Short-Circuit Protection For Low-Voltage DC Distribution Systems
Short-Circuit Protection For Low-Voltage DC Distribution Systems
ScholarWorks@UARK
5-2017
Part of the Systems and Communications Commons, and the VLSI and Circuits, Embedded and
Hardware Systems Commons
Citation
Munasib, S. (2017). Short-Circuit Protection for Low-Voltage DC Distribution Systems Based on Solid-
State Circuit Breakers. Graduate Theses and Dissertations Retrieved from https://scholarworks.uark.edu/
etd/1875
This Thesis is brought to you for free and open access by ScholarWorks@UARK. It has been accepted for inclusion
in Graduate Theses and Dissertations by an authorized administrator of ScholarWorks@UARK. For more
information, please contact [email protected].
Short-Circuit Protection for Low-Voltage DC Distribution Systems Based on Solid-State Circuit
Breakers
by
Sharthak Munasib
Bangladesh University of Engineering and Technology
Bachelor of Science in Electrical Engineering, 2012
May 2017
University of Arkansas
_______________________
Dr. Juan C. Balda
Thesis Director
_______________________ _______________________
Dr. Simon S. Ang Dr. Yue Zhao
Committee member Committee member
ABSTRACT
coordination and reliability still continues. The objective of this thesis is to analyze issues
propose a short-circuit protection methodology based on solid-state circuit breakers (SSCBs) that
provides fault-current limiting (FCL). Simulation results for a simplified notional 1-kVdc
feasible for low-voltage dc distribution systems but requires connecting several devices in
parallel to open fast-rising fault currents. To validate the implementation of the FCL function,
the coordination between upstream and downstream SSCBs during a fault at different operating
compared by means of the let-through energies, and the impact of FCL on the thermal handling
I would like to express my sincere gratitude to my advisor, Dr. Juan C. Balda, for his
guidance and encouragement throughout my Master’s degree. His constructive advices and
critiques helpmed me progress my research in a timely manner. I would also like to thank my
thesis committee members Dr. Simon S. Ang and Dr. Yue Zhao.
The work accomplished for this thesis was supported under research contract from ONR
and ABB (Raleigh, NC). I would like to express my gratefulness for their financial support for
Finally, I would like to thank my caring parents, my younger brother, and my lovely wife
This MSEE thesis is dedicated to my parents, my younger brother Swapno, and my wife
Joyotree. I would not have accomplished this degree without your continuous help and
reassurance.
TABLE OF CONTENTS
1 Introduction .........................................................................................................................1
1.1 DC Electric Power Distribution .....................................................................................1
1.2 Protection Challenges Associated with DC Distribution Systems ..................................3
1.3 Literature Review of the Proposed SSCB Topologies ....................................................5
1.4 Thesis Objectives ..........................................................................................................8
1.5 Organization of the Theis ..............................................................................................9
1.6 References .................................................................................................................. 10
2 Notional Low-Voltage DC Distribution System ................................................................. 14
2.1 Introduction ................................................................................................................ 14
2.2 System Description ..................................................................................................... 14
2.3 System Simulations ..................................................................................................... 17
2.4 Modeling of SSCB ...................................................................................................... 18
2.4.1 Commonly used semiconductors for SSCBs ....................................................... 18
2.4.2 Development of the IGCT .................................................................................. 19
2.4.3 Modeling of an RB-IGCT as Solid-state Switch in a SSCB ................................ 19
2.4.4 Switching Characteristics ................................................................................... 21
2.5 Summary .................................................................................................................... 22
2.6 References .................................................................................................................. 23
3 Short-Circuit Protection Methodology incorporating a Fault-Current-Limiting Function .... 24
3.1 Introduction ................................................................................................................ 24
3.2 Fault Behavior of Notional Low-Voltage DC Distribution System .............................. 25
3.3 Proposed FCL Control Circuit based on Overcurrent Protection .................................. 29
3.4 Fault Analysis under FCL operation Integrated with Controller Delays ....................... 31
3.5 Fault Analysis without Energy-Storage Filter Capacitor at 1kVdc Load-Center Bus ... 33
3.6 Coordination between Upstream and Downstream SSCBs during FCL Operation……….37
3.7 Summary .................................................................................................................... 41
3.8 References .................................................................................................................. 41
4 Impact of FCL Function on the Operation of the Notional 1-kVDC System........................ 42
4.1 Introduction ................................................................................................................ 42
4.2 Fault-Current Detection Techniques ........................................................................... 42
4.3 Let-through Energy Comparison between Different Fault-Detection Techniques ........ 44
4.4 Comparison of Undervoltage and Overcurrent Threshold ............................................ 44
4.5 Impact of Fault-Current-Limiting on RB-IGCT’s Thermal Handling Requirement ...... 46
4.6 Impact of Fault-Current-Limiting on Metal-Oxide Varistors ...................................... 52
4.7 Summary .................................................................................................................... 55
4.8 References .................................................................................................................. 55
5 Conclusions and Recommendations for Future Work ........................................................ 57
5.1 Conclusions ................................................................................................................ 57
5.2 Recommendations for Future Work............................................................................. 59
Appendix A ....................................................................................................................... 60
LIST OF FIGURES
Fig. 1.1: Notional MVDC ring bus topology ..............................................................................2
Fig. 1.2: Schematic diagram for SiC SGTO Fault Current Limiter ...............................................6
Fig. 1.3: Schematic diagram for Emitter Turn-off DC Circuit Breaker ........................................7
Fig. 1.4: Schematic diagram of solid-state protection device........................................................7
Fig. 1.5: A unidirectional self-powered SSCB using a normally-on SiC JFET .............................8
Fig. 2.1: Circuit diagram of a post-regulated isolated dc-dc converter powering a simplified
1kVdc zone ............................................................................................................................... 15
Fig. 2.2: Single-bus single-breaker configuration for 1kVdc zone ............................................. 15
Fig. 2.3: Current waveforms at the 1-kVdc load center bus, DC Load 1, DC Load 2 and AC Load
Center input under rated steady-state conditions ....................................................................... 17
Fig. 2.4: GTO model in SimulinkTM: (a) symbol (b) equivalent circuit ...................................... 20
Fig. 2.5: Circuit-based modeling of the RB-IGCT ..................................................................... 20
Fig. 2.6: RB-IGCT turn-off waveforms .................................................................................... 22
Fig. 3.1: (a) Circuit schematic1-kVdc load center during a pole-to-pole fault at “DC Load 1”,
(b) equivalent circuit during the fault......................................................................................... 26
Fig. 3.2: Fault-current contributions from the buck and energy-storage capacitor for a pole to-
pole fault at DC Load 1 (without short-circuit protection at the 1-kVdc load center) .................. 27
Fig. 3.3: Fault-current control circuit implementing FCL function (a) block diagram (b) Simulink
representation ............................................................................................................................ 29
Fig. 3.4: XOR Gate: (a) structure (b) truth table ....................................................................... 30
Fig. 3.5: Current waveforms at the the buck converter output, 1-kVdc load center filter capacitor,
DC Load 1, DC Load 2, AC Load for a pole-to-pole fault at “DC Load 1” at t = 0.5 s ............. 31
Fig. 3.6: Voltage waveforms at the buck converter output, load center and ac load buses for a
pole-to-pole fault at “DC Load 1” at t=0.5 s .............................................................................. 32
Fig. 3.7: Current waveforms at the buck converter output, DC Load 1, DC Load 2, AC Load for
a pole-to-pole fault at “DC Load 1” at t = 0.5 s (filter capacitor at load-center bus removed) ..... 35
Fig. 3.8: Voltage waveforms at the buck converter output, dc load and ac load buses for a pole-
to-pole fault at “DC Load 1” at t = 0.5 s; load capacitors sized for 10% voltage ripple............... 35
Fig. 3.9: Voltage waveforms at the buck converter output, dc load and ac load buses for a pole-
to-pole fault at “DC Load 1” at t = 0.5 s; load capacitors sized for 5% voltage ripple ................ 36
Fig. 3.10: Voltage waveforms at the buck converter output, dc load and ac load buses for a pole-
to-pole fault at “DC Load 1” at t = 0.5 s; load capacitors sized for 1% voltage ripple ................ 36
Fig. 3.11: Current waveforms at the buck converter output, DC Load 1, DC Load 2, AC Load for
a pole-to-pole fault at “DC Load 1” at t = 0.5 s (case 1) ............................................................. 37
Fig. 3.12: Voltage waveforms at the buck converter output, dc load and ac load buses for a pole-
to-pole fault at “DC Load 1” at t = 0.5 s (case 1) ...................................................................... 38
Fig. 3.13: Current waveforms at the buck converter output, DC Load 1, DC Load 2, AC Load for
a pole-to-pole fault at “DC Load 1” at t = 0.5 s (case 2)............................................................. 39
Fig. 3.14: Voltage waveforms at the buck converter output, dc load and ac load buses for a pole-
to-pole fault at “DC Load 1” at t = 0.5 s (case 2) ....................................................................... 40
Fig. 4.1: Simplified circuit diagram for 1-kVDC load center for simulation of FCL impact on
MOV ........................................................................................................................................ 53
Fig. 4.2: RB-IGCT turn-off waveforms ..................................................................................... 53
CHAPTER 1
INTRODUCTION
The use of direct current (dc) for low-voltage distribution systems has recently gained
momentum, as validated by recent trends and developments in the power industry. Traditionally,
alternating current (AC) systems have been adopted worldwide as the main means of
distribution. The main systems of an electrical power grid can be classified as - generation,
transmission and distribution of power to loads [1,2]. Conventionally, each of these stages
handles ac power and the necessary AC equipment have been in use for years. But with
advancements in power electronic equipment, research community and industry alike have
architectures and relevant power electronic and protection devices. There are three main types of
Radial distribution: This is the most basic configuration for distribution of power, in
which a source supplies power to one or more loads via a common point, i.e. busbar.
