5 Overcurrent Protection / 7SJ62

SIPROTEC 4 7SJ62
Multifunction Protection Relay
Function overview

Protection functions
• Time-overcurrent protection
• Directional time-overcurrent protection
• Sensitive dir. earth-fault detection
• Displacement voltage
• Intermittent earth-fault protection
• High-impedance restricted earth fault
• Inrush restraint
• Motor protection
LSP2299-afpen.eps

SIPV6_116.eps
– Undercurrent monitoring
– Starting time supervision
– Restart inhibit
– Locked rotor
– Load jam protection
• Overload protection 5
• Temperature monitoring
Fig. 5/75 SIPROTEC 4 7SJ62 multifunction protection relay • Under-/overvoltage protection
with text (left) and graphic display • Under-/overfrequency protection
• Breaker failure protection
• Negative-sequence protection
• Phase-sequence monitoring
Description • Synchro-check
• Fault locator
The SIPROTEC 4 7SJ62 relays can be used • Lockout
for line protection of high and medium
• Auto-reclosure
voltage networks with earthed (grounded),
low-resistance earthed, isolated or com- Control functions/programmable logic
pensated neutral point. With regard to • Commands f. ctrl of CB and of isolators
motor protection, the SIPROTEC 4 7SJ62 • Position of switching elements is shown
is suitable for asynchronous machines of on the graphic display
all sizes. The relay performs all functions • Control via keyboard, binary inputs,
of backup protection supplementary to DIGSI 4 or SCADA system
transformer differential protection. • User-defined logic with CFC
7SJ62 is featuring the "flexible protection (e.g. interlocking)
functions". Up to 20 protection functions Monitoring functions
can be added according to individual • Operational measured values V, I, f
requirements. Thus, for example, a rate- • Energy metering values Wp, Wq
of-frequency-change protection or reverse • Circuit-breaker wear monitoring
power protection can be implemented.
• Slave pointer
The relay provides control of the circuit- • Trip circuit supervision
breaker, further switching devices and • Fuse failure monitor
automation functions. The integrated • 8 oscillographic fault records
programmable logic (CFC) allows the • Motor statistics
user to implement their own functions,
Communication interfaces
e. g. for the automation of switchgear
(interlocking). The user is also allowed • System interface
to generate user-defined messages. – IEC 60870-5-103/ IEC 61850
– PROFIBUS-FMS/-DP
The flexible communication interfaces
– DNP 3.0/MODBUS RTU
are open for modern communication
• Service interface for DIGSI 4 (modem)
architectures with control systems.
• Front interface for DIGSI 4
• Time synchronization via IRIG B/DCF77
Hardware
• 4 current transformers
• 3/4 voltage transformers
• 8/11 binary inputs
• 8/6 output relays

Siemens SIP · Edition No. 6 5/83


5 Overcurrent Protection / 7SJ62

Application

Fig. 5/76 Function diagram

The SIPROTEC 4 7SJ62 unit is a numerical Line protection Backup protection


protection relay that also performs control The 7SJ62 units can be used for line pro- The 7SJ62can be used universally for
and monitoring functions and therefore tection of high and medium-voltage net- backup protection.
supports the user in cost-effective power works with earthed (grounded), low-
system management, and ensures reliable resistance earthed, isolated or compensated Flexible protection functions
supply of electric power to the customers. neutral point.
Local operation has been designed accord- By configuring a connection between a
ing to ergonomic criteria. A large, easy-to- standard protection logic and any mea-
Synchro-check sured or derived quantity, the functional
read display was a major design aim.
In order to connect two components of a scope of the relays can be easily expanded
Control power system, the relay provides a synchro- by up to 20 protection stages or protection
check function which verifies that switching functions.
The integrated control function permits ON does not endanger the stability of the
control of disconnect devices, earthing power system. Metering values
switches or circuit-breakers via the inte-
grated operator panel, binary inputs, Extensive measured values, limit values
Motor protection and metered values permit improved
DIGSI 4 or the control and protection
system (e.g. SICAM). The present status When protecting motors, the 7SJ62 relay is system management.
(or position) of the primary equipment suitable for asynchronous machines of all
can be displayed, in case of devices with sizes.
graphic display. A full range of command
processing functions is provided. Transformer protection
The relay performs all functions of backup
Programmable logic protection supplementary to transformer
The integrated logic characteristics (CFC) differential protection. The inrush sup-
allow the user to implement their own pression effectively prevents tripping by
functions for automation of switchgear inrush currents.
(interlocking) or a substation via a graphic The high-impedance restricted earth-fault
user interface. The user can also generate protection detects short-circuits and insu-
user-defined messages. lation faults on the transformer.

5/84 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Application

ANSI No. IEC Protection functions

50, 50N I>, I>>, I>>>, IE>, IE>>, IE>>> Definite time-overcurrent protection (phase/neutral)

51, 51V, 51N Ip, IEp Inverse time-overcurrent protection (phase/neutral), phase function with voltage-dependent option

67, 67N Idir>, Idir>>, Ip dir Directional time-overcurrent protection (definite/inverse, phase/neutral),
IEdir>, IEdir>>, IEp dir Directional comparison protection

67Ns/50Ns IEE>, IEE>>, IEEp Directional/non-directional sensitive earth-fault detection

– Cold load pick-up (dynamic setting change)

59N/64 VE, V0> Displacement voltage, zero-sequence voltage

– IIE> Intermittent earth fault

87N High-impedance restricted earth-fault protection

50BF Breaker failure protection 5


79 Auto-reclosure

25 Synchro-check

46 I2> Phase-balance current protection (negative-sequence protection)

47 V2>, phase-sequence Unbalance-voltage protection and/or phase-sequence monitoring

49 ϑ> Thermal overload protection

48 Starting time supervision

51M Load jam protection

14 Locked rotor protection

66/86 Restart inhibit

37 I< Undercurrent monitoring

38 Temperature monitoring via external device (RTD-box), e.g. bearing temperature monitoring

27, 59 V<, V> Undervoltage/overvoltage protection

59R dV/dt Rate-of-voltage-change protection

32 P<>, Q<> Reverse-power, forward-power protection

55 cos ϕ Power factor protection

81O/U f>, f< Overfrequency/underfrequency protection

81R df/dt Rate-of-frequency-change protection

21FL Fault locator

Siemens SIP · Edition No. 6 5/85


5 Overcurrent Protection / 7SJ62

Construction

Connection techniques and


housing with many advantages
1/3-rack size (text display variants) and
1/2-rack size (graphic display variants) are
the available housing widths of the 7SJ62 re-
lays, referred to a 19" module frame system.
This means that previous models can always
be replaced. The height is a uniform 244 mm
for flush-mounting housings and 266 mm

LSP2099-afpen.eps
for surface-mounting housing. All cables can
be connected with or without ring lugs.
In the case of surface mounting on a panel,
the connection terminals are located above
and below in the form of screw-type termi-
nals. The communication interfaces are
located in a sloped case at the top and
5 bottom of the housing. Fig. 5/79 Rear view with screw-type terminals, 1/3-rack size

Protection functions

Time-overcurrent protection
(ANSI 50, 50N, 51, 51V, 51N)
This function is based on the phase-
selective measurement of the three phase
currents and the earth current (four trans-
formers). Three definite-time overcurrent
protection elements (DMT) exist both for
the phases and for the earth. The current
threshold and the delay time can be set
within a wide range. In addition, inverse-
time overcurrent protection characteristics
(IDMTL) can be activated.
The inverse-time function provides – as
an option – voltage-restraint or voltage-
controlled operating modes.
Fig. 5/77 Fig. 5/78
Definite-time overcurrent protection Inverse-time overcurrent protection
Available inverse-time characteristics User-definable characteristics
Characteristics acc. to ANSI/IEEE IEC 60255-3 Instead of the predefined time characteris-
Inverse • • tics according to ANSI, tripping character-
istics can be defined by the user for phase
Short inverse • and earth units separately. Up to 20 cur-
rent/time value pairs may be programmed.
Long inverse • • They are set as pairs of numbers or graphi-
Moderately inverse • cally in DIGSI 4.
Very inverse • • Inrush restraint
Extremely inverse • • The relay features second harmonic re-
straint. If the second harmonic is detected
during transformer energization, pickup of
Reset characteristics non-directional and directional normal el-
ements are blocked.
For easier time coordination with emulation), a reset process is initiated after
electromechanical relays, reset characte- the fault current has disappeared. This
Cold load pickup/dynamic setting change
ristics according to ANSI C37.112 and reset process corresponds to the reverse
IEC 60255-3 /BS 142 standards are applied. movement of the Ferraris disk of an elec- For directional and non-directional time-
When using the reset characteristic (disk tromechanical relay (thus: disk emulation). overcurrent protection functions the initia-
tion thresholds and tripping times can be
switched via binary inputs or by time control.
5/86 Siemens SIP · Edition No. 6
5 Overcurrent Protection / 7SJ62

Protection functions

Directional time-overcurrent protection


(ANSI 67, 67N)
Directional phase and earth protection are
separate functions. They operate in parallel
to the non-directional overcurrent ele-
ments. Their pickup values and delay times
can be set separately. Definite-time and in-
verse-time characteristics are offered. The
tripping characteristic can be rotated about
± 180 degrees. Fig. 5/80
By means of voltage memory, Directional characteristic of
the directional
directionality can be determined reliably time-overcurrent
even for close-in (local) faults. If the protection
switching device closes onto a fault and the
voltage is too low to determine direction,
directionality (directional decision) is
made with voltage from the voltage mem- 5
ory. If no voltage exists in the memory,
tripping occurs according to the coordina-
tion schedule.
For earth protection, users can choose
whether the direction is to be determined
via zero-sequence system or negative-se-
quence system quantities (selectable).
Using negative-sequence variables can be
advantageous in cases where the zero volt-
age tends to be very low due to unfavorable
zero-sequence impedances.

Directional comparison protection


(cross-coupling)
It is used for selective protection of Fig. 5/81
sections fed from two sources with instan- Directional determination
taneous tripping, i.e. without the disad- using cosine measurements
vantage of time coordination. The direc- for compensated networks
tional comparison protection is suitable
if the distances between the protection
stations are not significant and pilot wires For networks with an isolated neutral, the • Each element can be set in forward,
are available for signal transmission. In reactive current component is evaluated; reverse, or non-directional.
addition to the directional comparison for compensated networks, the active cur- • The function can also be operated in the
protection, the directional coordinated rent component or residual resistive cur- insensitive mode as an additional
time-overcurrent protection is used for rent is evaluated. For special network short-circuit protection.
complete selective backup protection. If conditions, e.g. high-resistance earthed
operated in a closed-circuit connection, networks with ohmic-capacitive earth-fault (Sensitive) earth-fault detection
an interruption of the transmission line is current or low-resistance earthed networks (ANSI 50Ns, 51Ns / 50N, 51N)
detected. with ohmic-inductive current, the tripping
characteristics can be rotated approxi- For high-resistance earthed networks, a
(Sensitive) directional earth-fault detection mately ± 45 degrees. sensitive input transformer is connected
(ANSI 64, 67Ns, 67N) to a phase-balance neutral current trans-
Two modes of earth-fault direction detec- former (also called core-balance CT).
For isolated-neutral and compensated net- tion can be implemented: tripping or
works, the direction of power flow in the “signalling only mode”. The function can also be operated in the
zero sequence is calculated from the zero- insensitive mode as an additional short-
sequence current I0 and zero-sequence It has the following functions: circuit protection.
voltage V0. • TRIP via the displacement voltage VE.
• Two instantaneous elements or one
instantaneous plus one user-defined
characteristic.

Siemens SIP · Edition No. 6 5/87


5 Overcurrent Protection / 7SJ62

Protection functions High-impedance restricted earth-fault


protection (ANSI 87N)
Intermittent earth-fault protection The high-impedance measurement princi-
Intermittent (re-striking) faults occur due ple is an uncomplicated and sensitive
to insulation weaknesses in cables or as a method for detecting earth faults, espe-
result of water penetrating cable joints. cially on transformers. It can also be ap-
Such faults either simply cease at some plied to motors, generators and reactors
stage or develop into lasting short-circuits. when these are operated on an earthed
During intermittent activity, however, network.
star-point resistors in networks that are When the high-impedance measurement
impedance-earthed may undergo thermal principle is applied, all current transform-
overloading. The normal earth-fault pro- ers in the protected area are connected in
tection cannot reliably detect and interrupt parallel and operated on one common re-
the current pulses, some of which can be sistor of relatively high R whose voltage is
very brief. measured (see Fig. 5/82). In the case of
The selectivity required with intermittent 7SJ6 units, the voltage is measured by de-
earth faults is achieved by summating the tecting the current through the (external)
duration of the individual pulses and by resistor R at the sensitive current measure-
5 triggering when a (settable) summed time ment input IEE. The varistor V serves to Fig. 5/82 High-impedance restricted
earth-fault protection
is reached. The response threshold IIE> limit the voltage in the event of an internal
evaluates the r.m.s. value, referred to one fault. It cuts off the high momentary volt-
systems period. age spikes occurring at transformer satura-
tion. At the same time, this results in
Phase-balance current protection (ANSI 46) smoothing of the voltage without any
(Negative-sequence protection) noteworthy reduction of the average value.
In line protection, the two-element phase- If no faults have occurred and in the event
balance current/negative-sequence protec- of external faults, the system is at equilib-
tion permits detection on the high side of rium, and the voltage through the resistor
high-resistance phase-to-phase faults and is approximately zero. In the event of in-
phase-to-earth faults that are on the low ternal faults, an imbalance occurs which
side of a transformer (e.g. with the switch leads to a voltage and a current flow
group Dy 5). This provides backup protec- through the resistor R.
tion for high-resistance faults beyond the The current transformers must be of the
transformer. same type and must at least offer a separate
core for the high-impedance restricted
Breaker failure protection (ANSI 50BF) earth-fault protection. They must in par-
If a faulted portion of the electrical circuit ticular have the same transformation ratio
is not disconnected upon issuance of a trip and an approximately identical knee-point
command, another command can be initi- voltage. They should also demonstrate only
ated using the breaker failure protection minimal measuring errors.
which operates the circuit-breaker, e.g.
of an upstream (higher-level) protection
relay. Breaker failure is detected if, after a
trip command, current is still flowing in
the faulted circuit. As an option, it is possi-
ble to make use of the circuit-breaker posi-
tion indication.

