SIPROTEC 4 7SJ62
Multifunction Protection Relay
Function overview
Protection functions
• Time-overcurrent protection
• Directional time-overcurrent protection
• Sensitive dir. earth-fault detection
• Displacement voltage
• Intermittent earth-fault protection
• High-impedance restricted earth fault
• Inrush restraint
• Motor protection
LSP2299-afpen.eps
SIPV6_116.eps
– Undercurrent monitoring
– Starting time supervision
– Restart inhibit
– Locked rotor
– Load jam protection
• Overload protection 5
• Temperature monitoring
Fig. 5/75 SIPROTEC 4 7SJ62 multifunction protection relay • Under-/overvoltage protection
with text (left) and graphic display • Under-/overfrequency protection
• Breaker failure protection
• Negative-sequence protection
• Phase-sequence monitoring
Description • Synchro-check
• Fault locator
The SIPROTEC 4 7SJ62 relays can be used • Lockout
for line protection of high and medium
• Auto-reclosure
voltage networks with earthed (grounded),
low-resistance earthed, isolated or com- Control functions/programmable logic
pensated neutral point. With regard to • Commands f. ctrl of CB and of isolators
motor protection, the SIPROTEC 4 7SJ62 • Position of switching elements is shown
is suitable for asynchronous machines of on the graphic display
all sizes. The relay performs all functions • Control via keyboard, binary inputs,
of backup protection supplementary to DIGSI 4 or SCADA system
transformer differential protection. • User-defined logic with CFC
7SJ62 is featuring the "flexible protection (e.g. interlocking)
functions". Up to 20 protection functions Monitoring functions
can be added according to individual • Operational measured values V, I, f
requirements. Thus, for example, a rate- • Energy metering values Wp, Wq
of-frequency-change protection or reverse • Circuit-breaker wear monitoring
power protection can be implemented.
• Slave pointer
The relay provides control of the circuit- • Trip circuit supervision
breaker, further switching devices and • Fuse failure monitor
automation functions. The integrated • 8 oscillographic fault records
programmable logic (CFC) allows the • Motor statistics
user to implement their own functions,
Communication interfaces
e. g. for the automation of switchgear
(interlocking). The user is also allowed • System interface
to generate user-defined messages. – IEC 60870-5-103/ IEC 61850
– PROFIBUS-FMS/-DP
The flexible communication interfaces
– DNP 3.0/MODBUS RTU
are open for modern communication
• Service interface for DIGSI 4 (modem)
architectures with control systems.
• Front interface for DIGSI 4
• Time synchronization via IRIG B/DCF77
Hardware
• 4 current transformers
• 3/4 voltage transformers
• 8/11 binary inputs
• 8/6 output relays
Application
Application
50, 50N I>, I>>, I>>>, IE>, IE>>, IE>>> Definite time-overcurrent protection (phase/neutral)
51, 51V, 51N Ip, IEp Inverse time-overcurrent protection (phase/neutral), phase function with voltage-dependent option
67, 67N Idir>, Idir>>, Ip dir Directional time-overcurrent protection (definite/inverse, phase/neutral),
IEdir>, IEdir>>, IEp dir Directional comparison protection
25 Synchro-check
38 Temperature monitoring via external device (RTD-box), e.g. bearing temperature monitoring
Construction
LSP2099-afpen.eps
for surface-mounting housing. All cables can
be connected with or without ring lugs.
In the case of surface mounting on a panel,
the connection terminals are located above
and below in the form of screw-type termi-
nals. The communication interfaces are
located in a sloped case at the top and
5 bottom of the housing. Fig. 5/79 Rear view with screw-type terminals, 1/3-rack size
Protection functions
Time-overcurrent protection
(ANSI 50, 50N, 51, 51V, 51N)
This function is based on the phase-
selective measurement of the three phase
currents and the earth current (four trans-
formers). Three definite-time overcurrent
protection elements (DMT) exist both for
the phases and for the earth. The current
threshold and the delay time can be set
within a wide range. In addition, inverse-
time overcurrent protection characteristics
(IDMTL) can be activated.
The inverse-time function provides – as
an option – voltage-restraint or voltage-
controlled operating modes.
Fig. 5/77 Fig. 5/78
Definite-time overcurrent protection Inverse-time overcurrent protection
Available inverse-time characteristics User-definable characteristics
Characteristics acc. to ANSI/IEEE IEC 60255-3 Instead of the predefined time characteris-
Inverse • • tics according to ANSI, tripping character-
istics can be defined by the user for phase
Short inverse • and earth units separately. Up to 20 cur-
rent/time value pairs may be programmed.
Long inverse • • They are set as pairs of numbers or graphi-
Moderately inverse • cally in DIGSI 4.
Very inverse • • Inrush restraint
Extremely inverse • • The relay features second harmonic re-
straint. If the second harmonic is detected
during transformer energization, pickup of
Reset characteristics non-directional and directional normal el-
ements are blocked.
For easier time coordination with emulation), a reset process is initiated after
electromechanical relays, reset characte- the fault current has disappeared. This
Cold load pickup/dynamic setting change
ristics according to ANSI C37.112 and reset process corresponds to the reverse
IEC 60255-3 /BS 142 standards are applied. movement of the Ferraris disk of an elec- For directional and non-directional time-
When using the reset characteristic (disk tromechanical relay (thus: disk emulation). overcurrent protection functions the initia-
tion thresholds and tripping times can be
switched via binary inputs or by time control.
5/86 Siemens SIP · Edition No. 6
5 Overcurrent Protection / 7SJ62
Protection functions
Protection functions
Protection functions
n Motor protection
Restart inhibit (ANSI 66/86)
If a motor is started up too many times in
succession, the rotor can be subject to ther-
mal overload, especially the upper edges of
the bars. The rotor temperature is calcu-
lated from the stator current. The reclosing
lockout only permits start-up of the motor
if the rotor has sufficient thermal reserves
for a complete start-up (see Fig. 5/84).
Emergency start-up
This function disables the reclosing lock-
out via a binary input by storing the state
of the thermal replica as long as the binary
5 input is active. It is also possible to reset
the thermal replica to zero.