This type of distribution system is easier to protect against faults and is comparatively
cheaper to construct.
Ring bus: The ring bus architecture, as shown in Fig. 1.1, provides an additional
supply path for distribution of power, and hence, added tolerance against faults on the
line.
1
the zones, increasing redundancy of supply and presenting the opportunity to optimise
the power dispatch of generation across the entire network. Zones are classified based
on the operation, i.e. supply zones, zones containing load centers. Of particular
interest for the application of this type of distribution are shipboard power systems
Higher power transfer capability through the power line having the same voltage rating
as an ac system: AC conductors deliver power dictated by the RMS voltage, whilst the
insulation level of the cables is determined using the peak voltage. However, DC
conductors can transmit power using the full voltage rating of the cable. This provides a
higher power transfer than ac systems by a factor of √2. Other attributes include zero
skin effect and zero reactive voltage drop. All of these combine to facilitate reduction
prime mover speed at optimum into the dc distribution bus. This ensures better dynamic
Reduction of power conversion stages starting from the source side moving on to the
load side;
Overall increase in system efficiency complemented by reduced weight and volume [7].
These advantages are driving a major shift in the use of dc distribution systems in recent
years. Typical applications range from large scale multiterminal dc systems to physically
compact power networks such as dc microgrids [8,9], shipboard power systems [10] and aircraft
applications [11,12]. The discussion of benefits presented above directly apply to all of these
applications, thus justifying the need for an analysis of the challenges and opportunities posed by
the applications. One of the prime challenges, protection against faults in dc systems, will be
briefly discussed in the next section along with the proposed solutions in literature.
Any protection system design needs to abide by the following criteria [8]:
Reliability
Selectivity
Stability
Speed
Sensitivity
disrupting the operation of the entire dc system. Typical faults that are evident are : short-circuit
3
faults, ground or pole-to-pole faults, and open-circuit faults, existing in architectures like multi-
terminal dc lines and multi-source distribution systems. Fault currents in dc systems have much
higher rates of rise compared to ac systems because the commonly-employed filter dc capacitors
at the output of power converters normally discharge through low cable impedances [8]. This
coordination among downstream and upstream protection devices because the time for the
downstream device to open before the upstream device operates is very short [13]. So, it may be
possible that an upstream breaker trips simultaneously with a downstream breaker. So,
research topic.
Unlike traditional ac systems where a natural zero crossing of the current is utilized for
opening a circuit breaker and fault isolation, short-circuit currents in dc systems must be
interrupted at high values to open the faulted branch. Major approaches for dc microgrid short-
circuit protection can be divided into “breaker-less” and “breaker-based” schemes [16-17]. The
former utilizes coordinated control of power converters to interrupt first the current and then no-
load mechanical contactors to isolate the faulted section, as well as reconfigure and re-energize
the system [18-19]. A “breaker-based” approach should provide more flexibility because the
circuit breaker should isolate the fault but enable continued operation of the non-faulted system
faster. The challenge is developing a compact and power-dense SSCB with the capability of
Mechanical circuit breakers have been used as the go-to solution for the traditional ac
distribution systems for a number of decades now. But in comparison with the fault current
behavior in a dc system, these breakers suffer from several disadvantages. A comparatively slow
4
response time, thus exposing the network components to an extremely high amplitude of fault
current, risks severe damage to both equipment and personnel. The longer time also results in
voltage sags near the faulted portion of the system, which threaten the required continuous
operation of critical loads which would then require equipment like UPS for constant power
flow. Another major disadvantage is the lack of natural zero-crossing of current, meaning the
presence of arc cannot be ignored by controlling the switching of the circuit breaker. All of these
demerits have prompted the researchers to look for solutions that are able to meet the protection
applications, SSCBs have proved to be the potentially effective solution. SSCB solutions
proposed in literature along with their applications will be briefly discussed in the following
section.
Cost-effective commercial dc SSCBs are not yet available, although many prospective
topologies are offered in the literature [15-36]. The semiconductor devices usually used are:
thyristors, insulated gate bipolar transistors (IGBTs), integrated gate commutated thyristors
(IGCTs), and gate turn-off thyristors (GTO). The major disadvantages remain to be the on-state
losses, robustness to overvoltages, and solution cost. So far, significant research has only been
done on HVDC or MVDC systems, but for low-voltage dc distribution, the research stage is still
the advantages of low conduction losses and high short-circuit current capability. GTOs were
5
Fig. 1.2. Schematic diagram for SiC SGTO Fault Current Limiter
considered because of not only their lower conduction losses and higher short-circuit current
capabilities compared to IGBTs, but also for not requiring auxiliary circuits for turn off.
References [29-31] presented proposals based on super GTOs making use of silicon carbide
materials.
A new topology for a fault current limiter was proposed using a combination of a silicon
controlled rectifier (SCR) and an IGBT forming the main switch in [32]. An input buffer was
necessary to absorb energy during fault current limiting. The purpose of using SCR in the main
conducting path is to get a comparatively lower voltage drop since electromechanical circuit
breakers have ideally zero voltage drops. RCD or a voltage-clamped snubber was used across the
commutation performed in two stages to counter overvoltages usually observed in a single stage
commutation has been suggested [33]. The prototype was built to handle a maximum rate of rise
of fault current of 12 A/s for a 700 V dc source with a source inductance of about 60 μH.
6
Fig. 1.3. Schematic diagram for Emitter Turn-off DC Circuit Breaker
Fig. 1.3 [34]. An RC snubber in parallel is provided to limit rate of voltage rise and a diode
provides freewheeling path. The ETO was chosen for its built-in current sensing feature because
of the emitter switch voltage providing an indication of the current flowing during the on-state.
The gate drive circuit for over-current protection was designed such that the emitter switch
voltage is above a certain reference value. The main features include fast switching, built-in
current sensing and voltage-control capability. A 1.5 kA/2.5 kV DC circuit breaker prototype
was built, which provides a compact structure and a fast response time of about 5 μs.
7
A bidirectional Solid-State Protection Device is shown in Fig. 1.4 [35]. The power
semiconductor devices suggested for this application are IGBT or IGCT. IGBT- and IGCT-based
SSPDs are proposed, which are rated at 1000V, 1800A and 1000V, 1000A respectively. These
devices implement fault interruption by quickly driving the fault current to zero. Wide-Band-Gap
(WBG) devices (i.e., mainly SiC or GaN devices) are the latest addition to SSCB applications.
One topology uses SiC JFET for a self-powered SSCB which senses voltage across the JFET to
send a signal to the driver circuit to reverse-bias the JFET, as shown in Fig. 1.5 [36].
Experimental results show a current-capability of 180 Amps interrupted within 0.8 μs for a 400-
V dc system.
There are many topologies for SSCBs proposed by researchers, among which the more
important ones are discussed above. The topologies try to address the concerns regarding the
short-circuit protection of dc distribution systems mentioned in Section 1.2. The use of an SSCB
8
1.4 Thesis Objectives
systems, which asks for challenging protection schemes. The main objective of this thesis is to
develop a solution that would be able to provide fault-current limiting, delivering unhampered
power to unfaulted loads and achieve coordination between the upstream and downstream
protection devices. To accomplish this objective and to augment the analysis to be applied to
dc-dc converter,
and
with an overview of system followed by brief descriptions of the components and modeling of
the SSCB using RB-IGCT. A detailed short-circuit analysis of the simplified 1kVdc system,
along with comparison between different fault detection techniques, and a sensitivity analysis
9
The proposed fault-current-limiting algorithm, control circuit and simulations performed
in MATLAB/SimulinkTM, together with the algorithm’s impact on the thermal capability of the
RB-IGCT, will be demonstrated in chapter 4. The conclusions and the recommendations for
1.6 References
[1] T. Gonen, Electric Power Distribution System Engineering, Second Edition. Boca Raton,
FL: CRC Press Taylor & Taylor Group, 2008.
[3] Chalfant, J.S. and Chryssostomos C., "Analysis of various all-electric-ship electrical
distribution system topologies." In Electric Ship Technologies Symposium (ESTS), 2011
IEEE, pp. 72-77. IEEE, 2011.
[5] D. Nilsson, A. Sannino, “Efficiency analysis of low- and medium voltage dc distribution
systems,” Power Engineering Society General Meeting, vol. 2, pp. 2315 – 2321, June
2004.
[6] M. E. Baran and N. R. Mahajan, “DC Distribution for Industrial Systems: Opportunities
and Challenges,” IEEE Trans. Industry Applications, vol. 39, no. 6, pp. 1596–1601,
November/December 2003
[7] K. Shenai and K. Shah, “Smart dc micro-grid for efficient utilization of distributed
renewable energy,” in Energytech, 2011 IEEE, May 2011.
10
[10] R. Schmerda, R. Cuzner, R. Clark, D. Nowak and S. Bunzel, "Shipboard Solid-State
Protection: Overview and Applications," in IEEE Electrification Magazine, vol. 1, no. 1,
pp. 32-39, Sept. 2013.
[11] S. Fletcher, P. Norman, S. Galloway and G. Burt, "Solid state circuit breakers enabling
optimised protection of DC aircraft power systems," in Power Electronics and
Applications (EPE 2011), Proceedings of the 2011-14th European Conference on,
Birmingham, 2011, pp. 1-10.
[12] M. Komatsu, N. Ide and S. Yanabu, "A Solid-State Current Limiting Switch for
Application of Large-scale Space Power Systems," in 2007 IEEE Power Electronics
Specialists Conference, Orlando, FL, 2007, pp. 1471-1476.