5/88 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Protection functions

Flexible protection functions


The 7SJ62 units enable the user to easily
add on up to 20 protective functions. To
this end, parameter definitions are used to
link a standard protection logic with any
chosen characteristic quantity (measured
or derived quantity) (Fig. 5/80). The stand-
ard logic consists of the usual protection
elements such as the pickup message, the
parameter-definable delay time, the TRIP
command, a blocking possibility, etc. The
mode of operation for current, voltage,
power and power factor quantities can be
three-phase or single-phase. Almost all
quantities can be operated as greater than Fig. 5/83 Flexible protection functions
or less than stages. All stages operate with
protection priority.
Auto-reclosure (ANSI 79) Thermal overload protection (ANSI 49)
5
Protection stages/functions attainable on
the basis of the available characteristic Multiple reclosures can be defined by the For protecting cables and transformers,
quantities: user and lockout will occur if a fault is an overload protection with an integrated
present after the last reclosure. The follow- pre-warning element for temperature and
Function ANSI No. ing functions are possible: current can be applied. The temperature is
calculated using a thermal homogeneous-
I>, IE> 50, 50N • 3-pole ARC for all types of faults
body model (according to IEC 60255-8),
V<, V>, VE>, dV/dt 27, 59, 59R, 64 • Separate settings for phase and earth faults which takes account both of the energy en-
• Multiple ARC, one rapid auto-reclosure tering the equipment and the energy losses.
3I0>, I1>, I2>, I2/I1 50N, 46
3V0>, V1><, V2>< 59N, 47 (RAR) and up to nine delayed The calculated temperature is constantly
auto-reclosures (DAR) adjusted accordingly. Thus, account is
P><, Q>< 32 taken of the previous load and the load
• Starting of the ARC depends on the trip fluctuations.
cos ϕ (p.f.)>< 55
command selection (e.g. 46, 50, 51, 67)
f>< 81O, 81U For thermal protection of motors (espe-
• Blocking option of the ARC via binary cially the stator) a further time constant
df/dt>< 81R inputs can be set so that the thermal ratios can be
For example, the following can be imple- • ARC can be initiated externally or via CFC detected correctly while the motor is rotat-
ing and when it is stopped. The ambient
mented: • The directional and non-directional ele-
temperature or the temperature of the
• Reverse power protection (ANSI 32R) ments can either be blocked or operated
coolant can be detected serially via an ex-
non-delayed depending on the auto-
• Rate-of-frequency-change protection reclosure cycle
ternal temperature monitoring box (resis-
(ANSI 81R) tance-temperature detector box, also called
• Dynamic setting change of the directional RTD- box). The thermal replica of the
Synchro-check (ANSI 25) and non-directional elements can be acti- overload function is automatically adapted
vated depending on the ready AR to the ambient conditions. If there is no
In case of switching ON the circuit-
RTD-box it is assumed that the ambient
breaker, the units can check whether the
temperatures are constant.
two subnetworks are synchronized.
Voltage-, frequency- and phase-angle-
Settable dropout delay times
differences are being checked to determine
whether synchronous conditions are If the devices are used in parallel with elec-
existent. tromechanical relays in networks with in-
termittent faults, the long dropout times
of the electromechanical devices (several
hundred milliseconds) can lead to prob-
lems in terms of time grading. Clean time
grading is only possible if the dropout time
is approximately the same. This is why the
parameter of dropout times can be defined
for certain functions such as time-over-
current protection, earth short-circuit and
phase-balance current protection.

Siemens SIP · Edition No. 6 5/89


5 Overcurrent Protection / 7SJ62

Protection functions

n Motor protection
Restart inhibit (ANSI 66/86)
If a motor is started up too many times in
succession, the rotor can be subject to ther-
mal overload, especially the upper edges of
the bars. The rotor temperature is calcu-
lated from the stator current. The reclosing
lockout only permits start-up of the motor
if the rotor has sufficient thermal reserves
for a complete start-up (see Fig. 5/84).

Emergency start-up
This function disables the reclosing lock-
out via a binary input by storing the state
of the thermal replica as long as the binary
5 input is active. It is also possible to reset
the thermal replica to zero.
Fig. 5/84
Temperature monitoring (ANSI 38)
Up to two temperature monitoring boxes The characteristic (equation) can be shaft breakage, no-load operation of
with a total of 12 measuring sensors can be adapted optimally to the state of the motor pumps or fan failure.
used for temperature monitoring and de- by applying different tripping times TA in
tection by the protection relay. The ther- dependence of either cold or warm motor Motor statistics
mal status of motors, generators and state. For differentiation of the motor state Essential information on start-up of the
transformers can be monitored with this the thermal model of the rotor is applied. motor (duration, current, voltage) and
device. Additionally, the temperature of If the trip time is rated according to the general information on number of starts,
the bearings of rotating machines are mon- above formula, even a prolonged start-up total operating time, total down time, etc.
itored for limit value violation. The tem- and reduced voltage (and reduced start-up are saved as statistics in the device.
peratures are being measured with the help current) will be evaluated correctly. The
of temperature detectors at various loca- tripping time is inverse (current depend- n Voltage protection
tions of the device to be protected. This ent).
data is transmitted to the protection relay Overvoltage protection (ANSI 59)
via one or two temperature monitoring A binary signal is set by a speed sensor to The two-element overvoltage protection
boxes (see “Accessories”, page 5/115). detect a blocked rotor. An instantaneous detects unwanted network and machine
tripping is effected. overvoltage conditions. The function can
Starting time supervision (ANSI 48/14) operate either with phase-to-phase,
Load jam protection (ANSI 51M) phase-to-earth, positive phase-sequence
Starting time supervision protects the mo-
tor against long unwanted start-ups that Sudden high loads can cause slowing down or negative phase-sequence system voltage.
might occur in the event of excessive load and blocking of the motor and mechanical Three-phase and single-phase connections
torque or excessive voltage drops within damages. The rise of current due to a load are possible.
the motor, or if the rotor is locked. Rotor jam is being monitored by this function
temperature is calculated from measured (alarm and tripping). Undervoltage protection (ANSI 27)
stator current. The tripping time is calcu- The overload protection function is too The two-element undervoltage protection
lated according to the following equation: slow and therefore not suitable under these provides protection against dangerous
circumstances. voltage drops (especially for electric ma-
for I > IMOTOR START chines). Applications include the isolation
2
Phase-balance current protection (ANSI 46) of generators or motors from the network
t = ⎛⎜ A ⎞⎟ ⋅ TA
I
⎝ I ⎠ (Negative-sequence protection) to avoid undesired operating states and a
possible loss of stability. Proper operating
I = Actual current flowing The negative-sequence / phase-balance
conditions of electrical machines are best
IMOTOR START = Pickup current to detect a motor current protection detects a phase failure
evaluated with the positive-sequence quan-
start or load unbalance due to network asym-
tities. The protection function is active
t = Tripping time metry and protects the rotor from imper-
over a wide frequency range (45 to 55, 55
IA = Rated motor starting current missible temperature rise.
to 65 Hz)1). Even when falling below this
TA = Tripping time at rated motor frequency range the function continues to
starting current (2 times, for Undercurrent monitoring (ANSI 37)
work, however, with a greater tolerance
warm and cold motor) With this function, a sudden drop in cur- band.
rent, which can occur due to a reduced
1) The 45 to 55, 55 to 65 Hz range is available
motor load, is detected. This may be due to for fN = 50/60 Hz.

5/90 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

The CB manufacturers double-logarithmic


Protection functions/Functions
switching cycle diagram (see Fig. 5/107)
and the breaking current at the time of
The function can operate either with
contact opening serve as the basis for this
phase-to-phase, phase-to-earth or positive
method. After CB opening, the two-point
phase-sequence voltage and can be
method calculates the number of still pos-
monitored with a current criterion.
sible switching cycles. To this end, the two
Three-phase and single-phase connections
points P1 and P2 only have to be set on the
are possible.
device. These are specified in the CB's tech-
Frequency protection (ANSI 81O/U) nical data.

Frequency protection can be used for over- All of these methods are phase-selective
frequency and underfrequency protection. and a limit value can be set in order to ob-
Electric machines and parts of the system tain an alarm if the actual value falls below
are protected from unwanted speed devia- or exceeds the limit value during determi-
tions. Unwanted frequency changes in the nation of the remaining service life.
network can be detected and the load can
Customized functions (ANSI 32, 51V, 55, etc.)
be removed at a specified frequency set-
ting. Additional functions, which are not time
Frequency protection can be used over a
critical, can be implemented via the CFC 5
using measured values. Typical functions
wide frequency range (40 to 60, 50 to
include reverse power, voltage controlled
70 Hz)1). There are four elements (select-
overcurrent, phase angle detection, and Fig. 5/85 CB switching cycle diagram
able as overfrequency or underfrequency)
zero-sequence voltage detection.
and each element can be delayed sepa-
rately. Blocking of the frequency protec- contacts and communicated to the 7SJ62
Commissioning via binary inputs. Therefore it is possible
tion can be performed if using a binary
input or by using an undervoltage element. Commissioning could hardly be easier and to detect and indicate both the OPEN and
is fully supported by DIGSI 4. The status of CLOSED position or a fault or intermedi-
Fault locator (ANSI 21FL) the binary inputs can be read individually ate circuit-breaker or auxiliary contact
and the state of the binary outputs can be position.
The integrated fault locator calculates the
set individually. The operation of switch- The switchgear or circuit-breaker can be
fault impedance and the distance-to-fault.
ing elements (circuit-breakers, disconnect
The results are displayed in Ω, kilometers controlled via:
devices) can be checked using the switch- – integrated operator panel
(miles) and in percent of the line length.
ing functions of the bay controller. The an- – binary inputs
Circuit-breaker wear monitoring alog measured values are represented as – substation control and protection system
wide-ranging operational measured values. – DIGSI 4
Methods for determining circuit-breaker To prevent transmission of information to
contact wear or the remaining service life the control center during maintenance, the Automation / user-defined logic
of a circuit-breaker (CB) allow CB mainte- bay controller communications can be dis-
nance intervals to be aligned to their actual abled to prevent unnecessary data from be- With integrated logic, the user can set, via a
degree of wear. The benefit lies in reduced ing transmitted. During commissioning, all graphic interface (CFC), specific functions
maintenance costs. indications with test marking for test pur- for the automation of switchgear or substa-
poses can be connected to a control and tion. Functions are activated via function
There is no mathematically exact method
protection system. keys, binary input or via communication
of calculating the wear or the remaining
interface.
service life of circuit-breakers that takes
into account the arc-chamber's physical Test operation
Switching authority
conditions when the CB opens. This is why During commissioning, all indications can
various methods of determining CB wear be passed to an automatic control system Switching authority is determined accord-
have evolved which reflect the different op- for test purposes. ing to parameters and communication.
erator philosophies. To do justice to these, If a source is set to “LOCAL”, only local
the devices offer several methods: n Control and automatic functions switching operations are possible. The fol-
• I lowing sequence of switching authority is
Control
laid down: “LOCAL”; DIGSI PC program,
• Σ I , with x = 1... 3
x
In addition to the protection functions, the “REMOTE”.
• Σ i 2t SIPROTEC 4 units also support all control
and monitoring functions that are required Command processing
The devices additionally offer a new for operating medium-voltage or high-
method for determining the remaining All the functionality of command process-
voltage substations. ing is offered. This includes the processing
service life:
The main application is reliable control of of single and double commands with or
• Two-point method
switching and other processes. without feedback, sophisticated monitor-
ing of the control hardware and software,
The status of primary equipment or auxil-
1) The 40 to 60, 50 to 70 Hz range is checking of the external process, control
available for fN= 50/60 Hz
iary devices can be obtained from auxiliary
actions using functions such as runtime

Siemens SIP · Edition No. 6 5/91


5 Overcurrent Protection / 7SJ62

All units are designed specifically to meet


Functions
the requirements of high/medium-voltage
applications.
monitoring and automatic command ter-
mination after output. Here are some typi- In general, no separate measuring instru-
cal applications: ments (e.g., for current, voltage, frequency,
…) or additional control components are
• Single and double commands using 1,
necessary.
1 plus 1 common or 2 trip contacts
• User-definable bay interlocks Measured values
• Operating sequences combining several The r.m.s. values are calculated from the
switching operations such as control of acquired current and voltage along with
circuit-breakers, disconnectors and the power factor, frequency, active and
earthing switches reactive power. The following functions
• Triggering of switching operations, in- are available for measured value process-
dications or alarm by combination with ing:
existing information • Currents IL1, IL2, IL3, IE, IEE (67Ns)

Assignment of feedback to command • Voltages VL1, VL2, VL3, VL1L2, VL2L3, VL3L1
5 • Symmetrical components

LSP2077f.eps
The positions of the circuit-breaker or
switching devices and transformer taps are I1, I2, 3I0; V1, V2, V0
acquired by feedback. These indication in- • Power Watts, Vars, VA/P, Q, S
puts are logically assigned to the corre- (P, Q: total and phase selective)
sponding command outputs. The unit can • Power factor (cos ϕ),
therefore distinguish whether the indica- (total and phase selective)
tion change is a consequence of switching
operation or whether it is a spontaneous • Frequency
change of state. • Energy ± kWh, ± kVarh, forward and
reverse power flow
Chatter disable
• Mean as well as minimum and maximum
Chatter disable feature evaluates whether, Fig. 5/86
current and voltage values NXAIR panel (air-insulated)
in a configured period of time, the number
of status changes of indication input ex- • Operating hours counter
ceeds a specified figure. If exceeded, the • Mean operating temperature of overload
indication input is blocked for a certain function
period, so that the event list will not record
• Limit value monitoring
excessive operations.
Limit values are monitored using pro-
grammable logic in the CFC. Commands
Indication filtering and delay
can be derived from this limit value indi-
Binary indications can be filtered or de- cation.
layed.
• Zero suppression
Filtering serves to suppress brief changes in In a certain range of very low measured
potential at the indication input. The indi- values, the value is set to zero to suppress
cation is passed on only if the indication interference.
voltage is still present after a set period of
time. In the event of indication delay, there Metered values
is a wait for a preset time. The information For internal metering, the unit can calcu-
is passed on only if the indication voltage is late an energy metered value from the
still present after this time. measured current and voltage values. If an
external meter with a metering pulse out-
Indication derivation
put is available, the SIPROTEC 4 unit can
A further indication (or a command) can obtain and process metering pulses via an
be derived from an existing indication. indication input.
Group indications can also be formed. The
The metered values can be displayed and
volume of information to the system inter-
passed on to a control center as an accu-
face can thus be reduced and restricted to
mulation with reset. A distinction is made
the most important signals.
between forward, reverse, active and reac-
tive energy.
Switchgear cubicles for
high/medium voltage