Fig. 5/84
Temperature monitoring (ANSI 38)
Up to two temperature monitoring boxes The characteristic (equation) can be shaft breakage, no-load operation of
with a total of 12 measuring sensors can be adapted optimally to the state of the motor pumps or fan failure.
used for temperature monitoring and de- by applying different tripping times TA in
tection by the protection relay. The ther- dependence of either cold or warm motor Motor statistics
mal status of motors, generators and state. For differentiation of the motor state Essential information on start-up of the
transformers can be monitored with this the thermal model of the rotor is applied. motor (duration, current, voltage) and
device. Additionally, the temperature of If the trip time is rated according to the general information on number of starts,
the bearings of rotating machines are mon- above formula, even a prolonged start-up total operating time, total down time, etc.
itored for limit value violation. The tem- and reduced voltage (and reduced start-up are saved as statistics in the device.
peratures are being measured with the help current) will be evaluated correctly. The
of temperature detectors at various loca- tripping time is inverse (current depend- n Voltage protection
tions of the device to be protected. This ent).
data is transmitted to the protection relay Overvoltage protection (ANSI 59)
via one or two temperature monitoring A binary signal is set by a speed sensor to The two-element overvoltage protection
boxes (see “Accessories”, page 5/115). detect a blocked rotor. An instantaneous detects unwanted network and machine
tripping is effected. overvoltage conditions. The function can
Starting time supervision (ANSI 48/14) operate either with phase-to-phase,
Load jam protection (ANSI 51M) phase-to-earth, positive phase-sequence
Starting time supervision protects the mo-
tor against long unwanted start-ups that Sudden high loads can cause slowing down or negative phase-sequence system voltage.
might occur in the event of excessive load and blocking of the motor and mechanical Three-phase and single-phase connections
torque or excessive voltage drops within damages. The rise of current due to a load are possible.
the motor, or if the rotor is locked. Rotor jam is being monitored by this function
temperature is calculated from measured (alarm and tripping). Undervoltage protection (ANSI 27)
stator current. The tripping time is calcu- The overload protection function is too The two-element undervoltage protection
lated according to the following equation: slow and therefore not suitable under these provides protection against dangerous
circumstances. voltage drops (especially for electric ma-
for I > IMOTOR START chines). Applications include the isolation
2
Phase-balance current protection (ANSI 46) of generators or motors from the network
t = ⎛⎜ A ⎞⎟ ⋅ TA
I
⎝ I ⎠ (Negative-sequence protection) to avoid undesired operating states and a
possible loss of stability. Proper operating
I = Actual current flowing The negative-sequence / phase-balance
conditions of electrical machines are best
IMOTOR START = Pickup current to detect a motor current protection detects a phase failure
evaluated with the positive-sequence quan-
start or load unbalance due to network asym-
tities. The protection function is active
t = Tripping time metry and protects the rotor from imper-
over a wide frequency range (45 to 55, 55
IA = Rated motor starting current missible temperature rise.
to 65 Hz)1). Even when falling below this
TA = Tripping time at rated motor frequency range the function continues to
starting current (2 times, for Undercurrent monitoring (ANSI 37)
work, however, with a greater tolerance
warm and cold motor) With this function, a sudden drop in cur- band.
rent, which can occur due to a reduced
1) The 45 to 55, 55 to 65 Hz range is available
motor load, is detected. This may be due to for fN = 50/60 Hz.
Frequency protection can be used for over- All of these methods are phase-selective
frequency and underfrequency protection. and a limit value can be set in order to ob-
Electric machines and parts of the system tain an alarm if the actual value falls below
are protected from unwanted speed devia- or exceeds the limit value during determi-
tions. Unwanted frequency changes in the nation of the remaining service life.
network can be detected and the load can
Customized functions (ANSI 32, 51V, 55, etc.)
be removed at a specified frequency set-
ting. Additional functions, which are not time
Frequency protection can be used over a
critical, can be implemented via the CFC 5
using measured values. Typical functions
wide frequency range (40 to 60, 50 to
include reverse power, voltage controlled
70 Hz)1). There are four elements (select-
overcurrent, phase angle detection, and Fig. 5/85 CB switching cycle diagram
able as overfrequency or underfrequency)
zero-sequence voltage detection.
and each element can be delayed sepa-
rately. Blocking of the frequency protec- contacts and communicated to the 7SJ62
Commissioning via binary inputs. Therefore it is possible
tion can be performed if using a binary
input or by using an undervoltage element. Commissioning could hardly be easier and to detect and indicate both the OPEN and
is fully supported by DIGSI 4. The status of CLOSED position or a fault or intermedi-
Fault locator (ANSI 21FL) the binary inputs can be read individually ate circuit-breaker or auxiliary contact
and the state of the binary outputs can be position.
The integrated fault locator calculates the
set individually. The operation of switch- The switchgear or circuit-breaker can be
fault impedance and the distance-to-fault.
ing elements (circuit-breakers, disconnect
The results are displayed in Ω, kilometers controlled via:
devices) can be checked using the switch- – integrated operator panel
(miles) and in percent of the line length.
ing functions of the bay controller. The an- – binary inputs
Circuit-breaker wear monitoring alog measured values are represented as – substation control and protection system
wide-ranging operational measured values. – DIGSI 4
Methods for determining circuit-breaker To prevent transmission of information to
contact wear or the remaining service life the control center during maintenance, the Automation / user-defined logic
of a circuit-breaker (CB) allow CB mainte- bay controller communications can be dis-
nance intervals to be aligned to their actual abled to prevent unnecessary data from be- With integrated logic, the user can set, via a
degree of wear. The benefit lies in reduced ing transmitted. During commissioning, all graphic interface (CFC), specific functions
maintenance costs. indications with test marking for test pur- for the automation of switchgear or substa-
poses can be connected to a control and tion. Functions are activated via function
There is no mathematically exact method
protection system. keys, binary input or via communication
of calculating the wear or the remaining
interface.
service life of circuit-breakers that takes
into account the arc-chamber's physical Test operation
Switching authority
conditions when the CB opens. This is why During commissioning, all indications can
various methods of determining CB wear be passed to an automatic control system Switching authority is determined accord-
have evolved which reflect the different op- for test purposes. ing to parameters and communication.
erator philosophies. To do justice to these, If a source is set to “LOCAL”, only local
the devices offer several methods: n Control and automatic functions switching operations are possible. The fol-
• I lowing sequence of switching authority is
Control
laid down: “LOCAL”; DIGSI PC program,
• Σ I , with x = 1... 3
x
In addition to the protection functions, the “REMOTE”.
