A Source Data
kV 6.60 kV
kA_SC 25.00 kA Zs (Ohm) = kVL-L / (√3 x Ifault)
MVA_SC 285.79 MVA
B Motor Data
MVA 6.94 MVA
LRC 4.20 pu at V= 1 pu
Zmtr_LR 0.24 pu on motor base MVA (Applying Ohm's Law --> Z = V/I)
C Calculate all Z in pu of common base MVA of 100 MVA
Base MVA 100.00 MVA
Zsource_pu 0.35 pu on common base
Zmtr_LR_pu 3.43 pu on common base
D Vsource 1.00 pu
Vmtr
0.91 pu 𝑉𝑚=𝑉𝑠
90.74 % ∗((𝑍𝑚𝑡𝑟_𝑙𝑟)/(𝑍𝑠𝑜𝑢𝑟𝑐𝑒+𝑍𝑚𝑡𝑟_𝑙𝑟 ))
0.09 pu
Voltage Dip
9.26 %
Step 1: Enter Source / Grid Input Data
Voltage = 6.6 kV
kA (fault) = 25 kA
MVA (fault) = 285.788 MVA
Base MVA = 100 MVA
Source Bus (E)
𝒁𝒑𝒖=((𝑲𝑽𝑨 𝒃𝒂𝒔𝒆)/(𝑲𝑽𝑨 𝒂𝒄𝒕𝒖𝒂𝒍))
(System Impedance) Z2 0.35 Per Unit on 100 MVA Common Base
Motor Terminal Bus (V) Voltage = 6.6 kV
(Motor Impedance) Z1 3.43 Per Unit on 100 MVA Common Base [Vbase(old) and Vbase(n
Step 2: Enter Motor Input Data
Rating 6 MW LRC
Voltage 6.6 kV Z1 (ZLR)
𝑍𝑚𝑡𝑟_𝑙𝑟 )) PF 0.91
Efficiency 0.95
MVA Rating 6.94 MVA
Step 3:Convert All Impedances (Z1, Z2) in Per Unit Common
(𝑲𝑽𝑨 𝒃𝒂𝒔𝒆)/(𝑲𝑽𝑨 𝒂𝒄𝒕𝒖𝒂𝒍))
ase
ase [Vbase(old) and Vbase(new) are same
4.2 Per Unit at 1 Per Unit Voltage
0.238095 Per Unit (Motor Base)
1, Z2) in Per Unit Common Base of 100 MVA
Source / Grid Input Data
Voltage = 6.6 kV
kA (fault) = 25 kA
MVA (fault) = 285.788383249 MVA
Base MVA = 100 MVA
Source Bus (E) Z2 = 0.3499 Per Unit
V(source) = 1 Per Unit
𝒁𝒑𝒖=((𝑲𝑽𝑨 𝒃𝒂𝒔𝒆)/(𝑲𝑽𝑨
(System Impedance) Z2 0.3499 Per Unit on 100 MVA Common Base
Motor Terminal Bus (V) Voltage = 0.90732606276 Per Unit =
(Motor Impedance) Z1 3.43 Per Unit on 100 MVA Common Base [Vbase(old) and Vba
Voltage Dip During Motor Start Motor Input Data
9.27% Rating 6 MW
Voltage 6.6 kV
PF 0.89
Efficiency 0.97
MVA Rating 6.9501 MVA
𝒁𝒑𝒖=((𝑲𝑽𝑨 𝒃𝒂𝒔𝒆)/(𝑲𝑽𝑨 𝒂𝒄𝒕𝒖𝒂𝒍))
Base
90.73%
Base [Vbase(old) and Vbase(new) are same
LRC 4.2 Per Unit at 1 Per Unit Voltage
Z1 (ZLR) 0.238095 Per Unit (Motor Base)