Manual Ups Black RT Iot 6-10kva
Manual Ups Black RT Iot 6-10kva
Manual Ups Black RT Iot 6-10kva
KOLFF
Scan to Download APP
Service and support:
Call your local service representative
SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be
followed during installation and maintenance of the UPS and batteries.
The UPS that are covered in this manual are intended for installation in an environment
within 0 to 50°C, free of conductive contaminant.
Special symbols
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric
shock symbol.
EU separate collection and lead content mark for lead acid batteries. Indicates
that the battery must not be disposed of to the normal household waste but be
separately collected and recycled.
EU separate collection mark for waste electrical and electronic equipment (WEEE).
Indicates that the item must not be disposed of to the normal household waste
but be separately collected and recycled.
Safety of persons
RISK OF VOLTAGE BACKFEED. The system has its own power source (the battery). Isolate
the UPS and check for hazardous voltage upstream and downstream during lockout-
tagout operation. Terminal blocks may be energized even if the system is disconnected
from the AC power source.
Dangerous voltage levels are present within the system. It should be opened exclusively
by qualified service personnel.
The system must be properly grounded.
The battery supplied with the system contains small amounts of toxic materials. To avoid
accidents, the directives listed below must be observed:
- Servicing of batteries should be performed or supervised by personnel knowledgeable
about batteries and the required precautions.
- When replacing batteries, replace with the same type and number of batteries or
battery packs.
- Do not dispose of batteries in a fire. The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may
be very high.
Precautions must be taken for all handling:
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
- Determine if battery is inadvertently grounded. If inadvertently grounded, remove
source from ground. Contact with any part of a grounded battery can result in
electrical shock. The likelihood of such shock can be reduced if such grounds are
removed during installation and maintenance (applicable to equipment and remote
battery supplies not having a grounded supply circuit).
Product safety
The UPS connection instructions and operation described in the manual must be followed
in the indicated order.
UPS enclosure IP rating IP20.
CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with
branch circuit overcurrent protection.
The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible. The unit
can be disconnected from AC power source by opening this circuit breaker.
An additional AC contactor is used for back feed protection and must comply with IEC/EN
62040-1 (the creepage and clearance distances shall meet the basic insulation
requirements for pollution degree 2).
Disconnection and overcurrent protection devices shall be provided by others for
permanently connected AC input (Normal AC/Bypass AC) and AC output circuits.
Check that the indications on the rating plate correspond to your AC powered system and
to the actual electrical consumption of all the equipment to be connected to the system.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and
shall be easily accessible
Never install the system near liquids or in an excessively damp environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -25°C to +55°C without battery (-15°C to
+40°C with battery).
TN-S/IT/TN-C/TT of electrical supply system may be connected by UPS.
This UPS may be provided with a maximum of 6 extension battery cabinets or equivalent.
Special precautions
The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling
operations.
All handling operations will require at least two people (unpacking, lifting, installation in
rack system).
Before and after the installation, if the UPS remains de-energized for a long period, the
UPS must be energized for a period of 24 hours, at least once every 6 months (for a normal
storage temperature less than 25°C). This charges the battery, thus avoiding possible
irreversible damage.
For three-phase AC input installation, this equipment complies with IEC 61000-3-12
provided that the short-circuit power Ssc is greater than or equal to 3.63MW at the
interface point between the user’s supply and the public system. It is the responsibility of
the installer or user of the equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to 3.63MW.
During the replacement of the Battery Module, it is imperative to use the same type and
number of elements as the original Battery Module provided with the UPS to maintain
an identical level of performance and safety.
This is a category C3 UPS product. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.