• Σ i 2t SIPROTEC 4 units also support all control
and monitoring functions that are required Command processing
The devices additionally offer a new for operating medium-voltage or high-
method for determining the remaining All the functionality of command process-
voltage substations. ing is offered. This includes the processing
service life:
The main application is reliable control of of single and double commands with or
• Two-point method
switching and other processes. without feedback, sophisticated monitor-
ing of the control hardware and software,
The status of primary equipment or auxil-
1) The 40 to 60, 50 to 70 Hz range is checking of the external process, control
available for fN= 50/60 Hz
iary devices can be obtained from auxiliary
actions using functions such as runtime
Assignment of feedback to command • Voltages VL1, VL2, VL3, VL1L2, VL2L3, VL3L1
5 • Symmetrical components
LSP2077f.eps
The positions of the circuit-breaker or
switching devices and transformer taps are I1, I2, 3I0; V1, V2, V0
acquired by feedback. These indication in- • Power Watts, Vars, VA/P, Q, S
puts are logically assigned to the corre- (P, Q: total and phase selective)
sponding command outputs. The unit can • Power factor (cos ϕ),
therefore distinguish whether the indica- (total and phase selective)
tion change is a consequence of switching
operation or whether it is a spontaneous • Frequency
change of state. • Energy ± kWh, ± kVarh, forward and
reverse power flow
Chatter disable
• Mean as well as minimum and maximum
Chatter disable feature evaluates whether, Fig. 5/86
current and voltage values NXAIR panel (air-insulated)
in a configured period of time, the number
of status changes of indication input ex- • Operating hours counter
ceeds a specified figure. If exceeded, the • Mean operating temperature of overload
indication input is blocked for a certain function
period, so that the event list will not record
• Limit value monitoring
excessive operations.
Limit values are monitored using pro-
grammable logic in the CFC. Commands
Indication filtering and delay
can be derived from this limit value indi-
Binary indications can be filtered or de- cation.
layed.
• Zero suppression
Filtering serves to suppress brief changes in In a certain range of very low measured
potential at the indication input. The indi- values, the value is set to zero to suppress
cation is passed on only if the indication interference.
voltage is still present after a set period of
time. In the event of indication delay, there Metered values
is a wait for a preset time. The information For internal metering, the unit can calcu-
is passed on only if the indication voltage is late an energy metered value from the
still present after this time. measured current and voltage values. If an
external meter with a metering pulse out-
Indication derivation
put is available, the SIPROTEC 4 unit can
A further indication (or a command) can obtain and process metering pulses via an
be derived from an existing indication. indication input.
Group indications can also be formed. The
The metered values can be displayed and
volume of information to the system inter-
passed on to a control center as an accu-
face can thus be reduced and restricted to
mulation with reset. A distinction is made
the most important signals.
between forward, reverse, active and reac-
tive energy.
Switchgear cubicles for
high/medium voltage
Serial front interface The IEC 60870-5-103 protocol is an inter- Fig. 5/87
national standard for the transmission of IEC 60870-5-103: Radial fiber-optic connection
There is a serial RS232 interface on the protective data and fault recordings. All
front of all the units. All of the unit’s func- messages from the unit and also control 5
tions can be set on a PC by means of the commands can be transferred by means of
DIGSI 4 protection operation program. published, Siemens-specific extensions to
Commissioning tools and fault analysis are the protocol.
also built into the program and are avail- Redundant solutions are also possible.
able through this interface. Optionally it is possible to read out and
alter individual parameters (only possible
Rear-mounted interfaces1) with the redundant module).
A number of communication modules
suitable for various applications can be fit- PROFIBUS-DP protocol
ted in the rear of the flush-mounting hous- PROFIBUS-DP is the most widespread
ing. In the flush-mounting housing, the protocol in industrial automation. Via
modules can be easily replaced by the user. PROFIBUS-DP, SIPROTEC units make
The interface modules support the follow- their information available to a SIMATIC
ing applications: controller or, in the control direction, re-
• Time synchronization interface ceive commands from a central SIMATIC.
All units feature a permanently integrated Measured values can also be transferred.
electrical time synchronization interface.
MODBUS RTU protocol Fig. 5/88
It can be used to feed timing telegrams in Bus structure for station bus with Ethernet and
IRIG-B or DCF77 format into the units This uncomplicated, serial protocol is IEC 61850, fiber-optic ring
via time synchronization receivers. mainly used in industry and by power sup-
• System interface ply corporations, and is supported by a
Communication with a central control number of unit manufacturers. SIPROTEC
system takes place through this interface. units function as MODBUS slaves, making
Radial or ring type station bus topologies their information available to a master or
can be configured depending on the cho- receiving information from it. A time-
sen interface. Furthermore, the units can stamped event list is available.
exchange data through this interface via
Ethernet and IEC 61850 protocol and can
also be operated by DIGSI.
• Service interface
The service interface was conceived for re-
mote access to a number of protection
units via DIGSI. On all units, it can be an
electrical RS232/RS485 or an optical inter-
face. For special applications, a maximum
of two temperature monitoring boxes
(RTD-box) can be connected to this inter-
face as an alternative.
Communication
Typical connections
n Connection of current
and voltage transformers
Standard connection
For earthed networks, the earth current is
obtained from the phase currents by the
residual current circuit.
Fig. 5/91
Residual current
circuit without
directional element
5
Fig. 5/92
Sensitive earth-
current detection
without directional
element
Fig. 5/93
Residual current
circuit with
directional element
Typical connections
Fig. 5/94
Sensitive directional
earth-fault detection
with directional
element for phases
5
Connection for isolated-neutral
or compensated networks only
If directional earth-fault protection is not
used, the connection can be made with
only two phase current transformers.
Directional phase short-circuit protection
can be achieved by using only two primary
transformers.
Fig. 5/95
Isolated-neutral or
compensated
networks
Fig. 5/96
Measuring of the
busbar voltage and
the outgoing feeder
voltage for the
synchro-check
Typical applications
n Connection of circuit-breaker
Undervoltage releases
Undervoltage releases are used for auto-
matic tripping of high-voltage motors.
