Manual Ups Black RT Iot 6-10kva

Download as pdf or txt
Download as pdf or txt
You are on page 1of 56

On Line UPS

BLACK TT/RT IoT

6-10K USER MANUAL

KOLFF
Scan to Download APP
Service and support:
Call your local service representative
SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be
followed during installation and maintenance of the UPS and batteries.
The UPS that are covered in this manual are intended for installation in an environment
within 0 to 50°C, free of conductive contaminant.
Special symbols
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric
shock symbol.

Important instructions that must always be followed.

EU separate collection and lead content mark for lead acid batteries. Indicates
that the battery must not be disposed of to the normal household waste but be
separately collected and recycled.
EU separate collection mark for waste electrical and electronic equipment (WEEE).
Indicates that the item must not be disposed of to the normal household waste
but be separately collected and recycled.

Information, advice, help.

Refer to the user manual.

Safety of persons
 RISK OF VOLTAGE BACKFEED. The system has its own power source (the battery). Isolate
the UPS and check for hazardous voltage upstream and downstream during lockout-
tagout operation. Terminal blocks may be energized even if the system is disconnected
from the AC power source.
 Dangerous voltage levels are present within the system. It should be opened exclusively
by qualified service personnel.
 The system must be properly grounded.
 The battery supplied with the system contains small amounts of toxic materials. To avoid
accidents, the directives listed below must be observed:
- Servicing of batteries should be performed or supervised by personnel knowledgeable
about batteries and the required precautions.
- When replacing batteries, replace with the same type and number of batteries or
battery packs.
- Do not dispose of batteries in a fire. The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may
be very high.
 Precautions must be taken for all handling:
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
- Determine if battery is inadvertently grounded. If inadvertently grounded, remove
source from ground. Contact with any part of a grounded battery can result in
electrical shock. The likelihood of such shock can be reduced if such grounds are
removed during installation and maintenance (applicable to equipment and remote
battery supplies not having a grounded supply circuit).

Product safety

 The UPS connection instructions and operation described in the manual must be followed
in the indicated order.
 UPS enclosure IP rating IP20.
 CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with
branch circuit overcurrent protection.
 The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible. The unit
can be disconnected from AC power source by opening this circuit breaker.
 An additional AC contactor is used for back feed protection and must comply with IEC/EN
62040-1 (the creepage and clearance distances shall meet the basic insulation
requirements for pollution degree 2).
 Disconnection and overcurrent protection devices shall be provided by others for
permanently connected AC input (Normal AC/Bypass AC) and AC output circuits.
 Check that the indications on the rating plate correspond to your AC powered system and
to the actual electrical consumption of all the equipment to be connected to the system.
 For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and
shall be easily accessible
 Never install the system near liquids or in an excessively damp environment.
 Never let a foreign body penetrate inside the system.
 Never block the ventilation grates of the system.
 Never expose the system to direct sunlight or source of heat.
 If the system must be stored prior to installation, storage must be in a dry place.
 The admissible storage temperature range is -25°C to +55°C without battery (-15°C to
+40°C with battery).
 TN-S/IT/TN-C/TT of electrical supply system may be connected by UPS.
 This UPS may be provided with a maximum of 6 extension battery cabinets or equivalent.

Special precautions

 The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling
operations.
 All handling operations will require at least two people (unpacking, lifting, installation in
rack system).
 Before and after the installation, if the UPS remains de-energized for a long period, the
UPS must be energized for a period of 24 hours, at least once every 6 months (for a normal
storage temperature less than 25°C). This charges the battery, thus avoiding possible
irreversible damage.
 For three-phase AC input installation, this equipment complies with IEC 61000-3-12
provided that the short-circuit power Ssc is greater than or equal to 3.63MW at the
interface point between the user’s supply and the public system. It is the responsibility of
the installer or user of the equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to 3.63MW.
 During the replacement of the Battery Module, it is imperative to use the same type and
number of elements as the original Battery Module provided with the UPS to maintain
an identical level of performance and safety.
 This is a category C3 UPS product. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.
CONTENTS
1. Introduction ........................................................................................................................ 1
1.1 Product Features .......................................................................................................... 1
1.2 Environmental protection ............................................................................................ 2
2. Product Overview ............................................................................................................... 3
2.1 Model list ..................................................................................................................... 3
2.2 Presentation ................................................................................................................. 5
3. Installation ........................................................................................................................ 10
3.1 Unpacking and Inspecting .......................................................................................... 10
3.2 Checking the accessory kit ......................................................................................... 11
3.3 Mechanical Install ...................................................................................................... 12
3.4 Power cables connection ........................................................................................... 17
4. Parallel system Installation and Operation (Optional) ...................................................... 24
4.1 Wiring for AC Cable .................................................................................................... 24
4.2 Wiring for parallel signal cable ................................................................................... 28
4.3 Parallel system Operation .......................................................................................... 28
5. Operation .......................................................................................................................... 29
5.1 LCD panel ................................................................................................................... 29
5.2 LCD description .......................................................................................................... 31
5.3 Display functions ........................................................................................................ 32
5.4 User settings .............................................................................................................. 33
5.5 Starting the UPS with utility ....................................................................................... 34
5.6 Starting the UPS on Battery ....................................................................................... 34
5.7 UPS Shutdown............................................................................................................ 35
6. Communication ................................................................................................................ 36
6.1 RS232 and USB ........................................................................................................... 36
6.2 UPS remote control functions .................................................................................... 36
6.3 IoT .............................................................................................................................. 37
6.4 Modbus TCP ............................................................................................................... 38
6.5 Intelligent Card (optional) .......................................................................................... 38
6.6 UPS Management Software ....................................................................................... 38
7. UPS maintenance .............................................................................................................. 40
7.1 Equipment care .......................................................................................................... 40
7.2 Transporting the UPS ................................................................................................. 40
7.3 Storing the equipment ............................................................................................... 40
7.4 Recycle ....................................................................................................................... 40
8. Troubleshooting ................................................................................................................ 41
8.1 Typical alarms and faults ............................................................................................ 41
8.2 Silencing the alarm..................................................................................................... 43
9. Specifications .................................................................................................................... 44
9.1 UPS Block Diagram ..................................................................................................... 44
9.2 UPS Specification ....................................................................................................... 44
1. Introduction
Thank you for selecting our UPS to protect your electrical equipment.
We recommend that you take the time to read this manual to take full advantage of
the many features of your UPS.
Before installing your UPS, please read the booklet presenting the safety instructions.
Then follow the indications in this manual.