[13] Fletcher, S.D.A.; Norman, P.J.; Galloway, S.J.; Crolla, P.; Burt, G.M., "Optimizing the
Roles of Unit and Non-unit Protection Methods Within DC Microgrids," in Smart Grid,
IEEE Transactions on , vol.3, no.4, pp.2079-2087, Dec. 2012
[14] Cuzner, R.M.; Singh, V.; Rashidi, M.; Nasiri, A., "Converter topological and solid state
protective device trade-offs for future shipboard MVDC systems," in Electric Ship
Technologies Symposium (ESTS), 2015 IEEE , vol., no., pp.34-39, 21-24 June 2015
[15] Park, J.-D.; Candelaria, J., "Fault Detection and Isolation in Low-Voltage DC-Bus
Microgrid System," in Power Delivery, IEEE Transactions on , vol.28, no.2, pp.779-
787, April 2013
[16] Qiu, D., Liu ,X., Soman, R., Steurer, M. and Dougal, R.A. "Primary and backup protection
for fault current limited MVDC shipboard power systems." In Electric Ship
Technologies Symposium (ESTS), IEEE, pp. 40-47, 2015.
[17] Cairoli, P.; Dougal, R.A.; Lentijo, K., “Coordination between supply power
converters and contactors for fault protection in multi-terminal MVDC distribution
systems,” In Electric Ship Technologies Symposium (ESTS), IEEE , vol., no., pp.493,499,
22-24 April 2013
[18] Jin, C., Dougal, R.A. and Liu, S. “Solid-state Over-current Protection for Industrial DC
Distribution Systems,” In 4th International Energy Conversion Engineering
Conference and Exhibit (IECEC), pp. 26-29. June 2006.
[19] Cuzner, R.; MacFarlin, D.; Clinger, D.; Rumney, M.; Castles, G., "Circuit breaker
protection considerations in power converter-fed DC Systems," In Electric Ship
Technologies Symposium, 2009. ESTS 2009. IEEE , vol., no., pp.360-367, 20-22 April
2009
11
[20] Agostini, F., Umamaheswara V., Daniele T., Martin Arnold, Munaf R., Antonello A.,
Luca R., Davide P., and Harish S.. "1MW bi-directional DC solid state circuit breaker
based on air cooled reverse blocking IGCT." In Electric Ship Technologies Symposium
(ESTS), 2015 IEEE, pp. 287-292. IEEE, 2015.
[21] Steurer, M., Klaus F., Walter H., and Kaltenegger, K. "A novel hybrid current-limiting
circuit breaker for medium voltage: principle and test results." Power Delivery, IEEE
Transactions on 18, no. 2 (2003): 460-467.
[22] Sano, K, and Masahiro T. "A surge-less solid-state dc circuit breaker for voltage source
converter based HVDC transmission systems." In Energy Conversion Congress and
Exposition (ECCE), 2012 IEEE, pp. 4426-4431. IEEE, 2012.
[23] C. Meyer, S. Schroder and R. DeDoncker, “Solid-State Circuit Breakers and Current
Limiters for Medium-Voltage Systems Having Distributed Power Systems”, in IEEE
Transactions on Power Electronics, vol. 19, no. 5, pp. 1333-1340, 2004.
[24] Kempkes, M., I. Roth, and M. Gaudreau. "Solid-state circuit breakers for medium voltage
DC power.", in Electric Ship Technologies Symposium (ESTS), IEEE, 2011
[25] C. Meyer, M. Hoing and R. W. De Doncker, "Novel solid-state circuit breaker based on
active thyristor topologies," Power Electronics Specialists Conference, 2004. PESC 04.
2004 IEEE 35th Annual, 2004, pp. 2559-2564 Vol.4.
[28] Mantooth, H.A.; Saadeh, O.; Johnson, E.; Balda, J.C.; Ang, S.S.; Lostetter, A.B.;
Schupbach, R.M.; , "Solid-state fault current limiters: Silicon versus silicon carbide,"
in Power and Energy Society General Meeting - Conversion and Delivery of
Electrical Energy in the 21st Century, 2008 IEEE , vol., no., pp.1-5, 20-24 July 2008.
[29] A. Escobar, M. Saadeh, J.C. Balda, J. Bourne, Y. Feng, H. A. Mantooth, "A methodology
to coordinate solid-state fault current limiters with conventional protective devices,"
in IEEE/PES Power Systems Conference and Exposition (PSCE), 2011, Phoenix (AZ),
20-23 March 2011.
12
[30] Y. Feng, M. Saadeh, A. Escobar Mejia, J.C. Balda, S. S. Ang, H. A. Mantooth, “A
Solid State Fault Current Limiter Control Algorithm”, 9th International Power and
Energy Conference, October 27-29, 2010, Singapore.
[32] McEwan, Peter M., and Sarath B. Tennakoon. "A two-stage DC thyristor circuit
breaker." Power Electronics, IEEE Transactions on 12, no. 4, pp. 597-607. (1997)
[33] Luo, F., Jian C., Xinchun L., Yong K., and Shanxu D. "A novel solid state fault current
limiter for DC power distribution network." In Applied Power Electronics Conference
and Exposition, 2008. APEC 2008. Twenty-Third Annual IEEE, pp. 1284-1289. IEEE,
2008
[34] Xu, Z., Bin Z.,Sirisukprasert, S. Zhou,X. and Huang, A.Q. "The emitter turn-off thyristor-
based DC circuit breaker." In Power Engineering Society Winter Meeting, IEEE, vol. 1, pp.
288-293. IEEE, 2002.
[35] Schmerda, R., Cuzner R., Robin C., Damian N., and Bunzel.,S. "Shipboard solid-state
protection: Overview and applications." Electrification Magazine, IEEE , no.1,pp. 32-39
(2013)
[36] Z. Miao et al., "A self-powered ultra-fast DC solid state circuit breaker using a normally-
on SiC JFET," In IEEE Applied Power Electronics Conference and Exposition
(APEC), Charlotte, NC, 2015, pp. 767-773.
13
CHAPTER 2
2.1 Introduction
protection studies in later chapters, will be presented in this chapter. Relevant component and
device data are also provided. This system can be considered as a low-voltage dc microgrid, with
various loads powered through the use of power converters. This system would facilitate the
study of dc faults, and the impact of filter capacitors of power converters during short-circuit
systems would enable developing a concrete approach to defining protection requirements and
Figure 2.1 depicts the circuit schematic of a post-regulated isolated dc-dc converter
powering a simplified 1kVdc load center bus, which has two dc loads and one ac load. The
parameters for the 1-kVdc load center are given in Table 2.1. The complete system parameters
can be obtained by combining the parameters provided in Table 2.1 and Appendix A. The bus
ac power distribution systems, which is shown in Fig. 2.2. Characteristics of this simplified 1-
14
2.2.1 Unidirectional Post-Regulated Isolated DC-DC Converter: The medium-voltage dc side
is simply modeled by an ideal voltage source rated 20 kV, and a 20kV-1kV, 7.5 MW
evaluating the 1-kVdc zone performance under different scenarios. The PRIDCC consists
and a diode-based half bridge on the secondary side, followed by a buck converter
Fig. 2.1. Circuit diagram of a post-regulated isolated dc-dc converter powering a simplified
1kVdc zone
15
Table 2.1: 1-kVdc load center parameters
Parameters Values
Rated Total Power 7.5 MW
Rated DC Load Power 2x3.25 MW
Rated AC Load Power 1 MW
DC Bus Voltage 1 kV
Buck SSCB Rating 7.5 kA
Buck SSCB Short-Circuit Threshold 15 kA
Cable Resistance (1kV Sivacon busduct, 3.7 kA) 30 μΩ/m
Cable Inductance (1kV Sivacon busduct, 3.7 kA) 0.07 μH/m
Buck Converter to DC Load Center Bus Distance 100 m
DC Load Center Bus to DC Load Distance 50 m
L1 235 μH/ph
LCL Filter (AC load) C1 278 μF/ph
L2 52 μH/ph
regulating the 1kVdc output voltage. In the simulations, the SST is modeled as a
simplified two-level system. The SST practical implementation would require multiple
modules connected in series on the primary side and in parallel on the secondary side [1].
The use of SST is a favorable solution for microgrid systems because it provides suitable
voltage conversion with galvanic isolation, controllability and high power density (i.e.,
2.2.2 DC Loads: There are two dc loads equally rated at 3.25 MW and protected by SSCBs and
when the load SSCB opens. A filter capacitor has been included at the load center 1-kVdc
bus to provide bus voltage support during FCL operations, and its influence on short-
2.2.3 AC Load: There is also an ac load rated at 1 MW that represents a three-phase electric
motor load fed by a three-phase inverter with an output LCL filter. The dc input side is
protected by a SSCB.
16
2.2.4 DC Cables: The considered cable inductances have lengths of 100 m from the post-
regulated buck converter to the load center 1kVdc bus (nodes 1-2) powering the dc load
centers, and 50 m to each of the dc loads (nodes 2-3 and 2-4). The impact of
be discussed in chapter 4.
MATLAB/Simulink™ was selected as the software package for modeling the simple 1-kVdc
distribution system since it is the software package widely used for this type of analyses. A time
Figure 2.3 displays the steady-state current waveforms at the 1-kVdc load center bus, “DC
Load 1”, “DC Load 2” and input dc current to AC Load under rated conditions. Each of the dc
Fig. 2.3. Current waveforms at the 1-kVdc load center bus, DC Load 1, DC Load 2 and AC
Load Center input under rated steady-state conditions
17
2.4 Modeling of SSCB
This section briefly summarizes different semiconductor devices targeted for SSCB. An
RB-IGCT was selected by ABB as the solid-state switching waveforms are described next.