5/92 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

System interface protocols (retrofittable)


Communication
IEC 61850 protocol
In terms of communication, the units offer The Ethernet-based IEC 61850 protocol is
substantial flexibility in the context of con- the worldwide standard for protection and
nection to industrial and power automa- control systems used by power supply cor-
tion standards. Communication can be porations. Siemens was the first manufac-
extended or added on thanks to modules turer to support this standard. By means of
for retrofitting on which the common pro- this protocol, information can also be ex-
tocols run. Therefore, also in the future it changed directly between bay units so as
will be possible to optimally integrate units to set up simple masterless systems for bay
into the changing communication infra- and system interlocking. Access to the
structure, for example in Ethernet net- units via the Ethernet bus is also possible
works (which will also be used increasingly with DIGSI.
in the power supply sector in the years to
come). IEC 60870-5-103 protocol

Serial front interface The IEC 60870-5-103 protocol is an inter- Fig. 5/87
national standard for the transmission of IEC 60870-5-103: Radial fiber-optic connection
There is a serial RS232 interface on the protective data and fault recordings. All
front of all the units. All of the unit’s func- messages from the unit and also control 5
tions can be set on a PC by means of the commands can be transferred by means of
DIGSI 4 protection operation program. published, Siemens-specific extensions to
Commissioning tools and fault analysis are the protocol.
also built into the program and are avail- Redundant solutions are also possible.
able through this interface. Optionally it is possible to read out and
alter individual parameters (only possible
Rear-mounted interfaces1) with the redundant module).
A number of communication modules
suitable for various applications can be fit- PROFIBUS-DP protocol
ted in the rear of the flush-mounting hous- PROFIBUS-DP is the most widespread
ing. In the flush-mounting housing, the protocol in industrial automation. Via
modules can be easily replaced by the user. PROFIBUS-DP, SIPROTEC units make
The interface modules support the follow- their information available to a SIMATIC
ing applications: controller or, in the control direction, re-
• Time synchronization interface ceive commands from a central SIMATIC.
All units feature a permanently integrated Measured values can also be transferred.
electrical time synchronization interface.
MODBUS RTU protocol Fig. 5/88
It can be used to feed timing telegrams in Bus structure for station bus with Ethernet and
IRIG-B or DCF77 format into the units This uncomplicated, serial protocol is IEC 61850, fiber-optic ring
via time synchronization receivers. mainly used in industry and by power sup-
• System interface ply corporations, and is supported by a
Communication with a central control number of unit manufacturers. SIPROTEC
system takes place through this interface. units function as MODBUS slaves, making
Radial or ring type station bus topologies their information available to a master or
can be configured depending on the cho- receiving information from it. A time-
sen interface. Furthermore, the units can stamped event list is available.
exchange data through this interface via
Ethernet and IEC 61850 protocol and can
also be operated by DIGSI.
• Service interface
The service interface was conceived for re-
mote access to a number of protection
units via DIGSI. On all units, it can be an
electrical RS232/RS485 or an optical inter-
face. For special applications, a maximum
of two temperature monitoring boxes
(RTD-box) can be connected to this inter-
face as an alternative.

1) For units in panel surface-mounting housings


please refer to note on page 5/114.

Siemens SIP · Edition No. 6 5/93


5 Overcurrent Protection / 7SJ62

Communication

DNP 3.0 protocol


Power supply corporations use the serial
DNP 3.0 (Distributed Network Protocol)
for the station and network control levels.
SIPROTEC units function as DNP slaves,
supplying their information to a master
system or receiving information from it.

System solutions for protection and


station control
Together with the SICAM power automa-
tion system, SIPROTEC 4 can be used with
PROFIBUS-FMS. Over the low-cost elec-
trical RS485 bus, or interference-free via
the optical double ring, the units exchange
information with the control system.
5 Units featuring IEC 60870-5-103 interfaces
can be connected to SICAM in parallel via
the RS485 bus or radially by fiber-optic
link. Through this interface, the system is
open for the connection of units of other
manufacturers (see Fig. 5/87).
Fig. 5/90
Because of the standardized interfaces, System solution/communication
SIPROTEC units can also be integrated
into systems of other manufacturers or in
SIMATIC. Electrical RS485 or optical in-
terfaces are available. The optimum physi-
cal data transfer medium can be chosen
thanks to opto-electrical converters. Thus,
LSP3.01-0021.tif

the RS485 bus allows low-cost wiring in


the cubicles and an interference-free opti-
cal connection to the master can be estab-
lished.
For IEC 61850, an interoperable system
solution is offered with SICAM PAS. Via
the 100 Mbits/s Ethernet bus, the units are
linked with PAS electrically or optically to
the station PC. The interface is standard-
ized, thus also enabling direct connection Fig. 5/89
of units of other manufacturers to the Optical Ethernet communication module
Ethernet bus. With IEC 61850, however, for IEC 61850 with integrated Ethernet-switch
the units can also be used in other manu-
facturers’ systems (see Fig. 5/88).

5/94 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Typical connections

n Connection of current
and voltage transformers
Standard connection
For earthed networks, the earth current is
obtained from the phase currents by the
residual current circuit.

Fig. 5/91
Residual current
circuit without
directional element
5

Fig. 5/92
Sensitive earth-
current detection
without directional
element

Fig. 5/93
Residual current
circuit with
directional element

Siemens SIP · Edition No. 6 5/95


5 Overcurrent Protection / 7SJ62

Typical connections

Connection for compensated networks


The figure shows the connection of two
phase-to-earth voltages and the VE voltage
of the open delta winding and a phase-
balance neutral current transformer for the
earth current. This connection maintains
maximum precision for directional earth-
fault detection and must be used in com-
pensated networks.
Fig. 5/94 shows sensitive directional
earth-fault detection.

Fig. 5/94
Sensitive directional
earth-fault detection
with directional
element for phases
5
Connection for isolated-neutral
or compensated networks only
If directional earth-fault protection is not
used, the connection can be made with
only two phase current transformers.
Directional phase short-circuit protection
can be achieved by using only two primary
transformers.

Fig. 5/95
Isolated-neutral or
compensated
networks

Connection for the synchro-check function


The 3-phase system is connected as refer-
ence voltage, i. e. the outgoing voltages as
well as a single-phase voltage, in this case
a busbar voltage, that has to be checked for
synchronism.

Fig. 5/96
Measuring of the
busbar voltage and
the outgoing feeder
voltage for the
synchro-check

5/96 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Typical applications

Overview of connection types


Type of network Function Current connection Voltage connection
(Low-resistance) earthed network Time-overcurrent protection Residual circuit, with 3 phase-current -
phase/earth non-directional transformers required, phase-balance
neutral current transformer possible
(Low-resistance) earthed networks Sensitive earth-fault protection Phase-balance neutral current -
transformers required
Isolated or compensated networks Time-overcurrent protection Residual circuit, with 3 or 2 phase -
phases non-directional current transformers possible
(Low-resistance) earthed networks Time-overcurrent protection Residual circuit, with 3 phase-current Phase-to-earth connection or
phases directional transformers possible phase-to-phase connection
Isolated or compensated networks Time-overcurrent protection Residual circuit, with 3 or 2 phase- Phase-to-earth connection or
phases directional current transformers possible phase-to-phase connection
(Low-resistance) earthed networks Time-overcurrent protection Residual circuit, with 3 phase-current Phase-to-earth connection required
earth directional transformers required, phase-balance
neutral current transformers possible
5
Isolated networks Sensitive earth-fault Residual circuit, if earth current 3 times phase-to-earth connection or
protection > 0.05 IN on secondary side, other- phase-to-earth connection with open
wise phase-balance neutral current delta winding
transformers required
Compensated networks Sensitive earth-fault protection Phase-balance neutral current Phase-to-earth connection with open
cos ϕ measurement transformers required delta winding required

n Connection of circuit-breaker
Undervoltage releases
Undervoltage releases are used for auto-
matic tripping of high-voltage motors.
Example:
DC supply voltage of control system fails
and manual electric tripping is no longer
possible.
Automatic tripping takes place when volt-
age across the coil drops below the trip
limit. In Fig. 5/97, tripping occurs due to
failure of DC supply voltage, by automatic
opening of the live status contact upon Fig. 5/97 Undervoltage release with make contact (50, 51)
failure of the protection unit or by short-
circuiting the trip coil in event of network
fault.

In Fig. 5/98 tripping is by failure of auxil-


iary voltage and by interruption of tripping
circuit in the event of network failure.
Upon failure of the protection unit, the
tripping circuit is also interrupted, since
contact held by internal logic drops back
into open position.

Fig. 5/98 Undervoltage trip with locking contact (trip signal 50 is inverted)

Siemens SIP · Edition No. 6 5/97


5 Overcurrent Protection / 7SJ62

Typical applications

Trip circuit supervision (ANSI 74TC)


One or two binary inputs can be used for
monitoring the circuit-breaker trip coil
including its incoming cables. An alarm
signal occurs whenever the circuit is inter-
rupted.

Lockout (ANSI 86)


All binary outputs can be stored like LEDs
and reset using the LED reset key. The
lockout state is also stored in the event of
supply voltage failure. Reclosure can only
occur after the lockout state is reset.

Reverse-power protection for dual supply


(ANSI 32R)
5 If power is fed to a busbar through two
parallel infeeds, then in the event of any Fig. 5/99 Trip circuit supervision with 2 binary inputs
fault on one of the infeeds it should be
selectively interrupted. This ensures a con-
tinued supply to the busbar through the
remaining infeed. For this purpose, direc-
tional devices are needed which detect a
short-circuit current or a power flow from
the busbar in the direction of the infeed.
The directional time-overcurrent protec-
tion is usually set via the load current. It
cannot be used to deactivate low-current
faults. Reverse-power protection can be set
far below the rated power. This ensures
that it also detects power feedback into the
line in the event of low-current faults with
levels far below the load current.
Reverse-power protection is performed via
the “flexible protection functions” of the
7SJ62.

Fig. 5/100 Reverse-power protection for dual supply

5/98 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Technical data

General unit data Binary outputs/command outputs


Measuring circuits Type 7SJ621, 7SJ622
System frequency 50 / 60 Hz (settable) 7SJ623, 7SJ624
7SJ625 7SJ626
Current transformer
Command/indication relay 8 6
Rated current Inom 1 or 5 A (settable)
Contacts per command/ 1 NO / form A
Option: sensitive earth-fault CT IEE < 1.6 A indication relay (Two contacts changeable to NC/form
Power consumption B, via jumpers)
at Inom = 1 A Approx. 0.05 VA per phase Live status contact 1 NO / NC (jumper) / form A/B
at Inom = 5 A Approx. 0.3 VA per phase
for sensitive earth-fault CT at 1 A Approx. 0.05 VA Switching capacity
Make 1000 W / VA
Overload capability
Thermal (effective) 100 x Inom for 1 s Break 30 W / VA / 40 W resistive /
30 x Inom for 10 s 25 W at L/R ≤ 50 ms
4 x Inom continuous Switching voltage ≤ 250 V DC
Dynamic (impulse current) 250 x Inom (half cycle) Permissible current 5 A continuous,
Overload capability if equipped with 30 A for 0.5 s making current,
sensitive earth-fault CT
Thermal (effective) 300 A for 1 s
2000 switching cycles 5
100 A for 10 s
15 A continuous Electrical tests
Dynamic (impulse current) 750 A (half cycle) Specification
Voltage transformer Standards IEC 60255
Type 7SJ621, 7SJ623, 7SJ625, ANSI C37.90, C37.90.1, C37.90.2,
7SJ622 7SJ622 7SJ626 UL508
Number 3 4 4 Insulation tests
Rated voltage Vnom 100 V to 225 V Standards IEC 60255-5; ANSI/IEEE C37.90.0
Measuring range 0 V to 170 V Voltage test (100 % test) 2.5 kV (r.m.s. value), 50/60 Hz
all circuits except for auxiliary
Power consumption at Vnom = 100 V < 0.3 VA per phase voltage and RS485/RS232 and
Overload capability in voltage path time synchronization
(phase-neutral voltage) Auxiliary voltage 3.5 kV DC
Thermal (effective) 230 V continuous
Communication ports 500 V AC
Auxiliary voltage and time synchronization
Rated auxiliary DC 24/48 V 60/125 V 110/250 V Impulse voltage test (type test) 5 kV (peak value); 1.2/50 µs; 0.5 J
voltage Vaux AC 115/230 V all circuits, except communication 3 positive and 3 negative impulses
Permissible tolerance DC 19–58 V 48–150 V 88–300 V ports and time synchronization, at intervals of 5 s
AC 92-138 V 184–265 V class III
Ripple voltage, ≤ 12 % EMC tests for interference immunity; type tests
peak-to-peak Standards IEC 60255-6; IEC 60255-22
Power consumption (product standard)
Quiescent Approx. 4 W EN 50082-2 (generic specification)
Energized Approx. 7 W DIN 57435 Part 303
Backup time during ≥ 50 ms at V ≥ 110 V DC High-frequency test 2.5 kV (peak value); 1 MHz; τ =15 ms;
loss/short circuit of ≥ 20 ms at V ≥ 24 V DC IEC 60255-22-1, class III 400 surges per s; test duration 2 s
auxiliary voltage ≥ 200 ms at 115 V/230 V AC and VDE 0435 Part 303, class III
Binary inputs/indication inputs Electrostatic discharge 8 kV contact discharge;
Type 7SJ621, 7SJ622, IEC 60255-22-2 class IV 15 kV air gap discharge;
7SJ623, 7SJ624, and EN 61000-4-2, class IV both polarities; 150 pF; Ri = 330 Ω
7SJ625 7SJ626 Irradiation with radio-frequency 10 V/m; 27 to 500 MHz
Number 8 11 field, non-modulated
IEC 60255-22-3 (Report) class III
Voltage range 24–250 V DC
Irradiation with radio-frequency 10 V/m, 80 to 1000 MHz;
Pickup threshold modifiable by plug-in jumpers field, amplitude-modulated AM 80 %; 1 kHz
Pickup threshold 19 V DC 88 V DC IEC 61000-4-3; class III
For rated control voltage 24/48/60/ 110/125/ Irradiation with radio-frequency 10 V/m, 900 MHz; repetition
110/125 V 220/250 V DC field, pulse-modulated rate 200 Hz, on duration 50 %
IEC 61000-4-3/ENV 50204; class III
Response time/drop-out Approx. 3.5
time Fast transient interference/burst 4 kV; 5/50 ns; 5 kHz;
IEC 60255-22-4 and IEC 61000-4-4, burst length = 15 ms;
Power consumption 1.8 mA (independent of operating voltage)
class IV repetition rate 300 ms; both polarities;
energized
Ri = 50 Ω; test duration 1 min