1.1 Product Features


The UPS protects your sensitive electronic equipment from the most common power
problems, including power failures, power sags, power surges, brownouts, line noise,
high voltage spikes, frequency variations, switching transients, and harmonic distortion.
Special characteristic:
• Double converter with pure sine waveform output
• Full digital control
• Output PF = 1
• High charger capability, the charger current is up to 12Amps
• Smart charging method to expand battery life time
• EBM quantity auto detection
• Communication ports: RPO, Dry in, Dry out, intelligent slot, USB, RS232
• IoT: Ethernet(default) and Wireless (optional)
• Dot-matrix LCD, it supports multi-language
• ECO Mode
• Start-able without battery

1
1.2 Environmental protection
Products are developed according to an eco-design approach.

Substances
This product does not contain CFCs, HCFCs or asbestos.

Packing
To improve waste treatment and facilitate recycling, separate the various packing
components.
• The cardboard we use comprises over 50% of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packing materials are recyclable.
Follow all local regulations for the disposal of packing materials.
Product
The product is mainly made up of recyclable materials.
Dismantling and disassembly must take place in compliance with all local regulations
concerning waste. At the end of its service life, the product must be transported to
recycling centers, re-use and treatment facilities for waste electrical and electronic
equipment (WEEE).

Battery
The product contains lead-acid batteries that must be processed according to
applicable local regulations concerning batteries.
The battery may be removed to comply with regulations and in view of correct disposal.

2
2. Product Overview
2.1 Model list
1. ‘xxK’ model means ‘standard model’ with batteries, ‘xxKS’ model means ‘long backup model’
without battery.
2. 16 or 20 batteries could be selected for UPS and EBM (External Battery Modular).
3. The weight in the table below is reference only, please see the labels on the carton for details.
4. Dimension ‘D’ is chassis only, not including panel.

 Tower model:
Product Description Net Weights (kg) Unit Size
(W x H x D)(mm)
Tower 6KS 16
13.5
Tower 6KS 20
225*353.2*416
Tower 10KS 16
15.5
UPS(1-1) Tower 10KS 20
model Tower 6K 16 49.5
Tower 6K 20 57.9
Tower 10K 16 59
Tower 10K 20 68.2
Tower 3-1 10K 16 59.5
225*589*416
UPS(3-1) Tower 3-1 10K 20 68.7
model Tower 3-1 10KS 16
22.7
Tower 3-1 10KS 20
Tower EBM (2) 192 9AH 94.5
EBM
Tower EBM (2) 240 9AH 115.6

 RT model:
Product Description Net Weights (kg) Unit Size
(W x H x D)(mm)
RT 6KS 16
13.6
RT 6KS 20
RT 10KS 16
15.5
UPS(1-1) RT 10KS 20
438*86.3(2U)*540
Model RT 6K 16
13.3
RT 6K 20
RT 10K 16
15.2
RT 10K 20

3
Product Description Net Weights (kg) Unit Size
(W x H x D)(mm)
RT 3-1 10KS 16
15.8
UPS(3-1) RT 3-1 10KS 20
438*86.3(2U)*540
model RT 3-1 10K 16
15.5
RT 3-1 10K 20
RT EBM 192 9AH (1) 51.8
(1)
RT EBM 240 9AH 60.5
EBM 438*129(3U)*559
RT EBM 192 7AH (2) 46.1
RT EBM 240 7AH (2) 56.1
(1) For RT 10kVA UPS.
(2) For RT 6kVA UPS

 Optional modular or accessory:

If order other type function modular or accessories, please contact distributors/agents.