Example:
DC supply voltage of control system fails
and manual electric tripping is no longer
possible.
Automatic tripping takes place when volt-
age across the coil drops below the trip
limit. In Fig. 5/97, tripping occurs due to
failure of DC supply voltage, by automatic
opening of the live status contact upon Fig. 5/97 Undervoltage release with make contact (50, 51)
failure of the protection unit or by short-
circuiting the trip coil in event of network
fault.
Fig. 5/98 Undervoltage trip with locking contact (trip signal 50 is inverted)
Typical applications
Technical data
Technical data
EMC tests for interference immunity; type tests (cont'd) During transportation
High-energy surge voltages Standards IEC 60255-21 and IEC 60068-2
(Surge) Vibration Sinusoidal
IEC 61000-4-5; class III IEC 60255-21-1, class 2 5 to 8 Hz: ± 7.5 mm amplitude;
Auxiliary voltage From circuit to circuit: 2 kV; 12 Ω; 9 µF IEC 60068-2-6 8 to 150 Hz; 2 g acceleration,
across contacts: 1 kV; 2 Ω ;18 µF frequency sweep 1 octave/min
Binary inputs/outputs From circuit to circuit: 2 kV; 42 Ω; 0.5 µF 20 cycles in 3 perpendicular axes
across contacts: 1 kV; 42 Ω; 0.5 µF Shock Semi-sinusoidal
Line-conducted HF, 10 V; 150 kHz to 80 MHz; IEC 60255-21-2, Class 1 Acceleration 15 g, duration 11 ms
amplitude-modulated AM 80 %; 1 kHz IEC 60068-2-27 3 shocks in both directions of 3 axes
IEC 61000-4-6, class III Continuous shock Semi-sinusoidal
Power frequency magnetic field 30 A/m; 50 Hz, continuous IEC 60255-21-2, class 1 Acceleration 10 g, duration 16 ms
IEC 61000-4-8, class IV 300 A/m; 50 Hz, 3 s IEC 60068-2-29 1000 shocks in both directions
IEC 60255-6 0.5 mT, 50 Hz of 3 axes
Oscillatory surge withstand 2.5 to 3 kV (peak value), 1 to 1.5 MHz
capability damped wave; 50 surges per s; Climatic stress tests
ANSI/IEEE C37.90.1 duration 2 s, Ri = 150 to 200 Ω
5 Fast transient surge withstand 4 to 5 kV; 10/150 ns; 50 surges per s
Temperatures
Type-tested acc. to IEC 60068-2-1 -25 °C to +85 °C /-13 °F to +185 °F
capability ANSI/IEEE C37.90.1 both polarities; duration 2 s, Ri = 80 Ω
and -2, test Bd, for 16 h
Radiated electromagnetic 35 V/m; 25 to 1000 MHz;
interference amplitude and pulse-modulated Temporarily permissible operating -20 °C to +70 °C /-4 °F to -158 °F
ANSI/IEEE C37.90.2 temperature, tested for 96 h
Damped wave 2.5 kV (peak value, polarity Recommended permanent operat- -5 °C to +55 °C /+25 °F to +131 °F
IEC 60694 / IEC 61000-4-12 alternating) ing temperature acc. to IEC 60255-6
100 kHz, 1 MHz, 10 and 50 MHz, (Legibility of display may be
Ri = 200 Ω impaired above +55 °C /+131 °F)
– Limiting temperature during -25 °C to +55 °C /-13 °F to +131 °F
EMC tests for interference emission; type tests permanent storage
Standard EN 50081-* (generic specification) – Limiting temperature during -25 °C to +70 °C /-13 °F to +158 °F
Conducted interferences 150 kHz to 30 MHz transport
only auxiliary voltage IEC/CISPR 22 Limit class B Humidity
Radio interference field strength 30 to 1000 MHz Permissible humidity Annual average 75 % relative
IEC/CISPR 11 Limit class B It is recommended to arrange the humidity; on 56 days a year up to
Units with a detached operator units in such a way that they are not 95 % relative humidity; condensation
panel must be installed in a metal exposed to direct sunlight or not permissible!
cubicle to maintain limit class B pronounced temperature changes
that could cause condensation.
Unit design
Mechanical stress tests
Housing 7XP20
Vibration, shock stress and seismic vibration
Dimensions See dimension drawings, part 15
During operation
Weight
Standards IEC 60255-21 and IEC 60068-2 Surface-mounting housing 4.5 kg
Vibration Sinusoidal Flush-mounting housing 4.0 kg
IEC 60255-21-1, class 2 10 to 60 Hz; +/- 0.075 mm amplitude; Degree of protection
IEC 60068-2-6 60 to 150 Hz; 1 g acceleration acc. to EN 60529
frequency sweep 1 octave/min Surface-mounting housing IP 51
20 cycles in 3 perpendicular axes Flush-mounting housing Front: IP 51, rear: IP 20;
Shock Semi-sinusoidal Operator safety IP 2x with cover
IEC 60255-21-2, class 1 Acceleration 5 g, duration 11 ms;
IEC 60068-2-27 3 shocks in both directions of 3 axes
Seismic vibration Sinusoidal
IEC 60255-21-3, class 1 1 to 8 Hz: ± 3.5 mm amplitude
IEC 60068-3-3 (horizontal axis)
1 to 8 Hz: ± 1.5 mm amplitude
(vertical axis)
8 to 35 Hz: 1 g acceleration
(horizontal axis)
8 to 35 Hz: 0.5 g acceleration
(vertical axis)
Frequency sweep 1 octave/min
1 cycle in 3 perpendicular axes
Technical data
Isolated interface for data transfer Port C: DIGSI 4/modem/RTD-box Connection Two RJ45 connectors
For flush-mounting housing/ mounting location "B"
Transmission rate Factory setting 38400 baud,
surface-mounting housing with
min. 4800 baud, max. 115200 baud
detached operator panel
RS232/RS485
Distance Max. 20 m / 65.6 ft
Connection Test voltage 500 V AC against earth
For flush-mounting housing/ 9-pin subminiature connector,
surface-mounting housing with mounting location “C” Ethernet, optical
detached operator panel Connection Intergr. LC connector for FO
For surface-mounting housing At the bottom part of the housing:
with two-tier terminal at the shielded data cable For flush-mounting housing/
connection
Mounting location "B" 5
top/bottom part surface-mounting housing with
Distance RS232 15 m /49.2 ft detached operator panel
Distance RS485 Max. 1 km/3300 ft Optical wavelength 1300 nmm
Distance 1.5 km/0.9 miles
