Loading Output

The document contains tables with static and dynamic force data for overhead power line conductors and suspension strings. Table 1 lists static forces for various conductor spans under different temperature, wind velocity, and angle conditions. Table 2 provides similar static force data for shield wire spans. Table 3 shows dynamic forces during short circuits for some conductor spans. Table 4 gives the suspension string load values for 220kV and 132kV lines.

Uploaded by

Mian M Khurram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views6 pages

Loading Output

The document contains tables with static and dynamic force data for overhead power line conductors and suspension strings. Table 1 lists static forces for various conductor spans under different temperature, wind velocity, and angle conditions. Table 2 provides similar static force data for shield wire spans. Table 3 shows dynamic forces during short circuits for some conductor spans. Table 4 gives the suspension string load values for 220kV and 132kV lines.

Uploaded by

Mian M Khurram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 6

Table 1: STATIC FORCES DUE TO CONDUCTOR SPANS

SR. DESIGNATION SPAN T V θ D TO TH TV LC


o
C m/s deg m kN kN kN m
1 32 m DOUBLE CONDUCTOR 75 0 0 1.300 22.74 0.00 3.81 21.434
2 32 m DOUBLE CONDUCTOR 0 45 0 1.048 28.20 0.00 3.81 21.360
F1
3 32 m DOUBLE CONDUCTOR 0 45 45 0.804 36.75 3.34 3.81 21.300
4 32 m DOUBLE CONDUCTOR 0 45 90 0.682 43.35 4.73 3.81 21.280
5 37 m DOUBLE CONDUCTOR 75 0 0 1.300 27.28 0.00 3.94 26.394
6 37 m DOUBLE CONDUCTOR 0 45 0 0.960 36.93 0.00 3.94 26.320
F2
7 37 m DOUBLE CONDUCTOR 0 45 45 0.750 47.29 3.47 3.94 26.280
8 37 m DOUBLE CONDUCTOR 0 45 90 0.644 55.11 4.90 3.94 26.260
9 37 m DOUBLE CONDUCTOR (132 kV SWITCHYARD) 75 0 0 1.050 22.57 0.00 2.64 29.534
10 37 m DOUBLE CONDUCTOR (132 kV SWITCHYARD) 0 45 0 0.617 38.42 0.00 2.64 29.470
F3
11 37 m DOUBLE CONDUCTOR (132 kV SWITCHYARD) 0 45 45 0.504 46.97 2.26 2.64 29.460
12 37 m DOUBLE CONDUCTOR (132 kV SWITCHYARD) 0 45 90 0.444 53.34 3.20 2.64 29.450
13 37 m SINGLE CONDUCTOR 75 0 0 1.050 12.81 0.00 1.49 29.534
14 37 m SINGLE CONDUCTOR 0 45 0 0.626 21.49 0.00 1.49 29.470
F4
15 37 m SINGLE CONDUCTOR 0 45 45 0.427 31.52 2.09 1.49 29.450
16 37 m SINGLE CONDUCTOR 0 45 90 0.357 37.63 2.96 1.49 29.450
17 53 m DOUBLE CONDUCTOR 75 0 0 1.050 35.52 0.00 2.87 45.499
18 53 m DOUBLE CONDUCTOR 0 45 0 0.418 89.20 0.00 2.87 45.440
F5