Type Description Remark


RT 6K/10K MBP For RT 1-1 model only
RT MBP
RT 3-1 10K MBP For RT 3-1 model only
Dry Contact card (AS400)
Intelligent Card NMC card
See in chapter 6.5
MODBUS card (CMC)
EMP Temperature and humidity sensors
WLAN module WLAN module Wireless connection for IoT
COMM Cable RS232 CABLE For RS232 communication
Parallel Kit For parallel system installing See in chapter 4.0
Battery cable (16 batt.)
for UPS connect with user’s own EBM 1.8m length,
Battery cable
Battery cable (20 batt.) see in chapter 3.4.3
for UPS connect with user’s own EBM
Rail kit Rail kit for RT model in Rack installing See in chapter 3.3.2
Gland kit for RT 1-1 model For RT 1-1 UPS/MBP model
Gland kit Gland kit for Tower 1-1 model For Tower 1-1 UPS model
Gland kit for all 3-1 model For all 3-1 UPS/MBP model

4
2.2 Presentation
2.2.1 Tower model:

• UPS modular:

Front view
1. Ventilation area
2. LCD Modular, including:
2(1)---Button,
2(2)---LCD screen,
2(3)---LED indicator

Tower UPS Tower UPS


6~10KS(1-1) 6~10K(1-1)/10K(S)(3-1)

5
Rear view
1. Intelligent slot 8. RJ45 (for EBM detect)
2. RS232 9. AC Input /Output port (Terminal Block)
3. Ethernet port (RJ45, for IoT function) 10. Input switch
4. USB 11. External battery port
5. Wireless (HDMI, For IoT function) 12. Maintenance bypass switch (optional,
6. RPO& DRY in/out default is yes)
7. Parallel Slot

6KS(1-1) 10KS(1-1)

6K(1-1) 10K(1-1) 10K/10KS(3-1)

6
• EBM(External Battery Modular):

Front view
1. Ventilation area
2. EBM label

Rear view
1. EBM port 1
2. EBM port 2
3. Fuse board cover (replace EBM fuse)
4. EBM detection Box (RJ45 port)

7
2.2.2 RT model:
• UPS Modular
Front view

1. Ventilation area
2. LCD Modular, including: 2(1)---Button ,2(2)---LCD screen,2(3)---LED indicator
Rear view
1. INTELLIGENT SLOT 7. PARALLEL SLOT
2. RS232 8. RJ45 (for EBM detect /RT MBP detect)
3. Ethernet port (RJ45, for IoT function) 9. AC Input /Output port(Terminal Block)
4. USB 10. Breaker of input(only for 1-1 model,
5. Wireless (HDMI, For IoT function) optional ,default is no)
6. RPO& DRY in/out 11. External battery port

UPS (1-1)

UPS (3-1)

8
• EBM(External Battery Modular):
Front view
1. EBM label area
2. EBM label

Rear view
1. Fuse board cover (replace EBM fuse)
2. EBM port 1
3. EBM port 2
4. EBM detection Box (RJ45 port)

9
3. Installation
It is recommended to move the equipment to the installation site by using a pallet jack
or a truck before unpacking.
The system may be installed only by qualified electricians in accordance with applicable
safety regulations.
Some of cabinet is heavy, please install it with at least two peoples.

3.1 Unpacking and Inspecting


Unpacking the unit in a low-temperature environment may cause condensation
occurred in and on the cabinet. Do not install the unit until the inside and outside of
the unit are absolutely dry (hazard of electric shock).
If any equipment has been damaged during shipment, keep the shipping cartons and
packing materials for the carrier or place of purchase and file a claim for shipping
damage. If you discover damage after acceptance, file a claim for concealed damage.
• Tower 6KS/10KS (1-1)

• Tower 6K/10K (1-1) /10K(3-1) /10KS(3-1)

• Tower EBM

10
• RT UPS

• RT EBM

Note:
The cabinet is heavy, please see spec weight provided on the carton/label.
Do not lift the unit’s front panel and rear panel.
Discard or recycle the packaging in a responsible manner, or store it for future use.
Packing materials must be disposed in compliance with all local regulations concerning
waste.

3.2 Checking the accessory kit


Verify that the following additional items are included with the unit.
Tower model:
1-1 model 3-1 model
Tower UPS Tower UPS Tower UPS Tower UPS Tower EBM
6K/10K 6KS/10KS 10K 10KS
Battery cable O O √
EBM detection cable √
Copper bus-bar √ √
USB cable √ √ √ √
RS232 cable O O O O

Parallel cable O O O O

Tower foot √ O √ √ √
Quick start (EBM) √
User manual (UPS) √ √ √ √

11
RT model
1-1 model 3-1 model
RT UPS RT UPS RT EBM
RT UPS 10K RT UPS 10KS
6K/10K 6KS/10KS
Battery cable O O √
EBM detection cable √
Copper bus-bar √ √
USB cable √ √ √ √
RS232 cable O O O O

Parallel cable O O O O

Tower foot √ √ √ √
Extension plate
of Tower foot

Rack ear √ √ √ √ √
Rack rail kit O O O O O

Quick start(EBM) √
User manual(UPS) √ √ √ √
Note :√--- Standard configuration; O---Optional, default is Not configured;

3.3 Mechanical Install


3.3.1 Tower model
To keep air-flowing freely, it is recommended to keep a clearance with 500mm space
both for front and rear side.