CONTENTS
1. Introduction ........................................................................................................................ 1
1.1 Product Features .......................................................................................................... 1
1.2 Environmental protection ............................................................................................ 2
2. Product Overview ............................................................................................................... 3
2.1 Model list ..................................................................................................................... 3
2.2 Presentation ................................................................................................................. 5
3. Installation ........................................................................................................................ 10
3.1 Unpacking and Inspecting .......................................................................................... 10
3.2 Checking the accessory kit ......................................................................................... 11
3.3 Mechanical Install ...................................................................................................... 12
3.4 Power cables connection ........................................................................................... 17
4. Parallel system Installation and Operation (Optional) ...................................................... 24
4.1 Wiring for AC Cable .................................................................................................... 24
4.2 Wiring for parallel signal cable ................................................................................... 28
4.3 Parallel system Operation .......................................................................................... 28
5. Operation .......................................................................................................................... 29
5.1 LCD panel ................................................................................................................... 29
5.2 LCD description .......................................................................................................... 31
5.3 Display functions ........................................................................................................ 32
5.4 User settings .............................................................................................................. 33
5.5 Starting the UPS with utility ....................................................................................... 34
5.6 Starting the UPS on Battery ....................................................................................... 34
5.7 UPS Shutdown............................................................................................................ 35
6. Communication ................................................................................................................ 36
6.1 RS232 and USB ........................................................................................................... 36
6.2 UPS remote control functions .................................................................................... 36
6.3 IoT .............................................................................................................................. 37
6.4 Modbus TCP ............................................................................................................... 38
6.5 Intelligent Card (optional) .......................................................................................... 38
6.6 UPS Management Software ....................................................................................... 38
7. UPS maintenance .............................................................................................................. 40
7.1 Equipment care .......................................................................................................... 40
7.2 Transporting the UPS ................................................................................................. 40
7.3 Storing the equipment ............................................................................................... 40
7.4 Recycle ....................................................................................................................... 40
8. Troubleshooting ................................................................................................................ 41
8.1 Typical alarms and faults ............................................................................................ 41
8.2 Silencing the alarm..................................................................................................... 43
9. Specifications .................................................................................................................... 44
9.1 UPS Block Diagram ..................................................................................................... 44
9.2 UPS Specification ....................................................................................................... 44
1. Introduction
Thank you for selecting our UPS to protect your electrical equipment.
We recommend that you take the time to read this manual to take full advantage of
the many features of your UPS.
Before installing your UPS, please read the booklet presenting the safety instructions.
Then follow the indications in this manual.
1
1.2 Environmental protection
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing
components.
• The cardboard we use comprises over 50% of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packing materials are recyclable.
Follow all local regulations for the disposal of packing materials.
Product
The product is mainly made up of recyclable materials.
Dismantling and disassembly must take place in compliance with all local regulations
concerning waste. At the end of its service life, the product must be transported to
recycling centers, re-use and treatment facilities for waste electrical and electronic
equipment (WEEE).
Battery
The product contains lead-acid batteries that must be processed according to
applicable local regulations concerning batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
2
2. Product Overview
2.1 Model list
1. ‘xxK’ model means ‘standard model’ with batteries, ‘xxKS’ model means ‘long backup model’
without battery.
2. 16 or 20 batteries could be selected for UPS and EBM (External Battery Modular).
3. The weight in the table below is reference only, please see the labels on the carton for details.
4. Dimension ‘D’ is chassis only, not including panel.
Tower model:
Product Description Net Weights (kg) Unit Size
(W x H x D)(mm)
Tower 6KS 16
13.5
Tower 6KS 20
225*353.2*416
Tower 10KS 16
15.5
UPS(1-1) Tower 10KS 20
model Tower 6K 16 49.5
Tower 6K 20 57.9
Tower 10K 16 59
Tower 10K 20 68.2
Tower 3-1 10K 16 59.5
225*589*416
UPS(3-1) Tower 3-1 10K 20 68.7
model Tower 3-1 10KS 16
22.7
Tower 3-1 10KS 20
Tower EBM (2) 192 9AH 94.5
EBM
Tower EBM (2) 240 9AH 115.6
RT model:
Product Description Net Weights (kg) Unit Size
(W x H x D)(mm)
RT 6KS 16
13.6
RT 6KS 20
RT 10KS 16
15.5
UPS(1-1) RT 10KS 20
438*86.3(2U)*540
Model RT 6K 16
13.3
RT 6K 20
RT 10K 16
15.2
RT 10K 20
3
Product Description Net Weights (kg) Unit Size
(W x H x D)(mm)
RT 3-1 10KS 16
15.8
UPS(3-1) RT 3-1 10KS 20
438*86.3(2U)*540
model RT 3-1 10K 16
15.5
RT 3-1 10K 20
RT EBM 192 9AH (1) 51.8
(1)
RT EBM 240 9AH 60.5
EBM 438*129(3U)*559
RT EBM 192 7AH (2) 46.1
RT EBM 240 7AH (2) 56.1
(1) For RT 10kVA UPS.