Siemens SIP · Edition No. 6 5/99


5 Overcurrent Protection / 7SJ62

Technical data

EMC tests for interference immunity; type tests (cont'd) During transportation
High-energy surge voltages Standards IEC 60255-21 and IEC 60068-2
(Surge) Vibration Sinusoidal
IEC 61000-4-5; class III IEC 60255-21-1, class 2 5 to 8 Hz: ± 7.5 mm amplitude;
Auxiliary voltage From circuit to circuit: 2 kV; 12 Ω; 9 µF IEC 60068-2-6 8 to 150 Hz; 2 g acceleration,
across contacts: 1 kV; 2 Ω ;18 µF frequency sweep 1 octave/min
Binary inputs/outputs From circuit to circuit: 2 kV; 42 Ω; 0.5 µF 20 cycles in 3 perpendicular axes
across contacts: 1 kV; 42 Ω; 0.5 µF Shock Semi-sinusoidal
Line-conducted HF, 10 V; 150 kHz to 80 MHz; IEC 60255-21-2, Class 1 Acceleration 15 g, duration 11 ms
amplitude-modulated AM 80 %; 1 kHz IEC 60068-2-27 3 shocks in both directions of 3 axes
IEC 61000-4-6, class III Continuous shock Semi-sinusoidal
Power frequency magnetic field 30 A/m; 50 Hz, continuous IEC 60255-21-2, class 1 Acceleration 10 g, duration 16 ms
IEC 61000-4-8, class IV 300 A/m; 50 Hz, 3 s IEC 60068-2-29 1000 shocks in both directions
IEC 60255-6 0.5 mT, 50 Hz of 3 axes
Oscillatory surge withstand 2.5 to 3 kV (peak value), 1 to 1.5 MHz
capability damped wave; 50 surges per s; Climatic stress tests
ANSI/IEEE C37.90.1 duration 2 s, Ri = 150 to 200 Ω
5 Fast transient surge withstand 4 to 5 kV; 10/150 ns; 50 surges per s
Temperatures
Type-tested acc. to IEC 60068-2-1 -25 °C to +85 °C /-13 °F to +185 °F
capability ANSI/IEEE C37.90.1 both polarities; duration 2 s, Ri = 80 Ω
and -2, test Bd, for 16 h
Radiated electromagnetic 35 V/m; 25 to 1000 MHz;
interference amplitude and pulse-modulated Temporarily permissible operating -20 °C to +70 °C /-4 °F to -158 °F
ANSI/IEEE C37.90.2 temperature, tested for 96 h
Damped wave 2.5 kV (peak value, polarity Recommended permanent operat- -5 °C to +55 °C /+25 °F to +131 °F
IEC 60694 / IEC 61000-4-12 alternating) ing temperature acc. to IEC 60255-6
100 kHz, 1 MHz, 10 and 50 MHz, (Legibility of display may be
Ri = 200 Ω impaired above +55 °C /+131 °F)
– Limiting temperature during -25 °C to +55 °C /-13 °F to +131 °F
EMC tests for interference emission; type tests permanent storage
Standard EN 50081-* (generic specification) – Limiting temperature during -25 °C to +70 °C /-13 °F to +158 °F
Conducted interferences 150 kHz to 30 MHz transport
only auxiliary voltage IEC/CISPR 22 Limit class B Humidity
Radio interference field strength 30 to 1000 MHz Permissible humidity Annual average 75 % relative
IEC/CISPR 11 Limit class B It is recommended to arrange the humidity; on 56 days a year up to
Units with a detached operator units in such a way that they are not 95 % relative humidity; condensation
panel must be installed in a metal exposed to direct sunlight or not permissible!
cubicle to maintain limit class B pronounced temperature changes
that could cause condensation.
Unit design
Mechanical stress tests
Housing 7XP20
Vibration, shock stress and seismic vibration
Dimensions See dimension drawings, part 15
During operation
Weight
Standards IEC 60255-21 and IEC 60068-2 Surface-mounting housing 4.5 kg
Vibration Sinusoidal Flush-mounting housing 4.0 kg
IEC 60255-21-1, class 2 10 to 60 Hz; +/- 0.075 mm amplitude; Degree of protection
IEC 60068-2-6 60 to 150 Hz; 1 g acceleration acc. to EN 60529
frequency sweep 1 octave/min Surface-mounting housing IP 51
20 cycles in 3 perpendicular axes Flush-mounting housing Front: IP 51, rear: IP 20;
Shock Semi-sinusoidal Operator safety IP 2x with cover
IEC 60255-21-2, class 1 Acceleration 5 g, duration 11 ms;
IEC 60068-2-27 3 shocks in both directions of 3 axes
Seismic vibration Sinusoidal
IEC 60255-21-3, class 1 1 to 8 Hz: ± 3.5 mm amplitude
IEC 60068-3-3 (horizontal axis)
1 to 8 Hz: ± 1.5 mm amplitude
(vertical axis)
8 to 35 Hz: 1 g acceleration
(horizontal axis)
8 to 35 Hz: 0.5 g acceleration
(vertical axis)
Frequency sweep 1 octave/min
1 cycle in 3 perpendicular axes

5/100 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Technical data

Serial interfaces IEC 61850 protocol


Operating interface (front of unit) Isolated interface for data transfer: Port B, 100 Base T acc. to IEEE802.3
Connection Non-isolated, RS232; front panel, - to a control center
9-pin subminiature connector - with DIGSI
- between SIPROTEC 4 relays
Transmission rate Factory setting 115200 baud,
min. 4800 baud, max. 115200 baud Transmission rate 100 Mbit

Service/modem interface (rear of unit) Ethernet, electrical

Isolated interface for data transfer Port C: DIGSI 4/modem/RTD-box Connection Two RJ45 connectors
For flush-mounting housing/ mounting location "B"
Transmission rate Factory setting 38400 baud,
surface-mounting housing with
min. 4800 baud, max. 115200 baud
detached operator panel
RS232/RS485
Distance Max. 20 m / 65.6 ft
Connection Test voltage 500 V AC against earth
For flush-mounting housing/ 9-pin subminiature connector,
surface-mounting housing with mounting location “C” Ethernet, optical
detached operator panel Connection Intergr. LC connector for FO
For surface-mounting housing At the bottom part of the housing:
with two-tier terminal at the shielded data cable For flush-mounting housing/
connection
Mounting location "B" 5
top/bottom part surface-mounting housing with
Distance RS232 15 m /49.2 ft detached operator panel
Distance RS485 Max. 1 km/3300 ft Optical wavelength 1300 nmm
Distance 1.5 km/0.9 miles
Test voltage 500 V AC against earth
PROFIBUS-FMS/DP
System interface (rear of unit)
Isolated interface for data transfer Port B
IEC 60870-5-103 protocol to a control center
Isolated interface for data transfer Port B Transmission rate Up to 1.5 Mbaud
to a control center
RS485
Transmission rate Factory setting 9600 baud,
min. 1200 baud, max. 115200 baud Connection
RS232/RS485 For flush-mounting housing/ 9-pin subminiature connector,
surface-mounting housing with mounting location “B”
Connection detached operator panel
For flush-mounting housing/ Mounting location “B” For surface-mounting housing At the bottom part of the housing:
surface-mounting housing with with two-tier terminal on the shielded data cable
detached operator panel top/bottom part
For surface-mounting housing At the bottom part of the housing: Distance 1000 m/3300 ft ≤ 93.75 kbaud;
with two-tier terminal on the shielded data cable 500 m/1500 ft ≤ 187.5 kbaud;
top/bottom part 200 m/600 ft ≤ 1.5 Mbaud;
Distance RS232 Max. 15 m/49 ft 100 m/300 ft ≤ 12 Mbaud
Distance RS485 Max. 1 km/3300 ft Test voltage 500 V AC against earth
Test voltage 500 V AC against earth Fiber optic
Fiber optic Connection fiber-optic cable Integr. ST connector for FO
Connection fiber-optic cable Integrated ST connector for fiber- connection
optic connection For flush-mounting housing/ Mounting location “B”
For flush-mounting housing/ Mounting location “B” surface-mounting housing with
surface-mounting housing with detached operator panel
detached operator panel For surface-mounting housing At the bottom part of the housing
For surface-mounting housing At the bottom part of the housing with two-tier terminal on the Important: Please refer to footnotes
1)
with two-tier terminal on the top/bottom part and 2) on page 5/136
top/bottom part Optical wavelength 820 nm
Optical wavelength 820 nm Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
Distance 500 kB/s 1.6 km/0.99 miles
Distance Max. 1.5 km/0.9 miles 1500 kB/s 530 m/0.33 miles
IEC 60870-5-103 protocol, redundant MODBUS RTU, ASCII, DNP 3.0
RS485
Isolated interface for data transfer Port B
Connection to a control center
For flush-mounting housing/ Mounting location “B”
Transmission rate Up to 19200 baud
surface-mounting housing with
detached operator panel
For surface-mounting housing (not available)
with two-tier terminal on the
top/bottom part
Distance RS485 Max. 1 km/3300 ft
Test voltage 500 V AC against earth

Siemens SIP · Edition No. 6 5/101


5 Overcurrent Protection / 7SJ62

Technical data

System interface (rear of unit) (cont'd) Inverse-time overcurrent protection, directional/non-directional


RS485 (ANSI 51, 51N, 67, 67N)
Operating mode non-directional 3-phase (standard) or 2-phase
Connection phase protection (ANSI 51) (L1 and L3)
For flush-mounting housing/ 9-pin subminiature connector,
surface-mounting housing with mounting location “B” Setting ranges
detached operator panel Pickup phase element IP 0.5 to 20 A or ∞ 1) (in steps of 0.01 A)
For surface-mounting housing At bottom part of the housing: Pickup earth element IEP 0.25 to 20 A or ∞ 1) (in steps of 0.01 A)
with two-tier terminal at the shielded data cable Time multiplier T 0.05 to 3.2 s or ∞ (in steps of 0.01 s)
top/bottom part (IEC characteristics)
Time multiplier D 0.05 to 15 s or ∞ (in steps of 0.01 s)
Test voltage 500 V AC against earth (ANSI characteristics)
Fiber-optic Undervoltage threshold 10.0 to 125.0 V (in steps of 0.1 V)
V< for release Ip
Connection fiber-optic cable Integrated ST connector for fiber-optic
connection Trip characteristics
For flush-mounting housing/ Mounting location “B” IEC Normal inverse, very inverse,
surface-mounting housing with extremely inverse, long inverse
detached operator panel ANSI Inverse, short inverse, long inverse
moderately inverse, very inverse,
5 For surface-mounting housing
with two-tier terminal at the
At the bottom part of the housing
Important: Please refer to footnotes extremely inverse, definite inverse
1)
top/bottom part and 2) on page 5/136 User-defined characteristic Defined by a maximum of 20 value
Optical wavelength 820 nm pairs of current and time delay

Permissible path attenuation Max 8 dB. for glass fiber 62.5/125 µm Dropout setting
Without disk emulation Approx. 1.05 · setting value Ip for
Distance Max. 1.5 km/0.9 miles Ip/Inom ≥ 0.3, corresponds to approx.
Time synchronization DCF77/IRIG-B signal (Format IRIG-B000) 0.95 · pickup threshold
With disk emulation Approx. 0.90 · setting value Ip
Connection 9-pin subminiature connector
(SUB-D) Tolerances
(terminal with surface-mounting Pickup/dropout thresholds Ip, IEp 2 % of setting value or 50 mA1)
housing) Pickup time for 2 ≤ I/Ip ≤ 20 5 % of reference (calculated) value
+ 2 % current tolerance, respectively
Voltage levels 5 V, 12 V or 24 V (optional)
30 ms
Dropout ratio for 0.05 ≤ I/Ip 5 % of reference (calculated) value
Functions ≤ 0.9 + 2 % current tolerance, respectively
30 ms
Definite-time overcurrent protection, directional/non-directional
(ANSI 50, 50N, 67, 67N) Direction detection
Operating mode non-directional 3-phase (standard) or 2-phase For phase faults
phase protection (ANSI 50) (L1 and L3) Polarization With cross-polarized voltages;
Number of elements (stages) I>, I>>, I>>> (phases) With voltage memory for measure-
IE>, IE>>, IE>>> (earth) ment voltages that are too low
Setting ranges Forward range Vref,rot ± 86°
Rotation of reference voltage Vref,rot - 180° to 180° (in steps of 1°)
Pickup phase elements 1)
0.5 to 175 A or ∞ (in steps of 0.01 A)
Pickup earth elements 0.25 to 175 A or ∞1) (in steps of 0.01 A) Direction sensitivity For one and two-phase faults
unlimited;
Delay times T 0 to 60 s or ∞ (in steps of 0.01 s) For three-phase faults dynamically
Dropout delay time TDO 0 to 60 s (in steps of 0.01 s) unlimited;
Times Steady-state approx. 7 V
Pickup times (without inrush phase-to-phase
restraint, with inrush restraint For earth faults
+ 10 ms)
Polarization With zero-sequence quantities 3V0, 3I0
Non-directional Directional or with negative-sequence quantities
With twice the setting value Approx. 30 ms 45 ms 3V2, 3I2
With five times the setting value Approx. 20 ms 40 ms
Forward range Vref,rot ± 86°
Dropout times Approx. 40 ms
Rotation of reference voltage Vref,rot - 180° to 180° (in steps of 1°)
Dropout ratio Approx. 0.95 for
Direction sensitivity
I/Inom ≥ 0.3
Zero-sequence quantities 3V0, 3I0 VE ≈ 2.5 V displacement voltage,
Tolerances measured;
Pickup 2 % of setting value or 50 mA1) 3V0 ≈ 5 V displacement voltage,
Delay times T, TDO 1 % or 10 ms calculated
Negative-sequence quantities 3V2 ≈ 5 V negative-sequence voltage;
3V2, 3I2 3I2 ≈ 225 mA negative-sequence cur-
rent1)
Tolerances (phase angle error under
reference conditions)
1) At Inom = 1 A, all limits divided by 5. For phase and earth faults ± 3 ° electrical