The SSCB should meet protection requirements for dc microgrids due to availability of
semiconductor devices capable of interrupting high fault currents within microseconds and
used are: silicon controlled rectifiers or thyristors, insulated-gate bipolar transistors (IGBTs),
integrated gate-commutated thyristors (IGCTs), and gate turn-off thyristors (GTO). Wide-band-
gap (WBG) devices (i.e., mainly SiC or GaN devices) are the latest ones added to SSCB
applications. Thyristors are semi-controlled devices so they are mainly useful for AC circuit
breakers since they require a zero-crossing of the current to turn naturally off [4]. They require
auxiliary circuits to turn them off immediately at currents different from zero. Among the
controlled devices, the RB-IGCT displays a lower on-state voltage drop compared to similarly
rated commercial IGBT. For example, the ABB IGBT (5SNA 1500E250300), rated at 2.5-
kV/1.5-kA, displays an on-state voltage drop of 2.5 V [7]. A similarly-rated RB-IGCT displays
an on-state voltage drop of 1.25 V; approximately, half of the IGBT voltage drop. So, the RB-
IGCT was selected by ABB as the solid-state switch in the SSCB because of its extremely low
conduction losses and the “thyristor” high turn-off current capability [3]. The RB-IGCT is able
to block voltages in both forward and reverse diretions, while only carrying current in the
forward direction.
18
2.4.2 Development of the IGCT
diodes and a simplified power circuit [3]. Essentially, IGCTs are semiconductor devices having
GTO structure and an integrated gate-drive unit. Initially, IGCTs were supposed to be used in
applications such as medium-voltage drives, STATCOMs, wind energy conversion systems, etc.
However, IGCTs are gaining ground as the semiconductor device of choice due to recent trends
conduction losses and ability to have hard-switching functionality in low operating frequencies.
waveforms are described in this section. An IGCT block is not available in “SimPowerSystems”
library of Matlab/SimulinkTM. Thus, based on the similarities between GTOs and IGCTs as
discussed above, the RB-IGCT was modeled using (1) a GTO block with a diode in series, (2) a
shunt impedance in parallel with the GTO block, and (3) an inductor in series as a clamp to
match the critical rate of rise of current during the device turn on.
The GTO thyristor block in SimulinkTM is modeled as a series connection of a resistor Ron,
an inductor Lon, and a DC voltage source Vf, and an ideal switch, as shown in Fig. 2-4 [5]. The
control of the switch is obtained by a logic signal based on the voltage V ak, the current Iak, .the
gate signal g. The typical turnoff characteristic is built into the model consisting of two
segments. Upon the gate signal switched to 0, the first decrease of current I ak is from Imax to
Imax/10, within the fall time tf. In the second segment, current decreases then from I max/10 to 0
19
(a) (b)
Fig. 2.4 . GTO model in SimulinkTM: (a) symbol (b) equivalent circuit
within the tail time Tt. The turn-off is achieved when the current Iak reaches 0. The latching and
evaluate the RB-IGCT switching characteristics. Only the turn-off waveforms will be shown, as
the model does not allow to model the turn-on properties of the switch. The R_Load corresponds
to a dc load rated 3.25 MW and powered by a 1kV dc source, which is equal to 307 mΩ. The
R_s and L_s components correspond to line resistance of 1.5 mΩ and inductance of 3.5 μH,
respectively, for a distance of 50 m from the source to the load, based on the values provided in
Table 2.1. An MOV is connected across the RB-IGCT-diode series branch to protect the IGCT
20
From the datasheet of the ABB 5SHZ 11H6500 6.5kV IGCT, the minimum inductance to
keep the rate of the current rise below the critical value is calculated as follows [6]:
𝑉𝑑𝑐
𝐿𝑚𝑖𝑛 = = 1 𝜇𝐻
𝑑𝑖𝑐𝑟
𝑑𝑡
𝑑𝑖𝑐𝑟
𝑤ℎ𝑒𝑟𝑒, 𝑉𝑑𝑐 = 1000 𝑉, = 1000 𝐴/𝜇𝑠
𝑑𝑡
As the circuit inductance is above the minimum required inductance during IGCT turn-on,
Figure 2-6 illustrates the turn-off waveforms for a single RB-IGCT rated at 1.5 kA. The
total current fall time is approximately 40 μs which compares very well with the values obtained
from experimental results in [3]. The MOV was not required to operate as the turn-off voltage
overshoot of about 1.6 kV was well within the device breakdown voltage. The turn-off
Table 2.2: Device Parameters Used for Loss Calculations for Determining RB-IGCT’s
Thermal Requirements
Parameters Values
Threshold voltage, VT 1.1 V
Device resistance, rT 0.1 mΩ
Average on-state current, IT(AV)M 1.5 kA
Maximum controllable turn-off current, ITGQM 3 kA
Junction-to-case thermal resistance, Rth(j-c) 8.5 K/kW
Maximum allowable junction temperature, Tvjmax 125 ℃
21
Fig. 2-6. RB-IGCT turn-off waveforms
2.5 Summary
parameters
limiting algorithm for short-circuit protection of the notional low-voltage dc distribution system
22
2.6 References
[3] Vemulapati, U., Arnold, M., Rahimo, M., Antoniazzi, A. and Pessina, D. "Reverse
blocking IGCT optimised for 1 kV DC bi-directional solid state circuit breaker," in Power
Electronics, IET , vol.8, no.12, pp. 2308-2314, 2015.
[4] C. Meyer, M. Hoing and R. W. De Doncker, "Novel solid-state circuit breaker based on
active thyristor topologies," Power Electronics Specialists Conference, (PESC), 2004
IEEE 35th Annual, pp. 2559-2564, Vol.4.
[7] ABB, “HiPak IGBT Module 5SNA 1500E250300’. Available online at:
https://library.e.abb.com/public/7f2b388387f8cef1c1257dea0043b854/5SHZ%2011H6500
_5SYA1254-01%20Dec%2014.pdf
23
CHAPTER 3
CURRENT-LIMITING FUNCTION
3.1 Introduction
possible to minimize safety hazards while limiting the affected area. This refers to achieving
threshold values corresponding to the used fault-detection technique (e.g., overcurrent) [1-
4]. In dc distribution systems, the short-circuit analysis is cumbersome because of the presence
of power converters having their own short-circuit protection, and inrush currents of filter
dc capacitors that may lead to nuisance tripping, making the choice of thresholds at
All solid-state circuit breakers (SSCB) employed in the previously mentioned low-
voltage distribution system are equipped with overcurrent control circuits, which are activated
upon the (fault) current reaching a set threshold value that depends on the supplied dc load.
Generally, a downstream SSCB has lower threshold values than an upstream SSCB. In other
words, the bus SSCB or the buck converter switch acting as SSCB has a higher threshold value
than a load SSCB. Similar protection strategies for dc distribution systems have been discussed
system is subjected to temporary faults to allow returning to normal operation once the fault
disappears. For the execution of FCL function, a control circuit for overcurrent protection is
presented in this chapter, along with the simulation results demonstrating a faulted dc load SSCB
24
This chapter is organized as follows: the typical fault behavior of the notional low-voltage
circuit current, and an analysis demonstrating effective coordination obtained by applying the
capacitors behave as high fault-current contributing sources. The fault behavior of the
discharging capacitor is analogous to the natural response of an RLC circuit, where the resistance
and inductance correspond to the low line impedances due to short distances. The response can
The equivalent circuit of the 1-kVdc load center for a pole-to-pole fault at “DC Load 1” is
presented in Fig. 3.1. Figure 3.2 shows simulation results to illustrate the fault-current
contributions from the buck and energy-storage capacitors at the 1-kVdc load center in the
pole-to-pole fault at DC Load 1, the current waveforms through equivalent faulted branch is
dominated by the discharges from the buck and energy-storage capacitors, followed by the free-
wheeling action performed by the buck converter diode. The buck capacitor current reaches a
peak of about 32.5 kA, while the energy-storage capacitor current at the 1-kVdc load center
reaches a peak of about 48 kA. Thus, the combined peak fault-current during the pole-to-pole
fault reaches a magnitude of about 82 kA without the operation of any protection equipment. It is
evident that a fault response of this magnitude can be potentially damaging to the active
25
(a)
(b)
Fig. 3.1. (a) Circuit schematic1-kVdc load center during a pole-to-pole fault at “DC Load 1”,
(b) equivalent circuit during the fault
components of the system, including semiconductor switches and capacitors themselves. For
example, the combined peak fault current of 82 kA is about 26 times higher than the rated dc
load current of 3.25 kA. Thus, the SSCB would require 26 times more devices in parallel if a dc
load is faulted and the fault current is to be interrupted at the peak value. Similar over-
dimensioning of the other system components based on the fault responses would result in added
weight, volume and cost, affecting the expected compactness of the dc distribution system in
applications such as onboard electrical systems in all-electric ships, more electric aircrafts etc.