UPS model

1.Place the unit on a flat, stable surface in its final location,


2.Install ‘tower foot’ (if configured): remove side’s screw from the unit, then install
‘tower foot’.
3.Install the unit to ground(optional): place 4pcs bolts (M8 is recommended) to the
final location previously, bolt’s position please refer to below, then fix the unit to the
bolts.

12
EBM model
EBM model
EBM installation steps are the same as UPS as above.
It is recommended to place EBM modular to UPS’s left side.

3.3.2 RT model:
1. RT models support 2 installation modes: Rack installation and Tower installation.
2. To keep good ventilation, please keep a free-space (500mm at least) for front / rear
panels of the module.
3. Do not carry the front/rear panel of the module during installing.

 Rack installing
This procedure is suitable for 19 inch rack cabinet installation, it is recommended that
the depth of the cabinet be no less than 800mm.

UPS model
Identify the final position and keep ‘2U’ space for this installing.
1. Install the rail kit (if configured). This rail kit is '2U & with screw holes (M5)', the
depth of the rail kit is: 443-773 mm.

13
Fasten the rail kit to the cabinet with 8pcs M5 screws + washers (as below):

2. Install ‘Rack ear’ to the unit by the M4 screws(flat head).

3. Slide the unit into ‘rail kit’ and make sure tighten the ‘rack mounting screw’.

14
EBM model
Identify the final position and keep ‘3U’ space for this installing, and it is recommended
to be installed below to UPS.

1. Install the rail kit(if configured): same as UPS as above.


2. Install ‘Rack ear’ to the unit by the M4 screws(flat head).

3. Slide the unit into ‘rail kit’ and make sure tighten the ‘rack mounting screw’.

15
 Tower installing
UPS model
1. Rotate the LCD model to tower direction.

2. Set up the ‘Tower foot’, then take the unit into ‘Tower foot’.

EBM model
1. Set up the ‘Extension plate’ as below and install to ‘Tower foot’ from UPS.
2. Take the UPS& EBM into ‘Tower foot’ individually: Place EBM modular to UPS’s right
side and align with front-panel.

16
3.4 Power cables connection

This chapter introduces how to wiring AC IN/OUT cable to UPS in difference mode, and
UPS connecting with EBM/MBP.
3.4.1 Input /Output wiring specifications
Before wring UPS, upstream breaker and backfeed contactor should be configured to
avoid power backfeed to unity. And “backfeed voltage danger” warning label should
be added in backfeed contactor or device. Before operating, UPS input should cut off,
and check all terminals voltage to avoid voltage dangerous. Backfeed contactor rating
current should be larger than UPS rating input current.
Below figures show the wiring system of UPS input and output.

Single phase input system

Three phase input system

Danger!
The rated current of the utility power switch must be greater than the UPS input
current, otherwise the utility power switch may be burnt!

Recommended upstream protection and downstream switch:


UPS power rating Upstream circuit breaker Backfeed contactor Downstream switch
6000VA D curve – 63A (1 phase) 63A (1 phase) 40A (1 phase)
10000VA D curve – 80A (1 phase) 80A (1 phase) 63A (1 phase)
10000VA 3-1 D curve – 80A (3 phase) 80A (3 phase) 63A (1 phase)

17
Read the Safety instructions regarding backfeed protection requirements.
Recommended cable minimum cross-sectional:
Model 6K(S) 1-1 10K(S) 1-1 10K(S) 3-1
Protective earthing conductor 10mm2 10mm2 10mm2
Input L, N cable 6mm2 10mm2 10mm2
Output L, N cable 6mm2 10mm2 10mm2
Battery cable 6mm2 10mm2 10mm2
The length of the output cable is recommended not to exceed 10 meters, otherwise, it may cause
radio interference. If a length of output cable over 10 meters requests, please contact distributors/
agents for details.

3.4.2 Wiring for AC Cable (AC source to UPS)


High leakage current:
Earth connection essential before connecting supply.

This type of connection must be carried out by qualified electrical person.


Before carrying out any connection, check that the upstream protection devices
(Normal AC source and Bypass AC source) are open "O" (Off).
Always connect the ground wire first.

1. Remove the cover of terminal block.


2. Connect the AC cable to terminal blocks:
• Tower UPS
1-1 model:

18
3-1 model:
This model support 2 modes setting as below, default is setting with 3-1 mode.
1-1 mode
Short ‘UPS input terminal L1/L2/L3’ with ‘busbar’, then connect AC cable

3-1 mode

• RT UPS
1-1 model:

19
3-1 model:
This model support 2 modes setting as below, default is setting with 3-1 mode.
1-1 mode
Short ‘UPS input terminal L1/L2/L3’ with ‘busbar’, then connect AC cable

3-1 mode

For cables well fixed, it is recommended to tie these cables to the convex of rear-panel.

20
3.4.3 Wiring with external battery modular (EBM) (DC source to UPS)
1. Be sure to disconnect the battery cable from the EBM before connecting the
battery terminals of the UPS
2. Make sure the UPS is completely off before connecting or disconnecting the EBM.
3. Before connecting the EBM, make sure that the EBM specification is compatible
with UPS configuration.
4. Do not reverse the polarity of the external battery.
• Connect with the configured EBM:
Connect EBM to UPS with ‘Battery cable’ and ‘EBM detection cable’.
Tower EBM

Note:
1. Extended runtime with up to 6 Extended Battery Modules(EBMs) per UPS.
2. Extend more than 2 EBMs, additional ground wires (10mm2 cross-sectional area)
are required.