5/102 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Technical data

Inrush blocking Tolerances


Influenced functions Time-overcurrent elements, I>, IE>, Ip, Pickup threshold
IEp (directional, non-directional) For sensitive input 2 % of setting value or 1 mA
For normal input 2 % of setting value or 50 mA1)
Lower function limit phases At least one phase current Delay times 1 % of setting value or 20 ms
(50 Hz and 100 Hz) W 125 mA1)
Lower function limit earth Earth current Earth-fault pickup for all types of earth faults
(50 Hz and 100 Hz) W 125 mA1) Inverse-time characteristic (ANSI 51Ns)
Upper function limit 1.5 to 125 A1) (in steps of 0.01 A) User-defined characteristic Defined by a maximum of 20 pairs of
(setting range) current and delay time values
Setting range I2f /I 10 to 45 % (in steps of 1 %) Setting ranges
Crossblock (IL1, IL2, IL3) ON/OFF Pickup threshold IEEp
For sensitive input 0.001 A to 1.4 A (in steps of 0.001 A)
Dynamic setting change For normal input 0.25 to 20 A1) (in steps of 0.01 A)
Controllable function Directional and non-directional User defined
pickup, tripping time Time multiplier T 0.1 to 4 s or ∞ (in steps of 0.01 s)
Start criteria Current criteria, Times
CB position via aux. contacts, Pickup times Approx. 50 ms
binary input,
auto-reclosure ready
Pickup threshold Approx. 1.1 · IEEp 5
Dropout ratio Approx. 1.05 · IEEp
Time control 3 timers
Tolerances
Current criteria Current threshold Pickup threshold
(reset on dropping below threshold; For sensitive input 2 % of setting value or 1 mA
monitoring with timer) For normal input 2 % of setting value or 50 mA1)
(Sensitive) earth-fault detection (ANSI 64, 50 Ns, 51Ns, 67Ns) Delay times in linear range 7 % of reference value for 2 ≤ I/IEEp
≤ 20 + 2 % current tolerance, or 70 ms
Displacement voltage starting for all types of earth fault (ANSI 64)
Logarithmic inverse Refer to the manual
Setting ranges
Pickup threshold VE> (measured) 1.8 to 170 V (in steps of 0.1 V) Logarithmic inverse with knee point Refer to the manual
Pickup threshold 3V0> 10 to 225 V (in steps of 0.1 V) Direction detection for all types of earth-faults (ANSI 67Ns)
(calculated)
Measuring method “cos ϕ / sin ϕ”
Delay time TDelay pickup 0.04 to 320 s or ∞ (in steps of 0.01 s)
Additional trip delay TVDELAY 0.1 to 40000 s or ∞ (in steps of 0.01 s) Direction measurement IE and VE measured or
3I0 and 3V0 calculated
Times
Pickup time Approx. 50 ms Measuring principle Active/reactive power measurement
Dropout ratio 0.95 or (pickup value -0.6 V) Setting ranges
Measuring enable IRelease direct.
Tolerances For sensitive input 0.001 to 1.2 A (in steps of 0.001 A)
Pickup threshold VE (measured) 3 % of setting value or 0.3 V For normal input 0.25 to 150 A1) (in steps of 0.01 A)
Pickup threshold 3V0 (calculated) 3 % of setting value or 3 V Direction phasor ϕCorrection - 45 ° to + 45 ° (in steps of 0.1 °)
Delay times 1 % of setting value or 10 ms Dropout delay TReset delay 1 to 60 s (in steps of 1 s)
Phase detection for earth fault in an unearthed system Reduction of dir. area α Red.dir.area 1 ° to 15 ° (in steps of 1 °)
Measuring principle Voltage measurement (phase-to-earth) Tolerances
Setting ranges Pickup measuring enable
Vph min (earth-fault phase) 10 to 100 V (in steps of 1 V) For sensitive input 2 % of setting value or 1 mA
For normal input 2 % of setting value or 50 mA1)
Vph max (unfaulted phases) 10 to 100 V (in steps of 1 V) Angle tolerance 3°
Measuring tolerance 3 % of setting value, or 1 V Measuring method “ϕ (V0 / I0)”
acc. to DIN 57435 part 303
Direction measurement IE and VE measured or
Earth-fault pickup for all types of earth faults 3I0 and 3V0 calculated
Definite-time characteristic (ANSI 50Ns) Minimum voltage Vmin, measured 0.4 to 50 V (in steps of 0.1 V)
Minimum voltage Vmin, calculated 10 to 90 V (in steps of 1 V)
Setting ranges Phase angle ϕ - 180° to 180° (in steps of 0.1°)
Pickup threshold IEE>, IEE>> Delta phase angle Δ ϕ 0° to 180° (in steps of 0.1°)
For sensitive input 0.001 to 1.5 A (in steps of 0.001 A) Tolerances
For normal input 0.25 to 175 A1) (in steps of 0.01 A) Pickup threshold VE (measured) 3 % of setting value or 0.3 V
Delay times T for IEE>, IEE>> 0 to 320 s or ∞ (in steps of 0.01 s) Pickup threshold 3V0 (calculated) 3 % of setting value or 3 V
Dropout delay time TDO 0 to 60 s (in steps of 0.01 s) Angle tolerance 3°
Times Angle correction for cable CT
Pickup times Approx. 50 ms
Angle correction F1, F2
Dropout ratio Approx. 0.95 Current value I1, I2 0 ° to 5 ° (in steps of 0.1 °)
For sensitive input 0.001 to 1.5 A (in steps of 0.001 A)
For normal input 0.25 to 175 A1) (in steps of 0.01 A)

Note: Due to the high sensitivity the linear range of the measuring input IN
with integrated sensitive input transformer is from 0.001 A to 1.6 A. For cur-
1) For Inom = 1 A, all limits divided by 5. rents greater than 1.6 A, correct directionality can no longer be guaranteed.

Siemens SIP · Edition No. 6 5/103


5 Overcurrent Protection / 7SJ62

Technical data

High-impedance restricted earth-fault protection (ANSI 87N) / single-phase t = Tripping time


overcurrent protection τth = Temperature rise time constant
Setting ranges
Pickup thresholds I>, I>> I = Load current
For sensitive input 0.003 to 1.5 A or ∞ (in steps of 0.001 A) Ipre = Preload current
For normal input 0.25 to 175 A1) or ∞ (in steps of 0.01 A) k = Setting factor acc. to VDE 0435
Delay times TI>, TI>> 0 to 60 s or ∞ (in steps of 0.01 s)
Part 3011 and IEC 60255-8
Times Inom = Rated (nominal) current of the
Pickup times protection relay
Minimum Approx. 20 ms
Typical Approx. 30 ms Dropout ratios
Dropout times Approx. 30 ms Θ/ΘTrip Drops out with ΘAlarm
Θ/ΘAlarm Approx. 0.99
Dropout ratio Approx. 0.95 for I/Inom ≥ 0.5 I/IAlarm Approx. 0.97
Tolerances Tolerances
Pickup thresholds 3 % of setting value or With reference to k · Inom Class 5 acc. to IEC 60255-8
1 % rated current at Inom = 1 or 5 A; With reference to tripping time 5 % +/- 2 s acc. to IEC 60255-8
5 % of setting value or
3 % rated current at Inom = 0.1 A Auto-reclosure (ANSI 79)
5 Delay times 1 % of setting value or 10 ms Number of reclosures 0 to 9
Intermittent earth-fault protection Shot 1 to 4 individually adjustable

Setting ranges Program for phase fault


Start-up by Time-overcurrent elements
Pickup threshold (dir., non-dir.), negative sequence,
1)
For IE IIE> 0.25 to 175 A (in steps of 0.01 A) binary input
For 3I0 IIE> 0.25 to 175 A1) (in steps of 0.01 A)
For IEE IIE> 0.005 to 1.5 A (in steps of 0.001 A) Program for earth fault
Start-up by Time-overcurrent elements
Pickup prolon- TV 0 to 10 s (in steps of 0.01 s) (dir., non-dir.), sensitive earth-fault
gation time protection, binary input
Earth-fault accu- Tsum 0 to 100 s (in steps of 0.01 s)
Blocking of ARC Pickup of protection functions,
mulation time
three-phase fault detected by a protec-
Reset time for Tres 1 to 600 s (in steps of 1 s) tive element, binary input,
accumulation last TRIP command after the reclosing
Number of pickups for 2 to 10 (in steps of 1) cycle is complete (unsuccessful
intermittent earth fault reclosing),
TRIP command by the breaker failure
Times
protection (50BF),
Pickup times
opening the CB without ARC initia-
Current = 1.25 · pickup value Approx. 30 ms
tion, external CLOSE command
Current ≥ 2 · pickup value Approx. 22 ms
Dropout time Approx. 22 ms Setting ranges
Dead time 0.01 to 320 s (in steps of 0.01 s)
Tolerances (separate for phase and earth
1)
Pickup threshold IIE> 3 % of setting value, or 50 mA and individual for shots 1 to 4)
Times TV, Tsum, Tres 1 % of setting value or 10 ms Blocking duration for manual- 0.5 s to 320 s or 0 (in steps of 0.01 s)
Thermal overload protection (ANSI 49) CLOSE detection
Blocking duration after 0.5 s to 320 s (in steps of 0.01 s)
Setting ranges
reclosure
Factor k 0.1 to 4 (in steps of 0.01) Blocking duration after 0.01 to 320 s (in steps of 0.01 s)
Time constant 1 to 999.9 min (in steps of 0.1 min) dynamic blocking
Warning overtemperature 50 to 100 % with reference Start-signal monitoring time 0.01 to 320 s or ∞ (in steps of 0.01 s)
Θalarm/Θtrip to the tripping overtemperature Circuit-breaker supervision 0.1 to 320 s (in steps of 0.01 s)
(in steps of 1 %) time
Current warning stage Ialarm 0.5 to 20 A (in steps of 0.01 A) Max. delay of dead-time start 0 to 1800 s or ∞ (in steps of 0.1 s)
Extension factor when stopped 1 to 10 with reference to the time Maximum dead time extension 0.5 to 320 s or ∞(in steps of 0.01 s)
kτ factor constant with the machine running
Action time 0.01 to 320 s or ∞ (in steps of 0.01 s)
(in steps of 0.1)
The delay times of the following protection function can be altered
Rated overtemperature (for Inom) 40 to 200 °C (in steps of 1 °C)
individually by the ARC for shots 1 to 4
(I / k ⋅ I nom ) − (I pre / k ⋅ I nom ) (setting value T = T, non-delayed T = 0, blocking T = ∞):
2 2
Tripping characteristic
For (I/k · Inom) ≤ 8 t = τ th ⋅ ln I>>>, I>>, I>, Ip, Idir>>, Idir>, Ipdir
(I / k ⋅ I nom ) − 1
2
IE>>>, IE>>, IE>, IEp, IEdir>>, IEdir>, IEdir
Additional functions Lockout (final trip), delay of dead-time
start via binary input (monitored),
dead-time extension via binary input
(monitored), co-ordination with other
protection relays, circuit-breaker moni-
1) For Inom = 1 A, all limits divided by 5. toring, evaluation of the CB contacts

5/104 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Technical data

Breaker failure protection (ANSI 50 BF) Frequency of V1 and V2 f1, f2 in Hz


Setting ranges Range fN ± 5 Hz
Pickup thresholds 0.2 to 5 A1) (in steps of 0.01 A) Tolerance*) 20 mHz

Delay time 0.06 to 60 s or ∞ (in steps of 0.01 s) Voltage difference (V2 – V1) InkVprimary,inVsecondaryorin%Vnom
Range 10 to 120 % Vnom
Times Tolerance*) ≤1 % of measured value or 0.5 % of Vnom
Pickup times
with internal start is contained in the delay time Frequency difference (f2 – f1) In mHz
with external start is contained in the delay time Range fN ± 5 Hz
Dropout times Approx. 25 ms Tolerance*) 20 mHz

Tolerances Angle difference (α2 – α1) In °


Pickup value 2 % of setting value (50 mA)1) Range 0 to 180 °
Delay time 1 % or 20 ms Tolerance*) 0.5 °