Test voltage 500 V AC against earth
PROFIBUS-FMS/DP
System interface (rear of unit)
Isolated interface for data transfer Port B
IEC 60870-5-103 protocol to a control center
Isolated interface for data transfer Port B Transmission rate Up to 1.5 Mbaud
to a control center
RS485
Transmission rate Factory setting 9600 baud,
min. 1200 baud, max. 115200 baud Connection
RS232/RS485 For flush-mounting housing/ 9-pin subminiature connector,
surface-mounting housing with mounting location “B”
Connection detached operator panel
For flush-mounting housing/ Mounting location “B” For surface-mounting housing At the bottom part of the housing:
surface-mounting housing with with two-tier terminal on the shielded data cable
detached operator panel top/bottom part
For surface-mounting housing At the bottom part of the housing: Distance 1000 m/3300 ft ≤ 93.75 kbaud;
with two-tier terminal on the shielded data cable 500 m/1500 ft ≤ 187.5 kbaud;
top/bottom part 200 m/600 ft ≤ 1.5 Mbaud;
Distance RS232 Max. 15 m/49 ft 100 m/300 ft ≤ 12 Mbaud
Distance RS485 Max. 1 km/3300 ft Test voltage 500 V AC against earth
Test voltage 500 V AC against earth Fiber optic
Fiber optic Connection fiber-optic cable Integr. ST connector for FO
Connection fiber-optic cable Integrated ST connector for fiber- connection
optic connection For flush-mounting housing/ Mounting location “B”
For flush-mounting housing/ Mounting location “B” surface-mounting housing with
surface-mounting housing with detached operator panel
detached operator panel For surface-mounting housing At the bottom part of the housing
For surface-mounting housing At the bottom part of the housing with two-tier terminal on the Important: Please refer to footnotes
1)
with two-tier terminal on the top/bottom part and 2) on page 5/136
top/bottom part Optical wavelength 820 nm
Optical wavelength 820 nm Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
Distance 500 kB/s 1.6 km/0.99 miles
Distance Max. 1.5 km/0.9 miles 1500 kB/s 530 m/0.33 miles
IEC 60870-5-103 protocol, redundant MODBUS RTU, ASCII, DNP 3.0
RS485
Isolated interface for data transfer Port B
Connection to a control center
For flush-mounting housing/ Mounting location “B”
Transmission rate Up to 19200 baud
surface-mounting housing with
detached operator panel
For surface-mounting housing (not available)
with two-tier terminal on the
top/bottom part
Distance RS485 Max. 1 km/3300 ft
Test voltage 500 V AC against earth
Technical data
Permissible path attenuation Max 8 dB. for glass fiber 62.5/125 µm Dropout setting
Without disk emulation Approx. 1.05 · setting value Ip for
Distance Max. 1.5 km/0.9 miles Ip/Inom ≥ 0.3, corresponds to approx.
Time synchronization DCF77/IRIG-B signal (Format IRIG-B000) 0.95 · pickup threshold
With disk emulation Approx. 0.90 · setting value Ip
Connection 9-pin subminiature connector
(SUB-D) Tolerances
(terminal with surface-mounting Pickup/dropout thresholds Ip, IEp 2 % of setting value or 50 mA1)
housing) Pickup time for 2 ≤ I/Ip ≤ 20 5 % of reference (calculated) value
+ 2 % current tolerance, respectively
Voltage levels 5 V, 12 V or 24 V (optional)
30 ms
Dropout ratio for 0.05 ≤ I/Ip 5 % of reference (calculated) value
Functions ≤ 0.9 + 2 % current tolerance, respectively
30 ms
Definite-time overcurrent protection, directional/non-directional
(ANSI 50, 50N, 67, 67N) Direction detection
Operating mode non-directional 3-phase (standard) or 2-phase For phase faults
phase protection (ANSI 50) (L1 and L3) Polarization With cross-polarized voltages;
Number of elements (stages) I>, I>>, I>>> (phases) With voltage memory for measure-
IE>, IE>>, IE>>> (earth) ment voltages that are too low
Setting ranges Forward range Vref,rot ± 86°
Rotation of reference voltage Vref,rot - 180° to 180° (in steps of 1°)
Pickup phase elements 1)
0.5 to 175 A or ∞ (in steps of 0.01 A)
Pickup earth elements 0.25 to 175 A or ∞1) (in steps of 0.01 A) Direction sensitivity For one and two-phase faults
unlimited;
Delay times T 0 to 60 s or ∞ (in steps of 0.01 s) For three-phase faults dynamically
Dropout delay time TDO 0 to 60 s (in steps of 0.01 s) unlimited;
Times Steady-state approx. 7 V
Pickup times (without inrush phase-to-phase
restraint, with inrush restraint For earth faults
+ 10 ms)
Polarization With zero-sequence quantities 3V0, 3I0
Non-directional Directional or with negative-sequence quantities
With twice the setting value Approx. 30 ms 45 ms 3V2, 3I2
With five times the setting value Approx. 20 ms 40 ms
Forward range Vref,rot ± 86°
Dropout times Approx. 40 ms
Rotation of reference voltage Vref,rot - 180° to 180° (in steps of 1°)
Dropout ratio Approx. 0.95 for
Direction sensitivity
I/Inom ≥ 0.3
Zero-sequence quantities 3V0, 3I0 VE ≈ 2.5 V displacement voltage,
Tolerances measured;
Pickup 2 % of setting value or 50 mA1) 3V0 ≈ 5 V displacement voltage,
Delay times T, TDO 1 % or 10 ms calculated
Negative-sequence quantities 3V2 ≈ 5 V negative-sequence voltage;
3V2, 3I2 3I2 ≈ 225 mA negative-sequence cur-
rent1)
Tolerances (phase angle error under
reference conditions)
1) At Inom = 1 A, all limits divided by 5. For phase and earth faults ± 3 ° electrical
Technical data
Note: Due to the high sensitivity the linear range of the measuring input IN
with integrated sensitive input transformer is from 0.001 A to 1.6 A. For cur-
1) For Inom = 1 A, all limits divided by 5. rents greater than 1.6 A, correct directionality can no longer be guaranteed.