(2) For RT 6kVA UPS
4
2.2 Presentation
2.2.1 Tower model:
• UPS modular:
Front view
1. Ventilation area
2. LCD Modular, including:
2(1)---Button,
2(2)---LCD screen,
2(3)---LED indicator
5
Rear view
1. Intelligent slot 8. RJ45 (for EBM detect)
2. RS232 9. AC Input /Output port (Terminal Block)
3. Ethernet port (RJ45, for IoT function) 10. Input switch
4. USB 11. External battery port
5. Wireless (HDMI, For IoT function) 12. Maintenance bypass switch (optional,
6. RPO& DRY in/out default is yes)
7. Parallel Slot
6KS(1-1) 10KS(1-1)
6
• EBM(External Battery Modular):
Front view
1. Ventilation area
2. EBM label
Rear view
1. EBM port 1
2. EBM port 2
3. Fuse board cover (replace EBM fuse)
4. EBM detection Box (RJ45 port)
7
2.2.2 RT model:
• UPS Modular
Front view
1. Ventilation area
2. LCD Modular, including: 2(1)---Button ,2(2)---LCD screen,2(3)---LED indicator
Rear view
1. INTELLIGENT SLOT 7. PARALLEL SLOT
2. RS232 8. RJ45 (for EBM detect /RT MBP detect)
3. Ethernet port (RJ45, for IoT function) 9. AC Input /Output port(Terminal Block)
4. USB 10. Breaker of input(only for 1-1 model,
5. Wireless (HDMI, For IoT function) optional ,default is no)
6. RPO& DRY in/out 11. External battery port
UPS (1-1)
UPS (3-1)
8
• EBM(External Battery Modular):
Front view
1. EBM label area
2. EBM label
Rear view
1. Fuse board cover (replace EBM fuse)
2. EBM port 1
3. EBM port 2
4. EBM detection Box (RJ45 port)
9
3. Installation
It is recommended to move the equipment to the installation site by using a pallet jack
or a truck before unpacking.
The system may be installed only by qualified electricians in accordance with applicable
safety regulations.
Some of cabinet is heavy, please install it with at least two peoples.
• Tower EBM
10
• RT UPS
• RT EBM
Note:
The cabinet is heavy, please see spec weight provided on the carton/label.
Do not lift the unit’s front panel and rear panel.
Discard or recycle the packaging in a responsible manner, or store it for future use.
Packing materials must be disposed in compliance with all local regulations concerning
waste.
Parallel cable O O O O
Tower foot √ O √ √ √
Quick start (EBM) √
User manual (UPS) √ √ √ √
11
RT model
1-1 model 3-1 model
RT UPS RT UPS RT EBM
RT UPS 10K RT UPS 10KS
6K/10K 6KS/10KS
Battery cable O O √
EBM detection cable √
Copper bus-bar √ √
USB cable √ √ √ √
RS232 cable O O O O
Parallel cable O O O O
Tower foot √ √ √ √
Extension plate
of Tower foot
√
Rack ear √ √ √ √ √
Rack rail kit O O O O O
Quick start(EBM) √
User manual(UPS) √ √ √ √
Note :√--- Standard configuration; O---Optional, default is Not configured;
UPS model
12
EBM model
EBM model
EBM installation steps are the same as UPS as above.