Synchro- and voltage check (ANSI 25) Flexible protection functions (ANSI 27, 32, 47, 50, 55, 59, 81R)
Operating mode • Synchro-check Operating modes / measuring
Additional release conditions • Live-bus / dead line quantities
• Dead-bus / live-line 3-phase I, I1, I2, I2/I1, 3I0, V, V1, V2, 3V0, dV/dt, P,
• Dead-bus and dead-line 1-phase Q, cos ϕ I, IE, IE sens., V, VE, P, Q, cos ϕ
• Bypassing Without fixed phase relation f, df/dt, binary input 5
Pickup when Exceeding or falling below threshold
Voltages value
Max. operating voltage Vmax 20 to 140 V (phase-to-phase) Setting ranges
(in steps of 1 V) Current I, I1, I2, 3I0, IE 0.15 to 200 A1) (in steps of 0.01 A)
Min. operating voltage Vmin 20 to 125 V (phase-to-phase) Current ratio I2/I1 15 to 100 % (in steps of 1 %)
(in steps of 1 V) Sens. earth curr. IE sens. 0.001 to 1.5 A (in steps of 0.001 A)
V< for dead-line / dead-bus check 1 to 60 V (phase-to-phase) Voltages V, V1, V2, 3V0 2 to 260 V (in steps of 0.1 V)
(in steps of 1 V) Displacement voltage VE 2 to 200 V (in steps of 0.1 V)
V> for live-line / live-bus check 20 to 140 V (phase-to-phase) Power P, Q 0.5 to 10000 W (in steps of 0.1 W)
(in steps of 1 V) Power factor (cos ϕ) - 0.99 to + 0.99 (in steps of 0.01)
Primary rated voltage of 0.1 to 800 kV (in steps of 0.01 kV) Frequency fN = 50 Hz 40 to 60 Hz (in steps of 0.01 Hz)
transformer V2nom fN = 60 Hz 50 to 70 Hz (in steps of 0.01 Hz)
Tolerances 2 % of pickup value or 2 V Rate-of-frequency change df/dt 0.1 to 20 Hz/s (in steps of 0.01 Hz/s)
Drop-off to pickup ratios approx. 0.9 (V>) or 1.1 (V<) Voltage change dV/dt 4 V/s to 100 V/s (in steps of 1 V/s)
ΔV-measurement Dropout ratio >- stage 1.01 to 3 (insteps of 0.01)
Voltage difference 0.5 to 50 V (phase-to-phase) Dropout ratio <- stage 0.7 to 0.99 (in steps of 0.01)
(in steps of 1 V) Dropout differential f 0.02 to 1.00 Hz (in steps of 0.01 Hz)
Tolerance 1V Pickup delay time 0 to 60 s (in steps of 0.01 s)
Trip delay time 0 to 3600 s (in steps of 0.01 s)
Δf-measurement Dropout delay time 0 to 60 s (in steps of 0.01 s)
Δf-measurement (f2>f1; f2<f1) 0.01 to 2 Hz (in steps of 0.01 Hz)
Tolerance 15 mHz Times
Pickup times
Δα-measurement Current, voltage
Δα-measurement 2 ° to 80 ° (in steps of 1 °) (phase quantities)
(α2>α1; α2>α1) With 2 times the setting value Approx. 30 ms
Tolerance 2° With 10 times the setting value Approx. 20 ms
Max. phase displacement 5 ° for Δf ≤ 1 Hz Current, voltages
10 ° for Δf > 1 Hz (symmetrical components)
Adaptation With 2 times the setting value Approx. 40 ms
Vector group adaptation by angle 0 ° to 360 ° (in steps of 1 °) With 10 times the setting value Approx. 30 ms
Different voltage 0.5 to 2 (in steps of 0.01) Power
transformers V1/V2 Typical Approx. 120 ms
Maximum (low signals and Approx. 350 ms
Times
thresholds)
Minimum measuring time Approx. 80 ms
Power factor 300 to 600 ms
Max. duration TSYN DURATION 0.01 to 1200 s; ∞ (in steps of 0.01 s)
Frequency Approx. 100 ms
Supervision time TSUP VOLTAGE 0 to 60 s (in steps of 0.01 s)
Rate-of-frequency change
Closing time of CB TCB close 0 to 60 s (in steps of 0.01 s)
With 1.25 times the setting value Approx. 220 ms
Tolerance of all timers 1 % of setting value or 10 ms
Voltage change dV/dt
For 2 times pickup value Approx. 220 ms
Measuring values of synchro-check function
Binary input Approx. 20 ms
Reference voltage V1 In kV primary, in V secondary or in % Vnom
Range 10 to 120 % Vnom
Tolerance*) ≤1 % of measured value or 0.5 % of Vnom
Voltage to be synchronized V2 InkVprimary,inVsecondaryorin%Vnom
Range 10to120%Vnom
Tolerance*) ≤1 % of measured value or 0.5 % of Vnom
*) With rated frequency.
1) At Inom = 1 A, all limits divided by 5.

Siemens SIP · Edition No. 6 5/105


5 Overcurrent Protection / 7SJ62

Technical data

Flexible protection functions (ANSI 27, 32, 47, 50, 55, 59, 81R) (cont'd) Starting time monitoring for motors (ANSI 48)
Dropout times Setting ranges
Current, voltage (phase < 20 ms Motor starting current ISTARTUP 2.5 to 80 A1) (in steps of 0.01)
quantities) Pickup threshold IMOTOR START 2 to 50 A1) (in steps of 0.01)
Current, voltages (symmetrical < 30 ms Permissible starting 1 to 180 s (in steps of 0.1 s)
components) time TSTARTUP, cold motor
Power Permissible starting time 0.5 to 180 s (in steps of 0.1 s)
Typical < 50 ms TSTARTUP, warm motor
Maximum < 350 ms Temperature threshold 0 to 80 % (in steps of 1 %)
Power factor < 300 ms cold motor
Frequency < 100 ms Permissible blocked rotor 0.5 to 120 s or ∞ (in steps of 0.1 s)
Rate-of-frequency change < 200 ms time TLOCKED-ROTOR
Voltage change < 220 ms Tripping time characteristic 2

t = ⎛⎜
Binary input < 10 ms I STARTUP ⎞
For I > IMOTOR START ⎟ ⋅ TSTARTUP
Tolerances ⎝ I ⎠
Pickup threshold ISTARTUP = Rated motor starting
Current 0.5 % of setting value or 50 mA1) current
Current (symmetrical 1 % of setting value or 100 mA1) I = Actual current flowing
5
components) TSTARTUP = Tripping time for rated
Voltage 0.5 % of setting value or 0.1 V motor starting current
Voltage (symmetrical 1 % of setting value or 0.2 V t = Tripping time in seconds
components)
Power 1 % of setting value or 0.3 W Dropout ratio IMOTOR START Approx. 0.95
Power factor 2 degrees Tolerances
Frequency 5 mHz (at V = VN, f = fN) Pickup threshold 2 % of setting value or 50 mA1)
10 mHz (at V = VN) Delay time 5 % or 30 ms
Rate-of-frequency change 5 % of setting value or 0.05 Hz/s
Voltage change dV/dt 5 % of setting value or 1.5 V/s Load jam protection for motors (ANSI 51M)
Times 1 % of setting value or 10 ms Setting ranges
Negative-sequence current detection (ANSI 46) Current threshold for 0.25 to 60 A1) (in steps 0.01 A)
alarm and trip
Definite-time characteristic (ANSI 46-1 and 46-2) Delay times 0 to 600 s (in steps 0.01 s)
Setting ranges Blocking duration after 0 to 600 s (in steps 0.01 s)
Pickup current I2>, I2>> 0.5 to 15 A or ∞ (in steps of 0.01 A) CLOSE signal detection
Delay times 0 to 60 s or ∞ (in steps of 0.01 s) Tolerances
Dropout delay time TDO 0 to 60 s (in steps of 0.01 s) Pickup threshold 2 % of setting value or 50 mA1)
Delay time
Functional limit All phase currents ≤ 50 A 1) 1 % of setting value or 10 ms
Times Restart inhibit for motors (ANSI 66)
Pickup times Approx. 35 ms Setting ranges
Dropout times Approx. 35 ms Motor starting current relative 1.1 to 10 (in steps of 0.1)
Dropout ratio Approx. 0.95 for I2 /Inom > 0.3 to rated motor current
Tolerances IMOTOR START/IMotor Nom
Pickup thresholds 3 % of the setting value or 50 mA1) Rated motor current IMotor Nom 1 to 6 A1) (in steps of 0.01 A)
Delay times 1 % or 10 ms Max. permissible starting time 1 to 320 s (in steps of 1 s)
TStart Max
Inverse-time characteristic (ANSI 46-TOC)
Equilibrium time TEqual 0 min to 320 min (in steps of 0.1 min)
Setting ranges Minimum inhibit time 0.2 min to 120 min (in steps of 0.1 min)
Pickup current 0.5 to 10 A1) (in steps of 0.01 A) TMIN. INHIBIT TIME
Time multiplier T 0.05 to 3.2 s or ∞ (in steps of 0.01 s) Max. permissible number of 1 to 4 (in steps of 1)
(IEC characteristics) warm starts
Time multiplier D 0.5 to 15 s or ∞ (in steps of 0.01 s) Difference between cold and 1 to 2 (in steps of 1)
(ANSI characteristics) warm starts
Functional limit All phase currents ≤ 50 A 1) Extension k-factor for cooling 0.2 to 100 (in steps of 0.1)
simulations of rotor at zero
Trip characteristics speed kτ at STOP
IEC Normal inverse, very inverse, Extension factor for cooling time 0.2 to 100 (in steps of 0.1)
extremely inverse constant with motor running
ANSI Inverse, moderately inverse, kτ RUNNING
very inverse, extremely inverse nc − 1
Restarting limit Θ restart = Θ rot max perm ⋅
Pickup threshold Approx. 1.1 · I2p setting value nc
Dropout Θrestart = Temperature limit below
IEC and ANSI Approx. 1.05 · I2p setting value, which restarting is possible
(without disk emulation) which is approx. 0.95 · pickup threshold Θrot max perm = Maximum permissible
ANSI with disk emulation Approx. 0.90 · I2p setting value rotor overtemperature
Tolerances (= 100 % in operational
Pickup threshold 3 % of the setting value or 50 mA1) measured value
Time for 2 ≤ M ≤ 20 5 % of setpoint (calculated) Θrot/Θrot trip)
+2 % current tolerance, at least 30 ms 1) For Inom = 1 A, nc = Number of permissible
all limits divided by 5. start-ups from cold state

5/106 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Technical data

Undercurrent monitoring (ANSI 37) Tolerances


Signal from the operational Predefined with programmable logic Pickup thresholds 1 % of setting value or 1 V
measured values Times 1 % of setting value or 10 ms

Temperature monitoring box (ANSI 38) Frequency protection (ANSI 81)

Temperature detectors Number of frequency elements 4


Connectable boxes 1 or 2 Setting ranges
Number of temperature Max. 6 Pickup thresholds for fnom = 50 Hz 40 to 60 Hz (in steps of 0.01 Hz)
detectors per box Pickup thresholds for fnom = 60 Hz 50 to 70 Hz (in steps of 0.01 Hz)
Type of measuring Pt 100 Ω or Ni 100 Ω or Ni 120 Ω Dropout differential = |pickup 0.02 Hz to 1.00 Hz (in steps of 0.01 Hz)
Mounting identification “Oil” or “Environment” or “Stator” or threshold - dropout threshold|
“Bearing” or “Other” Delay times
Undervoltage blocking, with 0 to 100 s or ∞ (in steps of 0.01 s)
Thresholds for indications positive-sequence voltage V1 10 to 150 V (in steps of 1 V)
For each measuring detector
Stage 1 -50 °C to 250 °C (in steps of 1 °C) Times
-58 °F to 482 °F (in steps of 1 °F) Pickup times Approx. 150 ms
or ∞ (no indication) Dropout times Approx. 150 ms
Stage 2 -50 °C to 250 °C (in steps of 1 °C) Dropout
-58 °F to 482 °F (in steps of 1 °F)
or ∞ (no indication)
Ratio undervoltage blocking Approx. 1.05
5
Tolerances
Undervoltage protection (ANSI 27) Pickup thresholds
Frequency 5 mHz (at V = VN, f = fN)
Operating modes/measuring 10 mHz (at V = VN)
quantities Undervoltage blocking 3 % of setting value or 1 V
3-phase Positive phase-sequence voltage or Delay times 3 % of the setting value or 10 ms
phase-to-phase voltages or Fault locator (ANSI 21FL)
phase-to-earth voltages
Output of the fault distance in Ω primary and secondary,
1-phase Single-phase phase-earth or
in km or miles line length,
phase-phase voltage
in % of line length
Setting ranges
Starting signal Trip command, dropout of a
Pickup thresholds V<, V<<
protection element, via binary input
dependent on voltage 10 to 120 V (in steps of 1 V)
connection and chosen 10 to 210 V (in steps of 1 V) Setting ranges
measuring quantity Reactance (secondary) 0.001 to 1.9 Ω/km1) (in steps of 0.0001)
0.001 to 3 Ω/mile1) (in steps of 0.0001)
Dropout ratio r 1.01 to 3 (in steps of 0.01)
Delay times T 0 to 100 s or ∞ (in steps of 0.01 s)
Current Criteria "Bkr Closed 0.2 to 5 A1) (in steps of 0.01 A) Tolerances
IMIN" Measurement tolerance acc. to 2.5 % fault location, or 0.025 Ω
Times VDE 0435, Part 303 for sinusoi- (without intermediate infeed) for
Pickup times Approx. 50 ms dal measurement quantities 30 ° ≤ ϕK ≤ 90 ° and VK/Vnom ≥ 0.1
Dropout times As pickup times and IK/Inom ≥ 1
Tolerances Additional functions
Pickup thresholds 1 % of setting value or 1 V Operational measured values
Times 1 % of setting value or 10 ms
Currents In A (kA) primary,
Overvoltage protection (ANSI 59) IL1, IL2, IL3 in A secondary or in % Inom
Operating modes/measuring Positive-sequence component I1
quantities Negative-sequence component I2
IE or 3I0
3-phase Positive phase-sequence voltage or
negative phase-sequence voltage or Range 10 to 200 % Inom
phase-to-phase voltages or Tolerance2) 1 % of measured value or 0.5 % Inom
phase-to-earth voltages Phase-to-earth voltages In kV primary, in V secondary or in % Vnom
1-phase Single-phase phase-earth or VL1-E, VL2-E, VL3-E
phase-phase voltage Phase-to-phase voltages
Setting ranges VL1-L2, VL2-L3, VL3-L1, VE or V0
Pickup thresholds V>, V>> Positive-sequence component V1
dependent on voltage 40 to 260 V (in steps of 1 V) Negative-sequence component V2
connection and chosen 40 to 150 V (in steps of 1 V) Range 10 to 120 % Vnom
measuring quantity 2 to 150 V (in steps of 1 V) Tolerance2) 1 % of measured value or 0.5 % of Vnom
Dropout ratio r 0.9 to 0.99 (in steps of 0.01) S, apparent power In kVAr (MVAr or GVAr) primary
Delay times T 0 to 100 s or ∞ (in steps of 0.01 s) and in % of Snom
Times Range 0 to 120 % Snom
Pickup times V Approx. 50 ms Tolerance2) 1 % of Snom
Pickup times V1, V2 Approx. 60 ms for V/Vnom and I/Inom = 50 to 120 %
Dropout times As pickup times
P, active power With sign, total and phase-segregated in
1) For Inom = 1 A, all limits divided by 5. 2) At rated frequency. kW (MW or GW) primary and in % Snom