Technical data
Technical data
Delay time 0.06 to 60 s or ∞ (in steps of 0.01 s) Voltage difference (V2 – V1) InkVprimary,inVsecondaryorin%Vnom
Range 10 to 120 % Vnom
Times Tolerance*) ≤1 % of measured value or 0.5 % of Vnom
Pickup times
with internal start is contained in the delay time Frequency difference (f2 – f1) In mHz
with external start is contained in the delay time Range fN ± 5 Hz
Dropout times Approx. 25 ms Tolerance*) 20 mHz
Synchro- and voltage check (ANSI 25) Flexible protection functions (ANSI 27, 32, 47, 50, 55, 59, 81R)
Operating mode • Synchro-check Operating modes / measuring
Additional release conditions • Live-bus / dead line quantities
• Dead-bus / live-line 3-phase I, I1, I2, I2/I1, 3I0, V, V1, V2, 3V0, dV/dt, P,
• Dead-bus and dead-line 1-phase Q, cos ϕ I, IE, IE sens., V, VE, P, Q, cos ϕ
• Bypassing Without fixed phase relation f, df/dt, binary input 5
Pickup when Exceeding or falling below threshold
Voltages value
Max. operating voltage Vmax 20 to 140 V (phase-to-phase) Setting ranges
(in steps of 1 V) Current I, I1, I2, 3I0, IE 0.15 to 200 A1) (in steps of 0.01 A)
Min. operating voltage Vmin 20 to 125 V (phase-to-phase) Current ratio I2/I1 15 to 100 % (in steps of 1 %)
(in steps of 1 V) Sens. earth curr. IE sens. 0.001 to 1.5 A (in steps of 0.001 A)
V< for dead-line / dead-bus check 1 to 60 V (phase-to-phase) Voltages V, V1, V2, 3V0 2 to 260 V (in steps of 0.1 V)
(in steps of 1 V) Displacement voltage VE 2 to 200 V (in steps of 0.1 V)
V> for live-line / live-bus check 20 to 140 V (phase-to-phase) Power P, Q 0.5 to 10000 W (in steps of 0.1 W)
(in steps of 1 V) Power factor (cos ϕ) - 0.99 to + 0.99 (in steps of 0.01)
Primary rated voltage of 0.1 to 800 kV (in steps of 0.01 kV) Frequency fN = 50 Hz 40 to 60 Hz (in steps of 0.01 Hz)
transformer V2nom fN = 60 Hz 50 to 70 Hz (in steps of 0.01 Hz)
Tolerances 2 % of pickup value or 2 V Rate-of-frequency change df/dt 0.1 to 20 Hz/s (in steps of 0.01 Hz/s)
Drop-off to pickup ratios approx. 0.9 (V>) or 1.1 (V<) Voltage change dV/dt 4 V/s to 100 V/s (in steps of 1 V/s)
ΔV-measurement Dropout ratio >- stage 1.01 to 3 (insteps of 0.01)
Voltage difference 0.5 to 50 V (phase-to-phase) Dropout ratio <- stage 0.7 to 0.99 (in steps of 0.01)
(in steps of 1 V) Dropout differential f 0.02 to 1.00 Hz (in steps of 0.01 Hz)
Tolerance 1V Pickup delay time 0 to 60 s (in steps of 0.01 s)
Trip delay time 0 to 3600 s (in steps of 0.01 s)
Δf-measurement Dropout delay time 0 to 60 s (in steps of 0.01 s)
Δf-measurement (f2>f1; f2<f1) 0.01 to 2 Hz (in steps of 0.01 Hz)
Tolerance 15 mHz Times
Pickup times
Δα-measurement Current, voltage
Δα-measurement 2 ° to 80 ° (in steps of 1 °) (phase quantities)
(α2>α1; α2>α1) With 2 times the setting value Approx. 30 ms
Tolerance 2° With 10 times the setting value Approx. 20 ms
Max. phase displacement 5 ° for Δf ≤ 1 Hz Current, voltages
10 ° for Δf > 1 Hz (symmetrical components)
Adaptation With 2 times the setting value Approx. 40 ms
Vector group adaptation by angle 0 ° to 360 ° (in steps of 1 °) With 10 times the setting value Approx. 30 ms
Different voltage 0.5 to 2 (in steps of 0.01) Power
transformers V1/V2 Typical Approx. 120 ms
Maximum (low signals and Approx. 350 ms
Times
thresholds)
Minimum measuring time Approx. 80 ms
Power factor 300 to 600 ms
Max. duration TSYN DURATION 0.01 to 1200 s; ∞ (in steps of 0.01 s)
Frequency Approx. 100 ms
Supervision time TSUP VOLTAGE 0 to 60 s (in steps of 0.01 s)
Rate-of-frequency change
Closing time of CB TCB close 0 to 60 s (in steps of 0.01 s)
With 1.25 times the setting value Approx. 220 ms
Tolerance of all timers 1 % of setting value or 10 ms
Voltage change dV/dt
For 2 times pickup value Approx. 220 ms
Measuring values of synchro-check function
Binary input Approx. 20 ms
Reference voltage V1 In kV primary, in V secondary or in % Vnom
Range 10 to 120 % Vnom
Tolerance*) ≤1 % of measured value or 0.5 % of Vnom
Voltage to be synchronized V2 InkVprimary,inVsecondaryorin%Vnom
Range 10to120%Vnom
Tolerance*) ≤1 % of measured value or 0.5 % of Vnom
*) With rated frequency.
1) At Inom = 1 A, all limits divided by 5.