It is recommended to place EBM modular to UPS’s left side.
3.3.2 RT model:
1. RT models support 2 installation modes: Rack installation and Tower installation.
2. To keep good ventilation, please keep a free-space (500mm at least) for front / rear
panels of the module.
3. Do not carry the front/rear panel of the module during installing.
Rack installing
This procedure is suitable for 19 inch rack cabinet installation, it is recommended that
the depth of the cabinet be no less than 800mm.
UPS model
Identify the final position and keep ‘2U’ space for this installing.
1. Install the rail kit (if configured). This rail kit is '2U & with screw holes (M5)', the
depth of the rail kit is: 443-773 mm.
13
Fasten the rail kit to the cabinet with 8pcs M5 screws + washers (as below):
3. Slide the unit into ‘rail kit’ and make sure tighten the ‘rack mounting screw’.
14
EBM model
Identify the final position and keep ‘3U’ space for this installing, and it is recommended
to be installed below to UPS.
3. Slide the unit into ‘rail kit’ and make sure tighten the ‘rack mounting screw’.
15
Tower installing
UPS model
1. Rotate the LCD model to tower direction.
2. Set up the ‘Tower foot’, then take the unit into ‘Tower foot’.
EBM model
1. Set up the ‘Extension plate’ as below and install to ‘Tower foot’ from UPS.
2. Take the UPS& EBM into ‘Tower foot’ individually: Place EBM modular to UPS’s right
side and align with front-panel.
16
3.4 Power cables connection
This chapter introduces how to wiring AC IN/OUT cable to UPS in difference mode, and
UPS connecting with EBM/MBP.
3.4.1 Input /Output wiring specifications
Before wring UPS, upstream breaker and backfeed contactor should be configured to
avoid power backfeed to unity. And “backfeed voltage danger” warning label should
be added in backfeed contactor or device. Before operating, UPS input should cut off,
and check all terminals voltage to avoid voltage dangerous. Backfeed contactor rating
current should be larger than UPS rating input current.
Below figures show the wiring system of UPS input and output.
Danger!
The rated current of the utility power switch must be greater than the UPS input
current, otherwise the utility power switch may be burnt!
17
Read the Safety instructions regarding backfeed protection requirements.
Recommended cable minimum cross-sectional:
Model 6K(S) 1-1 10K(S) 1-1 10K(S) 3-1
Protective earthing conductor 10mm2 10mm2 10mm2
Input L, N cable 6mm2 10mm2 10mm2
Output L, N cable 6mm2 10mm2 10mm2
Battery cable 6mm2 10mm2 10mm2
The length of the output cable is recommended not to exceed 10 meters, otherwise, it may cause
radio interference. If a length of output cable over 10 meters requests, please contact distributors/
agents for details.
18
3-1 model:
This model support 2 modes setting as below, default is setting with 3-1 mode.
1-1 mode
Short ‘UPS input terminal L1/L2/L3’ with ‘busbar’, then connect AC cable
3-1 mode
• RT UPS
1-1 model:
19
3-1 model:
This model support 2 modes setting as below, default is setting with 3-1 mode.
1-1 mode
Short ‘UPS input terminal L1/L2/L3’ with ‘busbar’, then connect AC cable
3-1 mode
For cables well fixed, it is recommended to tie these cables to the convex of rear-panel.
20
3.4.3 Wiring with external battery modular (EBM) (DC source to UPS)
1. Be sure to disconnect the battery cable from the EBM before connecting the
battery terminals of the UPS
2. Make sure the UPS is completely off before connecting or disconnecting the EBM.
3. Before connecting the EBM, make sure that the EBM specification is compatible
with UPS configuration.
4. Do not reverse the polarity of the external battery.
• Connect with the configured EBM:
Connect EBM to UPS with ‘Battery cable’ and ‘EBM detection cable’.
Tower EBM
Note:
1. Extended runtime with up to 6 Extended Battery Modules(EBMs) per UPS.
2. Extend more than 2 EBMs, additional ground wires (10mm2 cross-sectional area)
are required.