Siemens SIP · Edition No. 6 5/107


5 Overcurrent Protection / 7SJ62

Technical data

Operational measured values (cont'd) Min./Max. values for voltages VL1-E, VL2-E, VL3-E
Range 0 to 120 % Snom V1 (positive-sequence component)
Tolerance2) 1 % of Snom VL1-L2, VL2-L3, VL3-L1
for V/Vnom and I/Inom = 50 to 120 % Min./Max. values for power S, P, Q, cos ϕ, frequency
and ⏐cos ϕ⏐ = 0.707 to 1 with Min./Max. values for overload Θ/ΘTrip
Snom = 3 ⋅ Vnom ⋅ I nom protection
Q, reactive power With sign, total and phase-segregated Min./Max. values for mean values IL1dmd, IL2dmd, IL3dmd
in kVAr (MVAr or GVAr)primary and I1 (positive-sequence component);
in % Snom Sdmd, Pdmd, Qdmd
Range 0 to 120 % Snom Local measured values monitoring
Tolerance2) 1 % of Snom
for V/Vnom and I/Inom = 50 to 120 % Current asymmetry Imax/Imin > balance factor,
and ⏐sin ϕ⏐ = 0.707 to 1 with for I>Ibalance limit
Snom = 3 ⋅ Vnom ⋅ I nom Voltage asymmetry Vmax/Vmin > balance factor,
cos ϕ, power factor (p.f.) Total and phase segregated for V>Vlim
Range - 1 to + 1 Current phase sequence Clockwise (ABC) / counter-clockwise
Tolerance2) 2 % for ⏐cos ϕ⏐ ≥ 0.707 (ACB)
5 Frequency f In Hz Voltage phase sequence Clockwise (ABC) / counter-clockwise
(ACB)
Range fnom ± 5 Hz
Tolerance2) 20 mHz Limit value monitoring Predefined limit values, user-defined
expansions via CFC
Temperature overload protection In %
Θ/ΘTrip Fuse failure monitor
For all network types With the option of blocking affected
protection functions
Range 0 to 400 %
Tolerance2) 5 % class accuracy per IEC 60255-8 Fault recording

Temperature restart inhibit In % Recording of indications of the last


ΘL/ΘL Trip 8 power system faults

Range 0 to 400 % Recording of indications of the last


Tolerance2) 5 % class accuracy per IEC 60255-8 3 power system ground faults

Restart threshold ΘRestart/ΘL Trip In % Time stamping

Reclose time TReclose In min Resolution for event log 1 ms


(operational annunciations)
Currents of sensitive ground fault In A (kA) primary and in mA second-
detection (total, real, and reactive ary Resolution for trip log 1 ms
current) IEE, IEE real, IEE reactive (fault annunciations)

Range 0 mA to 1600 mA Maximum time deviation 0.01 %


Tolerance2) 2 % of measured value or 1 mA (internal clock)

RTD-box See section "Temperature monitoring Battery Lithium battery 3 V/1 Ah,
box" type CR 1/2 AA, message "Battery
Fault" for insufficient battery charge
Long-term averages
Oscillographic fault recording
Time window 5, 15, 30 or 60 minuets
Maximum 8 fault records saved,
Frequency of updates Adjustable memory maintained by buffer bat-
Long-term averages tery in case of loss of power supply
of currents IL1dmd, IL2dmd, IL3dmd, I1dmd in A (kA) Recording time Total 20 s
of real power Pdmd in W (kW, MW) Pre-trigger and post-fault recording
of reactive power Qdmd in VAr (kVAr, MVAr) and memory time adjustable
of apparent power Sdmd in VAr (kVAr, MVAr)
Sampling rate for 50 Hz 1 sample/1.25 ms (16 samples/cycle)
Max. / Min. report Sampling rate for 60 Hz 1 sample/1.04 ms (16 samples/cycle)
Report of measured values With date and time Energy/power
Reset, automatic Time of day adjustable (in minutes, Meter values for power in kWh (MWh or GWh) and kVARh
0 to 1439 min) Wp, Wq (real and reactive power (MVARh or GVARh)
Time frame and starting time adjust- demand)
able (in days, 1 to 365 days, and ∞)
Tolerance1) ≤ 2 % for I > 0.1 Inom, V > 0.1 Vnom
Reset, manual Using binary input, and ⏐cos ϕ⏐ (p.f.) ≥ 0.707
using keypad,
via communication Statistics

Min./Max. values for current IL1, IL2, IL3, Saved number of trips Up to 9 digits
I1 (positive-sequence component) Number of automatic reclosing Up to 9 digits
commands (segregated according
to 1st and ≥ 2nd cycle)
1) At Inom = 1 A, all limits multiplied with 5.
2) At rated frequency.
5/108 Siemens SIP · Edition No. 6
5 Overcurrent Protection / 7SJ62

Technical data

Circuit-breaker wear CE conformity


Methods • ΣIx with x = 1 .. 3 This product is in conformity with the Directives of the European Commu-
• 2-point method (remaining service nities on the harmonization of the laws of the Member States relating to
life) electromagnetic compatibility (EMC Council Directive 89/336/EEC) and
electrical equipment designed for use within certain voltage limits (Council
• Σi2t Directive 73/23/EEC).
Operation Phase-selective accumulation of mea- This unit conforms to the international standard IEC 60255, and the Ger-
sured values on TRIP command, up to man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
8 digits, phase-selective limit values,
monitoring indication Further applicable standards: ANSI/IEEE C37.90.0 and C37.90.1.
The unit conforms to the international standard IEC 60255, and the Ger-
Motor statistics
man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
Total number of motor start-ups 0 to 9999 (resolution 1)
This conformity is the result of a test that was performed by Siemens AG in
Total operating time 0 to 99999 h (resolution 1 h)
accordance with Article 10 of the Council Directive complying with the
Total down-time 0 to 99999 h (resolution 1 h)
generic standards EN 50081-2 and EN 50082-2 for the EMC Directive and
Ratio operating time/down-time 0 to 100 % (resolution 0.1 %)
standard EN 60255-6 for the “low-voltage Directive”.
Active energy and reactive energy See operational measured values
Motor start-up data: Of the last 5 start-ups
– Start-up time 0.30 s to 9999.99 s (resolution 10 ms)
– Start-up current (primary)
– Start-up voltage (primary)
0 A to 1000 kA
0 V to 100 kV
(resolution 1 A)
(resolution 1 V)
5
Operating hours counter
Display range Up to 7 digits
Criterion Overshoot of an adjustable current
threshold (BkrClosed IMIN)
Trip circuit monitoring
With one or two binary inputs
Commissioning aids
Phase rotation field check,
operational measured values,
circuit-breaker/switching device
test, creation of a test measurement
report
Clock
Time synchronization DCF77/IRIG-B signal
(telegram format IRIG-B000),
binary input,
communication
Setting group switchover of the function parameters
Number of available setting groups 4 (parameter group A, B, C and D)
Switchover performed Via keypad, DIGSI, system (SCADA)
interface or binary input
Control
Number of switching units Depends on the binary inputs and
outputs
Interlocking Programmable
Circuit-breaker signals Feedback, close, open, intermediate
position
Control commands Single command / double command
1, 1 plus 1 common or 2 trip contacts
Programmable controller CFC logic, graphic input tool
Local control Control via menu,
assignment of a function key
Remote control Via communication interfaces,
using a substation automation and
control system (e.g. SICAM),
DIGSI 4 (e.g. via modem)

Siemens SIP · Edition No. 6 5/109


5 Overcurrent Protection / 7SJ62

Selection and ordering data Description Order No.


7SJ62 multifunction protection relay 7SJ62¨o – ¨¨¨¨¨ – ¨¨¨¨
Housing, inputs, outputs
Housing 1/3 19”, 4 line text display, 3 x U, 4 x I, 8 BI, 8 BO, 1 live status-contact 1
Housing 1/3 19”, 4 line text display, 3 x U, 4 x I, 11 BI, 6 BO, 1 live status-contact 2
Housing 1/3 19”, 4 line text display, 4 x U, 4 x I, 8 BI, 8 BO, 1 live status-contact 3 see
Housing 1/3 19”, 4 line text display, 4 x U, 4 x I, 11 BI, 6 BO, 1 live status-contact 4 next
Housing 1/2 19”, graphic display, 4 x U, 4 x I, 8 BI, 8 BO, 1 live status contact 7) 5 page
Housing 1/2 19”, graphic display, 4 x U, 4 x I, 11 BI, 6 BO, 1 live status contact 7) 6

Measuring inputs (3 x V / 4 x V, 4 x I)
Iph = 1 A1), Ie = 1 A1) (min. = 0.05 A)
Position 15 only with A, C, E, G 1
Iph = 1 A1), Ie = sensitive (min. = 0.001 A)
Position 15 only with B, D, F, H 2
Iph = 5 A1), Ie = 5 A1) (min. = 0.25 A)
Position 15 only with A, C, E, G 5
Iph = 5 A1), Ie = sensitive (min. = 0.001 A)
Position 15 only with B, D, F, H 6
5 Iph = 5 A1), Ie = 1 A1) (min. = 0.05 A)
Position 15 only with A, C, E, G 7

Rated auxiliary voltage (power supply, indication voltage)


24 to 48 V DC, threshold binary input 19 DC3) 2
60 to 125 V DC2), threshold binary input 19 DC3) 4
110 to 250 V DC2), 115 to 230 V4) AC, threshold binary input 88 V DC3) 5
110 to 250 V DC2), 115 to 230 V4) AC, threshold binary input 176 V DC3) 6

Unit version
For panel surface mounting, two-tier terminal top/bottom B
For panel flush mounting, plug-in terminal, (2/3 pin connector) D
For panel flush mounting, screw-type terminal (direct connection/ring-type cable lugs) E

Region-specific default settings/function versions and language settings


Region DE, 50 Hz, IEC, language: German, selectable A
Region World, 50/60 Hz, IEC/ANSI, language: English (GB), selectable B
Region US, 60 Hz, ANSI, language: English (US), selectable C
Region FR, 50/60 Hz, IEC/ANSI, language: French, selectable D
Region World, 50/60 Hz, IEC/ANSI, language: Spanish, selectable E
Region IT, 50/60 Hz, IEC/ANSI, language: Italian (language selectable) F
Region RU, 50/60 Hz, IEC/ANSI, language: Russian(language can be changed) G

System interface (Port B): Refer to page 5/114


No system interface 0
Protocols see page 5/114

Service interface (Port C)


1) Rated current can be selected by No interface at rear side 0
means of jumpers.
DIGSI 4/modem, electrical RS232 1
2) Transition between the two auxiliary DIGSI 4/modem/RTD-box5), electrical RS485 2
voltage ranges can be selected by
DIGSI 4/modem/RTD-box5)6), optical 820 nm wave length, ST connector 3
means of jumpers.
3) The binary input thresholds can be
Measuring/fault recording
selected per binary input by means of
jumpers.
Fault recording 1
Slave pointer, mean values, min/max values, fault recording 3
4) 230 V AC, starting from device version
…/EE.
5) Temperature monitoring box
7XV5662-oAD10, refer to “Accessories”.
6) When using the temperature monitoring
box at an optical interface, the additional
RS485 fiber-optic converter
7XV5650-0oA00 is required.
7) starting from device version .../GG
and FW-Version V4.82

5/110 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Selection and ordering data Description Order No.