26
Fig. 3.2. Fault-current contributions from the buck and energy-storage capacitor for a pole-
to-pole fault at DC Load 1 (without short-circuit protection at the 1-kVdc load center)
The distribution system presented in Fig. 2.1 of Chapter 2, will be used to derive the
expressions. The state equations based on the two capacitor voltages and two inductor currents
𝑑𝑉𝐶𝑏𝑢𝑐𝑘
𝑖𝐿𝑏𝑢𝑠 = 𝐶𝑏𝑢𝑐𝑘
𝑑𝑡
𝑑𝑉𝐶𝑏𝑢𝑐𝑘 𝑖𝐿𝑏𝑢𝑠
= (1)
𝑑𝑡 𝐶𝑏𝑢𝑐𝑘
𝑑𝑖𝐿𝑏𝑢𝑠
𝑖𝐿𝑏𝑢𝑠 𝑅𝑏𝑢𝑠 + 𝐿𝑏𝑢𝑠 = 𝑉𝐶𝑏𝑢𝑐𝑘 − 𝑉𝐶𝐹
𝑑𝑡
diLbus VCbuck −VCF −iLbus Rbus
= (2)
dt Lbus
𝑑𝑉𝐶𝐹
𝑖𝐿𝑏𝑢𝑠 + 𝐶𝐹 = 𝑖𝐿𝑒𝑞
𝑑𝑡
27
𝑑𝑉𝐶𝐹 𝑖𝐿𝑒𝑞 −𝑖𝐿𝑏𝑢𝑠
= (3)
𝑑𝑡 𝐶𝐹
𝑑𝑖𝐿𝑒𝑞
𝑖𝐿𝑒𝑞 𝑅𝑒𝑞 + 𝐿𝑒𝑞 = 𝑉𝐶𝐹
𝑑𝑡
𝑑𝑖𝐿𝑒𝑞 𝑉𝐶𝐹 −𝑖𝐿𝑒𝑞 𝑅𝑒𝑞
= (4)
𝑑𝑡 𝐿𝑒𝑞
The solution of this system of differential equations in the s-domain has been performed
in MATLABTM, and the details are provided in the Appendix A. The expression for the current
𝑖𝐿𝑒𝑞 (𝑡)
4
𝑒 𝑓(𝑡)𝑡
=∑
4𝑓(𝑡)3 + 3Leq 𝑓(𝑡)2 − 2(CF Lbus − Cbuck Lbus )𝑓(𝑡) − CF R eq − CF Lbus Leq + Cbuck Lbus Leq
𝑘=1
where, f(t)
k
= √t 4 + Leq t 3 − (CF Lbus − Cbuck Lbus )t 2 + (Cbuck Lbus Leq − CF Lbus Leq − CF R eq )𝑡 − CF Cbuck Lbus R eq
k=1,2,3,4
Considering only the effect of voltage from C buck, the expression of for the fault current
contributed by Cbuck current in the underdamped second-order RLC circuit is solved, and the
28
Solving and transforming (6) in time domain,
𝑉𝐶𝑏𝑢𝑐𝑘0 𝛼1 𝑖1 (0)
𝑖1 (𝑡) = 𝑒 −𝛼1 𝑡 [𝑖1 (0) cos 𝜔𝑟1 𝑡 + ( + ) sin 𝜔𝑟1 𝑡]
𝜔𝑟1 𝐿𝑏𝑢𝑠 𝜔𝑟1
𝑅
Where, damping factor, 𝛼1 = 2𝐿𝑏𝑢𝑠
𝑏𝑢𝑠
1
Resonant frequency, 𝜔01 =
√𝐿𝑏𝑢𝑠 𝐶𝑏𝑢𝑐𝑘
A control schematic for the SSCB providing short-circuit protection and implementing
the FCL function in MATLAB/SimulinkTM is proposed in Fig. 3.3. Figure 3.3 (a) displays
the block diagram of the control circuit while 3.3(b) details the MATLAB/SimulinkTM
(a)
(b)
Fig. 3.3. Fault-current control circuit implementing FCL function (a) block diagram (b) Simulink
representation
29
(a)
(b)
Fig. 3.4. XOR Gate: (a) structure (b) truth table
implementation. The “Switch” block sends the output which is inverted and transmitted to the
gate of the SSCB. The output of the block is “1” when the input of the block is a “0” from the
output of the “OR” gate. The condition for “0” is when the measured current is higher than the
overcurrent threshold.
An XOR gate is used to provide the FCL mode activation signal. The output of the
XOR gate is ‘0’ when two inputs are same. Before the fault, both the detection signal and the
output of switch are “0”. The output of the XOR gate is ‘0’ when two inputs are same (please,
refer to Fig. 3.4 for completeness). At the application of the fault and the measured current
crossing the overcurrent threshold, the “fault detection signal” provides a latched value of “1”,
hence, detecting the fault and making the output of XOR “1”. The switch output is now “1” and
the gate signal “0”. To repeat this action at a rate of 1 kHz, the latched “Comparator”
output block is passed through an “AND” gate with the other input being a pulse generator,
so that the fault detection and consequent interruption of gate signal is repeated every 1 ms.
The switching frequency under FCL operation would mainly depend on the thermal capability of
30
3.4 Fault Analysis under FCL Operation Integrated with Controller Delays
Delays are inevitable in practical circuits due to the current sensors, analog-to-digital
converters, digital signal processors and semiconductor device switching delays. The SSCB total
voltage waveforms in the main “1-kVdc bus”, “DC Load 1” and “DC Load 2” are illustrated in
Figs. 3-5 and 3-6, respectively. The bus steady-state current before the fault is applied is 7.5 kA
and there are no energy-storage capacitors at the load. The control circuit described above is
activated and the SSCB protecting “DC Load 1” enters into the FCL mode while the other loads
continue operating at their rated values. Most of the fault current is contributed by the energy-
storage capacitor at the “1-kVdc bus” so the “DC Load 2” and “AC Load” experience minimal
oscillations with the current transients diminishing within 0.15 s. The current ripple in the faulted
Fig. 3.5. Current waveforms at the buck converter output, 1-kVdc load center filter capacitor,
DC Load 1, DC Load 2, AC Load for a pole-to-pole fault at “DC Load 1” at t = 0.5 s
31
Fig. 3.6. Voltage waveforms at the buck converter output, load center and ac load buses for
a pole-to-pole fault at “DC Load 1” at t = 0.5 s
load results from the SSCB opening upon the current reaching approximately 18.78 kA followed
by freewheeling of the inductor current until the next switching cycle starts. Many cycles are
illustrated to show the positive effect of the SSCB equipped with the FCL function. It is not
anticipated that the faulted load SSCB will operate for these many cycles since the protection
scheme should open the SSCB to isolate the fault after few cycles determined through a
As discussed above, the FCL function is implemented including a controller delay of 40 μs.
32
So, the approximated rise rate of the current becomes:
di Vdc 1000
= = = 307 A/μs
dt Lline 3.25 μ
For a 40-μs controller delay after a fault at “DC Load 1” at t = 0.5 s, the trip fault current
Under steady-state conditions, the voltage ripple at the output capacitor of the buck
converter is 10 % or 100 V and the voltage ripple at the 1-kVdc load center bus is 1 %, or 10 V.
The voltage initial transient after the fault is applied at t = 0.5 s reaches a maximum value of 5%
or 50 V and diminishes to reach the steady-state value within 0.1 s. The MOV connected in
parallel to the “diode/RB-IGCT” series branch in the SSCB protecting “DC Load 1” does not
operate because of minimal overvoltage during device turn off under the FCL mode resulting
from the distributed capacitance across the system in Fig. 2.1, in particular, at the 1-kVdc bus,
The energy-storage capacitor at the 1-kVdc bus was removed so the buck capacitor served
as the only capacitive storage upstream (load-center) from the fault. Each of the loads has now
an energy-storage capacitor for voltage regulation and ride-through capabilities. Load capacitors
were selected based on 1%, 5% and 10% voltage ripple. Detailed calculations are shown in
Appendix A.
Table 3.1 shows impact of controller delays on the peak fault current where the dc loads
have capacitors selected for 1% voltage ripple, where the dc loads have capacitors selected for
1% voltage ripple and there is no energy-storage capacitors at the 1-kVdc load-center bus. As
33
Table 3.1: Impact of controller delays and capacitive discharge on the peak fault current and
i2t(t) for the “DC Load 1” SSCB
0 μs 6.250 3 3.65x106
7 μs 8.400 3 3.72x106
25 μs 13.925 5 3.8x106
40 μs 18.780 7 3.92x106
anticipated, the required number of power devices in parallel to sustain the higher currents
3.5.1 Impact on the load center bus current: Figure 3.7 illustrates current waveforms for at the
buck converter output, DC Load 1, DC Load 2, AC Load for a pole-to-pole fault at t = 0.5
s with the energy-storage capacitor removed. The peak current reached now is about 8.5
kA, which is less than half of the previously observed peak fault current of 18.78 kA
contributed by the energy-storage filter capacitor at the 1-kVdc bus. Thus, the removal of
during a fault.