21
RT EBM

Note:
Extended runtime with up to 6 Extended Battery Modules(EBMs) per UPS.

• Connect with user’s own EBM:


Connect EBM to UPS with ‘Battery cable’(optional configured).

Tower model RT model

Note:
1.If additional battery cable needed for installation, it must follow cable specification
and the maximum length of battery cable 10 meters for application.
2.If a length of battery cable over 10 meters requests, please contact distributors/
agents for details.

22
3.4.4 Wiring with RT MBP (MBP source to R/T UPS only)
RT MBP is RT UPS’s optional modular, UPS can be used with the MBP to implement the
maintenance bypass switching function to ensure that the output of the system is not
affected during the UPS maintenance.

See the User Manual of RT MBP for details.

23
4. Parallel system Installation and Operation (Optional)
If your UPS is configured with parallel function, up to 3 UPSs can be connected in
parallel to configure a sharing and redundant output power.

In parallel system, the mechanical installation for each modular is same as the single
system. Details please refer to Chapter 3.3.

Parallel system AC cable diagram:

4.1 Wiring for AC Cable


1. Wiring length requirement:
When the distance between the load and the parallel UPS is less than 10 meters, the
length difference between the input/output lines between the UPSs in the parallel
system is less than 20%.
When the distance between the load and the parallel UPS is greater than 20 meters,
the length difference between the input/output lines between the UPSs in the
parallel system is less than 5%.
2. In the parallel system, common battery application is not supported. independent
EBM connect to each UPS, please refer to chapter 3.4.3.
3. Professional installation is required, please set the parallel system in the restricted
area!

24
Tower model parallel system
• 1-1 model

• 3-1 model
1-1 mode

25
3-1 mode

RT model parallel system


• 1-1 model

26
• 3-1 model
1-1 mode

3-1 mode

27
4.2 Wiring for parallel signal cable
Parallel signal cable connection diagram:

Remove the cover of ‘parallel box’, then connect each UPS one by one with ‘parallel
cable’, make sure the cable is screwed to parallel port tightly.

It is recommended to lock the ‘parallel cable’ (as above) for preventing the parallel ports
suffering an unexpected pulling-force and causing the parallel system fault.

4.3 Parallel system Operation


1. Turn on the input breakers for the parallel UPS.
2. Pressing button continuously for one UPS of the system, then the system will
start to turn on and enter line mode.
3. Regulate the output voltage of each UPS separately, and check if the output voltage
difference is less than 0.5V among the parallel system. If the difference is more than
0.5V, the UPS need to be regulated.
4. If the output voltage difference is less than 0.5V, pressing button continuously
for one UPS of the system, then the system will turn off. Turn off the input breakers
to let UPS shut down. Then switch on the output breakers for all the UPS.
5. Turn on the input breakers for the parallel UPS. Pressing button continuously
for one UPS of the system, then the system will start to turn on and enter line mode
and the system will work normally in parallel.

28
5. Operation
5.1 LCD panel
The UPS has a five-button graphical LCD. It provides useful information about the UPS
itself, load status, events, measurements and settings.

The LED:
Indicator Status Description
The UPS is operating normally on Online or on High
On
Green Efficiency mode.

On The UPS is on Battery mode.


Orange

On The UPS is on Bypass mode.


Orange
The UPS has an active alarm or fault.
On Please refer to section 8.1 Trouble shooting for more
Red
information

29
The buttons:
The button Function Illustration
Press the Button for >100ms & < 1s can power on
Power on the UPS without utility input at the condition of
battery connected

When the Unity is powered on, press the button


Turn on
for >3s can turn on the UPS

Turn off Press the button > 4s can turn off the UPS

Scroll up Press to scroll up the menu option

Scroll down Press to scroll down the menu option

Enter menu Select/Confirm the current selection

Press to exit present menu to Main menu or the


Exit the present menu
higher-level menu without changing a setting

Press the button to mute the buzzer temporarily,


Mute buzzer once new warning or fault is active, buzzer will work
again

The Buzzer :
The buzzer General Meaning

1 beep every 2 minutes Load supplied on bypass


Load supplied on battery
1 beep every 4 seconds
If battery low, beep every second
1 beep every second General warning active

2 beeps every second Overload warning

Continuous Fault active

Back Light:
After 10 minutes of inactivity, the LCD backlight will automatically dim. Press any
button to restore the screen.

30
5.2 LCD description

Operation status Cause Description

Standby mode The UPS is Off without output.

The UPS is operating normally and protecting


Online mode
the equipment.

An utility failure has occurred, and the UPS is


Battery mode powering the equipment with battery.
1 beep every 4
Prepare your equipment for shutdown.
seconds

Battery mode with This warning is approximate, and the actual time
1 beep every 1 battery low to shutdown may vary significantly.
seconds

Once the mains are loss or abnormal, the UPS


High Efficiency mode would transfer to Line mode or Battery mode
and the load is supplied continuously.
The UPS would free run with fixed output
frequency (50Hz or 60Hz).
Converter mode The output maximum power and maximum
charging current should be derating to 60% in
converter mode.
Overload or fault has occurred, or a command
Bypass mode has been received, and the UPS is in Bypass
mode.