21
RT EBM
Note:
Extended runtime with up to 6 Extended Battery Modules(EBMs) per UPS.
Note:
1.If additional battery cable needed for installation, it must follow cable specification
and the maximum length of battery cable 10 meters for application.
2.If a length of battery cable over 10 meters requests, please contact distributors/
agents for details.
22
3.4.4 Wiring with RT MBP (MBP source to R/T UPS only)
RT MBP is RT UPS’s optional modular, UPS can be used with the MBP to implement the
maintenance bypass switching function to ensure that the output of the system is not
affected during the UPS maintenance.
23
4. Parallel system Installation and Operation (Optional)
If your UPS is configured with parallel function, up to 3 UPSs can be connected in
parallel to configure a sharing and redundant output power.
In parallel system, the mechanical installation for each modular is same as the single
system. Details please refer to Chapter 3.3.
24
Tower model parallel system
• 1-1 model
• 3-1 model
1-1 mode
25
3-1 mode
26
• 3-1 model
1-1 mode
3-1 mode
27
4.2 Wiring for parallel signal cable
Parallel signal cable connection diagram:
Remove the cover of ‘parallel box’, then connect each UPS one by one with ‘parallel
cable’, make sure the cable is screwed to parallel port tightly.
It is recommended to lock the ‘parallel cable’ (as above) for preventing the parallel ports
suffering an unexpected pulling-force and causing the parallel system fault.
28
5. Operation
5.1 LCD panel
The UPS has a five-button graphical LCD. It provides useful information about the UPS
itself, load status, events, measurements and settings.
The LED:
Indicator Status Description
The UPS is operating normally on Online or on High
On
Green Efficiency mode.
29
The buttons:
The button Function Illustration
Press the Button for >100ms & < 1s can power on
Power on the UPS without utility input at the condition of
battery connected
Turn off Press the button > 4s can turn off the UPS
The Buzzer :
The buzzer General Meaning
Back Light:
After 10 minutes of inactivity, the LCD backlight will automatically dim. Press any
button to restore the screen.
30
5.2 LCD description
Battery mode with This warning is approximate, and the actual time
1 beep every 1 battery low to shutdown may vary significantly.
seconds
31
Some unnecessary loads should be cut off to
Overload
reduce the load.
UPS status
UPS mode, IoT status, date/time, battery status ,
parallel information and current alarms
32
5.4 User settings
Note: if the utility power is IT system, the site wiring fault function should be disabled.
33
5.5 Starting the UPS with utility
34
5.7 UPS Shutdown
35
6. Communication
6.1 RS232 and USB
1. Communication cable to the serial or USB port on the computer.
2. Connect the other end of the communication cable to the RS232 or USB
communication port on the UPS.
6.2 UPS remote control functions
• Remote Power Off (RPO )
When RPO is activated, UPS will cut off output immediately, and continues to alarm.
RPO Comments
Connector type 16 AWG Maximum wires
External breaker specification 60 V DC/30 V AC 20 mA max
Reset :
1. Check the RPO connector status;
2. Clear fault state through LCD.
• Dry in
Dry in function can be configured (see Settings > Dry in).
Dry in Comments
Connector type 16 AWG Maximum wires
External breaker specification 60 V DC/30 V AC 20 mA max
• Dry out
Dry out is the relay out, dry out function can be configured (see Settings > Dry out).
36
6.3 IoT
Built-in ethernet port and WLAN (optional accessary) port enable market-leading and
easy-to-use IoT solutions for:
• Winpower View mobile app which allows you to remote monitor UPS(s) and keep
informed about critical UPS event always.
• Remote report UPS faults and status (contact with your service for detail) from
APP or registered APP account (Email address).
• Automatic UPS and battery warranty alert from APP or registered APP account
(Email address).
IoT Connection
- Wired network connection
1. Connect UPS to router or switch with network cable.
Please use CAT6 shielded network cable.
Make sure your IT settings can access the public network and Microsoft Azure Cloud.