3.5.2 Impact on voltage at different locations: Figures 3.8, 3.9 and 3.10 illustrate voltage
waveforms at the buck converter output, dc load and ac load buses for load capacitors
selected for 10%, 5% and 1% voltage ripple, respectively. Corresponding peak voltage
swings are 8.2%, 4.5% and 2.3%; decreasing as expected when load capacitance
increases. These voltage swings are higher compared to the system having the energy-
storage capacitor at the 1-kVdc bus and no capacitors across the loads. Thus, there is
34
need for a trade-off while choosing the location of the energy-storage capacitors to yield
Fig. 3.7. Current waveforms at the buck converter output, DC Load 1, DC Load 2, AC Load for a
pole-to-pole fault at “DC Load 1” at t = 0.5 s (energy-storage capacitor at load-center bus removed)
Fig. 3.8. Voltage waveforms at the buck converter output, dc load and ac load buses for a
pole-to-pole fault at “DC Load 1” at t = 0.5 s; load capacitors sized for 10% voltage ripple
35
Fig. 3.9. Voltage waveforms at the buck converter output, load center and ac load buses for a
pole-to-pole fault at “DC Load 1” at t = 0.5 s; load capacitors sized for 5% voltage ripple
Fig. 3.10. Voltage waveforms at the buck converter output, dc load and ac load buses for a
pole-to-pole fault at “DC Load 1” at t = 0.5 s; load capacitors sized for 5% voltage ripple
36
3.6 Coordination between Upstream and Downstream SSCBs during FCL Operation
The coordination between upstream and downstream devices during FCL operation will be
considered in this section by analyzing two cases of variable load conditions. A pole-to-pole
Case 1: “DC load 1” and “DC Load 2” operate at 80% and 20%, respectively, and ac load
3.25Mx0.8
Current through DC Load 1, ILoad1 = = 2.6 kA
1000
3.25Mx0.2
Current through DC Load 2, ILoad2 = = 650 A
1000
1M
Current at the AC Load Center input, ILoad,AC = = 1.0 kA
1000
Fig. 3.11. Current waveforms at the buck converter output, DC Load 1, DC Load 2, AC
Load for a pole-to-pole fault at “DC Load 1” at t = 0.5 s (case 1)
37
Fig. 3.12. Voltage waveforms at the buck converter output, dc load and ac load buses
for a pole-to-pole fault at “DC Load 1” at t = 0.5 s (case 1)
The FCL operation has a similar effect as the case where all loads are running at rated
power. The waveforms for this case are provided in Figs. 3.11 and 3.12 with the 1-kVdc bus
filter capacitor removed with load capacitors in place. The buck converter output current reaches
a value of 10.15 kA from the steady-state value of 4.25 kA, with the current through “DC Load
1” SSCB reaches a value of about 8.5 kA. The current drawn by unfaulted “DC Load 2” and
“AC load” currents remain the same as calculated above. The unfaulted load currents show
minimal oscillations pertaining to the transient in bus capacitor voltages; so these load operations
are not hampered as the transients diminishes within 0.2 s continuing steady-state operation. The
38
Case 2: “DC load 1” and “DC Load 2” operate at 50% each, and ac load operates at 100%
rated power:
3.25Mx0.2
Current through each dc load , ILoad,dc = = 1.625 kA
1000
1M
Current at the AC Load Center input, ILoad,AC = = 1.0 kA
1000
The waveforms for this case are provided in Figs. 3.13 and 3.14 with the 1-kVdc bus filter
capacitor removed and load capacitors in place. The buck converter output current reaches a
value of 11.125 kA from the steady-state value of 4.25 kA, with the current through “DC Load
1” SSCB reaches a value of about 8.5 kA. From these results, the faulted “DC Load 1” SSCB
goes only into FCL mode while the other sections of the system continue normal operation even
though FCL function was incorporated in the load SSCBs (protecting downstream loads) and the
Fig. 3.13. Current waveforms at the buck converter output, DC Load 1, DC Load 2, AC Load for a
pole-to-pole fault at “DC Load 1” at t = 0.5 s (case 2)
39
Fig. 3.14. Voltage waveforms at the buck converter output, dc load and ac load buses for a pole-
to-pole fault at “DC Load 1” at t = 0.5 s (case 2)
buck-converter SSCB (located upstream). This ensures that power flows are not disrupted
throughout the unfaulted portion of the load center, particularly, power flows to critical loads.
This selectivity is the basis for achieving proper coordination of protection devices because only
the SSCB protecting the faulted load goes into FCL mode while the other SSCBs are not
affected.
This ensures that power flows are not disrupted throughout the unfaulted portion of the dc
and ac load centers, particularly, power flows to critical loads. This selectivity is the basis for
achieving proper coordination of protection devices because only the SSCB protecting the
faulted load goes into FCL mode while the other SSCBs are not affected.
40
3.7 Summary
implementation.
Fault analysis including the impact of controller delays and capacitive discharge.
Assessment of the coordination between upstream and downstream SSCBs during FCL
The following chapter will focus on the comparison of different fault-current detection
techniques for implementing FCL, and the impact of FCL operation on RB-IGCT’s thermal
handling requirements.
3.8 References
[1] Cuzner, R.M.; Venkataramanan, G., "The Status of DC Micro-Grid Protection," in Industry
Applications Society Annual Meeting, 2008. IAS '08. IEEE , vol., no., pp.1-8, 5-9 Oct. 2008
[2] Jin, C., Dougal, R.A. and Shengyi, L. "Solid-state Over-current Protection for Industrial DC
Distribution Systems." in 4th International Energy Conversion Engineering Conference and
Exhibit (IECEC), pp 26-29. 2006.
[3] S. Munasib and J. C. Balda, "Short-circuit protection for low-voltage DC microgrids based
on solid-state circuit breakers," 2016 IEEE 7th International Symposium on Power
Electronics for Distributed Generation Systems (PEDG), Vancouver, BC, 2016, pp. 1-7.
[4] Fletcher, S.D.A.; Norman, P.J.; Galloway, S.J.; Crolla, P.; Burt, G.M., "Optimizing the
Roles of Unit and Non-unit Protection Methods Within DC Microgrids," in Smart Grid,
IEEE Transactions on , vol.3, no.4, pp.2079-2087, Dec. 2012
[5] Park, J.-D.; Candelaria, J., "Fault Detection and Isolation in Low-Voltage DC-Bus
Microgrid System," in Power Delivery, IEEE Transactions on , vol.28, no.2, pp.779-787,
April 2013
[6] K. G. Shin and Xianzhong Cui, "Computing time delay and its effects on real-time control
systems," IEEE Transactions on Control Systems Technology, vol. 3, no. 2, pp. 218-224,
June 1995.
41
CHAPTER 4
SYSTEM
4.1 Introduction
will be compared using the let-through energy at the fault location as the figure of merit. The
RB-IGCT’s thermal handling requirement and the impact of FCL operation on the MOV will
The FCL function considered earlier for a SSCB used an overcurrent threshold technique for
activating the FCL operation mode. However, there are other major fault-detection techniques
derivative and a combination of overcurrent and current derivative techniques [2-5]. These
techniques are compared in terms of the let-through energies [𝑖 2 (𝑡)𝑡]. The [𝑖 2 (𝑡)𝑡] is a
measurement of thermal energy linked with the flow of current, hence useful in determining the
impact of the heating of the conductors at the specified locations during short-circuit conditions.
Thus, the magnitudes of [𝑖 2 (𝑡)𝑡] would explain the stress on system components during FCL
protection requirements.
42
4.2.1 Overcurrent threshold: The overcurrent threshold technique is considered first since it is
the simplest fault-detection technique. The FCL mode is activated if the SSCB current exceeds a
specified current threshold set here at twice the rated current. An overcurrent threshold of 6.5 kA
is used for the selected case study with the load rated 3.25 MW and 1 kVdc. The choice of twice
the rated current is based on two main criteria: (1) avoidance of nuisance tripping following high
currents occurring due to normal operation of the load, and (2) fast enough response to enable
coordination with upstream SSCBs, avoiding damage to the semiconductor devices or any piece
4.2.2 Undervoltage threshold: The voltage across an output-filter capacitor decreases rapidly
when subjected to a fault since power converters do not contribute significantly to replenish the
capacitor charge and the fault current. In addition, the power converters would either shut down
or also operate under FCL mode to protect the converter semiconductor devices. Here, the FCL
mode is activated upon reaching an undervoltage threshold set at 500 V or 50% of the dc-bus
rated voltage.
4.2.3 Apparent resistance: This value is calculated as the ratio of the measured voltage and
current at the considered SSCB [4]. When this resistance is below a threshold set at a fraction of
the rated value, the SSCB goes into FCL mode. The apparent resistance threshold is set at half of
the rated apparent resistance; that is, corresponding to a fault current of twice the rated current, to
4.2.4 Current derivative threshold: This technique is based on the principle that current will
rise faster under short-circuit conditions than at rated operating conditions. The current
derivative of the SSCB is monitored, and the FCL mode is activated as the derivative exceeds a
set threshold. Here, thresholds of 20 A/μs (or 20 MA/s) and 5 A/μs are considered.
43
4.2.5 Combination of overcurrent and current derivative threshold: This method combines the
overcurrent and current derivative threshold techniques. The FCL mode is activated if either or
The let-through energies [𝑖 2 (𝑡)𝑡] for the buck-inductor and “DC Load 1” currents for
SSCB operation in FCL mode are used as the figure of merit to compare the effectiveness of the
five considered fault-detection techniques. The let-through energy is calculated as the integral of
the square of the current from the fault starting time until the SSCB would isolate the fault; the
A pole-to-pole fault at the “DC Load 1” (shown in Fig. 2.1) is applied at t = 0.5 ms. Upon
detection of the threshold crossing, the SSCB protecting “DC Load 1” enters into FCL mode,
and the let-through energy is calculated onwards for 10 ms. The results are analyzed in the
following section.