Battery test UPS is executing a battery test

The UPS detects bad battery or battery


Battery fail
disconnected

31
Some unnecessary loads should be cut off to
Overload
reduce the load.

Fault mode Some fatal problems happened.

Parallel mode UPS is working in parallel mode

5.3 Display functions


Use the two middle buttons ( and ) to scroll through the menu structure. Press
the Enter ( ) button to select an option. Press the ESC ( ) button to cancel or
return to the previous menu.
When starting the UPS, the display is in the default UPS status summary screen.

Main menu Submenu Display information or Menu function

UPS status
UPS mode, IoT status, date/time, battery status ,
parallel information and current alarms

Event log Displays the events and faults stored

[Load] W VA A P%, [Input L1/Output] V Hz, [Input


Measurements L2/Input L3] V Hz(if they exist),
[Battery] % min V EBM, [DC Bus] V, [Temperature] ℃
Load segment Load segment enable or disable
Start battery test Starts a manual battery test in stand-alone mode
(single mode) Or starts a single battery test in parallel mode
Single battery test (parallel
mode)
Parallel UPS battery test Starts a manual battery test in parallel mode
Control (parallel mode)
Single UPS turn off Operate this machine to exit parallel connection
(parallel mode)
Reset fault state Clear active fault
Reset event list Clear events and faults
Reset com card / Reset IoT Reset IoT and Modbus TCP function inside UPS
Restore factory settings Restore to default factory settings

Settings Refer to User settings

[Model name], [Serial number], [firmware version],


Identification
[comm card firmware], [IP/MAC address]

32
5.4 User settings

Submenu Available settings Default settings

Password Can be changed by user 4732


English, Italiano, Français, Deutsch, Español,
Language
Русский, Polski, 简体中文 English

User password [Enabled, ****], [Disabled] Enabled


Audible alarms [Enabled], [Disabled] Enabled
[230V]
Output voltage [220V], [230V], [240V]
[240V] for AU
Output frequency [Autosensing], [converter 50Hz, 60Hz] Autosensing
High efficiency [Disabled], [Enabled] Disabled
Auto bypass [Disabled], [Enabled] Enabled
Cold start : [Disabled], [Enabled] Enabled
Start/Restart
Auto restart : [Disabled], [Enabled] Enabled
Site wiring fault [Enabled], [Disabled] Disabled

Overload pre-alarm [50%~105%] 105%


[Auto detection], Auto detection
External battery [Manual EBM: 0~6], 0 EBM
[Manual Ah: 0~300Ah] 0 Ah
1.4A for 6K
1-4A for 6-10k
Charger current 2A for 10K
2-12A for 6-10KS
4A for 6-10KS
[Disabled], [Remote on], [Remote off],
Dry in signal Disabled
[Forced bypass]
[Load powered], [On bat], [Low bat], [Bat open],
Dry out signal Bypass
[Bypass], [UPS OK]
Ambient temperature alarm [Enabled], [Disabled] Enabled
Battery remaining time [Enabled], [Disabled] Enabled
dd/mm/yyyy 01/01/2020
Date and time 00:00
hh:mm
LCD contrast [0-100%] 50%
Modbus TCP [Enabled], [Disabled] Disabled
IoT Enable [Yes], [No] No

Note: if the utility power is IT system, the site wiring fault function should be disabled.

33
5.5 Starting the UPS with utility

5.6 Starting the UPS on Battery


Before using this feature, the UPS must have been powered by utility power with
output enabled at least once.
Battery start can be disabled. See the "Cold start" setting in "Start/Restart".

34
5.7 UPS Shutdown

35
6. Communication
6.1 RS232 and USB
1. Communication cable to the serial or USB port on the computer.
2. Connect the other end of the communication cable to the RS232 or USB
communication port on the UPS.
6.2 UPS remote control functions
• Remote Power Off (RPO )
When RPO is activated, UPS will cut off output immediately, and continues to alarm.

RPO Comments
Connector type 16 AWG Maximum wires
External breaker specification 60 V DC/30 V AC 20 mA max
Reset :
1. Check the RPO connector status;
2. Clear fault state through LCD.
• Dry in
Dry in function can be configured (see Settings > Dry in).

Dry in Comments
Connector type 16 AWG Maximum wires
External breaker specification 60 V DC/30 V AC 20 mA max

• Dry out
Dry out is the relay out, dry out function can be configured (see Settings > Dry out).

Dry out Comments


Connector type 16 AWG Maximum wires
Inner Relay specification 24Vdc/1A

36
6.3 IoT
Built-in ethernet port and WLAN (optional accessary) port enable market-leading and
easy-to-use IoT solutions for:
• Winpower View mobile app which allows you to remote monitor UPS(s) and keep
informed about critical UPS event always.
• Remote report UPS faults and status (contact with your service for detail) from
APP or registered APP account (Email address).
• Automatic UPS and battery warranty alert from APP or registered APP account
(Email address).
IoT Connection
- Wired network connection
1. Connect UPS to router or switch with network cable.
­ Please use CAT6 shielded network cable.
­ Make sure your IT settings can access the public network and Microsoft Azure Cloud.
2. Enable the IoT function in LCD (see Settings -> IoT)
3. Search the “WinPower View” from Google Play store or Apple APP store,
downloading and installing.
4. Open the app, register an account, log in, follow the instructions of the app.
5. Tap on the upper right corner, scan the SN barcode on UPS label to add device.