2. Enable the IoT function in LCD (see Settings -> IoT)
3. Search the “WinPower View” from Google Play store or Apple APP store,
downloading and installing.
4. Open the app, register an account, log in, follow the instructions of the app.
5. Tap on the upper right corner, scan the SN barcode on UPS label to add device.
For more detail information and Q&A about the IoT and APP, please refer to the HELP
menu in the app.
37
6.4 Modbus TCP
Built-in ethernet port offers Modbus TCP feature to facilitate remote monitoring of the
UPS into your own software. Contact with your service for protocol details.
6.5 Intelligent Card (optional)
Intelligent Card allow the UPS to communicate with different types of devices in
variety of networking environments. The UPS could use the following connectivity
cards, please contact your local distributor for details
• NMC Card - Ideal monitoring solution enables user to monitor and control the
status of UPS on web browser via internet
• CMC card - provides connection to Modbus protocol with standard RS485 signal.
• AS400 G2 card - Provides voltage-free dry-contact signals for programmable
controller and management system
• EMP - Supports temperature and humidity sensors for remote environment
monitoring, should work with NMC Card
6.6 UPS Management Software
6.6.1 WinPower
WinPower provides user-friendly interface to monitor and control your UPS. This
unique software provides safely auto shutdown for multi-computer systems while
power failure. With this software, users can monitor and control any UPS on the same
LAN no matter how far from the UPSs.
Installation procedure:
1. Go to the website: http://www.ups-software-download.com/content/ups-
download-software/download.html
38
2. Choose the operation system you need and follow the instruction described on the
website to download the software.
3. When downloading all required files from the internet, enter the serial No: 511C1-
01220-0100-478DF2A to install the software.
When you finish installation, restart your computer, the WinPower software will appear
as a green plug icon located in the system tray, near the clock.
WinPower View is a mobile app which allows you to centralized monitoring UPS(s)
connected to cloud. Please download it from Google Play store or Apple APP store.
Please refer to the chapter 6.3 for IoT connection.
39
7. UPS maintenance
7.1 Equipment care
For the best preventive maintenance, keep the area around the equipment clean and
dust free. If the atmosphere is very dusty, clean the outside of the system with a
vacuum cleaner.
For full battery life, keep the equipment at an ambient temperature of 25°C (77°F).
The batteries are rated for a 3-5 year service life. The length of service life varies,
depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace
batteries at least every 4 years to keep units running at peak efficiency.
7.2 Transporting the UPS
Please transport the UPS only in the original packaging. If the UPS requires any type
of transportation, verify that the UPS is disconnected and turned off.
40
8. Troubleshooting
The UPS is designed for durable, automatic operation and also alert you whenever
potential operating problems may occur. Usually the alarms shown by the control panel
do not mean that the output power is affected. Instead, they are preventive alarms
intended to alert the user.
Events are silent status information that are recorded into the Event log. Example =
"Battery charging".
Alarms are recorded into the Event log and displayed on the LCD status screen with
the logo blinking. Some alarms may be announced by a beep every 1 second.
Example = "Battery low".
Faults are announced by a continuous beep and red LED, recorded into the Event log.
Example = Out. short circuit.
Use the following troubleshooting chart to determine the UPS alarm condition.
8.1 Typical alarms and faults
To check the Event log:
1. By pressing on the menu of “Event log”.
2. Scroll through the listed events or faults.
3. The following table describes typical conditions.
WARNING
Problem Displayed Possible cause Remedy
Check the maintain bypass switch
On Maintain Bypass Maintain bypass switch is open
status
Site Wiring alarm Phase and neutral conductor at Reverse mains power wiring.
input of UPS system are reversed
No battery Battery pack is not connected Do the battery test to confirm.
correctly Check the battery bank is properly
connected to the UPS.
Check the battery breaker is turn on or
fuse OK.
Battery low Battery voltage is low When audible alarm sounding every
second, battery is almost empty.
