 0 45 0 1.564 0.93 0.00 0.17
F15
F15
35 56 m SPAN 0 45 45 0.700 2.07 0.22 0.17
36 56 m SPAN 0 45 90 0.528 2.75 0.31 0.17
Table 3: DYNAMIC FORCES (SHORT CIRCUIT)
Ft Fd
SR. SPAN
kN kN

1 32 m DOUBLE CONDUCTOR 58.23 21.43

2 37 m DOUBLE CONDUCTOR 72.28 26.39

3 37 m DOUBLE CONDUCTOR (132 kV SWITCHYARD) 70.42 29.53

4 37 m SINGLE CONDUCTOR 48.40 29.53

5 53 m DOUBLE CONDUCTOR 127.18 45.50

6 54 m DOUBLE CONDUCTOR 130.22 46.50


Table 4: SUSPENSION STRING LOAD

Sr. Designation Description Ws

kN

220 kV Double Suspension String


1 F16 2.96
Assembly

132 kV Double Suspension String


2 F17 1.85
Assembly