Zs (Ohm) KV / ( 3 X I) : A Source Data

1) The source voltage is 6.6kV, fault current is 25kA, and fault MVA is 285.79MVA. The source impedance (Z2) is 0.35pu on a common base of 100MVA. 2) The motor rating is 6MW, voltage is 6.6kV, power factor is 0.91, efficiency is 0.95, and MVA rating is 6.94MVA. The motor impedance (Z1) is 3.43pu on the common 100MVA base. 3) With the source voltage set to 1pu, the motor terminal voltage during start up is calculated to be 0.91pu, resulting in a 9.26

Uploaded by

Devoh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
94 views6 pages

Zs (Ohm) KV / ( 3 X I) : A Source Data

1) The source voltage is 6.6kV, fault current is 25kA, and fault MVA is 285.79MVA. The source impedance (Z2) is 0.35pu on a common base of 100MVA. 2) The motor rating is 6MW, voltage is 6.6kV, power factor is 0.91, efficiency is 0.95, and MVA rating is 6.94MVA. The motor impedance (Z1) is 3.43pu on the common 100MVA base. 3) With the source voltage set to 1pu, the motor terminal voltage during start up is calculated to be 0.91pu, resulting in a 9.26

Uploaded by

Devoh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 6

A Source Data

kV 6.60 kV
kA_SC 25.00 kA Zs (Ohm) = kVL-L / (√3 x Ifault)
MVA_SC 285.79 MVA

B Motor Data
MVA 6.94 MVA
LRC 4.20 pu at V= 1 pu
Zmtr_LR 0.24 pu on motor base MVA (Applying Ohm's Law --> Z = V/I)

C Calculate all Z in pu of common base MVA of 100 MVA


Base MVA 100.00 MVA
Zsource_pu 0.35 pu on common base
Zmtr_LR_pu 3.43 pu on common base

D Vsource 1.00 pu

Vmtr
0.91 pu 𝑉𝑚=𝑉𝑠
90.74 % ∗((𝑍𝑚𝑡𝑟_𝑙𝑟)/(𝑍𝑠𝑜𝑢𝑟𝑐𝑒+𝑍𝑚𝑡𝑟_𝑙𝑟 ))
0.09 pu
Voltage Dip
9.26 %
Step 1: Enter Source / Grid Input Data

Voltage = 6.6 kV
kA (fault) = 25 kA
MVA (fault) = 285.788 MVA
Base MVA = 100 MVA
Source Bus (E)

𝒁𝒑𝒖=((𝑲𝑽𝑨 𝒃𝒂𝒔𝒆)/(𝑲𝑽𝑨 𝒂𝒄𝒕𝒖𝒂𝒍))


(System Impedance) Z2 0.35 Per Unit on 100 MVA Common Base

Motor Terminal Bus (V) Voltage = 6.6 kV

(Motor Impedance) Z1 3.43 Per Unit on 100 MVA Common Base [Vbase(old) and Vbase(n

Step 2: Enter Motor Input Data


Rating 6 MW LRC
Voltage 6.6 kV Z1 (ZLR)
𝑍𝑚𝑡𝑟_𝑙𝑟 )) PF 0.91
Efficiency 0.95
MVA Rating 6.94 MVA

Step 3:Convert All Impedances (Z1, Z2) in Per Unit Common


(𝑲𝑽𝑨 𝒃𝒂𝒔𝒆)/(𝑲𝑽𝑨 𝒂𝒄𝒕𝒖𝒂𝒍))
ase

ase [Vbase(old) and Vbase(new) are same

4.2 Per Unit at 1 Per Unit Voltage


0.238095 Per Unit (Motor Base)

1, Z2) in Per Unit Common Base of 100 MVA


Source / Grid Input Data
Voltage = 6.6 kV
kA (fault) = 25 kA
MVA (fault) = 285.788383249 MVA
Base MVA = 100 MVA
Source Bus (E) Z2 = 0.3499 Per Unit
V(source) = 1 Per Unit

𝒁𝒑𝒖=((𝑲𝑽𝑨 𝒃𝒂𝒔𝒆)/(𝑲𝑽𝑨
(System Impedance) Z2 0.3499 Per Unit on 100 MVA Common Base

Motor Terminal Bus (V) Voltage = 0.90732606276 Per Unit =

(Motor Impedance) Z1 3.43 Per Unit on 100 MVA Common Base [Vbase(old) and Vba

Voltage Dip During Motor Start Motor Input Data


9.27% Rating 6 MW
Voltage 6.6 kV
PF 0.89
Efficiency 0.97
MVA Rating 6.9501 MVA
𝒁𝒑𝒖=((𝑲𝑽𝑨 𝒃𝒂𝒔𝒆)/(𝑲𝑽𝑨 𝒂𝒄𝒕𝒖𝒂𝒍))
Base

90.73%

Base [Vbase(old) and Vbase(new) are same

LRC 4.2 Per Unit at 1 Per Unit Voltage


Z1 (ZLR) 0.238095 Per Unit (Motor Base)