End battery life The battery has reached the end Consult dealer if replace the battery
of its life
Power overload Power requirements exceed the Check the loads and remove some
UPS capacity noncritical loads.
Check if some loads are failed
Overload pre-alarm The load exceeds the preset Check the loads or reset the pre-alarm
value value
Fan Lock Fan abnormal Check if the fan is running normally or
fan detection cable disconnected
UPS temp. alarm Inside temperature of UPS is too Check the ventilation of UPS and the
high ambient temperature.
41
Amb. temp. alarm The ambient temperature is too Check the environment ventilation
high
Imminent shutoff Insufficient battery backup time Protect load equipment in time
FAULT
Problem Displayed Possible cause Remedy
Inverter overload Overload Check the loads and remove some
noncritical loads.
Check if some loads are failed.
Bypass overload Overload Check the loads and remove some
noncritical loads.
Check if some loads are failed.
Out. short circuit abnormally low impedance Remove all the loads. Turn off the UPS.
placed on its output and Check if UPS output and loads is short
considers it a short circuit circuit.
Ensure short circuit is removed before
turning on again.
UPS temp. fault Inside temperature of UPS is too Check the ventilation of UPS and the
high ambient temperature.
DC bus + or - too high UPS internal fault, the + or -DC Consult dealer.
BUS voltage is too high
DC bus + or - too low UPS internal fault, the + or -DC Consult dealer.
BUS voltage is too low
DC bus unbalanced UPS internal fault, the voltage Consult dealer.
difference between DC Bus+ and
DC bus- is too large
DC bus short circ. UPS internal fault Consult dealer.
Max inverter volt UPS internal fault, the inverter Consult dealer.
voltage is too high
Min inverter volt UPS internal fault, the inverter Consult dealer.
voltage is too low
ELSE CASES
Problem Displayed Possible cause Remedy
No indication, no No input voltage Check the building wiring and input
warning tone even cable.
though system is Check if the input breaker is closed.
connected to mains
power supply
Green LED is not on Inverter not switched on Press On-Switch to turn on UPS.
even though the
power supply is
available
Emergency supply Batteries are not fully charged / Charge the batteries for at least 12
period shorter than batteries defect hours and then check capacity.
nominal value
42
8.2 Silencing the alarm
Press the ESC (Escape) button 3s on the front panel display to silence the alarm. Check
the alarm condition and perform the applicable action to resolve the condition. If the
alarm status changes or press the ESC button 3s on the front panel display, the alarm
beeps again, overriding the previous alarm silencing.
43
9. Specifications
9.1 UPS Block Diagram
Voltage range
(Phase voltage)
110Vac-276Vac
Input
Rated voltage
(Phase voltage) 220/230/240VAC
Rated current
(1phase) with 34A 42A 53A 61A 53A 61A
16pcs battery (2)
Rated current
(3phase) with NA NA NA NA 18A 21A
16pcs battery (2)
Rated current
(1phase) with 35A 45A 54A 65A 54A 65A
20pcs battery (2)
44
Models 6K 6KS 10K 10KS 10K 3-1 10KS 3-1
Rated current
(3phase) with NA NA NA NA 19A 22A
20pcs battery (2)
Input
≤60% rated load: 40-70Hz
Frequency
>60% rated load: 45-55Hz (50Hz system)/54-66Hz (60Hz system)
Charging Range 1~4A 2~12A 1~4A 2~12A 1~4A 2~12A
current (1) Default 1.4A 4A 2A 4A 2A 4A
Rated voltage
(Phase voltage) 220/230/240VAC
Battery
Environment
Operating altitude <3000m (Derating use above 1km, the load should de-rating 1% every up 100m)
Storage temperature
-15°C ~ 40°C
(with battery)
Storage temperature
-25°C ~ 55°C
(without battery)
Criterion
(1) In CVCF mode, UPS needs to be de-rated to 60% capacity (rated output power and maximum charging
current).
(2) @ 220VAC input phase voltage, rated output power and maximum charging.
45
614-40079GN1-00
46