CWP-01 Cable Sizing
CWP-01 Cable Sizing
INPUT:
Equipment name : Chilled Water Pumps
Motor tag no : CWP-01
Cable tag no : CWP-01
Voltage : 415 Volts
Connected load : 5.50 KW
Cable length : 10 mtrs
cable laid between : FROM Chiller Room MCC Panel to CWP-01
Derating factor : 0.47
Conductor operating temperature : 70 deg
Efficiency Factor : 85.0%
Power Factor : 80%
Cable :
Conductor current rating : 36 Amps
No of Runs : 1
Selected cable size
-Core : 3 core
-Sqmm : 4.0 sqmm
Method of starting :
Allowable voltage drop at running condition : 5%
Allowable voltage drop at starting condition : 15%
CALCULATION:
5.5kwx1000/{v/3 x0.85efx0.8pf x415volts}
Full load current of the motor : 11 Amps
Hence 1 run of 4/c -16sqmm.Al. Conductorpvc insulated armoured cable is accepted for this purpose.