Technical data
Flexible protection functions (ANSI 27, 32, 47, 50, 55, 59, 81R) (cont'd) Starting time monitoring for motors (ANSI 48)
Dropout times Setting ranges
Current, voltage (phase < 20 ms Motor starting current ISTARTUP 2.5 to 80 A1) (in steps of 0.01)
quantities) Pickup threshold IMOTOR START 2 to 50 A1) (in steps of 0.01)
Current, voltages (symmetrical < 30 ms Permissible starting 1 to 180 s (in steps of 0.1 s)
components) time TSTARTUP, cold motor
Power Permissible starting time 0.5 to 180 s (in steps of 0.1 s)
Typical < 50 ms TSTARTUP, warm motor
Maximum < 350 ms Temperature threshold 0 to 80 % (in steps of 1 %)
Power factor < 300 ms cold motor
Frequency < 100 ms Permissible blocked rotor 0.5 to 120 s or ∞ (in steps of 0.1 s)
Rate-of-frequency change < 200 ms time TLOCKED-ROTOR
Voltage change < 220 ms Tripping time characteristic 2
t = ⎛⎜
Binary input < 10 ms I STARTUP ⎞
For I > IMOTOR START ⎟ ⋅ TSTARTUP
Tolerances ⎝ I ⎠
Pickup threshold ISTARTUP = Rated motor starting
Current 0.5 % of setting value or 50 mA1) current
Current (symmetrical 1 % of setting value or 100 mA1) I = Actual current flowing
5
components) TSTARTUP = Tripping time for rated
Voltage 0.5 % of setting value or 0.1 V motor starting current
Voltage (symmetrical 1 % of setting value or 0.2 V t = Tripping time in seconds
components)
Power 1 % of setting value or 0.3 W Dropout ratio IMOTOR START Approx. 0.95
Power factor 2 degrees Tolerances
Frequency 5 mHz (at V = VN, f = fN) Pickup threshold 2 % of setting value or 50 mA1)
10 mHz (at V = VN) Delay time 5 % or 30 ms
Rate-of-frequency change 5 % of setting value or 0.05 Hz/s
Voltage change dV/dt 5 % of setting value or 1.5 V/s Load jam protection for motors (ANSI 51M)
Times 1 % of setting value or 10 ms Setting ranges
Negative-sequence current detection (ANSI 46) Current threshold for 0.25 to 60 A1) (in steps 0.01 A)
alarm and trip
Definite-time characteristic (ANSI 46-1 and 46-2) Delay times 0 to 600 s (in steps 0.01 s)
Setting ranges Blocking duration after 0 to 600 s (in steps 0.01 s)
Pickup current I2>, I2>> 0.5 to 15 A or ∞ (in steps of 0.01 A) CLOSE signal detection
Delay times 0 to 60 s or ∞ (in steps of 0.01 s) Tolerances
Dropout delay time TDO 0 to 60 s (in steps of 0.01 s) Pickup threshold 2 % of setting value or 50 mA1)
Delay time
Functional limit All phase currents ≤ 50 A 1) 1 % of setting value or 10 ms
Times Restart inhibit for motors (ANSI 66)
Pickup times Approx. 35 ms Setting ranges
Dropout times Approx. 35 ms Motor starting current relative 1.1 to 10 (in steps of 0.1)
Dropout ratio Approx. 0.95 for I2 /Inom > 0.3 to rated motor current
Tolerances IMOTOR START/IMotor Nom
Pickup thresholds 3 % of the setting value or 50 mA1) Rated motor current IMotor Nom 1 to 6 A1) (in steps of 0.01 A)
Delay times 1 % or 10 ms Max. permissible starting time 1 to 320 s (in steps of 1 s)
TStart Max
Inverse-time characteristic (ANSI 46-TOC)
Equilibrium time TEqual 0 min to 320 min (in steps of 0.1 min)
Setting ranges Minimum inhibit time 0.2 min to 120 min (in steps of 0.1 min)
Pickup current 0.5 to 10 A1) (in steps of 0.01 A) TMIN. INHIBIT TIME
Time multiplier T 0.05 to 3.2 s or ∞ (in steps of 0.01 s) Max. permissible number of 1 to 4 (in steps of 1)
(IEC characteristics) warm starts
Time multiplier D 0.5 to 15 s or ∞ (in steps of 0.01 s) Difference between cold and 1 to 2 (in steps of 1)
(ANSI characteristics) warm starts
Functional limit All phase currents ≤ 50 A 1) Extension k-factor for cooling 0.2 to 100 (in steps of 0.1)
simulations of rotor at zero
Trip characteristics speed kτ at STOP
IEC Normal inverse, very inverse, Extension factor for cooling time 0.2 to 100 (in steps of 0.1)
extremely inverse constant with motor running
ANSI Inverse, moderately inverse, kτ RUNNING
very inverse, extremely inverse nc − 1
Restarting limit Θ restart = Θ rot max perm ⋅
Pickup threshold Approx. 1.1 · I2p setting value nc
Dropout Θrestart = Temperature limit below
IEC and ANSI Approx. 1.05 · I2p setting value, which restarting is possible
(without disk emulation) which is approx. 0.95 · pickup threshold Θrot max perm = Maximum permissible
ANSI with disk emulation Approx. 0.90 · I2p setting value rotor overtemperature
Tolerances (= 100 % in operational
Pickup threshold 3 % of the setting value or 50 mA1) measured value
Time for 2 ≤ M ≤ 20 5 % of setpoint (calculated) Θrot/Θrot trip)
+2 % current tolerance, at least 30 ms 1) For Inom = 1 A, nc = Number of permissible
all limits divided by 5. start-ups from cold state
Technical data
Technical data
Operational measured values (cont'd) Min./Max. values for voltages VL1-E, VL2-E, VL3-E
Range 0 to 120 % Snom V1 (positive-sequence component)
Tolerance2) 1 % of Snom VL1-L2, VL2-L3, VL3-L1
for V/Vnom and I/Inom = 50 to 120 % Min./Max. values for power S, P, Q, cos ϕ, frequency
and ⏐cos ϕ⏐ = 0.707 to 1 with Min./Max. values for overload Θ/ΘTrip
Snom = 3 ⋅ Vnom ⋅ I nom protection
Q, reactive power With sign, total and phase-segregated Min./Max. values for mean values IL1dmd, IL2dmd, IL3dmd
in kVAr (MVAr or GVAr)primary and I1 (positive-sequence component);
in % Snom Sdmd, Pdmd, Qdmd