For more detail information and Q&A about the IoT and APP, please refer to the HELP
menu in the app.

- Wireless network connection


The wireless module is optional, please contact your local distributor for details.

37
6.4 Modbus TCP
Built-in ethernet port offers Modbus TCP feature to facilitate remote monitoring of the
UPS into your own software. Contact with your service for protocol details.
6.5 Intelligent Card (optional)
Intelligent Card allow the UPS to communicate with different types of devices in
variety of networking environments. The UPS could use the following connectivity
cards, please contact your local distributor for details
• NMC Card - Ideal monitoring solution enables user to monitor and control the
status of UPS on web browser via internet
• CMC card - provides connection to Modbus protocol with standard RS485 signal.
• AS400 G2 card - Provides voltage-free dry-contact signals for programmable
controller and management system
• EMP - Supports temperature and humidity sensors for remote environment
monitoring, should work with NMC Card
6.6 UPS Management Software
6.6.1 WinPower

WinPower provides user-friendly interface to monitor and control your UPS. This
unique software provides safely auto shutdown for multi-computer systems while
power failure. With this software, users can monitor and control any UPS on the same
LAN no matter how far from the UPSs.

Installation procedure:
1. Go to the website: http://www.ups-software-download.com/content/ups-
download-software/download.html

38
2. Choose the operation system you need and follow the instruction described on the
website to download the software.
3. When downloading all required files from the internet, enter the serial No: 511C1-
01220-0100-478DF2A to install the software.

When you finish installation, restart your computer, the WinPower software will appear
as a green plug icon located in the system tray, near the clock.

6.6.2 WinPower View APP

WinPower View is a mobile app which allows you to centralized monitoring UPS(s)
connected to cloud. Please download it from Google Play store or Apple APP store.
Please refer to the chapter 6.3 for IoT connection.

39
7. UPS maintenance
7.1 Equipment care
For the best preventive maintenance, keep the area around the equipment clean and
dust free. If the atmosphere is very dusty, clean the outside of the system with a
vacuum cleaner.
For full battery life, keep the equipment at an ambient temperature of 25°C (77°F).
The batteries are rated for a 3-5 year service life. The length of service life varies,
depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace
batteries at least every 4 years to keep units running at peak efficiency.
7.2 Transporting the UPS
Please transport the UPS only in the original packaging. If the UPS requires any type
of transportation, verify that the UPS is disconnected and turned off.

7.3 Storing the equipment


If you store the equipment for a long period, recharge the battery every 6 months by
connecting the UPS to utility power. Recommends that the batteries charge for 48
hours after long-term storage.
If batteries were never recharged over 6 months, do not use them. Contact your
service representative.
7.4 Recycle
Contact your local recycling or hazardous waste center for information on proper
disposal of the used equipment.
Do not dispose of the batteries in the fire. Which may cause battery explosion. The
batteries must be rightly disposed according to local regulation.
Do not open or destroy the batteries. Escaping electrolyte can cause injury to the skin
and eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash.
This product contains sealed lead acid batteries and must be disposed as it's explained
in this manual. For more information, contact your local recycling/reuse or hazardous
waste center.
The crossed-out wheeled bin symbol indicates that waste electrical and electronic
equipment should not be discarded together with unseparated household waste but
must be collected separately. The product should be handed in for recycling in
accordance with the local environmental regulations for waste disposal.
By separating waste electrical and electronic equipment, you will help reduce the
volume of waste sent for incineration or land-fills and minimize any potential negative
impact on human health and environment.

40
8. Troubleshooting
The UPS is designed for durable, automatic operation and also alert you whenever
potential operating problems may occur. Usually the alarms shown by the control panel
do not mean that the output power is affected. Instead, they are preventive alarms
intended to alert the user.
 Events are silent status information that are recorded into the Event log. Example =
"Battery charging".
 Alarms are recorded into the Event log and displayed on the LCD status screen with
the logo blinking. Some alarms may be announced by a beep every 1 second.
Example = "Battery low".
 Faults are announced by a continuous beep and red LED, recorded into the Event log.
Example = Out. short circuit.
Use the following troubleshooting chart to determine the UPS alarm condition.
8.1 Typical alarms and faults
To check the Event log:
1. By pressing on the menu of “Event log”.
2. Scroll through the listed events or faults.
3. The following table describes typical conditions.