19 53 m DOUBLE CONDUCTOR 0 45 45 0.389 95.78 2.60 2.87 45.440
20 53 m DOUBLE CONDUCTOR 0 45 90 0.369 101.17 3.67 2.87 45.440
21 54 m DOUBLE CONDUCTOR 75 0 0 1.050 36.35 0.00 2.88 46.497
22 54 m DOUBLE CONDUCTOR 0 45 0 0.414 92.11 0.00 2.88 46.440
F6
F6
23 54 m DOUBLE CONDUCTOR 0 45 45 0.387 98.50 2.61 2.88 46.440
24 54 m DOUBLE CONDUCTOR 0 45 90 0.367 103.77 3.68 2.88 46.440
Table 2: STATIC FORCES DUE TO SHIELD-WIRE SPAN
SR. DESIGNATION SPAN T V θ D TO TH TV
o
C m/s deg m kN kN kN
1 16 m SPAN 75 0 0 0.528 0.21 0.00 0.10
2 16 m SPAN 0 45 0 0.452 0.24 0.00 0.10
F7
3 16 m SPAN 0 45 45 0.199 0.55 0.06 0.10
4 16 m SPAN 0 45 90 0.148 0.74 0.08 0.10
5 24 m SPAN 75 0 0 0.792 0.32 0.00 0.11
6 24 m SPAN 0 45 0 0.674 0.38 0.00 0.11
F8
7 24 m SPAN 0 45 45 0.297 0.86 0.09 0.11
8 24 m SPAN 0 45 90 0.222 1.15 0.13 0.11
9 29 m SPAN 75 0 0 0.957 0.40 0.00 0.12
10 29 m SPAN 0 45 0 0.813 0.47 0.00 0.12
F9
11 29 m SPAN 0 45 45 0.359 1.05 0.11 0.12
12 29 m SPAN 0 45 90 0.269 1.41 0.16 0.12
13 32 m SPAN 75 0 0 1.056 0.44 0.00 0.13
14 32 m SPAN 0 45 0 0.896 0.52 0.00 0.13
F10
15 32 m SPAN 0 45 45 0.397 1.17 0.12 0.13
16 32 m SPAN 0 45 90 0.297 1.56 0.17 0.13
17 37 m SPAN 75 0 0 1.221 0.51 0.00 0.14
18 37 m SPAN 0 45 0 1.035 0.60 0.00 0.14
F11
19 37 m SPAN 0 45 45 0.459 1.36 0.14 0.14
20 37 m SPAN 0 45 90 0.345 1.81 0.20 0.14
21 41 m SPAN 75 0 0 1.353 0.57 0.00 0.15
22 41 m SPAN 0 45 0 1.146 0.67 0.00 0.15
F12
23 41 m SPAN 0 45 45 0.510 1.51 0.16 0.15
24 41 m SPAN 0 45 90 0.383 2.01 0.22 0.15
25 44 m SPAN 75 0 0 1.452 0.61 0.00 0.15
26 44 m SPAN 0 45 0 1.230 0.72 0.00 0.15
F13
27 44 m SPAN 0 45 45 0.548 1.62 0.17 0.15
28 44 m SPAN 0 45 90 0.412 2.16 0.24 0.15
29 53 m SPAN 75 0 0 1.749 0.74 0.00 0.17
30 53 m SPAN 0 45 0 1.480 0.88 0.00 0.17
F14
31 53 m SPAN 0 45 45 0.662 1.96 0.21 0.17
32 53 m SPAN 0 45 90 0.499 2.60 0.29 0.17
33 56 m SPAN 75 0 0 1.848 0.79 0.00 0.17
34 56 m SPAN 0 45 0 1.564 0.93 0.00 0.17
F15
F15
35 56 m SPAN 0 45 45 0.700 2.07 0.22 0.17
36 56 m SPAN 0 45 90 0.528 2.75 0.31 0.17
Table 3: DYNAMIC FORCES (SHORT CIRCUIT)
Ft Fd
SR. SPAN
kN kN

1 32 m DOUBLE CONDUCTOR 58.23 21.43

2 37 m DOUBLE CONDUCTOR 72.28 26.39

3 37 m DOUBLE CONDUCTOR (132 kV SWITCHYARD) 70.42 29.53

4 37 m SINGLE CONDUCTOR 48.40 29.53

5 53 m DOUBLE CONDUCTOR 127.18 45.50

6 54 m DOUBLE CONDUCTOR 130.22 46.50


Table 4: SUSPENSION STRING LOAD

Sr. Designation Description Ws

kN

220 kV Double Suspension String


1 F16 2.96
Assembly

132 kV Double Suspension String


2 F17 1.85
Assembly