Table 4.1 presents the let-through energies for all five techniques with the overcurrent and
apparent resistance techniques having the lowest values of [𝑖 2 (𝑡)𝑡] at the buck inductor current
with a value of 4.7x105 A2s for 10 ms from fault, and at the faulted “DC Load 1” SSCB with a
value of 1.66x105 A2s for 10 ms from fault. Thus, the overcurrent and apparent resistance
techniques lead to comparatively lower thermal and mechanical stresses on the protection
equipment as compared to the other techniques. The apparent resistance technique, however, is
difficult to implement practically as the fault impedance between the faulted poles is required to
be estimated. Thus, high fault impedances may result in erroneous calculation of the fault-current
44
Table 4.1: Comparison of 𝒊𝟐 (𝒕)𝒕 for different threshold types
Threshold Type Measured 𝒊𝟐 (𝒕)𝒕 for Measured 𝒊𝟐 (𝒕)𝒕 for
Buck Inductor Current Load SSCB Current
(10 ms from fault) (A2s) (10 ms from fault) (A2s)
Overcurrent (twice the rated
4.7x105 1.66x105
current)
Undervoltage (50% of rated
5.5x106 2.2x106
voltage)
Apparent resistance (half of
4.7x105 1.66x105
rated resistance)
Current derivative (20 A/μs) 2.2x106 1.06x106
Current derivative (5 A/μs) 7.2x105 2.8x105
Overcurrent+current derivative
9.79x105 3.75x105
(20 A/μs)
threshold. Hence, overcurrent technique was used in FCL implementation. The measured
[𝑖 2 (𝑡)𝑡] values in table 4.1 are comparable to IGCT load integral values, for example, ‘ABB
IGCT 5SHY 2035L4520’ has a limiting load integral of 5.12x106 A2s for a repetitive surge
current of 32 kA for 10 ms. For the overcurrent technique, the measured [𝑖 2 (𝑡)𝑡] for faulted “DC
varying the threshold level of the latter from 0.5 p.u. to 0.965 p.u. The results are presented in
Tables 4.2 and 4.3. The undervoltage threshold at 0.965 p.u. yields [i2 (t)t] values for the buck-
inductor and load-SSCB currents to be within 10% of the values obtained for the overcurrent
threshold set at twice the rated current. It is concluded that the overcurrent threshold produces
minimal transients during faults since the undervoltage technique having low threshold values
leads to higher voltage drops and larger current overshoots during the capacitor re-charging to
45
Table 4.2: Comparison of 𝒊𝟐 (𝒕)𝒕 for buck inductor current for two threshold types
Overcurrent Threshold Undervoltage Threshold
Criterion [𝒊𝟐 (𝒕)𝒕] for Buck [𝒊𝟐 (𝒕)𝒕] for Load
Inductor Current Criterion SSCB Current
2
Over 10 ms (A s) Over 10 ms (A2s)
0.5 p.u. 5.5x106
0.6 p.u. 3.8x106
0.7 p. u 2.6x106
Twice the rated
4.7x105 0.8 p.u. 1.9x106
current
0.9 p.u. 1.47x106
0.95 p.u. 1.12x106
0.965 p.u. 9.86x105
Table 4.3: Comparison of 𝒊𝟐 (𝒕)𝒕 for load SSCB current for two threshold types
Overcurrent Threshold Undervoltage Threshold
Criterion [𝒊𝟐 (𝒕)𝒕] for Load SSCB [𝒊𝟐 (𝒕)𝒕] for Load
Current Criterion SSCB Current
Over 10 ms (A2s) Over 10 ms (A2s)
0.5 p.u. 2.2x106
0.6 p.u. 1.63x106
0.7 p. u 1.15x106
Twice the
1.6x105 0.8 p.u. 7.65x105
rated current
0.9 p.u. 5.84x105
0.95 p.u. 4.23 x105
0.965 p.u. 3.78x105
thermal capability design. This is even more important for SSCB applications where the main
purpose is to provide short-circuit protection to a portion of the power system without exceeding
46
the thermal limits of the devices themselves. Thus, the selection of the RB-IGCT for an SSCB
application will be further validated by analyzing its thermal capability in FCL operation.
The methodology for analyzing the required thermal handling requirements of RB-IGCTs
Calculate the maximum allowable power dissipation through each RB-IGCT using the
thermal impedance, maximum allowable junction temperature and case temperature provided
Tvj,max −Tc
P(AV)M = (4.1)
Rth(j−c)
resistance.
For dc systems, the RMS and average currents are equal and denoted as Idc; so, solve for Idc
using:
where VT0 = threshold voltage; rT = device resistance both from the device datasheet.
Verify that the selected RB-IGCT with has an higher average on-stage current IT(AV)M higher
47
Determine the number of RB-IGCTs required to be connected in parallel taking into account
the safe operating area and reliability. A rule of thumb used here is that the required current
2xILoad,max
nRB−IGCT = (4.3)
IT(AV)M
ILoad,rated
IRB−IGCT = (4.4)
nRB−IGCT
Calculate the fault current to be carried by each RB-IGCT during the FCL mode; this current
has to be smaller than the maximum controllable turn-off current ITGQM. As before, the
Calculate the losses during normal operating conditions in a single RB-IGCT, and using
thermal impedance data, verify that the maximum junction temperature is not exceeded. If this
criterion is not met, then the number of devices would need to be recalculated.
Calculate the losses during the FCL mode for a single RB-IGCT and validate the junction
A simple thermal analysis based on the methodology described above under FCL operation
48
4.5.2 Calculations for Determining Operating Conditions for Thermal Analysis
According to the steps described in the previous section and using the parameters in
Table 4.4 having estimated values for a 2.5-kV RB-IGCT [5], the maximum dissipated power is
given by:
Tvj,max − Tc
P(AV)M = = 1,785.8 W
R th(j−c)
where, Tvj,max = 110 °C (applying a 15 °C safety margin); Tc = 85 °C; and Rth(j-c) = 8.5 K/kW.
1−0.9
Using VT0 = 1.1 V slope resistance, rT = 1,600−1,000 = 0.1 mΩ results in Idc = 1.435 kA,
3.25 M
At a rated power of 3.25 MW, the load current is ILoad = = 3.25 kA, yielding 5
1000
Considering that the overcurrent threshold for the load SSCB is set at 6.5 kA and a 40-μs
controller delay after the fault current reaches the overcurrent threshold, the peak fault current
18,780
The fault current per device is: ID,FCL = = 3.76 kA which is greater than the
5
So, 5 devices in parallel do not fulfill the current capability criterion. Therefore, the number
18,780
nRB−IGCT = ≈7
3,000
49
Table 4.4 Device Parameters Used for Loss Calculations for Determining RB-IGCT’s
Thermal Requirements
Parameters Values
3,250
Current to be carried by a single RB-IGCT under rated conditions is now, ID = =
7
464.3 A.
The SSCB experiences only conduction losses in this operating mode. Hence, conduction
TC + Pcond R th(j−c) = 89.52 ℃ and does not exceed as expected its maximum value.
The SSCB experiences both turn-off and turn-on losses; there are no conduction losses
in this mode because of the fast rise of the fault current. Using Table 4.4, the total switching
50
EFCL = Eon,FCL + Eoff,FCL = 2.85 + 2.3 = 5.15 J
Considering P(AV)M , the maximum operating switching frequency that RB-IGCT can be
1,785.8
fs,max = = 346.75 Hz
5.15
The calculated junction temperature value is under the specified maximum value of 110 oC
(that assumed a safety margin). At this point, the designer may decide on adding more RB-
IGCTs in parallel to improve the thermal capability of the SSCB if a higher switching frequency
is required, e.g., 1 kHz. The turn-on and turn-off switching energy losses per device would be
reduced by adding more devices, and hence meeting the maximum allowable junction
No. of Operating
Parameter Values
Devices Condition
Normal operating Conduction loss 0.53 kW
condition Operating junction temperature 89.52 ℃
Turn-on switching power loss 0.98 kW
7
Turn-off switching power loss 0.8 kW
FCL mode
Total dissipated power 1.78 kW
Operating junction temperature 101.3 ℃
51
temperature requirement. The results of this simple thermal analysis are summarized in Table
4.5.
The calculations shown above provide a simple step-by-step methodology for validating the
SSCB thermal requirements based on a fixed number of parallel RB-IGCTs. It has also been
shown that the maximum switching frequency is dependent on the number of RB-IGCTs
connected in parallel in order to comply with the maximum allowable power dissipation. If
parallel should be increased to reduce the device current and thus turn-on and turn-off switching
energy in the system inductance and thus preventing overvoltages across the SSCB during turn
off [8-10]. This section addresses the impact that operation FCL operation of a SSCB has upon a
MOV.
The MOV is modeled as a series branch of a 2-kV dc voltage source, a 28-mΩ resistor, a
1-nH inductor and a diode in reverse connection with respect to the RB-IGCT instead of using
Several cases based on different cable lengths in “DC Load 1” branch ranging from 50 m
to 200 m with no MOV in parallel with the SSCB have been run in the notional 1kVdc system
presented in Chapter 2. It has been observed that, for cable lengths greater than 150 m and less
52
The simplified circuit in Fig. 4.1 is based on the configuration of the RB-IGCT carrying
cable length was chosen based on the findings presented in the previous paragraph. The voltage-
current characteristics and RB-IGCT turn-off waveforms for one complete switching cycle are
shown in Fig. 4.2. The RB-IGCT current rises when a pole-to-pole fault is applied at “DC Load
1” at t = 0.02 s. The RB-IGCT turns off upon reaching the threshold limit of 3 kA and the
Fig. 4.1. Simplified circuit diagram for a 1kVDC load center for simulation of the FCL impact
on the MOV
The MOV is subjected to repetitive surges during the FCL mode. To analyze the impact
upon the MOV, the absorbed energy is calculated and compared with the rated values obtained
from the datasheet. The need for a cooling-down interval is also mentioned.
The energy absorbed by the MOV per cycle can be calculated as follows [8][9]:
From the datasheet of ABB surge arrester Polim R-2N [10], the energy absorption
capability at a clamping voltage of 2.5 kV is Ecapability = 24x2.5 = 60 kJ. Thus, the maximum
60 k
number of repetitive pulses under rated conditions is equal to 1.05 k = 57.14 ≈ 57. In other
words, the MOV operating under the above conditions will be able to withstand 57 repetitive
surges before its rated energy absorption capability is reached; i.e., 57 ms for a switching
frequency of 1 kHz.