WARNING
Problem Displayed Possible cause Remedy
Check the maintain bypass switch
On Maintain Bypass Maintain bypass switch is open
status
Site Wiring alarm Phase and neutral conductor at Reverse mains power wiring.
input of UPS system are reversed
No battery Battery pack is not connected Do the battery test to confirm.
correctly Check the battery bank is properly
connected to the UPS.
Check the battery breaker is turn on or
fuse OK.
Battery low Battery voltage is low When audible alarm sounding every
second, battery is almost empty.
End battery life The battery has reached the end Consult dealer if replace the battery
of its life
Power overload Power requirements exceed the Check the loads and remove some
UPS capacity noncritical loads.
Check if some loads are failed
Overload pre-alarm The load exceeds the preset Check the loads or reset the pre-alarm
value value
Fan Lock Fan abnormal Check if the fan is running normally or
fan detection cable disconnected
UPS temp. alarm Inside temperature of UPS is too Check the ventilation of UPS and the
high ambient temperature.

41
Amb. temp. alarm The ambient temperature is too Check the environment ventilation
high
Imminent shutoff Insufficient battery backup time Protect load equipment in time
FAULT
Problem Displayed Possible cause Remedy
Inverter overload Overload Check the loads and remove some
noncritical loads.
Check if some loads are failed.
Bypass overload Overload Check the loads and remove some
noncritical loads.
Check if some loads are failed.
Out. short circuit abnormally low impedance Remove all the loads. Turn off the UPS.
placed on its output and Check if UPS output and loads is short
considers it a short circuit circuit.
Ensure short circuit is removed before
turning on again.
UPS temp. fault Inside temperature of UPS is too Check the ventilation of UPS and the
high ambient temperature.
DC bus + or - too high UPS internal fault, the + or -DC Consult dealer.
BUS voltage is too high
DC bus + or - too low UPS internal fault, the + or -DC Consult dealer.
BUS voltage is too low
DC bus unbalanced UPS internal fault, the voltage Consult dealer.
difference between DC Bus+ and
DC bus- is too large
DC bus short circ. UPS internal fault Consult dealer.
Max inverter volt UPS internal fault, the inverter Consult dealer.
voltage is too high
Min inverter volt UPS internal fault, the inverter Consult dealer.
voltage is too low
ELSE CASES
Problem Displayed Possible cause Remedy
No indication, no No input voltage Check the building wiring and input
warning tone even cable.
though system is Check if the input breaker is closed.
connected to mains
power supply
Green LED is not on Inverter not switched on Press On-Switch to turn on UPS.
even though the
power supply is
available
Emergency supply Batteries are not fully charged / Charge the batteries for at least 12
period shorter than batteries defect hours and then check capacity.
nominal value

42
8.2 Silencing the alarm
Press the ESC (Escape) button 3s on the front panel display to silence the alarm. Check
the alarm condition and perform the applicable action to resolve the condition. If the
alarm status changes or press the ESC button 3s on the front panel display, the alarm
beeps again, overriding the previous alarm silencing.

43
9. Specifications
9.1 UPS Block Diagram

9.2 UPS Specification

Models 6K 6KS 10K 10KS 10K 3-1 10KS 3-1

6KVA/ 6KVA/ 10KVA/ 10KVA/ 10KVA/ 10KVA/


Rated power (1)
6KW 6KW 10KW 10KW 10KW 10KW
Rated frequency 50/60Hz

Voltage range
(Phase voltage)

110Vac-276Vac
Input
Rated voltage
(Phase voltage) 220/230/240VAC

Rated current
(1phase) with 34A 42A 53A 61A 53A 61A
16pcs battery (2)
Rated current
(3phase) with NA NA NA NA 18A 21A
16pcs battery (2)
Rated current
(1phase) with 35A 45A 54A 65A 54A 65A
20pcs battery (2)

44
Models 6K 6KS 10K 10KS 10K 3-1 10KS 3-1
Rated current
(3phase) with NA NA NA NA 19A 22A
20pcs battery (2)
Input
≤60% rated load: 40-70Hz
Frequency
>60% rated load: 45-55Hz (50Hz system)/54-66Hz (60Hz system)
Charging Range 1~4A 2~12A 1~4A 2~12A 1~4A 2~12A
current (1) Default 1.4A 4A 2A 4A 2A 4A

Rated voltage
(Phase voltage) 220/230/240VAC

105%-125% Load, 10 minutes transfer to Bypass;


Overload on
Output 125%-150% Load, 30 seconds transfer to Bypass;
normal mode
>150% Load, 0.5 seconds transfer to Bypass
Short-circuit
54A for 54A for 113A for 113A for 113A for 113A for
current on normal
mode 200ms max 200ms max 200ms max 200ms max 200ms max 200ms max

Transfer Time Line<->Battery 0ms

Transfer Time INV<->Bypass 0ms

Battery

Battery Voltage 192/240VDC selectable

Battery Number 16/20PCS selectable

Environment

Ambient temperature 0°C ~ 50°C (Derating 50% above 40°C)

Relative humidity 0 ~ 95%(no condensing)

Operating altitude <3000m (Derating use above 1km, the load should de-rating 1% every up 100m)
Storage temperature
-15°C ~ 40°C
(with battery)
Storage temperature
-25°C ~ 55°C
(without battery)
Criterion

Safety IEC/EN 62040-1

EMC IEC/EN 62040-2

Performance IEC/EN 62040-3

(1) In CVCF mode, UPS needs to be de-rated to 60% capacity (rated output power and maximum charging
current).
(2) @ 220VAC input phase voltage, rated output power and maximum charging.

45
614-40079GN1-00

46

You might also like