Range 0 to 120 % Snom Local measured values monitoring
Tolerance2) 1 % of Snom
for V/Vnom and I/Inom = 50 to 120 % Current asymmetry Imax/Imin > balance factor,
and ⏐sin ϕ⏐ = 0.707 to 1 with for I>Ibalance limit
Snom = 3 ⋅ Vnom ⋅ I nom Voltage asymmetry Vmax/Vmin > balance factor,
cos ϕ, power factor (p.f.) Total and phase segregated for V>Vlim
Range - 1 to + 1 Current phase sequence Clockwise (ABC) / counter-clockwise
Tolerance2) 2 % for ⏐cos ϕ⏐ ≥ 0.707 (ACB)
5 Frequency f In Hz Voltage phase sequence Clockwise (ABC) / counter-clockwise
(ACB)
Range fnom ± 5 Hz
Tolerance2) 20 mHz Limit value monitoring Predefined limit values, user-defined
expansions via CFC
Temperature overload protection In %
Θ/ΘTrip Fuse failure monitor
For all network types With the option of blocking affected
protection functions
Range 0 to 400 %
Tolerance2) 5 % class accuracy per IEC 60255-8 Fault recording
RTD-box See section "Temperature monitoring Battery Lithium battery 3 V/1 Ah,
box" type CR 1/2 AA, message "Battery
Fault" for insufficient battery charge
Long-term averages
Oscillographic fault recording
Time window 5, 15, 30 or 60 minuets
Maximum 8 fault records saved,
Frequency of updates Adjustable memory maintained by buffer bat-
Long-term averages tery in case of loss of power supply
of currents IL1dmd, IL2dmd, IL3dmd, I1dmd in A (kA) Recording time Total 20 s
of real power Pdmd in W (kW, MW) Pre-trigger and post-fault recording
of reactive power Qdmd in VAr (kVAr, MVAr) and memory time adjustable
of apparent power Sdmd in VAr (kVAr, MVAr)
Sampling rate for 50 Hz 1 sample/1.25 ms (16 samples/cycle)
Max. / Min. report Sampling rate for 60 Hz 1 sample/1.04 ms (16 samples/cycle)
Report of measured values With date and time Energy/power
Reset, automatic Time of day adjustable (in minutes, Meter values for power in kWh (MWh or GWh) and kVARh
0 to 1439 min) Wp, Wq (real and reactive power (MVARh or GVARh)
Time frame and starting time adjust- demand)
able (in days, 1 to 365 days, and ∞)
Tolerance1) ≤ 2 % for I > 0.1 Inom, V > 0.1 Vnom
Reset, manual Using binary input, and ⏐cos ϕ⏐ (p.f.) ≥ 0.707
using keypad,
via communication Statistics
Min./Max. values for current IL1, IL2, IL3, Saved number of trips Up to 9 digits
I1 (positive-sequence component) Number of automatic reclosing Up to 9 digits
commands (segregated according
to 1st and ≥ 2nd cycle)
1) At Inom = 1 A, all limits multiplied with 5.
2) At rated frequency.
5/108 Siemens SIP · Edition No. 6
5 Overcurrent Protection / 7SJ62
Technical data
Measuring inputs (3 x V / 4 x V, 4 x I)
Iph = 1 A1), Ie = 1 A1) (min. = 0.05 A)
Position 15 only with A, C, E, G 1
Iph = 1 A1), Ie = sensitive (min. = 0.001 A)
Position 15 only with B, D, F, H 2
Iph = 5 A1), Ie = 5 A1) (min. = 0.25 A)
Position 15 only with A, C, E, G 5
Iph = 5 A1), Ie = sensitive (min. = 0.001 A)
Position 15 only with B, D, F, H 6
5 Iph = 5 A1), Ie = 1 A1) (min. = 0.05 A)
Position 15 only with A, C, E, G 7
Unit version
For panel surface mounting, two-tier terminal top/bottom B
For panel flush mounting, plug-in terminal, (2/3 pin connector) D
For panel flush mounting, screw-type terminal (direct connection/ring-type cable lugs) E
DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows 2000/XP Professional Edition
Basis Full version with license for 10 computers, on CD-ROM
(authorization by serial number) 7XS5400-0AA00
Professional DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00
Professional + IEC 61850
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation)
+ IEC 61850 system configurator 7XS5403-0AA00
SIGRA 4
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers (Comtrade
format). Running under MS Windows 2000 or XP Professional Edition.
(generally contained in DIGSI Professional, but can be ordered additionally)
Authorization by serial number. On CD-ROM. 7XS5410-0AA00
Varistor/Voltage arrester
Voltage arrester for high-impedance REF protection
125 Vrms; 600 A; 1S/S 256 C53207-A401-D76-1
240 Vrms; 600 A; 1S/S 1088 C53207-A401-D77-1
Connecting cable
Cable between PC/notebook (9-pin con.) and protection unit (9-pin connector)
(contained in DIGSI 4, but can be ordered additionally) 7XV5100-4
Cable between temperature monitoring box and SIPROTEC 4 unit
- length 5 m /16.4 ft 7XV5103-7AA05
- length 25 m /82 ft 7XV5103-7AA25
- length 50 m /164 ft 7XV5103-7AA50
LSP2289-afp.eps
Terminal safety cover
Voltage/current terminal 18-pole/12-pole C73334-A1-C31-1 1 Siemens
Voltage/current terminal 12-pole/8-pole C73334-A1-C32-1 1 Siemens
Connector 2-pin C73334-A1-C35-1 1 Siemens
Mounting rail
Connector 3-pin C73334-A1-C36-1 1 Siemens
1)
Crimp connector CI2 0.5 to 1 mm2 0-827039-1 4000 AMP
taped on reel
LSP2091-afp.eps
LSP2090-afp.eps
2 1)
Crimp connector CI2 0.5 to 1 mm 0-827396-1 1 AMP
LSP2092-afp.eps
1)
5 and matching female 1-734387-1 1 AMP
Short-circuit links
for current terminals C73334-A1-C33-1 1 Siemens
for other terminals C73334-A1-C34-1 1 Siemens
Short-circuit links Short-circuit links
for current termi- for other terminals Mounting rail for 19" rack C73165-A63-D200-1 1 Siemens
nals
Connection diagram
Connection diagram
Connection diagram
Connection diagram