7SJ62 multifunction protection relay 7SJ62¨o – ¨¨¨¨¨ – ¨¨¨¨
Designation ANSI No. Description
Basic version Control
50/51 Time-overcurrent protection I>, I>>, I>>>, Ip
50N/51N Earth-fault protection IE>, IE>>, IE>>>, IEp
50N/51N Insensitive earth-fault protection via
IEE function: IEE>, IEE>>, IEEp1)
50/50N Flexible protection functions (index quantities derived
from current): Additional time-overcurrent protection
stages I2>, I>>>>, IE>>>>
51 V Voltage-dependent inverse-time overcurrent protection
49 Overload protection (with 2 time constants)
46 Phase balance current protection
(negative-sequence protection)
37 Undercurrent monitoring
47 Phase sequence
59N/64 Displacement voltage
50BF Breaker failure protection
74TC Trip circuit supervision
4 setting groups, cold-load pickup
Inrush blocking
5
86 Lockout
n V, P, f 27/59 Under-/overvoltage
81O/U Under-/overfrequency
27/47/59(N) Flexible protection (index quantities derived from
32/55/81R current and voltages): Voltage, power, p.f.,
rate-of-frequency-change protection F E
n IEF V, P, f 27/59 Under-/overvoltage
81O/U Under-/overfrequency
27/47/59(N) Flexible protection (index quantities derived from
32/55/81R current and voltages): Voltage, power, p.f.,
rate-of-frequency-change protection
Intermittent earth fault P E
n Dir 67/67N Direction determination for overcurrent,
phases and earth F C
n Dir V, P, f 67/67N Direction determination for overcurrent, phases and earth
27/59 Under-/overvoltage
81O/U Under-/overfrequency
27/47/59(N) Flexible protection (index quantities derived from
32/55/81R current and voltages): Voltage, power, p.f.,
rate-of-frequency-change protection F G
n Dir IEF 67/67N Direction determination for overcurrent,
phases and earth
Intermittent earth fault P C

Directional Dir 67/67N Direction determination for overcurrent,


earth-fault phases and earth
detection 67Ns Directional sensitive earth-fault detection
n 87N High-impedance restricted earth fault F D 2)
Directional V, P, f 67Ns Directional sensitive earth-fault detection
earth-fault 87N High-impedance restricted earth fault
detection 27/59 Under-/overvoltage
n 81O/U Under-/overfrequency
27/47/59(N) Flexible protection (index quantities derived from
32/55/81R current and voltages): Voltage, power, p.f.,
F F 2)
rate-of-frequency-change protection
Directional Dir IEF 67/67N Direction determination for overcurrent,
earth-fault phases and earth
n Basic version included detection 67Ns Directional sensitive earth-fault detection
V, P, f = Voltage, power, n 87N High-impedance restricted earth fault
frequency protection Intermittent earth fault P D 2)
Dir = Directional overcurrent protection
IEF = Intermittent earth fault
1) Only with insensitive earth-current
transformer when position 7 = 1, 5, 7.
2) For isolated/compensated networks
only with sensitive earth-current
transformer when position 7 = 2, 6. Continued on next page

Siemens SIP · Edition No. 6 5/111


5 Overcurrent Protection / 7SJ62

Selection and ordering data Description Order No. Order


code
7SJ62 multifunction protection relay 7SJ62¨o – ¨¨¨¨¨ – ¨¨¨¨–¨¨¨¨
Designation ANSI No. Description
Basic version Control
50/51 Time-overcurrent protection I>, I>>, I>>>, Ip
50N/51N Earth-fault protection IE>, IE>>, IE>>>, IEp
50N/51N Insensitive earth-fault protection via
IEE function: IEE>, IEE>>, IEEp1)
50/50N Flexible protection functions (index quantities
derived from current): Additional time-
overcurrent protection
stages I2>, I>>>>, IE>>>>
51 V Voltage-dependent inverse-time overcurrent
protection
49 Overload protection (with 2 time constants)
46 Phase balance current protection
(negative-sequence protection)
37 Undercurrent monitoring
47 Phase sequence
5 59N/64 Displacement voltage
50BF Breaker failure protection
74TC Trip circuit supervision
4 setting groups, cold-load pickup
Inrush blocking
86 Lockout
Directional 67Ns Directional sensitive earth-fault detection
earth-fault 87N High-impedance restricted earth fault
detection
n F B 2)
Directional Motor V, P, f 67Ns Directional sensitive earth-fault detection
earth-fault 87N High-impedance restricted earth fault
detection 48/14 Starting time supervision, locked rotor
n 66/86 Restart inhibit
51M Load jam protection, motor statistics
27/59 Under-/overvoltage
81O/U Under-/overfrequency
27/47/59(N) Flexible protection (index quantities derived from
32/55/81R current and voltages): Voltage, power, p.f.,
2)
rate-of-frequency-change protection H F
Directional Motor V, P, f 67/67N Direction determination for
earth-fault Dir overcurrent, phases and earth
detection 67Ns Directional sensitive earth-fault detection
87N High-impedance restricted earth fault
48/14 Starting time supervision, locked rotor
66/86 Restart inhibit
51M Load jam protection, motor statistics
27/59 Under-/overvoltage
81O/U Under-/overfrequency
27/47/59(N) Flexible protection (index quantities derived from
32/55/81R current and voltages): Voltage, power, p.f.,
2)
rate-of-frequency-change protection HH
Directional Motor IEF V, P, f 67/67N Direction determination for
earth-fault Dir overcurrent, phases and earth
detection 67Ns Directional sensitive earth-fault detection
n 87N High-impedance restricted earth fault
Intermittent earth fault
n Basic version included 48/14 Starting time supervision, locked rotor
V, P, f = Voltage, power, 66/86 Restart inhibit
frequency protection 51M Load jam protection, motor statistics
27/59 Undervoltage/overvoltage
Dir = Directional overcurrent protection 81O/U Underfrequency/overfrequency
IEF = Intermittent earth fault 27/47/59(N) Flexible protection (index quantities derived from
1) Only with insensitive earth-current 32/55/81R current and voltages): Voltage, power, p.f.,
2)
transformer when position 7 = 1, 5, 7. rate-of-frequency-change protection RH
2) For isolated/compensated networks
only with sensitive earth-current
transformer when position 7 = 2, 6. Continued on next page

5/112 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Selection and ordering data Description Order No. Order


code
7SJ62 multifunction protection relay 7SJ62¨o – ¨¨¨¨¨ – ¨¨¨¨–¨¨¨¨
Designation ANSI No. Description
Basic version Control
50/51 Time-overcurrent protection I>, I>>, I>>>, Ip
50N/51N Earth-fault protection IE>, IE>>, IE>>>, IEp
50N/51N Insensitive earth-fault protection via
IEE function: IEE>, IEE>>, IEEp1)
50/50N Flexible protection functions (index quantities
derived from current): Additional time-
overcurrent protection
stages I2>, I>>>>, IE>>>>
51 V Voltage-dependent inverse-time overcurrent
protection
49 Overload protection (with 2 time constants)
46 Phase balance current protection
(negative-sequence protection)
37 Undercurrent monitoring
47 Phase sequence
59N/64 Displacement voltage 5
50BF Breaker failure protection
74TC Trip circuit supervision
4 setting groups, cold-load pickup
Inrush blocking
86 Lockout
n Motor V, P, f 67/67N Direction determination for overcurrent,
Dir phases and earth
48/14 Starting time supervision, locked rotor
66/86 Restart inhibit
51M Load jam protection, motor statistics
27/59 Under-/overvoltage
81O/U Under-/overfrequency
27/47/59(N)Flexible protection (index quantities derived from
32/55/81R current and voltages): Voltage, power, p.f.,
rate-of-frequency-change protection HG
n Motor 48/14 Starting time supervision, locked rotor
66/86 Restart inhibit
51M Load jam protection, motor statistics HA
ARC, fault locator, synchro-check Without 0
79 With auto-reclosure 1
21FL With fault locator 2
79, 21FL With auto-reclosure, with fault locator 3
25 With synchro-check4) 4 5)
25, 79, 21FL With synchro-check4), auto-reclosure,
fault locator 7 5)
ATEX100 Certification
For protection of explosion-protected motos (increased-safety type of protection "e" Z X 9 9 3)
n Basic version included
V, P, f = Voltage, power,
frequency protection
Dir = Directional overcurrent protection
IEF = Intermittent earth fault
1) Only with insensitive earth-current
transformer when position 7 = 1, 5, 7.
2) For isolated/compensated networks
only with sensitive earth-current
transformer when position 7 = 2, 6.
3) This variant will be supplied with a
previous firmware version.
4) Synchro-check (no asynchronous
switching), one function group; available
only with devices 7SJ623 and 7SJ624
5) Ordering option only available for devices
7SJ623 and 7SJ624

Siemens SIP · Edition No. 6 5/113


5 Overcurrent Protection / 7SJ62

Order number for system port B Description Order No. Order


code
7SJ62 multifunction protection relay 7SJ62oo – ooooo – ¨¨¨¨–ooo
System interface (on rear of unit, Port B)
No system interface 0
IEC 60870-5-103 protocol, RS232 1
IEC 60870-5-103 protocol, RS485 2
IEC 60870-5-103 protocol, 820 nm fiber, ST connector 3
PROFIBUS-FMS Slave, RS485 4
PROFIBUS-FMS Slave, 820 nm wavelength, single ring, ST connector 1) 5
1)
PROFIBUS-FMS Slave, 820 nm wavelength, double ring, ST connector 6
PROFIBUS-DP Slave, RS485 9 L 0 A
1)
PROFIBUS-DP Slave, 820 nm wavelength, double ring, ST connector 9 L 0B
MODBUS, RS485 9 L 0D
2)
MODBUS, 820 nm wavelength, ST connector 9 L 0 E
5 DNP 3.0, RS485 9 L 0G
2)
DNP 3.0, 820 nm wavelength, ST connector 9 L 0H
IEC 60870-5-103 protocol, redundant, RS485, RJ45 connector 2) 9 L 0P
IEC 61850, 100 Mbit Ethernet, electrical, double, RJ45 connector (EN 100) 9 L 0R
IEC 61850, 100 Mbit Ethernet, optical, double, LC connector (EN 100) 2) 9 L 0 S
1) Not with position 9 = “B”; if 9 = “B”, please order 7SJ6 unit with RS485 port and separate fiber-optic converters.
For single ring, please order converter 6GK1502-2CB10, not available with position 9 = “B”.
For double ring, please order converter 6GK1502-3CB10, not available with position 9 = “B”.
The converter requires a 24 V AC power supply (e.g. power supply 7XV5810-0BA00)
2) Not available with position 9 = “B”

Sample order Position Order No. + Order code


7SJ6225-5EC91-3FC1+L0G

6 I/O’s: 11 BI/6 BO, 1 live status contact 2


7 Current transformer: 5 A 5
8 Power supply: 110 to 250 V DC, 115 V AC to 230 V AC 5
9 Unit version: Flush-mounting housing, screw-type terminals E
10 Region: US, English language (US); 60 Hz, ANSI C
11 Communication: System interface: DNP 3.0, RS485 9 L 0G
12 Communication: DIGSI 4, electric RS232 1
13 Measuring/fault recording: Extended measuring and fault records 3
14/15 Protection function package: Basic version plus directional TOC FC
16 With auto-reclosure 1

5/114 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Accessories Description Order No.

DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows 2000/XP Professional Edition
Basis Full version with license for 10 computers, on CD-ROM
(authorization by serial number) 7XS5400-0AA00
Professional DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00
Professional + IEC 61850
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation)
+ IEC 61850 system configurator 7XS5403-0AA00

IEC 61850 System configurator


Software for configuration of stations with IEC 61850 communication under
DIGSI, running under MS Windows 2000 or XP Professional Edition
Optional package for DIGSI 4 Basis or Professional
5
License for 10 PCs. Authorization by serial number. On CD-ROM 7XS5460-0AA00

SIGRA 4
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers (Comtrade
format). Running under MS Windows 2000 or XP Professional Edition.
(generally contained in DIGSI Professional, but can be ordered additionally)
Authorization by serial number. On CD-ROM. 7XS5410-0AA00

Temperature monitoring box


24 to 60 V AC/DC 7XV5662-2AD10
90 to 240 V AC/DC 7XV5662-5AD10

Varistor/Voltage arrester
Voltage arrester for high-impedance REF protection
125 Vrms; 600 A; 1S/S 256 C53207-A401-D76-1
240 Vrms; 600 A; 1S/S 1088 C53207-A401-D77-1

Connecting cable
Cable between PC/notebook (9-pin con.) and protection unit (9-pin connector)
(contained in DIGSI 4, but can be ordered additionally) 7XV5100-4
Cable between temperature monitoring box and SIPROTEC 4 unit
- length 5 m /16.4 ft 7XV5103-7AA05
- length 25 m /82 ft 7XV5103-7AA25
- length 50 m /164 ft 7XV5103-7AA50

Manual for 7SJ62


English C53000-G1140-C207-x 1)

1) x = please inquire for latest edition (exact Order No.).

Siemens SIP · Edition No. 6 5/115


5 Overcurrent Protection / 7SJ62

Accessories Description Order No. Size of package Supplier

LSP2289-afp.eps
Terminal safety cover
Voltage/current terminal 18-pole/12-pole C73334-A1-C31-1 1 Siemens
Voltage/current terminal 12-pole/8-pole C73334-A1-C32-1 1 Siemens
Connector 2-pin C73334-A1-C35-1 1 Siemens
Mounting rail
Connector 3-pin C73334-A1-C36-1 1 Siemens
1)
Crimp connector CI2 0.5 to 1 mm2 0-827039-1 4000 AMP
taped on reel
LSP2091-afp.eps
LSP2090-afp.eps

2 1)
Crimp connector CI2 0.5 to 1 mm 0-827396-1 1 AMP

Crimp connector: Type III+ 0.75 to 1.5 mm


2
0-163084-2 1 AMP 1)
Crimp connector: Type III+ 0.75 to 1.5 mm
2
0-163083-7 4000 AMP 1)
2-pin 3-pin
connector connector taped on reel

Crimping tool for Type III+ 0-539635-1 1 AMP 1)


and matching female 0-539668-2 1 AMP 1)
1)
Crimping tool for CI2 0-734372-1 1 AMP
LSP2093-afp.eps

LSP2092-afp.eps

1)
5 and matching female 1-734387-1 1 AMP
Short-circuit links
for current terminals C73334-A1-C33-1 1 Siemens
for other terminals C73334-A1-C34-1 1 Siemens
Short-circuit links Short-circuit links
for current termi- for other terminals Mounting rail for 19" rack C73165-A63-D200-1 1 Siemens
nals

1) Your local Siemens representative


can inform you on local suppliers.

5/116 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Connection diagram

Fig. 5/101 7SJ621 connection diagram

*) For pinout of communication ports see part 15 of this catalog.


For the allocation of the terminals of the panel surface mounting version
refer to the manual (http://www.siemens.com/siprotec).

Siemens SIP · Edition No. 6 5/117


5 Overcurrent Protection / 7SJ62

Connection diagram

Fig. 5/102 7SJ622 connection diagram

*) For pinout of communication ports see part 15 of this catalog.


For the allocation of the terminals of the panel surface mounting version
refer to the manual (http://www.siemens.com/siprotec).

5/118 Siemens SIP · Edition No. 6


5 Overcurrent Protection / 7SJ62

Connection diagram

Fig. 5/103 7SJ623, 7SJ625 connection diagram

*) For pinout of communication ports see part 15 of this catalog.


For the allocation of the terminals of the panel surface mounting version
refer to the manual (http://www.siemens.com/siprotec).

Siemens SIP · Edition No. 6 5/119


5 Overcurrent Protection / 7SJ62

Connection diagram

Fig. 5/104 7SJ624, 7SJ626 connection diagram

*) For pinout of communication ports see part 15 of this catalog.


For the allocation of the terminals of the panel surface mounting version
refer to the manual (http://www.siemens.com/siprotec).

5/120 Siemens SIP · Edition No. 6