Cool-down interval
For repetitive operations, the requirement of a cool-down interval can be ignored if the
total energy absorbed is less than the rated energy absorption capability of the MOV. Upon
reaching this limit (e.g., 57 surges considering the above case), a 45 to 60-minute cool-down
interval is advised by the manufacturer before the next set of FCL operations in order to
protect the MOV from severe degradation and subsequent failures [12]. The interval is
54
dependent on several attributes of the MOV (e.g., type of arrester material, ambient
temperature etc.).
4.7 Summary
4.8 References
[1] S. Munasib and J. C. Balda, "Short-circuit protection for low-voltage DC microgrids based on
solid-state circuit breakers," 2016 IEEE 7th International Symposium on Power Electronics
for Distributed Generation Systems (PEDG), Vancouver, BC, 2016, pp. 1-7.
[3] Fletcher, S.D.A.; Norman, P.J.; Galloway, S.J.; Crolla, P.; Burt, G.M., "Optimizing the
Roles of Unit and Non-unit Protection Methods Within DC Microgrids," in Smart Grid,
IEEE Transactions on , vol.3, no.4, pp.2079-2087, Dec. 2012
[4] Cairoli, P.; Dougal, R.A.; Lentijo, K., “Coordination between supply power converters
and contactors for fault protection in multi-terminal MVDC distribution systems,” In
Electric Ship Technologies Symposium (ESTS), IEEE , vol., no., pp.493,499, 22-24 April
2013
[5] E. Cinieri , A. Fumi , V. Salvatori and C. Spalvieri, "A new high-speed digital relay
protection of the 3-kvdc electric railway lines", in IEEE Trans. Power Del., vol. 22, no. 4, pp.
2262-2270, 2007
55
[6] ABB, “Reverse Blocking Integrated Gate-Commutated Thyristor 5SHZ 11H6500’. Available
online at:
https://library.e.abb.com/public/7f2b388387f8cef1c1257dea0043b854/5SHZ%2011H6500_5
SYA1254-01%20Dec%2014.pdf
[7] U. Vemulapati et al., “Recent Advancements in IGCT Technologies for High Power
Electronics Application”. Available online:
https://library.e.abb.com/public/b8d1316db3904af0bf9371b32d478b07/Recent%20Advance
ments%20in%20IGCT%20Technologies%20for%20High%20Power%20Electronics.pdf
[9] Littelfuse: “Selecting a Littelfuse Varistor”. Application note. Available online at:
http://www.littelfuse.com/~/media/electronics_technical/application_notes/varistors/littelfuse
_selecting_a_littelfuse_varistor_application_note.pdf
[12] ABB: “Overvoltage Protection: Metal Oxide Surge Arresters in Medium Voltage Systems”.
Application Note. Available online at:
https://library.e.abb.com/public/70e9fd6933c8c644c12578d200333cb5/952_abb_awr_mittel
spannung_E_low.pdf
56
CHAPTER 5
5.1 Conclusions
The work presented in this thesis addressed some important issues regarding the short-
contributions are drawn from the results presented and analyzed in the thesis:
The RB-IGCT seems the best semiconductor device for implementing a 1-kVdc SSCB
since it has the short-circuit capability of a thyristor (~ 3 kA), extremely low on-state
voltage drop (~1.25 V) during normal SSCB operation, and blocks voltages in forward
and reverse directions but conducts current only in the forward direction. It has low-
thermal resistance, assisted by double-sided cooling and hermetic sealing resulting from
its hockey-puck, thyristor-type package. All of these attributes should result in increased
sustain higher limiting fault currents. The evaluation of the FCL function incorporated an
unavoidable controller delay that impacted the RB-IGCT’s thermal requirements. FCL
The proposed fault-current-limiting algorithm ensured that the power flows were
continuous in the dc zone with only the current in the faulted section limited to a user-
57
specified threshold. The unfaulted portion of the dc zone experienced minimal transients
of short durations. For the evaluated case, the peak voltage swing was about 8.2% of the
rated voltage. This behavior is very important for achieving coordination of protection
devices because only the SSCB protecting the faulted load went into FCL mode while the
The impact of energy-storage filter capacitor at the 1-kVdc bus on the fault-current
response has been addressed. With the filter capacitor in use, the fault current reached a
peak of 18.78 kA before the SSCB on the faulted “DC Load 1” goes into FCL mode,
requiring 7 RB-IGCT devices to be in parallel in the SSCB to carry the current. The
removal of this filter capacitor bus resulted in a peak fault-current of 8.5 kA, requiring
only 3 RB-IGCT devices to be parallel in the SSCB. Thus, removing the filter capacitor
resulted in lesser number of devices in parallel, hence assuring better power density and
The FCL function was further evaluated using five different fault-detection techniques.
The choice of the overcurrent technique was validated by comparing the let-through
The comparatively slower switching frequency (≤ 1 kHz) did not have an impact on the
SSCB operation. The maximum switching frequency is dependent on the number of RB-
IGCTs connected in parallel in order to comply with the maximum allowable power
dissipation. For example, the case study required 7 RB-IGCTs in parallel in the SSCB at a
the number of RB-IGCT connected in parallel should be increased to reduce the device
current and thus turn-on and turn-off switching energy during FCL operation.
58
The impact of FCL operation on metal-oxide varistors were evaluated by calculating the
energy absorbed in each cycle by the MOV and quantifying the maximum number of
cycles that the MOV can operate on before a cool-down interval is required. The
application of the MOVs across SSCBs operating under FCL algorithm in dc systems
shows the MOV would be able to operate 57 times consecutively before its total dissipated
Several areas of improvement, pertaining both to the works within the thesis and the
progressing research field of developing short-circuit protection for dc systems, are mentioned
below:
The proposed FCL algorithm has the potential to deliver swift, coordinated protection
system operation for compact low-voltage dc distribution systems. A practical
optimal protection system, encompassing the firm protection requirements for the above
mentioned systems.
The applicability of the FCL operation can be extended to further analyze fault responses
and associated protection schemes using SSCBs throughout different zones of notional all-
electric ships. Even though the base system was a simple one having only one source and
systems, i.e. microgrids having multiple sources and power converters. Preventing high
fault currents by means of FCL operation results in reduced system costs and avoidance of
59
Appendix A: Design Equations for System Parameters
With reference to Fig. 2.1 in Chapter 2, the values selected for different system components are
addressed in this Appendix. In particular:
Buck-Converter Main Design Equations
𝑉𝑖𝑛 = 1200 𝑉, 𝑉𝑜𝑢𝑡 = 1000 𝑉, ∆𝐼 = 10% = 750 𝐴, ∆𝑉 = 10% = 100 𝑉, 𝑓𝑠 = 1 𝑘𝐻𝑧
I ∗ ∆t 3250
DC Load capacitor, CLoad = = = 325 mF, ∆V = 1% = 10 V
∆V 1000x10
I ∗ ∆t 3250
DC Load capacitor, CLoad = = = 166.25 mF, ∆V = 5% = 50 V
∆V 1000x1000
I ∗ ∆t 3250
DC Load capacitor, CLoad = = = 32.5 mF, ∆V = 10% = 100 V
∆V 1000x1000
Main Equations for the SST
𝑉1 𝑉 ′ 2
Leakage inductance = = 0.55 𝑚𝐻
8𝑓𝑃0
where 𝑉1 = 𝑉 ′ 2 = 10 𝑘𝑉, 𝑓 = 3 𝑘𝐻𝑧, 𝑃0 = 7.5 𝑀𝑊
𝐼 ∗ ∆𝑡 750
Input capacitor, 𝐶𝑖 = = = 0.25 𝑚𝐹, ∆𝑉 = 10% = 100 𝑉
∆𝑉 6000𝑥1000
𝐼 ∗ ∆𝑡 12500
Output Capacitor, 𝐶0 = = = 17.36 𝑚𝐹, ∆𝑉 = 10% = 120 𝑉
∆𝑉 6000𝑥120
60
Selection of Kp and Ki for closed-loop SST control:
The dynamics of the output capacitor can be described as follows:
𝑑𝑉𝑜
𝐶𝑜 = 𝐾𝑝 (𝑉𝑟𝑒𝑓 − 𝑉𝑜 ) + 𝐾𝑖 ∫(𝑉𝑟𝑒𝑓 − 𝑉𝑜 )𝑑𝑡
𝑑𝑡
𝐾𝑖
𝑠𝐶𝑜 𝑉𝑜 = 𝐾𝑝 (𝑉𝑟𝑒𝑓 − 𝑉𝑜 ) + (𝑉 − 𝑉𝑜 )
𝑠 𝑟𝑒𝑓
𝑉𝑜 𝑠𝐾𝑝 + 𝐾𝑖
(𝑠) =
𝑉𝑟𝑒𝑓 𝐾𝑝 𝐾
𝑠2 + 𝑠 𝐶 + 𝐶 𝑖
𝑜 𝑜
which could be compared with the closed-loop transfer function of a second-order system
𝐾
𝐺𝐻(𝑠) = .
𝑠2 + 2𝜉𝜔𝑛 𝑠 + 𝜔𝑛 2
𝑓𝑃𝑊𝑀
For 𝜉 = 0.707 and 𝜔𝑛 = = 212 𝑟𝑎𝑑/𝑠,
20𝜉
𝐾𝑝 = 2𝜉𝜔𝑛 𝐶𝑜 = 14.98
𝐾𝑖 = 𝜔𝑛 2 𝐶𝑜 = 2247.2
4
𝑆𝑒𝑡𝑡𝑙𝑖𝑛𝑔 𝑡𝑖𝑚𝑒 = = 0.0266 𝑠
𝜉𝜔𝑛
61
Fig. A.3. Step response of the PI controller
Fig. A.5. SST waveforms in closed-loop control at 50% (0-0.05s), 75% (0.05-0.1 s) and 100%
(0.1-0.15 s) load conditions
62